Ax 411
Ax 411
Ax 411
Model AX411
Dual Input Conductivity Analyzer
ABB
The Company BS EN ISO 9001:1994
We are an established world force in the design and manufacture of instrumentation for industrial
D
RE
GI
E
STER
process control, flow measurement, gas and liquid analysis and environmental applications.
Cert. No. Q05907
As a part of ABB, a world leader in process automation technology, we offer customers
application expertise, service and support worldwide.
EN 29001 (ISO 9001)
We are committed to teamwork, high quality manufacturing, advanced technology and unrivalled
service and support.
Lenno, Italy – Cert. No. 9/90A
The quality, accuracy and performance of the Company’s products result from over 100 years
experience, combined with a continuous program of innovative design and development to
incorporate the latest technology.
The NAMAS Calibration Laboratory No. 0255 is just one of the ten flow calibration plants
operated by the Company, and is indicative of our dedication to quality Stonehouse, U.K.
and accuracy.
0255
Use of Instructions
Warning. ✶ Note.
An instruction that draws attention to the risk of injury or Clarification of an instruction or additional information.
death.
Caution. Information.
An instruction that draws attention to the risk of damage to Further reference for more detailed information or technical
the product, process or surroundings. details.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it
must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process
system performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for
any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of the
Marketing Communications Department.
7 CALIBRATION ............................................................ 39
4 SETUP ........................................................................ 10
7.1 Equipment Required ......................................... 39
4.1 Sensor Calibration ............................................ 10
7.2 Preparation ....................................................... 39
7.3 Factory Settings ............................................... 40
5 PROGRAMMING ........................................................ 12
5.1 Security Code .................................................. 12
8 SIMPLE FAULT FINDING ........................................... 45
5.2 Configure Display ............................................. 13
8.1 Error Messages ................................................ 45
5.3 Configure Conductivity Sensors ....................... 14
8.2 No Response to Conductivity Changes ............ 45
5.4 Configure Alarms .............................................. 19
8.3 Checking the Temperature Input ...................... 45
5.5 Configure Outputs ............................................ 22
5.6 Output Functions ............................................. 24
5.6.1 Bi-Linear Output ................................. 24 APPENDIX A ....................................................................... 46
5.6.2 Logarithmic Output (2-decade) ........... 25 A1 Automatic Temperature Compensation ............ 46
5.6.3 Logarithmic Output (3-decade) ........... 25 A1.1 Calculation of
5.7 Configure Clock ................................................ 26 Temperature Coefficient ...................... 47
5.8 Configure Security ............................................ 27 A2 Relationship Between Conductivity and
5.9 Test Outputs ..................................................... 28 Total Dissolved Solids (TDS) Measurement ...... 47
A3 Inferred pH Derived from
Differential Conductivity .................................... 48
SPECIFICATION .................................................................. 49
1
1 INTRODUCTION
This conductivity analyzer has been designed for continuous
monitoring and control of conductivity. It is available in wall-/
pipe-mount or panel-mount versions and can be used with
either one or two sensors, each with a temperature input
channel. When used with two sensors, readings can be
compared to produce a range of extrapolated values.
When making temperature compensated measurements, the
sample temperature is sensed by a resistance thermometer
(Pt100 or Pt1000) mounted in the measuring cell.
Analyzer operation and programming are performed using five
tactile membrane keys on the front panel. Programmed
functions are protected from unauthorized alteration by a five-
digit security code.
