100% found this document useful (1 vote)
182 views2 pages

IA Consumption

This document calculates the instrument air and compressor capacity needs for a plant. It estimates instrument air consumption for control valves and on-off valves. The total instrument air demand is calculated as 551 Nm3/hr. An additional 10% is added for refrigeration systems. The total demand is increased by 30% for a margin. Utility air is 20% of instrument air demand. The compressor capacity is 150% of the total instrument air demand, which is calculated as 1200 Nm3/hr.

Uploaded by

RDMP U325
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
182 views2 pages

IA Consumption

This document calculates the instrument air and compressor capacity needs for a plant. It estimates instrument air consumption for control valves and on-off valves. The total instrument air demand is calculated as 551 Nm3/hr. An additional 10% is added for refrigeration systems. The total demand is increased by 30% for a margin. Utility air is 20% of instrument air demand. The compressor capacity is 150% of the total instrument air demand, which is calculated as 1200 Nm3/hr.

Uploaded by

RDMP U325
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Basis assumption

1. IA consumption for each control valve is 1 scfm (continuous, as per API 550)
2. IA consumption for on-off valve: < 8" = 1.15 scfm, 10" > = 1.51 scfm
3. IA consumption for on-off is intermitent. It is assumed as 10% from total IA consumption for on-off valve.
4. Utility air demand is based on 20% from total IA demand. Utility air demand already include blowing requirement
5. Compressor capacity is based on 150% from total instrument air demand

Demand Calculation
Instrument Air
Margin Consumption (Nm3/hr)
No. Item Description
1 On-off Valve at natural gas line to Boiler & DEG 0.2
2 OSBL Area Packaging Area 21
3 ISBL Area Physical Refining 170
4 ISBL Area Dry Fractination 360
Total Demand 551.2
Instrument Air for Refrigerant System 10% 55.12
Instrument Air Demand+Refrig System 606.32
Design Margin 30% 181.896
Total Instrument Air Demand 788.216

Utility Air Margin Consumption (Nm3/hr)


1 Total IA Demand 788.216
2 Utililty air demand 20% 157.6432
Total Instrument Air Demand 945.8592

Compressor Capacity
1 IA Demand 788.216
2 Margin 50% 394.108
3 Air Compressor Capacity 1182.324
Selected capacity air compressor 1200