SIMATIC TI545/TI555 System Manual: Order Number: PPX:545/555-8101-2 Manual Assembly Number: 2586546-0084 Second Edition
SIMATIC TI545/TI555 System Manual: Order Number: PPX:545/555-8101-2 Manual Assembly Number: 2586546-0084 Second Edition
System Manual
Reproduction, transmission or use of this document or contents is not permitted without express consent of
Siemens Industrial Automation, Inc. All rights, including rights created by patent grant or registration of a utility model or
design, are reserved.
Since Siemens Industrial Automation, Inc. does not possess full access to data concerning all of the uses and applications
of customer’s products, we do not assume responsibility either for customer product design or for any infringements of
patents or rights of others which may result from our assistance.
We check the contents of every manual for accuracy at the time it is approved for printing; however, there may be
undetected errors. Any errors found will be corrected in subsequent editions. Any suggestions for improvement are
welcomed.
MANUAL PUBLICATION HISTORY
SIMATIC TI545/TI555 System Manual
Order Manual Number: PPX:545/555–8101-2
Refer to this history in all correspondence and/or discussion about this manual.
Cover/Copyright Second
History/Effective Pages Second
iii — xii Second
1-1 — 1-8 Second
2-1 — 2-15 Second
3-1 — 3-21 Second
4-1 — 4-20 Second
5-1 — 5-10 Second
6-1 — 6-5 Second
7-1 — 7-16 Second
A-1 — A-4 Second
B-1 — B-4 Second
C-1 — C-4 Second
D-1 — D-13 Second
Index-1 — Index-4 Second
Registration Second
Contents
Preface
Chapter 1 System Overview
1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Contents iii
2.8 Power System Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Earth Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Grounding the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Grounding the Cabinet or Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Ground Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
iv Contents
Chapter 4 Cabling and Wiring the System
4.1 Connecting Input Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Wiring Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.2 Cable Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Cable Routing Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Under-Floor Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
In-Ceiling Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Surface Duct Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Mounting the Tap or Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3 Installing Remote I/O Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Cabling Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Trunk and Drop Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
User-Supplied Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Mounting the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Programmable Controller and RBC Drop Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Preparing Cables (for Drop Lines) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Connecting a CPU Drop Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Connecting the RBC Drop Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Connecting Terminal Block Trunk Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Alternate Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Configuration Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Preparing Trunk Line Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Connecting Trunk Line to Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
4.4 Connecting Modems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
Dedicated Line Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Dial-up Phone Line Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
4.5 Connecting a Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Contents v
Chapter 6 Starting Up the TI545/TI555 System
6.1 Powering Up the TI545/TI555 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Start-up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 TI545 CPU Memory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Memory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Maximum Configurable Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.3 TI555 CPU Memory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Memory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Maximum Configurable Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Chapter 7 Troubleshooting
7.1 Troubleshooting by Using Auxiliary Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Power-up Restart, Partial Restart, and Complete Restart . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Compare PLC to Disk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Run PLC Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Display Failed I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Show PLC Diagnostic Cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
7.2 Troubleshooting by Reading LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
vi Contents
Appendix A System Specifications
A.1 Series 505 System Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Contents vii
List of Figures
viii Contents
Figure 4-13 XON/XOFF Printer Handshaking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Figure 4-14 READY/BUSY Printer Handshaking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Contents ix
List of Tables
Table 7-1 Effects of Using AUX Functions 10, 11, and 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Table 7-2 CPU Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Table 7-3 Cable Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
x Contents
Preface
About this Manual This SIMATIC TI545/TI555 System Manual includes requirements and
specifications for preparing your control site and installing a
SIMATIC TI545/TI555 Programmable Logic Controller (PLC) system.
NOTE: This manual describes the SIMATIC TI545-1102 CPU, and both the
SIMATIC TI555-1101 and -1102 CPUs. Information in this manual does not
apply to the SIMATIC TI545-1101 CPU. For the information concerning the
SIMATIC TI545-1101 CPU refer to SIMATIC TI545 System Manual:
PPX:545-8101-x.
Agency Standards Series 505 products have been developed with consideration of the draft
standard of the International Electrotechnical Commission Committee
proposed standard (IEC-65A/WG6) for programmable controllers (released
as IEC 1131–2, Programmable Controllers Part 2: Equipment Requirements
and Tests, First Edition, 1992–09). Contact Siemens Industrial Automation,
Inc., for information about regulatory agency approvals that have been
obtained on the TI545/555 systems and Series 505 units.
Technical For technical assistance, contact your Siemens Industrial Automation, Inc.
Assistance distributor or sales office. If you need assistance in contacting your sales
agent or distributor in the United States, call 1–800–964–4114.
TI545 TI555
Feature –1102 –1101 –1102
User Memory (bytes) 192K 384K 1920K
EEPROM (EPROM) (bytes) 256K
Discrete I/O Points 2048 1
8192 2
Word I/O Points 1024 1
Control Relays 32,768
Scan Performance
(milliseconds/KW, best case) .67 .07
Notes:
1 Total I/O count may not exceed 2,048 points.
2 Total I/O count may not exceed 8,192 points.
• Cyclic RLL allows you to create an additional RLL program that runs
independently of the main RLL program.
Siemens
SIMATIC
SIMATIC TI555
TI505 CPU GOOD
RUN
BATT GOOD
R
S
2
3
2
#
1
I
/
O
R
S
2
3
2
#
2
555–1102
TI545/TI555 systems (see Figure 1-1) are designed for use in applications
that require discrete and analog control. Components include the CPU and
the support devices that provide operator communication, I/O control, and
power (see Figure 1-2).
You can communicate with the CPU by using the following devices:
• SIMATIC PCS.
The controllers can also communicate with other devices through the
SINECr H1 or SIMATICr TIWAY Local Area Networks. See documents
listed in the Preface of this manual for information on these systems.
Programming Unit
TIWAY SINEC H1
*The 8-slot and 16-slot I/O bases operate with the PPX:500–5840 Adapter.
Figure 1-2 TI545/TI555 System Using Series 500 and Series 505
Components
Series 505 Base The CPUs are housed in a Series 505 base assembly. A base assembly has
Assemblies slots for the CPU or remote base controller (RBC), a power supply, and the
I/O modules. Three base assembly models are currently available. Each has
the following number of slots for I/O modules.
Any base assembly may be used at any point in the system, depending upon
the number of I/O points required.
Local and Remote I/O modules are grouped into local and remote I/O categories depending
I/O upon their physical location. The local I/O comprises those modules located
in the same base assembly as the CPU. If you install the CPU in base
assembly Model PPX:505–6516, the local I/O may consist of as many as 16
I/O modules. The base assembly containing the local I/O is designated 0.
Individual I/O modules in the remote bases communicate with the CPU
through RBCs. The RBC in each remote base transmits information from
the I/O modules in that base directly to the CPU.
Series 505 The power supply provides up to 55 W at +5 VDC and 3.75 W at –5 VDC for
Power Supply use by the CPU and the I/O modules. The PPX:505–6660 power supply
operates at either 110 VAC or 220 VAC on user-supplied power. A jumper on
the inside of the back of the module is used to select voltage. The model
PPX:505–6663 power supply operates on 24 VDC user-supplied power.
I/O Port The CPU has one Remote I/O port, (9-pin female) used to communicate
directly with remote base controllers (RBCs). This port uses a twisted,
shielded-pair RS-485 cable to communicate with RBCs.
Both Series 505 (see NOTE and Appendix C) and Series 500 I/O modules can
be connected to the TI545/TI555 CPU as remote I/O. The CPU is capable of
directly addressing the PPX:505–6851–A RBC in a Series 505 base
assembly, or the PPX:500–5114–A RBC in a Series 500 base assembly
intermixed in the same system. Both RBC models use shielded twisted-pair
cable. They can be placed up to 3300 feet from the CPU.
NOTE: You cannot use some early model Series 505 I/O modules with a
TI545/TI555 CPU. Refer to Appendix C for details.
Battery Backup A permanent, rechargeable battery protects user memory and programming
during a power outage. Battery memory backup typically lasts six months
at temperatures ranging from 0° to 60°C.
! CAUTION Battery Damage: If the TI545/TI555 unit is left without power and
with the battery switch on for longer than six months, the battery
may be damaged to the point that it cannot be recharged.
Be aware that the battery will appear to charge, but the memory
backup time will be seriously degraded.
Real-time Clock The CPU contains a real-time clock which includes the following
information:
• Year (two digits), Month, Day of month, and Day of week.
• Hour, minute, second, tenths and hundredths of a second.
Programming You can use APT to program the CPU. APT is a graphic programming
Software environment that eliminates the need for you to work in relay ladder logic
when you create your application program. APT presents a familiar
structure for process engineers, allowing them to become more closely
involved in up-front design work. When the APT program is compiled, an
RLL program code is produced, generating the language with which the
electrician or maintenance person is already familiar. Refer to the APT
manual set for more information.
You can use the TISOFT programming software to create and edit your
application program. TISOFT allows you to work directly in the ladder logic
environment as you design the RLL program. For loops, analog alarms, and
SF programs, TISOFT presents menu-driven programming tools.
To program the latest features that are described in the Preface of this
manual, you need TISOFT Release 5.0, which runs on an IBM PC/AT (386
or higher) compatible personal computer running MS-DOS 3.3 or later.
Refer to your TISOFT manual for detailed instructions about how to enter a
program.