2
2 OPERATION
2.1 Powering Up the Analyzer 2.2.1 Key Functions
Display
Lines Page X
Parameter 1
Lower
0.000uS/cm Units Advance to
Display Line 0.000uS/cm next parameter
Dual Cond. Parameter 2
Parameter 3
Alarm Parameter 4
LEDs
C – Moving Between Parameters
New value is
automatically stored
3
…2 OPERATION
Use the Sidescroll Key to scroll through the Pages within each Menu
Section 2.3, Page 6 Section 3.1, Page 7 Section 3.2, Page 8 Section 3.3, Page 8 Section 3.4, Page 9 Section 3.5, Page 9
OPERATING PAGE VIEW SETPOINTS VIEW OUTPUTS VIEW HARDWARE VIEW SOFTWARE VIEW CLOCK
Use the Menu A1: Setpoint Analog Output 1 Sensor A Module AX400/2000 Issue Date 01:01:02
Key to scroll A2: Setpoint Analog Output 2 Sensor B Module Time 12:00
through Use the Downscroll
the Menus Key to scroll through A3: Setpoint Analog Output 3 Option Board
the Parameters
A4: Setpoint Analog Output 4
within each Page
A5: Setpoint
A: Temp.Comp. B: Temp.Comp.
A: Temp. Sensor B: Temp. Sensor
A: Temp.Coeff. B: Temp.Coeff.
A: TDS Factor B: TDS Factor
A: TDS Units B: TDS Units
To CONFIG. ALARMS A: Enable Cals. B: Enable Cals.
(see Fig. 2.3B)
Key
Available only if the
analog option board is fitted
4
2 OPERATION…
Use the Sidescroll Key to scroll through the Pages within each Menu
Use the Menu A1: Type A2: Type A3: Type A4: Type A5: Type
Key to scroll A1: Assign A2: Assign A3: Assign A4: Assign A5: Assign
through Use the Downscroll
the Menus Key to scroll through A1: Failsafe A2: Failsafe A3: Failsafe A4: Failsafe A5: Failsafe
the Parameters A1: Action A2: Action A3: Action A4: Action A5: Action
within each Page
A1: Setpoint A2: Setpoint A3: Setpoint A4: Setpoint A5: Setpoint
A1: Hysteresis A2: Hysteresis A3: Hysteresis A4: Hysteresis A5: Hysteresis
A1: Delay A2: Delay A3: Delay A4: Delay A5: Delay
AO1: Zero Value AO2: Zero Value AO3: Zero Value AO4: Zero Value
AO1: Set X Value AO2: Set X Value AO3: Set X Value AO4: Set X Value
AO1: Set Y Value AO2: Set Y Value AO3: Set Y Value AO4: Set Y Value
AO1: Default O/P AO2: Default O/P AO3: Default O/P AO4: Default O/P
AO1: Default Val AO2: Default Val AO3: Default Val AO4: Default Val
Time 12:00
Press To Set Press To Abort
Test Output 2
Test Output 3
To FACTORY SETTINGS
(see Section 7.3, Page 40) Test Output 4
Key
Available only if the
analog option board is fitted
5
…2 OPERATION
Measured Values
5.000uS/cm Conductivity.
25.0Deg.C Temperature.
Conductivity
SENSOR CAL.
If sensor calibration enabled – see Section 4.1.
Security Code
If Alter Sec. Code is not set to zero – see Section 5.1.
CONFIG. DISPLAY
If Alter Sec. Code is set to zero – see Section 5.2.
Measured Conductivity
5.000uS/cm Sensor A.
Measured Temperature
25.6Deg.C Sensor A.
24.4Deg.C Sensor B.
Temperature
Difference = A – B.
% Rejection = (1–B/A) x 100.
% Passage = B/A x 100
Ratio = A/B
Inferred pH = Uses an algorithm to calculate the pH value of the solution, inferred from
its conductivity. See Appendix A3 for further information on inferred pH.
SENSOR CAL.
If sensor calibration enabled – see Section 4.1.
Security Code
If Alter Sec. Code is not set to zero – see Section 5.1.
CONFIG. DISPLAY
If Alter Sec. Code is set to zero – see Section 5.2.
6
3 OPERATOR VIEWS
3.1 View Set Points
8.300uS/cm
A1: Setpoint
35.0Deg.C
A2: Setpoint
3.500uS/cm
A3: Setpoint
Note. Alarm 5 is available only if the optional analog output board is fitted.
