Example AHU Advanced
Example AHU Advanced
Example AHU Advanced
01/2009
2 (8)
INDEX
1 2 INTRODUCTION .................................................................................................................................................. 3 AIR HANDLING UNIT EXAMPLE ........................................................................................................................ 3 2.1 CONTROL DIAGRAM ...................................................................................................................... 3 2.2 FUNCTIONAL DESCRIPTION .......................................................................................................... 4 SOLUTION WITH LONIX TECHNOLOGIES ........................................................................................................ 5 REQUIRED DEVICES .......................................................................................................................................... 8
3 4
www.lonix.com
01/2009
3 (8)
1 Introduction
This document presents an implementation example for an air handling unit using Lonix technologies. The controls are done using Lonix Modules, and system design and configuration utilizes the Lonix Project Creation Tool (PCT).
Figure 1. Control diagram of an advanced air handling unit for office buildings The air handling unit includes a heat recovery unit, pre- and postheaters and a cooling unit for temperature and humidity control. Supply air fan TF1.1 and exhaust air fan PF1.1 are controlled with variable frequency drives SC10 and SC30. In addition, the system is equipped with several dampers, filters and a separate device TCZA1 for frost protection.
www.lonix.com
01/2009
4 (8)
www.lonix.com
01/2009
5 (8)
Figure 2. Temperature control of the air handling unit When controlling the temperature several issues (stated in previous chapter) need to be considered. In the above picture the three uppermost PID controllers are for temperature control. It is implemented using cascade control: The first PID (Temp Constant Cascade) is responsible for supplying a correct set point that varies with outdoor temperature for the two constant controllers (Temp Constant Control Drying and Temp Constant Control). Only one of the constant controllers is permitted to control the process at any one time. The other one takes care of the temperature when the exhaust air humidity is below a certain threshold and no drying is needed, the other one functions when drying is needed. The second lowest PID object (SC50 High ON) forces the heat recovery wheel to rotate on full speed when the exhaust air temperature is higher than outdoor temperature. The lowest PID (SC50 Speed Reduction Control) is responsible for reducing the rotation speed of the heat recovery wheel when the pressure difference over it gets too high i.e. it starts to frost. A scheduler rotates the heat recovery wheel at certain intervals to make sure it stays clean even if it is not used for a longer period of time.
www.lonix.com
01/2009
6 (8)
The proper sequence for adjusting the HRU speed and preheating, postheating and cooling valve drives is obtained by configuring the operational ranges of the corresponding AO objects.
Figure 3. Exhaust and supply air fan speed control The exhaust and supply air fans are controlled according to two pressure measurements (PE10 and PE30) that should be kept constant. In addition, both fans should be either on or off at the same time. Also the two dampers FG01 and FG30 work in conjunction with the fans. The power for the variable frequency drives SC10 and SC30 is supplied through separate relays so they can be shut down completely when necessary. Both variable frequency drives are capable of supplying their current run status. These DI objects (SC10 Run Status, SC30 Run Status) make a comparison between the variable frequency drives actual and wanted states and cause an alarm if necessary.
www.lonix.com
01/2009
7 (8)
Figure 4. Alarms, stops and scheduling of the air handling unit The air handling unit runs according to a schedule. The same scheduler also controls the dampers FG111, FG112, FG131 and FG132 that regulate the air flow to different sections of the building. System shutdown is achieved by binding all the alarms to the same module. This main alarm module should have no other alarming points. A DO object (Alarm Stop) residing in that module is configured as Alarm Priority Control and whenever an alarm with a high enough priority is generated, the DO object shuts down the power (with relays SC10 OnOff, SC30 OnOff) from the variable frequency drives SC10 and SC30. The alarm is acknowledged with a separate push button.
www.lonix.com
01/2009
8 (8)
4 Required devices
This chapter lists the required devices for the example implementation. Table 1. I/O objects I/O type DI DO AI AO PID TSM Switch Amount 9 7 18 11 8 2
As you can see in the above table, you will need six (6) units of Lonix Multimodules 2242P and one (1) Time Scheduler Module TSM. Table 2. Lonix Modules Module Type Lonix Multimodule 2242P Lonix Time Scheduler Module TSM Description 2 DI, 2 DO, 4 AI, 2 AO, 2 PID Time schedules Units 6 1
The following table lists the different sensors, transducers and actuators needed in the example implementation. Table 3. Sensors and actuators Device PDIE01, PDIE02 PDIE30, PDIE50 PE10, PE30 TE45 TE02, TE04, TE05, TE31 TE10+ME10, TE30+ME30 TE52, TE53 TCZA1 TV45, TV46 (2-way valve) TV52 (3-way valve) TF1/SC10, PF1/SC30 HRU/SC50 FG01, FG30 FG111,FG112, FG131, FG132 Details 0500 Pa 0500 Pa 0500 Pa -2080 C -20105 C -4085 0100 % C, -2080 C Model LX-PD-A-LCD LX-PD-A-LCD LX-PD-A-LCD e.g. TEPK Pt1000 LX-TE-D450 LX-RHTE-D-2 e.g. TEPK Pt1000 e.g. JVS 24 e.g. VUD065F300 + AVM234S F132 e.g. BUE065F300 + AVM234S F132 e.g. Mitsubishi E500 e.g. Mitsubishi E500 e.g. Belimo GM24A e.g. Belimo SM24A
www.lonix.com
01/2009