Program Storage The CPU offers the option of saving your RLL program in a non-volatile
in EEPROM form by downloading it to an EEPROM integrated circuit as shown in
Table 1-2. A separate programming device is not necessary. Once
programmed, an EEPROM can be removed and used in any Release 3.0 or
higher CPU as required. To help ensure equipment compatibility, use only
the EEPROM model supplied by your distributor.
Program Storage If your operating program does not change, you can store it permanently on
in EPROM EPROM(s) as shown in Table 1-2. By copying your program from an
EEPROM to an EPROM (using an EPROM copier), you can create
additional copies for CPUs that are running the same program.
Defining Control Use the following steps to define your control requirements:
• Define the number and type of inputs and outputs you need.
• Calculate the number of I/O modules and bases that you need.
Calculating Power Calculate a power budget for each base prior to installation. The power
Needs requirements of all modules must be included in the calculations — the
controller, the base controllers, as well as the I/O modules. The
user-supplied power to individual modules is not a part of the power budget
calculation. Refer to Appendix B for Series 505 module power consumption
information.
To help ensure reliable system operation, the total power required for the
controller and I/O modules must not exceed the total power available from
the system power supply. Refer to Chapter 3 for Series 505 power budget.
! WARNING Control devices can fail in an unsafe condition. This means that,
unless you incorporate proper safeguards, certain malfunctions of
these devices could lead to a sudden equipment startup or
shutdown. Such a startup or shutdown could result in property
damage and/or death or severe physical injury to the equipment
operator. Failure can also be exhibited as erratic or unexpected
operation.
The ICS 3-304.81 Safety Recommendations from NEMA ICS 3-304, Programmable Control-
ler Standard. Recommendations are reproduced by permission of the National Electrical
Manufacturers Association.
Operator Safety Provide a means for disconnecting power — independent of the controller —
Switches from the output loads when a machine is not operating, or when it is
necessary for the operator to reach into the machine. Power must be
removed by a non-semiconductor switch or a physically-wired relay contact,
placed to interrupt power to the output. It is not sufficient to rely solely on
the controller for this function. Figure 2-1 shows an operator safety switch.
User-supplied
critical loads
which could
Output cause injury
Module
Loads which
could not
cause injury
Emergency Stop Provide a means for removing power from the output if an emergency
Switch condition occurs with the machine during operation. Do this by
disconnecting output power with a non-semiconductor switch or hardwired
relay contact, not through the programmable control system (Figure 2-2).
C1 Electromechanical
Relay
Contacts of
electromechanical relay C1
C1
User-supplied
critical loads
C1 which could
Output cause injury
Module
Loads which
could not
cause injury
Switch or contact
Jog closed in the jog
or inch mode
User-supplied
critical loads
which could
Switch or contact cause injury
open in the JOG
Output or INCH mode
Module
• An electromagnetic shield.
Mount the components in a dustproof and drip tight enclosure such as the
NEMA Type enclosure. The enclosure must provide a minimum depth of
10 in. (25.4 cm) from the panel to the inside surface of the enclosure door.
The enclosure should be located so that the doors may be opened fully,
permitting easy access to the controller, wiring, and components. If
environmental conditions permit, a 19-inch rack may be used instead of a
NEMA enclosure. Use the 16-slot PPX:505–6516 I/O base for 19-inch rack
installations.
Temperature When preparing your installation, plan for an adequate air flow to ensure
Considerations proper cooling of equipment. Do not permit the convection cooling of the
controller to be hindered. Unless ambient temperatures are extremely high,
a fan or air-conditioned cooling is unnecessary for keeping controllers below
their maximum-rated operating temperature of 60°C provided that the
cabinet adequately dissipate heat.
For one local base and one remote base located in the bottom half of a 7-foot,
19-inch rack, place equipment that dissipates no more than 325 W in the
top half, above the System 505 bases, assuming a 25°C external ambient
temperature. If you must exceed these guidelines, use cooling equipment to
lower the equipment temperature to the recommended level.
Fusing the Use the following guidelines for installing fuses/circuit breakers; see
Controller and Figure 2-4. The sizes and types of fuses/circuit breakers depend on the
Remote I/O Base specified power distribution requirement.
Isolation
Transformer
Optional
Grounds
P/S
(Line)
(Neutral) Controller
(Ground)
P/S
(Line)
(Neutral) Remote I/O Base
(Ground)
Electrical Noise Electrical noise is defined as any unwanted electrical signal which enters
the control equipment. Noise signals cover the entire spectrum of
frequencies and may have any wave shape.
A major difficulty with noise problems is that they can occur at random
intervals. Continuous, or frequent, periodic noises generally are easy to
detect and remedy. Intermittent noise sources that produce short,
high-energy bursts at irregular and widely spaced intervals create problems
that can be harder to resolve.
The primary sources of noise in industry are those devices (and their wiring)
that produce and switch high voltage and current. Typical examples include
large motors, welders and contacts that switch heavily inductive loads such
as brakes or clutches.
When potential noise problem sources are identified, two general methods
are available to handle them. These methods are described in the following
sections.
• Noise snubbing.
• Noise isolation.
Noise Snubbing Noise snubbing reduces noise at its source. Applicable only to devices driven
by mechanical contacts, snubbing suppresses arcing at electrical contacts
caused by turnoff of inductive loads (e.g., relays, motors, motor starters,
solenoids, etc.).
Load snubbing (shown in Figure 2-5) reduces voltage transients at the load,
preventing them from traveling back to the contacts where they would
produce a showering arc and couple with adjacent wiring.
C R MOV
You can also use contact snubbing (shown in Figure 2-6) as an alternative
type of snubbing.
Both types of snubbing cause the physical devices to come on or go off more
slowly. The resistance-capacitance (RC) and metal oxide varistor (MOV)
elements should have minimal effect on system timing; their time constants
are substantially less than one millisecond.
R C MOV
NOTE: Noise snubbing shown in Figure 2-6 is built into the PPX:505-5518
Relay Output module.
Two cases of field wiring warrant special attention; wiring which enters the
harsh noise area to enable monitoring and control of those devices, and TTL
or low-level (less than 24 V) wiring. In these cases, supplement the physical
separation between control and noise-prone wiring with shielded,
twisted-pair wiring (12 twists/ft) for the control signals.
Shielding Shielding
Twisted Pair
Transmitter
Guidelines Consider the following guidelines before installing any system or power
wiring.
• Keep field input wiring, output wiring, and all other types of wiring in
the panel physically separated when possible.
• Avoid sharp bends to power and data cables. Use 7.6 cm (3 inches)
radius on all bends.
• Ensure that a good low earth ground impedance of 0.1 ohm or less
exists for all components in the system.
• For long return lines to the power supply, do not use the same wire for
input and output modules. Using separate return wiring for these
modules minimizes the voltage drop on the return lines of the input
connections.
Earth Ground In some installations, a metal conduit that connects to the neutral phase at
the circuit-breaker box supplies the earth ground of the power receptacle.
Depending on site conditions, this metal conduit may conduct current from
other sources that can interfere with the operation of the equipment.
To reduce this possibility, isolate earth ground and neutral from the conduit
(except at the service entrance housing); see Figure 2-8. Ensure that system
power is wired in accordance with National Electrical Manufacturers
Association specifications. Also comply with the following:
• Ensure that the protective ground wire resistance is less than 0.1 ohm.
Power
company
transformer Circuit
Service breaker TI545/TI555
entrance Conduit panel Conduit Base
power supply
AC line
AC neutral
Ground
Protective
Ground
Power Earth
company ground rod
earth ground
Grounding the When installing the controller, ensure that noise is minimized by following
Controller these guidelines. Use the ground connection (Figure 2-9) to attach one end
of a ground wire; attach the other end to a nearby grounding rod that meets
all electrical specifications required for an earth ground. Use the shortest
possible length of #8-gauge copper wire, or equivalent braided cable to make
the connection.
Grounding the If the controller is mounted in a cabinet or rack, use the same grounding
Cabinet or Rack procedure. Ensure that a good cabinet or rack ground connection is achieved
by removing existing paint and attaching a #8-gauge copper wire (or
equivalent) using a bolt, washers, and nut as necessary. You can attach the
other end of the wire to the same ground rod used to ground the controller.
Ground Use particular care when establishing the ground connections. The
Connections following techniques will help to establish good electrical connections and
decrease noise interference:
• Terminate grounding braid and green wires at both ends with copper
eye lugs to provide a good contact surface. Lugs should be crimped and
soldered.
• Use #10 copper bolts (or equivalent) for those fasteners providing
electrical connections to the single-point ground. This applies to
device-mounting bolts and braid termination bolts for subpanel and
user-supplied single points. Tapped holes for these fasteners are better
than nut-bolt arrangements.
• Paints, coatings, and corrosion can prevent good electrical contact at
ground points. Remove these impediments in the area of contact and
use external toothed lock washers (star washers) to ensure good
continuity and low impedance. This practice should be used for all
terminations — lug to subpanel, device to lug, device to subpanel,
subpanel to conduit, etc. Examples of ground connections are shown in
Figure 2-10.
Ensure that you have a good grounding system when you install
your equipment.