-----Off
A5: Setpoint
VIEW SETPOINTS
VIEW OUTPUTS Return to main menu.
7
…3 OPERATOR VIEWS
----- Note. Analog outputs 3 and 4 are available only if the optional analog output board
VIEW OUTPUTS is fitted.
50.0% Current output as a percentage of full scale for the output range selected.
Analog Output 1
Analog Output 2
Analog Output 2 – repeat for outputs 2 to 4.
-----
VIEW HARDWARE
Sensor A Module
Shows the type of sensor connected to the analyzer's Sensor A input.
-----Cond.
Sensor A Module
-----Cond.
Sensor B Module
Option Board
Shows the type of option board fitted to the analyzer (if applicable).
Modbus
Off
----- Analog
Option Board
Analog Output 2
VIEW SOFTWARE See Section 3.4.
8
3 OPERATOR VIEWS
-----
VIEW SOFTWARE
Issue
Shows the version number of the operating software.
1.00
AX400/2000 Issue
VIEW SOFTWARE
VIEW CLOCK If optional analog output board fitted – see Section 3.5.
Dual Cond. Operating Page (if optional analog output board not fitted) – see Section 2.3.
Note. The VIEW CLOCK function is available only if the optional analog output board is fitted.
-----
VIEW CLOCK
Date
Shows the current date.
-----
Date 01:01:01
Time
Shows the current time.
-----
Time 12:00
VIEW CLOCK
Dual Cond. Operating Page – see Section 2.3.
SENSOR CAL.
If sensor calibration enabled – see Section 4.1.
Security Code
If Alter Sec. Code is not set to zero – see Section 5.1.
CONFIG. DISPLAY
If Alter Sec. Code is set to zero – see Section 5.2.
9
4 SETUP
4.1 Sensor Calibration
Sensor Calibration
Note. Applicable only if Enable Cals. is set to Yes – see Section 5.3.
-----
SENSOR CAL.
Calibrate Sensor A
-----
Sensor Cal. A
Sensor Cal. B Dual input conductivity only – Sensor B calibration is identical to Sensor A
calibration.
10
4 SETUP
Sensor Slope
100.0uS/cm The upper display shows the measured conductivity. The lower display shows the process
sensor slope.
1.000
A: Sensor Slope Adjust the slope within the valid range 0.2000 to 5.000 until the conductivity reading is
correct.
Sensor Offset
100.0uS/cm The upper display shows the measured conductivity. The lower display shows the process
sensor offset.
0.0uS/cm
A: Sensor Offset Adjust the offset until the conductivity reading is correct.
Temperature Slope
25.0Deg.C The upper display shows the measured temperature. The lower display shows the
temperature sensor slope.
1.000
A: Temp. Slope Adjust the slope within the valid range 0.2000 to 1.500 until the temperature reading is
correct.
Temperature Offset
25.0Deg.C The upper display shows the measured temperature. The lower display shows the
temperature sensor offset.
0.0Deg.C
A: Temp. Offset Adjust the offset within the valid range –40.0 to 40.0°C (–40° to 104°F) until the
temperature reading is correct.
Sensor Cal. A
Sensor Cal. B Dual input conductivity only – Sensor B calibration is identical to Sensor A
calibration.
SECURITY CODE
If Alter Sec. Code is not set to zero – see Section 5.1.
CONFIG. DISPLAY If Alter Sec. Code is set to zero – see Section 5.2.
Reset
Reset Calibration
Select Yes and press to reset the calibration data.
Yes Select No and press to abort.
----- No
A: Reset?
Sensor Cal. A
Sensor Cal. B Dual input conductivity only – Sensor B calibration is identical to Sensor A
calibration.
SECURITY CODE If Alter Sec. Code is not set to zero – see Section 5.1.
CONFIG. DISPLAY If Alter Sec. Code is set to zero – see Section 5.2.
11
5 PROGRAMMING
5.1 Security Code
Enter the required code number, between 00000 and 19999, to gain access to the secure
parameters. If an incorrect value is entered, access to subsequent programming pages is
prevented and the display reverts to the Operating Page – see Section 2.3.
