NEC Table 430.32-Overload
NEC Table 430.32-Overload
NEC Table 430.32-Overload
32(A)(1)
Separate Overload Device for Continuous-Duty Motors
A separate overload device that is responsive to motor current. This device shall be
selected to trip or shall be rated at no more than the following percent of the motor
nameplate full-load current rating:
Motors with a marked service factor (SF) 1.15 or greater 125%
o
Motors with a marked temperature rise 40 C or less 125%
All other motors 115%