Star
washers
Step 2 Step 3 Subpanel
or user-supplied
Step 1 single point
ground
To ground equipment directly to the sub-panel, To attach ground leads to the sub-panel,
follow these steps: follow these steps:
1. Remove the finish from the equipment at 1. Remove the finish from the equipment at
areas of contact. areas of contact.
2. Tighten the first nut. 2. Tighten the bolt.
3. Tighten the second nut.
You may need a lock washer to prevent the nut
in Step 3 from backing off.
The following chart identifies the tasks for installing Series 505 system
hardware.
Install Base
• Rack mounting (Section 3.3)
• Panel mounting (Section 3.4)
Description The controller is housed in a Series 505 base assembly. A base assembly has
slots for the programmable controller or remote base controller (RBC),
power supply, and the I/O modules. Four base assembly models are
currently available (see Table 3-1).
Connecting Series Series 500 bases can be connected to a TI545/TI555 PLC system as a remote
500 Bases I/O base assembly. The TI545/TI555 controller is capable of addressing the
Series 500 base assembly through the RBC (PPX:500–5114–A). See
Appendix D for information about upgrading Series 500 bases.
PPX:505–6516, Use the following steps, and Figure 3-1, for mounting the base in a standard
16-Slot Base 19-inch rack.
1. Align two bracket holes with two screw holes located on the sides of
base.
2. Secure each bracket to base with two screws installed through the
bracket holes.
3. Position the base in the 19-inch rack. Depth of base is 7.99 inches
(20.3 cm).
NOTE: There should be at least 6 inches (15.24 cm.) of clearance at the top
and bottom of base for adequate airflow.
4. Align two bracket slots with two screw holes located on each side of the
19-inch rack. See Figure 3-1.
5. Secure each bracket to the 19-inch rack with two screws installed
through the the bracket slots. See Figure 3-1.
Series 505 Bases Use the following steps for panel mounting in an NEMA enclosure.
PPX:505–6516,
PPX:505–6508, 1. Open NEMA enclosure door.
PPX:505–6504
2. Drill four holes in sub-panel of NEMA enclosure with a #21 drill bit.
Refer to Figure 3-2 through Figure 3-4 for screw-hole dimensions for
each base.
NOTE: There should be at least 6 inches (15.24 cm.) of clearance at the top
and bottom of base for adequate airflow. The base depth is 7.99 inches
(20.3 cm.).
10.47
(265.94)
8.97
(227.81)
1.47
(37.31)
18.34
(465.84)
10.47
(265.94)
8.97
(227.81)
1.47
(37.31)
8.69
(220.79)
Note: in.
PPX:505–6504 (mm)
10.47
(265.94)
8.97
(227.81)
1.47
(37.31)
11.93
(303.2)
PPX:505–6508
Note: in.
(mm)
4. Align two bracket holes with two screw holes located on each side of
base. See Figure 3-5.
5. Secure each bracket to base with two screws installed through the
bracket holes. See Figure 3-5.
NOTE: Be sure that the bracket holes and the tapped holes in the sub-panel
are aligned.
7. Install #10 screws through each bracket hole to attach the base to the
sub-panel. See Figure 3-6.
Power Budget for The total power consumption of all I/O modules (including the
Series 505 Base programmable controller and RBC) drawing power from a Series 505 power
supply must not exceed 55.0 W from the +5 VDC output and 3.75 W from
the –5 VDC output. Refer to Appendix B for power consumption listings for
the controller and all currently available Series 505 I/O modules and RBCs.
Power Supply See Figure 3-7 for power supply placement in Series 505 bases. The power
Placement in Bases supply must always be installed in the left-most slot.
C
P
P U I I I I I I I I
/ / / / / / / / / /
S R O O O O OO O O
B
C
Installing and Use the steps that follow to install or remove the Series 505 base power
Removing the supply.
Power Supply
1. Disconnect power to the base.
! WARNING Disable all power to the base before installing or removing any
module.
Ensure that all power is disabled before you install or remove any
module.
2. Connect the voltage selector connector to TAB1 for 110 VAC input
power or TAB2 for 220 VAC input power when installing the
PPX:505–6660 power supply only. See Figure 3-8.
TAB2 TAB1
220 V 110 V
5. Carefully push the power supply into the slot until it mates with the
backplane connectors.
6. Tighten top and bottom bezel screw. (Refer also to Figure 3-10.)
To remove the Series 505 Power Supply, simply reverse the procedures used
during installation.
CPU/RBC Location The CPU/RBC must always be installed in the second slot from the left
in a Base (beside the power supply module), as shown in Figure 3-9.
C
P
P U I I I I I I I I
/ / / / / / / / / /
S R O O O O OO O O
B
C
Installing and Refer to Figure 3-10 and follow the steps below to install the CPU.
Removing the CPU
1. Disconnect power to the base.
4. Carefully push the module into the slot until it mates with the back
plane connectors.
To remove the CPU, disconnect the RS-485 cable from the I/O port, if it is
connected, and reverse the installation procedure.
! CAUTION Battery Damage: Do not leave the unit powered down with the
battery switch on for longer than six months.
Doing so could damage the battery to the point it cannot be
recharged.
Return a unit in this condition to the factory for battery
replacement.
Setting CPU Dipswitches are used to set CPU operating parameters. The dipswitches are
Dipswitches located near the front of the CPU behind the bezel door; see Figure 3-11. To
gain access, lower the access door. With the CPU in its (normal) vertical
position, dipswitches pushed to the left are On; dipswitches pushed to the
right are Off.
ON OFF
Port 1
Baud rate
Dipswitch
Port 2
Baud rate
Using Port 1 Switch 2 selects Port 1 as, either a programming port, or a printer port; see
Figure 3-12 for port locations. This port uses a RS-232/RS-423 signaling
protocol and uses a RS-232 pinout arrangement with a RS-423 (+5 V) signal
level extending up to 50 feet. A modem may be used to increase the cable
distance.
• Setting Switch 2 to the left selects Port 1 as a programming port.
• Setting Switch 2 to the right selects Port 1 as a printer port.
Dipswitches
Baud Rate 3 4 5
19200 On On On
9600 Off On On
2400 Off Off On
1200 Off On Off
300 Off Off Off
Dipswitches
Baud Rate 6 7 8
19200 On On On
9600 Off On On
2400 Off Off On
1200 Off On Off
300 Off Off Off
Enabling Battery Switch 9 is used to set the backup battery On or Off; see Figure 3-11.
Backup Moving the switch to the left sets the backup battery On; setting the switch
to the right sets the backup battery Off.
NOTE: The battery in the CPU is rechargeable. The battery LED indicates
the state of the battery backup circuit (when switch 9 is ON) as follows:
RBC Placement in The RBC must always be installed in the second slot from the left (adjacent
Bases to the power supply module) in a remote base.
Dipswitches There are two dipswitches, SW 2 and SW 3, located on the components side
of the RBC. SW 2 (Figure 3-13) is used to set baud rates. SW 3 is a
factory-use-only switch.
Off
SW 2 Front bezel
1 2 3 4
On
Setting RS-232 Port Dipswitch SW 2 is used to set baud rates for the RBC RS-232 port. The
Baud Rates (SW 2) RS-232 port is used to program the controller or to troubleshoot from a
remote I/O base.
See Figure 3-13 for positions of SW 2 on the board; refer to Table 3-4 for
individual dipswitch settings.
Dipswitch
Baud Rate 1 2 3 4
Dipswitch
1 2 3 4
On Off Off Off
Output State You can select the state you want the outputs, controlled by the RBC, to be
Selection set to whenever a communication error occurs. Previous models of the RBC
automatically set all outputs to off (0) when communication is lost. The A
version of RBCs allow you to either freeze the outputs in the state they were
in when communication was lost, or have the outputs set to off (0).
If the RBC fails or the system loses power, the outputs will go off (0)
regardless of the jumper selection.
The RBC has a jumper to select the output state during a communication
loss (Figure 3-14). If the output modules in the remote base have a selection
switch, the freeze selection will override the output module’s selection.
Outputs off
(default)
OFF FRZ
Freeze
OFF FRZ
! WARNING Disable all power to the base before installing or removing the
RBC.
4. Carefully push the RBC into the slot until it mates with the back plane
connectors.
Assigning RBC A base thumbwheel is used to assign a base number to the RBC for system
Base Numbers identification. If you are using more than one RBC, each RBC must be
uniquely numbered. Base numbers are the same as the thumbwheel
number except for base 0, which is reserved for local base assignment and
cannot be used by Series 505 RBCs.
! WARNING Control devices can fail in an unsafe condition that could result in
death or serious injury and/or damage to equipment.
Do not change the base thumbwheel numbers when the system is
operating. This may cause the base to be logged off the system.
When the base is logged off the system, all discrete outputs will be
turned off, analog outputs will be frozen, and word and discrete
inputs will go to 0.
Series 505 RBC The display at the top of the module (see Figure 3-15) indicates the status of
LED Display the Series 505 RBC. Status is displayed in integer format; see Table 3-6 for
definitions of the displays.
Display Definitions
0 RBC Good
1 Self Diagnostics Failure
2 Module Mismatch
3 I/O Communication Time Out
4 RAM Parity Error
5 Standby, No Configuration
6 Address Mismatch
7 Communication Good, No Configuration
8 Watchdog Time Out
C Standby, Configuration
LED Display
Base Thumbwheel
Mixing I/O A mix of I/O modules can be used with one base; you can combine input,
Modules output, word input, word output, and intelligent modules in a single base.