0000 Note. This item is displayed only if Alter Sec. Code is not set to zero – see Section 5.8.
Security Code
CONFIG. DISPLAY See Section 5.2.
12
5 PROGRAMMING…
-----
CONFIG. DISPLAY
-----
Set Language
Language Page
Select the language to be used on all subsequent pages.
-----
English
Italiano
Espanol Set Temp. Units See below.
Francais
Deutsch
Set Language
-----
Set Temp. Units
Temperature Units
Select the sample temperature display units:
Deg. F °C or °F.
----- Deg. C
Off
Temp. Units
Set Backlight
Set Backlight See below.
-----
Set Backlight
Backlight
Select the backlight option:
On On – Backlight is always on.
-----Auto. Auto. – Backlight comes on at each button press and switches off one minute after
LED Backlight the last button press.
Set Backlight
CONFIG. DISPLAY Return to main menu.
13
…5 PROGRAMMING
-----
CONFIG. SENSORS
Configure Sensor A
-----Cond.
Config. Sensor A
Config. Sensor B Dual input conductivity only – Sensor B configuration is identical to Sensor A
configuration.
14
5 PROGRAMMING…
Table 5.2 Conductivity Range Limits for Different Cell Constants (K)
Cell Constant
Enter the cell constant for the type of measuring cell used – see the relevant cell manual.
0.10
A: Cell Constant
15
…5 PROGRAMMING
Notes.
1) If UPW is selected, the temperature coefficient (α x 100) of the solution must be
calculated if unknown – see Appendix A1.1.
16
5 PROGRAMMING…
Temperature Sensor
Select the type of temperature sensor used, Pt100 or Pt1000.
Pt100
-----Pt1000
A: Temp.Sensor
Temperature Coefficient
Note. Displayed only if Temp.Comp. is set to Linear or UPW – see previous page.
2.00%/°C Enter the temperature coefficient (α x 100) of the solution (0.01 to 5.0%/°C). If unknown,
A: Temp.Coeff.
the temperature coefficient (α) of the solution must be calculated – see Appendix A1.1.
If the value has not yet been calculated, set it to 2%/°C provisionally.
TDS Factor
TDS Units
mg/kg
mg/l Note. Displayed only if Cond.Units is set to TDS – see page 15.
----- ppm
A: TDS Units Select the TDS units (ppm, mg/l or mg/kg).
Enable Calibration
If Sensor Calibration is required, select Yes.
Yes If No is selected the sensor calibration menus for Sensor A are disabled.
No
-----
A: Enable Cals.
Config. Sensor A
Config. Sensor B Dual input conductivity only – Sensor B configuration is identical to Sensor A
configuration.
CONFIG. SENSORS
Single input conductivity only – return to main menu.
17
…5 PROGRAMMING
-----
Config. Sensor B
Yes
-----No
B: Enable Cals.
Config. Sensor B
Signal Calc. Dual input conductivity only – see below.
Note. Inferred pH is available only if units for both Sensors A and B are set
to uS/cm and temperature compensation for Sensor A is set to NaOH or NH3.
After-cation Limit
Set the required after-cation conductivity limit between 0.060 and 1.000 µS cm–1 in 0.001
0.060 uS/cm steps.
After Cat. Limit Note. Applicable only if Signal Calc. is set to Inferred pH.
Signal Calc.
CONFIG. SENSORS Return to main menu.
18
5 PROGRAMMING…
-----
CONFIG. ALARMS
Configure Alarm 1
-----
Config. Alarm 1
Config. Alarm 2 Alarm 2 (and Alarms 3 and 4 if optional analog output board is fitted)
configuration is identical to Alarm 1.
Alarm 1 Type
Select the type of alarm required:
Off
-----Off
Alarm
Status
Off – The alarm is disabled, the alarm LED is off and the relay is de-energized at all
A1: Type times.
