1. IA consumption for each control valve is 1 scfm (continuous, as per API 550)
2. IA consumption for on-off valve: < 8" = 1.15 scfm, 10" > = 1.51 scfm
3. IA consumption for on-off is intermitent. It is assumed as 10% from total IA consumption for on-off valve.
4. Utility air demand is based on 20% from total IA demand. Utility air demand already include blowing requirement
5. Compressor capacity is based on 150% from total instrument air demand
Demand Calculation
Instrument Air
Margin Consumption (Nm3/hr)
No. Item Description
1 On-off Valve at natural gas line to Boiler & DEG 0.2
2 OSBL Area Packaging Area 21
3 ISBL Area Physical Refining 170
4 ISBL Area Dry Fractination 360
Total Demand 551.2
Instrument Air for Refrigerant System 10% 55.12
Instrument Air Demand+Refrig System 606.32
Design Margin 30% 181.896
Total Instrument Air Demand 788.216
Compressor Capacity
1 IA Demand 788.216
2 Margin 50% 394.108
3 Air Compressor Capacity 1182.324
Selected capacity air compressor 1200