Installing and Use the following steps for installing and removing Series 505 I/O modules
Removing in the base. (Refer to Figure 3-16.)
I/O Modules
1. Disconnect power to the base.
! WARNING Disable all power to the base before installing or removing I/O
modules.
Failure to do so could cause death or serious injury and/or damage
to equipment.
Ensure that all power is disabled before you install or remove I/O
modules.
2. Use specification sheets provided with the modules to install option and
wiring selections for your application.
3. Position the I/O module so the bezel is facing you.
4. Grasp the top and bottom of the I/O module.
5. Carefully push the I/O module into the slot until it mates with the back
plane connectors.
6. Tighten top and bottom bezel screws.
Guidelines To connect the Series 505 power supply, and the Series 500 remote I/O base
to the external power source, follow these guidelines.
• Use 14 AWG solid or stranded wire. If you use stranded wire, the wire
should be twisted and trimmed.
• Insert the wires fully into the terminal block so that the insulation
butts against the block.
Wiring Use the following steps for connecting input power to the power supply. See
Power Supply Figure 4-1.
Model PPX:505–6663: insert chassis ground, DC–, and DC+ line wires
into socket on the power supply. This power supply requires 24 VDC.
Siemens
SIMATIC
TI505
DC POWER GOOD
AC LINE
AC NEUTRAL
GROUND
• Allow for system growth. Provide for attachment of future I/O bases by
routing cable through all possible areas of plant expansion.
• The TI545/TI555 can have a trunk line (attached to its I/O) that
extends up to 3300 feet (1000 m) using RS-485 (twisted pair) cables.
• Do not allow the trunk cable to come into contact with any other
electrical conductor.
V Power lines
V Electric motors and motor starters
V Generators
V Electric welders
Cable Routing The type of routing is usually determined by the type of building in which
Methods the cables are being installed. Any combination of the following may be used
to route the cables: under-floor, in-ceiling, or surface duct.
• Open air systems provide more freedom of access, and allow maximum
system expansion and flexibility.
In-Ceiling Routing For in-ceiling routing, cables are usually supported in troughs or with hooks
and clamps every 10 or 15 feet (3.05 or 4.57 m).
• Flexibility.
• Accessibility of cabling.
Surface Duct Surface ducting is usually installed along baseboards or attached to walls at
Routing desktop height. While surface ducting ordinarily protects cables from both
physical and electro-magnetic (E/M) effects, it usually requires I/O bases to
be positioned near a wall.
NOTE: Consult your cable vendor for proper cable-pulling techniques so that
no kinks occur in the cable during installation.
Mounting the Tap Installation procedures for mounting the tap or terminal block depend upon
or Terminal Block the cable installation technique used. Refer to mounting instructions
provided by the tap or terminal block vendor.
Cabling Options Effective with Firmware Release 3.0 the TI545/TI555 provides two cabling
options for the remote I/O system:
This manual describes the twisted pair media. If you are installing a
Redundant I/O system follow the instructions in the SIMATIC TI505
Redundant I/O Systems User Manual, PPX:505–8125–2.
Trunk and Drop Use RS-485 cabling to install your trunk and drop lines after you have
Lines installed other system hardware items.
Figure 4-2 shows a typical application. The following sections provide
information on cabling the TI545/TI555 controller and RBCs designed for
RS-485 cables. These models are as follows:
Local
Base
Drop Line
T T T
Trunk Lines
Remote Remote
Base Base
Drop Lines
T = Terminal Block
• Terminal lugs.
Mounting the Installation procedures for mounting the terminal block depend upon the
Terminal Block cable installation technique used. Refer to mounting instructions provided
by the terminal block vendor for additional information.
Programmable The cable that connects the programmable controller and RBC to a terminal
Controller and block is called a drop line (Figure 4-2). Belden cable type 9271 and 9182
RBC Drop Lines should be used for all drop lines.
NOTE: If the trunk line is Belden cable type 9182, the drop line must be
Belden cable type 9182.
If the trunk line is Belden cable type 9860 or 9271, the drop line can be
Belden cable type 9271 or 9182.
Preparing Cables Use the following procedures to prepare drop line cables to connect the
(for Drop Lines) programmable controller and RBC to terminal blocks:
1. Strip back 1.50 inches (3.8 cm) of the sleeving on one end of the cable.
There are three wires when the sleeving is stripped back; two wires
have color coded insulation jackets and one is bare.
2. Remove 0.13 in. (0.33 cm) of each color coded insulation jacket to
expose the bare wires.
NOTE: Install the wire without insulation to pin #5 of the 9-pin D-connector.
Install the wires with the color-coded insulation to pins #3 and #8.
It does not matter which wire is installed to pin #3 or #8, but all connectors
must be installed identically. See Figure 4-3 for pin-out information.
5
9 Ground (5)
Signal (8) Signal (3)
6 1
5. Remove 0.13 in. (0.33 cm) of each color-coded insulation to expose the
bare wires.
NOTE: The size of the terminal lug depends on the type of terminal block
used. Consult your vendor for the appropriate terminal lug size.
Connecting a CPU Use the following procedure to connect a drop line cable between the
Drop Line programmable controller and terminal block.
1. Ensure that the cable has been prepared as described on page 4-8.
4. Loosen three terminal screws on the terminal block and install the
cable lug terminals onto the terminal block. See Figure 4-4.
From TI545/TI555
NOTE: The terminating resistor value depends on the type of cable being
used. See Table 4-1.
From CPU
Terminating
Resistor
4. Loosen three terminal screws on the terminal block and install the
cable terminal lugs onto the terminal block. See Figure 4-6.
NOTE: Ensure that the RBC cable wires match with the CPU cable wires at
the terminal block. For example, if a wire at a bottom terminal screw is
blue, the wire directly above it must also be blue.
From CPU
To RBC
Connecting The cable that connects the terminal blocks is called a trunk line. See
Terminal Figure 4-2. The maximum trunk length depends on the cable type and
Block Trunk Lines number of terminal blocks used in your installation. See Table 4-2.
NOTE: Cable types 9860 and 9271 can be mixed on the trunk line, but cable
type 9182 must be used alone.
• Belden cable 9271 is a smaller and more flexible cable suitable for short
trunk lines and all drop line cables.
Characteristics of the cables listed in Table 4-2 are provided in Table 4-3 as
a guide for selecting alternate cables.
Configuration Follow these guidelines when installing RS-485 trunk line cabling.
Requirements
• Measure the maximum length (listed in Table 4-2) from the CPU to the
most distant tap. See Figure 4-7.
P
L
C
*Terminating
*Terminating Resistor
Resistor Maximum Trunk Length
T T T T
T = Terminal Block
*A terminating resistor must be installed on the end terminal blocks. If only one terminal block is
used, a terminating resistor must be installed on that terminal block. See Figure 4-11 for details.
P
L
C
*Terminating
*Terminating Resistor
Resistor Max. Trunk Length Max. Trunk Length
T T T T T T T
T = Terminal Block
*A terminating resistor must be installed on the end terminal blocks. If only one terminal block is
used, a terminating resistor must be installed on that terminal block. See Figure 4-11 for details.
• Short drop lines of 1 m (3.3 feet) do not measurably affect signal quality
and do not have to be counted for the length reduction shown in
Table 4-2.
T T T
... but not like this.
L3
T T
L1 L2
Remote Remote
Base Base
NOTE: For installations with five connections or less that have a cable
length between the controller and the most distant RBC less than 30m
(100 feet), any cable configuration can be used. Always use at least one
termination resistor, even with the simplest installation.
Preparing Trunk Use the following procedures to prepare trunk-line cables for connecting
Line Cables terminal blocks.
1. Strip back 1.50 in. (3.8 cm) of the sleeving on both ends of the cable.
NOTE: You will see three wires when the sleeving is stripped back. Two
wires have color coded insulation jackets and one is bare.
2. Remove 0.13 in. (0.33 cm) of each color-coded insulation jacket (both
ends) to expose the bare wires.
3. Install each wire (both cable ends) onto a terminal lug according to
directions provided by the vendor.
NOTE: The size of the terminal lug depends on the type of terminal block
used. Consult your vendor for the appropriate terminal lug size.
NOTE: Ensure that the wires of the second set of terminal lugs match with
those of the first set of terminal lugs. For example, if a wire at a terminal
screw is blue, the second wire installed with it on the same terminal screw
must also be blue.
Terminating
resistor
4. Install the terminal lugs on the other cable end to the terminal screws
in terminal block B.
NOTE: The terminating resistor value depends on the type of cable being
used; see Table 4-1. A terminating resistor must be installed on the end
terminal blocks.
Overview The CPU can communicate through Port 1 to an operator interface via
dedicated line or dial-up phone modems. Dedicated line operation is a line
used exclusively to connect the modems. Dial-up phone operation connects
the modems by telephone lines. Refer to Figure 4-12 for a typical
configuration.
NOTE: The modems must provide an EIA RS-232C DCE interface to the
TI545/TI555 controller and operator interface and must have a built-in V.32
error correction capability.
Although the TI545 and TI555 controllers support both full- and half-duplex
communications, TISOFT only supports full-duplex communications.
Cable Cable
(2462553–0001) (2462553–0001)
Connect in accordance
with the modem manual
2. Ensure that the CPU controller and modem baud rates are set to the
same value.