Alarm – The analyzer is configured using the Assign parameter (following) to
generate an alarm in response to a specified sensor reading.
2 Status – The analyzer alerts the operator to either a power failure or a condition that
causes an error message to be displayed – see Table 8.1.
%Pass
Temp.B Alarm 1 Assign
Sen.B When Alarm 1 Type is set to Alarm, this enables the alarm to alert the operator to one of two
Temp.A alarm conditions for a specified sensor:
----- Sen.A
A1: Assign Temp.A – The analyzer alerts the operator if the temperature of the process fluid
measured by the selected sensor exceeds or drops below the value set in
the Alarm 1 Set Point parameter (see next page), depending on the type of
Alarm 1 Action selected – see next page.
Sen.A – The analyzer alerts the operator if the conductivity of the process fluid
measured by the selected sensor exceeds or drops below the value set in
the Alarm 1 Set Point parameter (see next page), depending on the type of
Alarm 1 Action selected opposite – see next page.
Notes.
1) Sensor B alarms and signal calculation are applicable only to dual input conductivity.
2) If Signal Calc. is set to any parameter other than No Calculation (see opposite), the
display shows the selected parameter:
% Pass – If Signal Calc. is set to % Passage
% Rej – If Signal Calc. is set to % Rejection
A – B – If Signal Calc. is set to Difference A – B
A/B – If Signal Calc. is set to Ratio A/B
pH – If Signal Calc. is set to Inferred pH (see Appendix A3 for further
information on inferred pH)
The analyzer alerts the operator if the value of the calculation exceeds or drops below the
value set in the Alarm 1 Set Point parameter (see next page), depending on the type of
Alarm 1 Action selected – see next page.
A1: Failsafe
Continued on next page…
19
…5 PROGRAMMING
Alarm 1 Failsafe
If failsafe action is required select Yes, otherwise select No.
No
-----Yes
A1: Failsafe
Alarm 1 Action
Select the alarm action required, High or Low.
Low
----- High
A1: Action
Alarm 1 Hysteresis
A differential set point can be defined between 0 and 5% of the alarm set point value. Set
the required hysteresis, adjustable in steps of 0.1%.
0.0%
A1: Hysteresis
Alarm 1 Delay
When an alarm condition occurs, the activation of the relays and LEDs is delayed for the
specified time period. If the alarm clears within the period, the alarm is not activated.
0Secs Set the required delay, in the range 0 to 60 seconds in steps of 1 second.
A1: Delay
Config. Alarm 1
Config. Alarm 2 Alarm 2 (and Alarms 3 and 4 if optional analog output board is fitted)
configuration is identical to Alarm 1.
20
5 PROGRAMMING…
Relay Energized,
LED Off Relay Energized, LED On
Relay De-energized,
Relay De-energized, LED On LED Off
Fig. 5.1 High Failsafe Alarm without Fig. 5.4 High Non–Failsafe Alarm without
Hysteresis and Delay Delay and Hysteresis
Hysteresis
Delay
Relay De-energized, LED On Relay De-energized, LED On
Fig. 5.2 High Failsafe Alarm with Fig. 5.5 High Failsafe Alarm with
Hysteresis but no Delay Delay but no Hysteresis
Process Variable
Hysteresis
Relay Energized,
LED Off
Delay
Relay De-energized, LED On
21
…5 PROGRAMMING
-----
CONFIG. OUTPUTS
Configure Output 1
-----
Config. Output 1
2 Config. Output 2 Output 2 configuration (and Outputs 3 and 4 if optional analog output board
is fitted) is identical to Output 1 configuration.
% Pass
Temp.B Assign
Sen.B Select the sensor and analog output required:
Temp.A Temp – Temperature for the selected sensor
----- Sen.A Sen – Conductivity for the selected sensor
AO1: Assign
Notes.
1) Sensor B outputs and signal calculation are applicable only to dual input conductivity.