NOTE: If the modems are auto-bauding, ensure that the controller baud rate
is set within the baud rate range of the modems.
Dial-up Phone Line Use these procedures to establish communication between modems in a
Operation dial-up phone line configuration.
2. Ensure that the CPU controller and modem baud rates are set to the
same value.
3. Depending on the type of modems being used, the following are three
ways to establish communication between the modems.
• Manually call from one modem station to the other modem station
and then switch on both modems.
Overview The CPU has the capability to send information to a printer through the use
of an SF program or SF subroutine. The printer connects to Port 1 and uses
RS-232 protocol. Cabling for the two available handshaking options are as
follows:
RSD 1
DSR RCV XMT
RTS 6
XMT RCV
Serial Printer
CTS or
DTR
GND Programming
9 Device
5
RTS
CTS
Port 1 (RS-232/423)
RSD 1
DSR
6
XMT RCV
Serial Printer
DTR CTS CTS
9 GND
5
Port 1 (RS-232/423)
Program Storage The CPU offers the option of storing your application program in
non-volatile form. Using Electrically Erasable Programmable Read-Only
Memory (EEPROM), or Erasable Programmable Read-Only Memory
(EPROM [UV-EPROM]), is discussed in the following sections. See Table 5-1
for a description of available EEPROMs and EPROMs.
After your EEPROM has been programmed, it is portable; that is, it can be
used in any other TI545–1102 or TI555 controller.
Using an EEPROM If you install an EEPROM, the CPU allows you to save your current
program without using a separate EEPROM programming device. The
program can be downloaded directly from RAM to a 128K byte or 256K byte
EEPROM by using Auxiliary Function 84. Complete instructions on storing
a program using an EEPROM appear later in this chapter. Refer to
Table 5-2 for EEPROM compatibility.
After storage in the EEPROM, this data is saved even if power is cycled
without a backup battery. However, other data in memory will be lost if you
do not have a backup battery.
NOTE: To help ensure that the data listed above is saved, the total user
memory space to be stored in the EEPROM must not exceed 126K bytes or
254K bytes. If the total user memory (not system memory) space occupied
by these areas is greater than 126K bytes or 254 K bytes, no data is saved.
The error message, OPERATION FAILED, is displayed on the screen if the
user memory exceeds the applicable size when attempting to save the data.
Using an EPROM If your operating program does not change, you can store it permanently on
an EPROM. You can use an EPROM copier to copy your program from an
EEPROM to an EPROM. (The EPROM cannot be programmed in the CPU.)
This is a cost-effective method for creating duplicate copies if you have
additional CPUs running the same program.
EEPROM Functions After your EPROM has been programmed, it is portable and can be used
in any other TI545–1102 or TI555 CPU of compatible or newer software
revision. EPROMS are available from your distributor for EPROM
applications.
When you power up a TI545/TI555 system, the CPU checks the status of the
EEPROM (EPROM) and the battery. A clear (un-programmed) EEPROM
(EPROM) is equivalent to having no EEPROM (EPROM) installed.
Table 5-3 lists mode and memory status (after power up) that result from
various battery and EEPROM (EPROM) conditions.
Conditions Results
Programmed
Battery Controller
EEPROM (or EPROM) Controller Memory
Status Mode
Installed and Selected
Bad or Off No Cleared PROGRM
Cleared, then loaded with
Bad or Off Yes program that is in RUN
EEPROM (EPROM)
Mode prior
Good and
No No change to power
On
loss
Mode prior
Good and
Yes (same program) No change to power
On
loss
Cleared, then loaded with
Good and
Yes (different program) program that is in RUN
On
EEPROM (EPROM)
1. Place the CPU in PROGRAM Mode. You may want to use TISOFT AUX
60 (SAVE PLC ALL) to save program to disk before proceeding.
2. Ensure that switch 9 on the CPU dipswitch is turned On (to the left).
This enables backup battery.
4. Remove the CPU from the base assembly and place component-side up
on a non-conductive surface.
6. Check the pins to make sure that they are all seated properly in the
socket.
8. Re-install the CPU in the base and turn the base power On. Refer to
the Troubleshooting chapter if the EEPROM (EPROM) fails to function
correctly.
To copy a program into your EEPROM, you must first enter the program
into the CPU. Verify that your program is correct, save your program to
your programming unit hard disk, and then continue with the steps listed
below.
1. Ensure that the battery enable dipswitch is On, and that jumper pins
(E18) are strapped to enable programming.
4. Use the Source Toggle option to select RAM as your program source.
6. Use the Copy option to copy the program from RAM to the EEPROM.
NOTE: The CPU does not allow changes to program memory during the
programming of the EEPROM.
The CPU returns to the PROGRAM mode when the copy process is
completed.
9. Use AUX 17 to check the program carefully, while the CPU is in the
PROGRAM mode, before allowing the CPU to control equipment
connected to the I/O.
• Ensure that all EEPROM pins are properly seated in the socket.
• The EEPROM may already have been programmed (and not erased).
Use the AUX Function 84 to erase program data on the EEPROM.
• The size of your user program that is being stored may exceed the size
of the installed EEPROM (126K bytes or 254K bytes).
You can edit the program and data stored in an EEPROM by following the
steps listed below.
1. Using your programming unit and the AUX Function 84 option, select
EEPROM as the program source. This will copy the EEPROM program
to RAM.
Overview This section provides general guidelines for powering up your TI545/TI555
system system.
! WARNING You must be fully informed about safety procedures before you
power up the TI545/TI555 system.
Start-up Follow these procedures when powering up your TI545/TI555 system for the
Procedures first time.
• If any of your installed 505 bases have empty I/O slots, use
filler bezels (part #2587705-8003) and bezel screws
(part #2587705–8001) to cover the openings in the base. This
prevents debris from getting into the system; it also helps prevent
electrostatic discharge and other types of electrical noise
interference.
• Ensure that all modules are securely plugged into the base(s),
connector pins are not bent, and bezel screws are tightened.
• Ensure that all I/O interface cables are properly connected to I/O
interface connectors.
• Ensure that all configured bases are properly connected, there are
no crimps or breaks in the cable, and base addresses are correct.
• If you have not already done so, disable the CPU battery by
turning off switch 9 on the dipswitch. Ensure that a programmed
EEPROM (EPROM) is not installed.
NOTE: If the battery LED does not come on, the battery may be discharged.
The LED should light when fully charged with the switch enabled and
power applied. A blinking light means marginal charge. The battery will be
fully charged after 24 hours of operation.
6. Using your programming device, enter the memory (refer to Table 6-1
and Table 6-2) and I/O configuration.
After all the steps are performed and verified, place the controller in RUN
mode.
Memory The TI545 CPU memory is user configurable. The actual ranges of memory
Configuration types depend upon how the memory has been configured. Ranges for
memory types are listed in Table 6-1.
You can increase the memory allocated to a particular memory type, a block
at a time, up to the maximum listed in Table 6-1. Block sizes vary with the
memory type as shown in Table 6-1.
Some overhead is associated with certain memory types. For example, each
K byte of L-memory uses a total of 3K bytes of system memory. Each
timer/counter uses 5 bytes of system memory. A drum uses 48 bytes.
When you increase L-memory by one block, from 16K bytes to 20K bytes,
system memory reserved for L-memory increases from 48K bytes to
60K bytes. When you increase the number of drums by one block, from 64 to
128, system memory reserved for drums increases from 3K bytes to
6K bytes.
Maximum Up to 192K bytes of configurable system memory are available on the TI545
Configurable CPU. You cannot configure all memory types to their maximum allocation
Memory size simultaneously. For example, if V-memory is configured to 177K bytes,
then S memory cannot be configured to 176K bytes because the 192K bytes
of system memory would be exceeded.
Memory The TI555 CPU memory is user configurable. The actual ranges of memory
Configuration types for each model of the CPU depend upon how the memory has been
configured. Ranges for memory types are listed in Table 6-2.
You can increase the memory allocated to a particular memory type, a block
at a time, up to the maximum listed in Table 6-2. Block sizes vary with the
memory type as shown in Table 6-2.
Some overhead is associated with certain memory types. For example, each
K-byte of L-memory uses a total of 3K bytes of system memory. Each
timer/counter uses 5 bytes of system memory. A drum uses 48 bytes. When
you increase L-memory by one block, from 16K bytes to 20K bytes, system
memory reserved for L-memory increases from 48K bytes to 60K bytes.
When you increase the number of drums by one block, from 64 to 128,
system memory reserved for drums increases from 3K bytes to 6K bytes.
Total Memory
Block Memory Required for
Minimum Maximum
Memory Type Allocation Required Maximum Size
Size Size
Size per Block
–1101 –1102 –1101 –1102
Ladder (L) 1K bytes 3K bytes 1K bytes 123K bytes 635K bytes 369K bytes 1905K bytes
Variable (V) 1K bytes 1K bytes 1K bytes 369K bytes 1905K bytes 369K bytes 1905K bytes
Constant (K) 1K bytes 1K bytes 0K bytes 368K bytes 1904K bytes 368K bytes 1904K bytes
Special (S) 1K bytes 1K bytes 0K bytes 368K bytes 1904K bytes 368K bytes 1904K bytes
User (U) 1K bytes 1K bytes 0K bytes 368K bytes 1904K bytes 368K bytes 1904K bytes
Timer 1024* 5K bytes 1024* 20480 20480 100K bytes 100K bytes
Drum 64* 3K bytes 64* 2304 2304 108K bytes 108K bytes
Shift Register 1024* 1K bytes 1024* 16384 16384 16K bytes 16K bytes
Table Move 1024* 2K bytes 1024* 14336 14336 28K bytes 28K bytes
One Shot 1024* 1K bytes 1024* 32768 32768 32K bytes 32K bytes
*Number per block.
Overview The TI545/TI555 CPU has self-checking and diagnostic capabilities that can
be used for troubleshooting purposes. The diagnostics and self-checks are
accessible through the Auxiliary Function menu on your programming
device.
When you display the Auxiliary Function menu, the following functions are
available for resetting the CPU, initiating diagnostics or displaying
diagnostic information:
Power-up Restart, AUX Function 10 (power-up restart), AUX Function 11 (partial restart), and
Partial Restart, and AUX Function 12 (complete restart) are restart/clear functions. See
Complete Restart Table 7-1 for AUX Function 10, 11, and 12 restart states.
Compare PLC AUX Function 17 (Compare PLC to Disk) compares program disk and
to Disk controller data. It allows you to save and load your VERIFY options to and
from the disk or directory.
Run PLC AUX Function 20 (run PLC diagnostics) initiates the CPU self-checks. The
Diagnostics CPU must be in PROGRAM mode in order to execute self-tests. The CPU
executes the equivalent of an AUX Function 20 at every power up. If any
area fails, a message detailing the failure is displayed. AUX Function 20
makes the following tests.
Display Failed I/O AUX Function 25 (display failed I/O) displays the locations of any failed I/O
modules which are capable of diagnosing and indicating failure. Some
modules, such as word and analog modules, report that they have failed if
the user-supplied voltage is not correct.
Show PLC AUX Function 29 checks the operational status of the CPU and displays the
Diagnostic Cell results. The display provides the information illustrated in Figure 7-1. Field
descriptions are listed below.
• Scan = scan time reported by AUX Function 29; it is the highest scan
time recorded since the last CPU reset, PROGRAM–RUN mode
transition, or user peak resets. Status Word 10 (STW10) contains a
continuously updated report of the scan time.
• Loop Fatal Error = status word 161 (STW161) reports the causes and
indicates the corrective actions.
• Loop Non-fatal Error = status word 162 (STW162) reports the causes
and indicates the corrective actions.
Three LEDs on the CPU are labeled CPU GOOD, RUN, and BATT GOOD.
These LEDs provide CPU status as shown in Table 7-2.
NOTE: Since the CPU receives power from the base power supply module,
the power supply must be on and functioning correctly to turn the LEDs on.
Obviously, if the base power supply module is defective or Off, all CPU
indicators will be Off.
NOTE: The situation may occur when the battery dipswitch is on and the
battery is marginally charged, i.e., the battery is okay when not under load,
but is low when under load. In this case, the battery test is still done hourly,
but the battery LED flashes. This indicates that the battery is charging (or
discharging, if it was good). While in this state, a power-up restart following
a brief power outage will probably result in a battery-good restart.
CPU Fatal Error A fatal error is indicated when both the following conditions are present.
Indications
• CPU GOOD LED is not lighted.
Causes of CPU The CPU enters a fatal error condition and ceases operation if one of the
Fatal Errors problems listed below occurs. AUX Function 20 or 29 displays the problem
that caused the CPU to enter the fatal error condition.
Controller When a fatal error occurs, the CPU attempts the following actions.
Responses to Fatal
Errors • The CPU GOOD LED is turned off.
• I/O ports are disabled, discrete outputs are turned off, and word
outputs are held in their last valid state.
Steps to Attempt to clear the fatal error by following the steps listed below. When the
Clear Fatal Errors CPU GOOD LED turns on, the fatal error has been cleared.
NOTE: Always execute AUX Function 29 and make a list of the errors before
attempting to clear them. If you clear errors before listing them, it will be
impossible to determine what errors occurred and difficult to identify the
problem that caused them.
3. If the fatal error persists, ensure that the battery backup is enabled,
power cycle the CPU, then reattempt step 2 and execute the AUX
Function 10 — CPU power-up restart.
4. If you have been unable to clear the fatal error to this point, you must
re-initialize the CPU. Disable the battery backup (turn off switch 9 of
the dipswitch) and cycle power to the CPU (or execute AUX
Function 10). This clears the CPU memory.
5. If the CPU GOOD LED comes on, restore the battery backup by
turning on switch 9 of the dipswitch. You must now use your
programming unit to restore your program.
6. If the CPU GOOD LED does not turn on at this time, your CPU may
have a hardware failure.
Calling for Before calling for assistance, be sure that you have the following
Assistance information available.
• List of fatal and non-fatal errors
• Model number
Definitions of non-fatal errors are listed in this section along with suggested
courses of action.
• Scan overrun — The CPU scan time is not sufficient to execute the user
program.
• I/O table does not agree with modules installed — The configured I/O
does not match what is installed in the base. Check the I/O
configuration and/or run AUX 25.
NOTE: Series 505 I/O modules with date codes before January 1988 cannot
be used with a TI545/TI555 CPU. See Appendix C for details.
Status words supported by the CPU are described in detail in the SIMATIC
TI505 Programming Reference Manual.
EEPROMs and EPROMs are generally not serviceable and must be replaced
if they become defective. Before replacement however, review material in
Chapter 5, Using an EEPROM or EPROM, and perform the following
checks.
• Ensure that all EEPROM (EPROM) pins are properly seated in the
socket.
• The EEPROM may already have been programmed (and not erased).
Use the AUX Function 84 to erase program data on the EEPROM.
• The size of your user program (L, K, S, and U memories) that is being
stored may exceed the size of the (E)EPROM (126 or 254K bytes).
NOTE: To help ensure that the user program will be saved, the total user
memory space occupied by the user program must not exceed the size of the
(E)EPROM minus 2K bytes (126K or 254K bytes). If the total user memory
(not system memory) space occupied by these user programs is greater than
this value, none of the data is saved and the error message, OPERATION
FAILED, is displayed on the screen when attempting to save the data.
1. Ensure that the power budget has not been exceeded and that the
module is properly installed.
2. After making sure the backup battery is on (so the program will not be
lost), disable all power to the system for at least 90 seconds.
! WARNING To minimize risk of shock hazard, always turn off the controller
before removing or installing a CPU or I/O module.
Failure to do so could cause death or serious injury and/or damage
to equipment.
Ensure that controller power is turned off before removing or
installing a CPU or I/O module.
5. Remove the power supply module from the base. This step is not
required for the PPX:505–6663 power supply.
a. Ensure that the jumper in the back of the power supply module is
set to the correct line voltage.
b. If the voltage has been set incorrectly, wait at least one minute
before touching the jumper. Then move the jumper to the
appropriate quick-connect pin.
6. Ensure that the wires attached to the terminal screws on the bezel are
secure and that the user-supplied power source is functional.
7. Verify that the fuse (located on the bezel) has not opened. Follow steps
8. through 12. to replace the fuse, if necessary, with the appropriate
fuse. See Figure 7-2 .
! WARNING Before you replace a fuse, disable all power to the base .
Failure to do so could cause death or serious injury and/or damage
to equipment.
Disable all power to the base before replacing a fuse.
12. Place the fuse cap in socket and turn it clockwise with a standard
screwdriver.
Front Bezel
Fuse
Fuse Cap
13. Re-install the power supply and apply power to the system.
Using Digital or To locate problems with RS-485 communication links, use a digital or analog
Analog Meter meter capable of measuring resistance between 0 and 150 ohms.
2. Disconnect the CPU and all RBCs from the cable by removing the 9-pin
D-connector.
3. Measure the resistance from either isolated wire to the other isolated
wire (line-to-line) and record this value.
4. Measure the resistance from one line to the shield wire and record this
value.
5. Measure the resistance from the other line to the shield wire and
record this value.
Resistance Below Line-to-line resistance that is below the minimum specified in Table 7-3
Minimum may be caused by the following:
Resistance Above Line-to-line resistance that is above the maximum specified in Table 7-3
Maximum may be caused by the following:
• The cable is open between the point of measurement and one or both of
the termination resistors.
Order the following spare parts as needed from your supplier or Siemens
Industrial Automation:
PPX:545–1102 Controller
PPX:555–1101 Controller
PPX:555–1102 Controller
Models
PPX:505–6851 Remote Base Controller
PPX:505–6660A Power Supply
PPX:505–6663 Power Supply
Storage Temperature –40° to 70°C; –40° to 158°F
Operating Temperature 0° to 60°C; 32° to 140°F
Relative Humidity 5% to 95% noncondensing
Vibration
Sinusoidal: IEC 68-2-6, Test Fc;
0.15 mm peak-to-peak, 10–57 Hz;
1.0 g, 57–150 Hz
Series 505 products have been developed with consideration of the draft
standard for programmable controllers as described in the proposed
standard of the International Electrotechnical Commission Committee
(IEC-65A/WG6, Part 2).