2) If Signal Calc. is set to any parameter other than No Calculation (see page 18), the
display shows the selected parameter:
% Pass – If Signal Calc. is set to % Passage
% Rej – If Signal Calc. is set to % Rejection
A – B – If Signal Calc. is set to Difference A – B
A/B – If Signal Calc. is set to Ratio A/B
pH – If Signal Calc. is set to Inferred pH (see Appendix A3 for further
information on inferred pH)
Range
0-10mA Set the analog output current range for the selected output.
0-20mA
----- 4-20mA
AO1: Range
Linear Curve
Bi-Lin Select the analog output scale required.
Log. 2
----- Log. 3 Linear – Straight line between zero and span
AO1: Curve Bi-Lin – Bi-linear – see Fig. 5.6
Log. 2 – Logarithmic, 2-decades – see Fig. 5.7
Log. 3 – Logarithmic, 3-decades – see Fig. 5.8
22
5 PROGRAMMING…
Span Value
100.0uS/cm Span value – set the required span value.
Zero Value
100.0uS/cm Span value.
0.000uS/cm Zero value – set the required zero value – see Fig. 5.6.
AO1: Zero Value
Note. Applicable only if the Curve parameter is set to Linear or Bi-Lin – see opposite.
When set to Log. 2 and Log. 3, the zero value is set automatically.
12.00mA Current at which the breakpoint occurs. This is Point B in Fig. 5.6.
AO1: Set X Value
Note. Applicable only if the Curve parameter is set to Bi-Lin – see opposite.
12.00mA Set the current at which the breakpoint occurs. This is Point C in Fig. 5.6.
AO1: Set Y Value
Note. Applicable only if the Curve parameter is set to Bi-Lin – see opposite.
Default Output
Off Set the system reaction to failure:
----- On
Hold
mA
Off – Ignore failure and continue operation.
On – Stop on failure. This drives the analog output to the level set in the Default Val
AO1: Default O/P parameter below.
Hold – Hold the analog output at the value prior to the failure.
Default Value
The level to which the analog output is driven if a failure occurs.
12.00mA
AO1: Default Val
Config. Output 1
Config. Output 2 Output 2 configuration (and Outputs 3 and 4 if optional analog output board
is fitted) is identical to Output 1 configuration.
CONFIG. CLOCK If optional analog output board fitted – see Section 5.7.
CONFIG. SECURITY If optional analog output board not fitted – see Section 5.8.
23
…5 PROGRAMMING
Programmable between 0.1% Linear = Subject to a minimum range as per Table 5.2
Conductivity Bi-lin = Subject to a minimum range as per Table 5.2
and 100% of conductivity span
(Table 5.1) Log. 2 = 1.0% of Analog Output Span
Log. 3 = 0.1% of Analog Output Span
Span
A Value
20
18
16
14
12
Analog Output (mA)
C 10
Breakpoint
8
0
0 10 20 30 40 50 60 70 80 90 100
Zero
D Value
B Conductivity Measurement
24
5 PROGRAMMING…
100
90
80
70
% Analog Output
60
50
40
30
20
10
0
1% 10% 100%
Conductivity Measurement – shown as % of Analog Output Span Value
100
90
80
70
60
% Analog Output
50
40
30
20
10
0
0.1% 1% 10% 100%
Conductivity Measurement – shown as % of Analog Output Span Value
25
…5 PROGRAMMING
-----
CONFIG. CLOCK
Set Clock
Set the system clock.
-----
Set Clock?
Format
Select the required clock format.
-----
mm:dd:yy
Format dd:mm:yy
Date
Set the date in the form dd:mm:yy.
----- Press to move between the day, month and year fields.
Date 01:01:01 Press or to adjust each field.
Time
Set the time in the form hh:mm.
Press the appropriate button to set the clock or abort the changes.
----- ✶ Note. Press to Set and Press to Abort are displayed alternately on the lower
Press To Set display line.
Press To Abort
Set Clock?
CONFIG. CLOCK Return to main menu.