Special
Immediate Maximum DC Power
Model Number Description Function
I/O Consumption (Watts)
Module
PPX:505–48081 220 VAC Output (8 point) – n 5.0 –
PPX:505–48161 220 VAC Output (16 point) – n 5.0 –
PPX:505–48321 220 VAC Output (32 point) – n 5.0 –
PPX:505–49081 Relay Output Form C (8 point) – n 2.5 –
PPX:505–49161 Relay Output Form A (16 point) – n 2.5 –
PPX:505–49321 Relay Output Form A (32 point) – n 2.5 –
PPX:505–5100 TurboPlastic n 7.0 0
PPX:505–5103 TurboParison n 7.0 0
PPX:505–5184 MODNIM (Modbus NIM) n 8.0 –
PPX:505–5190 6MTCC: TI505-to-6MT Interface n 4.0 –
PPX:505–54171 Relay Output, 115 VDC (16 point) n 3.0 –
PPX:505–60101 Input Simulator n 2.0 –
PPX:505–60111 Output Simulator n 2.5 –
PPX:505–6108 Analog Input n3 4.0 –
PPX:505–6108A Analog Input n3 4.0 –
PPX:505–6202 Analog Output (2 point) n3 2.5 –
PPX:505–6204 Analog Output (4 point) n3 5.0 –
PPX:505–6208 Analog Output (8 point) n3 5.0 –
PPX:505–6208A Analog Output (8 point) n3 2.0 –
PPX:505–6308 Word Input n3 4.0 –
PPX:505–6408 Word Output n3 5.0 –
1 Modules that are affected by date code restrictions. See Appendix C.
2 Interrupt mode operation requires TI545 with Firmware Release 2.1 or later, or TI555 with Firmware Release 1.1 or later.
3 Supported by TI555 Release 3.0 or TI545–1102 Release 3.0.
For any module not listed here, see the manual for that module.
I/O Modules not Unmodified Series 505 discrete I/O modules manufactured prior to
Compatible with January, 1988 are unable to report module status and, therefore, cannot be
TI545/TI555 CPUs recognized by the TI545/TI555 CPU (that is, inputs are not read and
outputs are not written). Series 505 discrete I/O modules manufactured in
January, 1988 or later and those manufactured prior to this date that have
been modified contain the status reporting mechanism and are compatible
with the TI545/TI555 CPU.
The following modules are fully compatible with the TI545/TI555 CPU,
regardless of the manufacturing date.
• All Series 500 I/O and all non-discrete Series 505 I/O, such as analog
modules (except for the High Speed Counter, as described on page C-3)
NOTE: Units manufactured prior to January, 1988 that have been modified
have the letter G immediately following the serial number.
Before you install Series 505 discrete modules into a TI545/TI555 system,
check the serial number of each module to ensure it is compatible with the
TI545/TI555 CPU.
Series 505 High High Speed Counter modules (PPX:505-7002) manufactured prior to May
Speed Counter 1990 will not operate properly in a TI545/TI555 controller’s local base
configuration. If a High Speed Counter is placed in a TI545/TI555
controller’s local base configuration, the WX inputs will intermittently set to
FFs, which could cause improper operation.
NOTE: High Speed Counter modules manufactured prior to May 1990 that
have been modified for TI545/TI555 controller’s local base compatibility
have the letter A immediately following the serial number.
Before you install Series 505 High Speed Counter modules into a
TI545/TI555 local base, check the serial number of each module to ensure
that it is compatible with the TI545/TI555 local base.
! WARNING Do not use an unmodified Series 505 High Speed Counter module
manufactured prior to May 1990 in a TI545/TI555 controller’s local
base.
In a Series 505 High Speed Counter, WX inputs may change to FFs
that could change the High Speed Counter outputs to an unsafe
condition. This could result in death or serious injury and/or
damage to equipment.
Refer to the Safety Considerations Guidelines, part no.
2588015-0003 (shipped with each TI545/TI555 controller), for details.
Follow Siemens Industrial Automation, Inc.’s recommended safety
installation guidelines.
Determining the The fifth through the eighth characters of the serial number determines the
Manufacturing manufacturing date. Figure C-1 shows how to read the serial numbers.
Date
Serial Number
FF DD YY MM SSSSS C X
Month of Manufacture
Device Indicator
Family Indicator
Examples The following examples demonstrate how to read the serial number on the
modules.
86ML8712020175_ This module was manufactured in December (12) of 1987 (87). This unit is
not compatible with the TI545/TI555 controller because it was
manufactured prior to January, 1988 and the letter G (designating that a
modification occurred) does not appear at the end of the serial number.
86ML8712020175G This module was manufactured in December (12) of 1987 (87). This unit is
compatible with the TI545/TI555 controller because it was manufactured
prior to January, 1988 and the letter G (designating that a modification
occurred) appears at the end of the serial number.
86ML8801041324_ This module was manufactured in January (01) of 1988 (88). This unit is
compatible with the TI545/TI555 controller because it was manufactured in
January, 1988. (The letter G is not required if the module was
manufactured in January, 1988 or later.)
You can upgrade an existing Series 500 system, by replacing the controller
with a TI545–1102 or a TI555. The following Series 500 systems can be
upgraded:
You must also convert each of the existing series 500 bases to a series 500
remote base by replacing the existing programmable controller (and I/O
channel controller, if present) or the existing distributed base controller
with a PPX:500–5114A (RS-485) Remote Base Controller (RBC). If the base
contains a TI520, TI530, or a PPX:500–2103 distributed base controller you
must install an adapter base and modular power supply before you can
install the RBC in the Series 500 base.
• The Series 500 physical base assembly is composed of one or two logical
bases. A logical base is defined as a contiguous group of eight I/O slots.
For example, the 16-slot physical base assembly has two 8-slot logical
bases. Each logical base has a unique base address.
• To reduce down time for your process, plan to install the new RS-485
twin axial cables for the I/O trunkline before upgrading the hardware
for each I/O base.
Install RS-485 Twin Refer to Chapter 4 “Cabling and Wiring the System,” for information about
Axial Cabling installing RS-485 twin axial cabling for the I/O trunk line. To reduce the
down time for your process, install the cabling before installing new
hardware in each I/O base.
Check Base to be Determine the number of I/O slots in the base to be upgraded. For some
Upgraded bases, a PPX:500–5840 adapter base must be installed. The 14-slot, 12-slot
and 6-slot bases (Upgrade Path A) do not require an adapter base. For a
16-slot or 8-slot base (Upgrade Path B), you need to install an adapter base.
Upgrading 14-Slot, For 14-slot, 12-slot and 6-slot bases follow these steps (Upgrade Path A):
12-Slot, 6-Slot
Bases 1. Remove the existing controlling device(s): the controller and IOCC (if
an IOCC is present), or the DBC.
2. If the power supply is in slot B, move it to slot A of the I/O base. This
makes slot B of the I/O base available for an I/O module. In your I/O
configuration, the slot that was previously slot #1 becomes slot #2.
Upgrading 16-Slot For 16-slot and 8-slot bases follow these steps (Upgrade Path B):
and 8-Slot Bases
1. Remove the existing controlling device(s): the controller and IOCC (if
an IOCC is present), or the DBC.
Finish Upgrade with These steps finish the upgrade for both Upgrade Paths A and B.
these Steps
1. Install an RBC (PPX:500–5114A) in the controller slot. See Section D.5
for information about installing the RBC.
2. Set the base address (1–15) using the thumbwheel on the RBC. Base
number 0 is reserved for the local base and cannot be used for an RBC.
3. Connect the twin axial cable to the RS-485 port on the RBC(s) and to
the I/O port of the TI545/TI555.
4. Use APT or TISOFT to set the I/O configuration for the upgrade.
TI545
P/S or Series 505 I/O
TI555 4, 8, or 16 slots
Local I/O
NOTE: Note that the TI545/TI555 cannot directly replace an hot backup
HBU configuration.
1. If the series 500 remote I/O installation consists of more than one
twin-axial (RS-485) remote I/O channel, combine these channels into a
single remote I/O channel. Refer to Section 4, “Cabling and Wiring the
System,” for information about installation of a twin axial remote I/O
trunk line.
2. Renumber your bases so that no two bases have the same number and
so that base number 0 is not used.
Update time for a special function module is significantly faster when you
install the module in the local base, versus a remote base. You can improve
SF module performance, and scan performance, by replacing the Series 500
SF modules with Series 505 SF modules and installing them in the
TI545/TI555 local base.
1 2 3
Upgrade Path
TI545
P/S or Series 505 I/O
TI555 4, 8, or 16 slots
Local I/O
NOTE: Note that the TI545/TI555 cannot directly replace an hot backup
HBU configuration.
1. If the series 500 remote I/O installation consists of more than one
coaxial (RF) remote I/O channel, combine these channels into a single
remote I/O channel. Refer to your existing controller’s documentation
for information about installation of a coaxial remote I/O channel.
2. Renumber your bases so that no two bases have the same number and
so that base number 0 is not used.
4. Connect the resulting I/O channel to the TI545/TI555 system using the
PPX:505–6860 RF to RS-485 converter.
Update time for a special function module is significantly faster when you
install the module in the local base, versus a remote base. You can improve
SF module performance, and scan performance, by replacing the Series 500
SF modules with Series 505 SF modules and installing them in the
TI545/TI555 local base.