26
5 PROGRAMMING…
-----
CONFIG. SECURITY
27
…5 PROGRAMMING
-----
TEST/MAINTENANCE
Test Outputs
Displays the output test details for the four channels. Test Output 1 only is shown; the
remaining outputs are identical.
-----
Test Outputs Note. Outputs 3 and 4 are available only if the optional analog output board is fitted.
Maintenance
-----
Maintenance
Hold Outputs
6 Hrs
Off Enables the relay action and analog outputs to be maintained.
----- On
Auto. On – Changes in relay action and analog outputs are inhibited.
Hold Outputs Off – Changes in relay action and analog outputs are not inhibited.
Auto. – Hold is released automatically after six hours.
Maintenance
TEST/MAINTENANCE Return to main menu.
28
6 INSTALLATION
6.1 Siting Requirements
Caution.
• Mount in a location free from excessive vibration.
• Mount away from harmful vapours and/or dripping
fluids.
65°C
Max.
–20°C
Min.
IP66
NEMA 4X
C – Within Environmental Limits
29
…6 INSTALLATION
6.2 Mounting
192 (7.56)
R1 96 (3.76)
0(
0.4
)
150 (5.9)
175 (6.9)
192 (7.56)
6)
.2
(0
50
6.
Ø
25
61 (23/8) OD
Position 'U' bolts on pipe 1
Vertical or
Horizontal
Drill suitable Position plate over 'U' bolts 2 Post
2 holes
1
Mark fixing centres
(see Fig. 6.2)
3
Secure plate
3
Secure instrument to
wall using 4 Secure transmitter to mounting plate
suitable fixings
A – Wall-mounting B – Pipe-mounting
Fig. 6.3 Wall-/Pipe-mounting
30
6 INSTALLATION…
…6.2 Mounting
Dimensions in mm (in.)
25 92 +0.8
–0 (3.62 +0.03
–0 )
96 (3.78) 137.50 (5.41) (0.98)
91.60 (3.6)
96 (3.78)
92 +0.8
–0
Panel Cut-out (3.62 +0.03 )
–0
5.40 (0.2)
Loosen the
retaining screw on 2
each panel clamp.
31
…6 INSTALLATION
Warning. The power supply earth (ground) must be connected to ensure safety to personnel, reduction of the effects of
RFI interference and correct operation of the power supply interference filter.
Caution. The metal braid in the conductivity cell connecting cable must not be earthed, or allowed to touch earthed
components, and must be cut back to the insulation at the conductivity cell end.
Information.
• Earthing (grounding) – stud terminal(s) is fitted to the analyzer case for bus-bar earth (ground) connection – see Fig. 6.8 (wall-
/pipe-mount analyzers) or Fig. 6.10 (panel-mount analyzers).
• Cable lengths – the integral cable may be extended using a suitable junction box, but the total cable length must not exceed
50m (137.5 ft) for cells with a constant of <0.1 or 100m (275 ft) for cells with a constant of 0.1.
• Cable routing – always route signal output/conductivity cell cable leads and mains-carrying/relay cables separately, ideally
in earthed metal conduit. Use twisted pair output leads or screened cable with the screen connected to the case earth stud.
Ensure that the cables enter the analyzer through the glands nearest the appropriate screw terminals and are short and direct.
Do not tuck excess cable into the terminal compartment.
• Cable glands & conduit fittings – ensure that the NEMA4X/IP66 rating is not compromised when using cable glands, conduit
fittings and blanking plugs/bungs (M20 holes). The M20 glands accept cable of between 5 and 9mm (0.2 and 0.35 in.) diameter.
• Relays –the relay contacts are voltage-free and must be appropriately connected in series with the power supply and the
alarm/control device which they are to actuate. Ensure that the contact rating is not exceeded. Refer also to Section 6.3.1 for
relay contact protection details when the relays are to be used for switching loads.
• Analog output – Do not exceed the maximum load specification for the selected analog output range.