1 2 3
Upgrade Path
5
0
TI545
5 Series 505 I/O
P/S or –
TI555 4, 8, or 16 slots
6
8 Local I/O
6
0
Output State With the PPX:500–5114A RBC you can select the state of the outputs
Selection whenever a communication error occurs. Previous models of the RBC
automatically set all outputs to off (0) when communication is lost. You
must configure the RBC to freeze outputs in the state they were in when
communication was lost, or to have them set to off (0).
The Series 500 output modules in the remote base have a selection switch
for the state of the outputs during a communication loss (Figure D-4). If the
output modules in the remote base have a selection switch, the freeze
selection will override the output module’s selection.
NOTE: If the RBC fails or the system loses power, the outputs will go off (0)
regardless of the jumper selection.
FREEZE
OFF
(Factory Set)
3. Carefully push the RBC into the slot until it mates with the back plane
connectors.
Power Supply
Setting Baud Rates The RBC is equipped with a RS-232 port to program the TI545/TI555 CPU
or, to troubleshoot from a remote I/O base. A baud rate thumbwheel (see
Figure D-6) is used to set the baud rate for this port.
LED Display
Base Thumbwheel
Thumbwheel Baud
Number Rate
Baud Rate Thumbwheel
0 . . . . . . . . 9600
1 . . . . . . . . 2400
2 . . . . . . . . 1200
3 . . . . . . . . . 300
Remote
Base
4 . . . . . . . . 9600
Controller 5 . . . . . . . . 2400
6 . . . . . . . . 1200
7 . . . . . . . . . 300
8 . . . . . . . . 9600
9 . . . . . . . . 2400
10 . . . . . . . . 1200
11 . . . . . . . . . 300
12 . . . . . . . . 9600
13 . . . . . . . . 2400
14 . . . . . . . . 1200
15 . . . . . . . . . 300
Figure D-6 Series 500 Remote Base Controller and Baud Rate Settings
Assigning Base The base thumbwheel (Figure D-6) is used to assign a base number to the
Numbers RBC for system identification. If you are using more than one RBC, each
RBC must be uniquely numbered. Refer to Table D-1 for assigning base
numbers. Base number 0 is reserved for the TI545/TI555 and must not be
assigned to the RBC.
Thumbwheel Thumbwheel
Base Number Base Number
Number Number
Do Not Use 0* 8 8
1 1 9 9
2 2 10 10
3 3 11 11
4 4 12 12
5 5 13 13
6 6 14 14
7 7 15 15
Notes: *Base 0 is reserved on the model TI545/TI555 controller for local base
assignment. Therefore, do not select number 0 on the Series 500 RBC.
Series 500 RBC The display at the top of the module (refer to Table D-2) indicates the status
LED Display of the Series 500 RBC. Status is displayed in integer format; see Table D-2
for definitions of the displays.
Display Definitions
0 RBC Good
1 Self Diagnostics Failure
2 Module Mismatch
3 I/O Communication Time Out
4 RAM Parity Error
5 Not used
6 Not used
7 Communication Good, Not Configured
8 Watchdog Timer Expired
E
C EEPROM
errors and corrections, 5-9
Cable
installing, 5-6
alternate cables, 4-13
list of functions, 5-4
characteristics, 4-13
overview, 5-2
connecting drop line, 4-9, 4-12, 4-14, 4-16
program
connecting modems, overview, 4-18
copying, 5-8
connecting to terminal block, 4-8, 4-10
editing, 5-10
installing drop lines, 4-8, 4-10
errors, 5-9
overview, 4-6
resistance of line-to-line, 7-15 Electrical noise
routing guidelines, 4-4 avoiding, 2-8
RS-485 correcting, 2-9
connecting drop line, 4-8, 4-10 isolating from, 2-11
Index-1
Emergency, stop switch, 2-4 controller compatibility, C-2
Enclosure, planning for PLC, 2-6 local, overview, 1-6
mismatches, troubleshooting, 7-4
EPROM remote, overview, 1-6
installing, 5-6 serial number, C-4
overview, 5-3 series 505
EPROM/EEPROM installing and removing, 3-21
compatability, 5-2 mixing, 3-21
troubleshooting, 7-11 troubleshooting, 7-4
using, 5-2 I/O port, description, 1-7
Errors Inch switch, location, 2-5
correcting fatal errors, 7-7
troubleshooting fatal, 7-7 Installing
EEPROM and EPROM, 5-6
planning for, 2-2
F series 500 RBC
in adapters, D-11
Fatal errors, steps to clear, 7-8 in bases, D-11
series 505, 3-4
Features, 1-2 power supply, 3-9
Fuse series 505 RBC, 3-19
guidelines for fuses/circuit breakers, 2-7 Installing and removing
series 505, replacing in power supply, 7-12
series 500 RBC, D-11
series 505
I/O modules, 3-21
G power supply, 3-9
RBC, 3-19
Grounding
cabinet or rack, 2-14
connections, 2-14
controller, 2-14 J
earth, 2-13
planning for, 2-13 Jog switch, location, 2-5
sample connection, 2-15
L
H
Local area networks, supported, 1-5
H1 support, 1-5
Hardware, description, 1-6
Hot backup, D-8 M
Memory, configuration, list of types, 6-4, 6-5
I Modem
connecting, overview, 4-18
I/O modules dedicated line operation, 4-18, 4-19
compatibility, determing of module, C-2 dial-up phone line, 4-19
Index-2
setting baud rate, 3-16
N
RBE, support, 1-2
Noise
avoiding electrical, 2-8 Restart
isolating from, 2-11 list of auxiliary functions, 7-3–7-16
snubbing, contact noise, 2-9 using auxiliary functions, 7-2
RF to RS-485 converter, D-8
P
Power needs, planning for, 2-2
S
Power supply Safety
connecting input, 4-2 guidelines, 2-3
series 505, 1-7 inch switch, 2-5
installing, 3-9 jog switch, 2-5
installing and removing, 3-9 operator safety switches, 2-4
power consumption, 3-9 Series 500, base numbers, assigning, D-12
replacing fuse, 7-12
troubleshooting, 7-12 Series 500 RBC
installing and removing, D-11
Power-up LED messages, D-13
memory and mode status, 5-5
placing in bases, D-11
procedures, 6-2
setting baud rates, D-12
Printer
Series 505
connecting, 4-20
base
handshaking, 4-20
installing controller, 3-11–3-15
overview, 4-20
models available, 3-3
Program panel mounting, 3-5
copying into EEPROM, 5-8 models available, 3-3
editing in EEPROM, 5-10 rack mounting, 3-4
software, 1-8 models available, 3-3
storage in EEPROM, 1-8 connecting base, 3-3
storage in EPROM, 1-8 dipswitch, ports, 3-14
environmental specifications, A-2
general specifications, A-3
I/O modules, installing and removing, 3-21
R installing, flowchart, 3-2
module power requirements, B-2
RBC
power supply
series 500
installing and removing, 3-9
assigning base numbers, D-12
replacing fuse, 7-12
installing and removing, D-11
specifications, power supply electrical, A-4
placing in bases, D-11
setting baud rate, D-12 Series 505 RBC
series 505 base, installing, 3-19
assigning base numbers, 3-19 base numbers, assigning, 3-19
description, 3-3 dipswitch (factory), 3-17
installing and removing, 3-19 installing and removing, 3-19
installing in base, 3-19 LED messages, 3-20
Index-3
Spare parts, list of, 7-16 Troubleshooting
Specifications, series 505 cable, RS-485, 7-14
general, A-3 compare disk to PLC, 7-4
power supply electrical, A-4 EPROM/EEPROM, 7-11
system specifications, A-2 fatal errors, 7-7
non-fatal errors, list of, 7-9
Start-up, procedures, 6-2 reading LEDs, 7-6
Status words, using in troubleshooting, 7-10 restart, 7-2
series 505, power supply, 7-12
Switch, emergency stop, 2-4
using auxiliary functions, 7-2
Switches using status words, 7-10
inch, 2-5
jog, 2-5
safety, 2-4
U
Upgrading
T series 500 system, D-3–D-5
TI560/TI565 system, D-6–D-7, D-8–D-9
Temperature, planning for PLC, 2-6
Thumbwheels
series 500 RBC
assigning base numbers, D-12
W
setting baud rate, D-12 Wiring
series 505 RBC, assigning base numbers, 3-19 connecting input power, 4-2
TIWAY, support, 1-5 planning for installation, 2-12
Index-4
SIMATIC and SINEC are trademarks of Siemens AG.
Series 505, Series 500, APT, CVU100, CVU1000, CVU10000, Peerlink, TISOFT, TIWAY, PCS, 386/ATM, and 7MT are trademarks of
Siemens Industrial Automation, Inc.
IBM and AT are registered trademarks of International Business Machines Incorporated.
MS-DOS is a registered trademark of Microsoft corporation.
Belden is a registered trademark of Cooper Industries, Inc.
TI505, TI520, TI520C, TI530, TI530C, TI530T, TI545, TI555, TI560, TI565, TI560T, and TI565P are trademarks of Texas Instruments
Incorporated.
CSA is a registered trademark of the Canadian Standards Association.
Customer Registration
We would like to know what you think about our user manuals so that we can serve you better.
How would you rate the quality of our manuals?
Would you be interested in giving us more detailed comments about our manuals?
Your Name:
Title:
Telephone Number: ( )
Company Name:
Company Address:
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
FOLD