Since the analog output is isolated, the –ve terminal must be connected to earth (ground) if connecting to the isolated input
of another device.
32
6 INSTALLATION…
✶ Note. For reliable switching the minimum voltage must be greater than 12V and the minimum current greater than 100mA.
Diode
R C
Load Load
External L N External + –
AC Supply DC Supply
A – AC Applications B – DC Applications
Fig. 6.6 Relay Contact Protection
33
…6 INSTALLATION
34
6 INSTALLATION…
Warning. Before making any connections, ensure that the power supply, any high voltage-operated control circuits and
high common mode voltages are switched off.
Release Captive
Screws and Remove
Terminal Cover Plate
Terminal Block C
(Analog Option Board)
Earth (Ground)
Stud Terminal Block A Terminal Block B
35
…6 INSTALLATION
Terminal Block C
(Analog Option Board)
Analog Output 3
Analog Output 4
Earth (Ground)
Terminal Block B
Relay 4
Third Lead
Third Lead
NO
C12 NO
NC
C11 NC
Common
Common
C14 —
C16 —
C
C10 C
C13 +
C15 +
C1
C2
C3
C4
C5
C6
C7
C8
C9
TC
TC
B16
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
L
N
E
A4
A5
A6
A7
A8
A9
C A10
NC A11
NO A12
+ A13
— A14
+ A15
— A16
Earth (Ground)
Line
Neutral
C
NC
NO
C
NC
NO
Analog Output 1
Analog Output 2
Relay 1
Relay 2
Relay 3
Terminal block A
Terminal Block B
Sensor B* Sensor A Conductivity Cell Connections
1 9 TC Common, Link B1 to B2 (Dual Conductivity Only) / B9 to B10**
2 10 TC Third Lead
3 11 TC
4 12 Screen
5 13 Cell (Cell Electrode)
6 14 Cell (Earth Electrode)
7 15 Not Used
8 16 Not Used
* Dual Conductivity Only
** When a 2-wire Pt100, Pt1000 or 'balco 3k' temperature compensator is fitted.
TC = Temperature Compensator.
36
6 INSTALLATION…
Warning. Before making any connections, ensure that the power supply, any high voltage-operated control circuits and
high common mode voltages are switched off.
Terminal Block A
Terminal Block C
(Analog Option Board) Terminal Block B
37
…6 INSTALLATION
L Line C1 Common B1
N Neutral C2 Third Lead B2
E Earth (Ground) C3 TC B3
Temperature Compensator
A4 C C4 B4
Connections
A5 NC Relay 1 C5 B5
A6 NO C6 Earth (Ground) B6
A7 C C7 C B7
A8 NC Relay 2 C8 NC Relay 4 B8
A9 NO C9 NO Common B9
A10 C C10 C Third Lead B10
A11 NC Relay 3 C11 NC Relay 5 TC B11
A12 NO C12 NO Temperature Compensator B12
Connections
A13 + C13 + B13
Analog Output 1 Analog Output 3
A14 — C14 — B14
A15 + C15 + B15
Analog Output 2 Analog Output 4
A16 — C16 — B16
Terminal Block B
Sensor B* Sensor A Conductivity Cell Connections
1 9 TC Common, Link B1 to B2 (Dual Conductivity Only) / B9 to B10**
2 10 TC Third Lead
3 11 TC
4 12 Screen
5 13 Cell (Cell Electrode)
6 14 Cell (Earth Electrode)
7 15 Not Used
8 16 Not Used
* Dual Conductivity Only
** When a 2-wire Pt100, Pt1000 or 'balco 3k' temperature compensator is fitted.
TC = Temperature Compensator.
38
7 CALIBRATION
✶ Notes.
• The analyzer is calibrated by the Company prior to dispatch and routine recalibration is not necessary. High stability
components are used in the analyzer's input circuitry and, once calibrated, the Analog to Digital converter chip self-
compensates for zero and span drift. It is therefore unlikely that the calibration will change over time. It is not advisable to
attempt recalibration unless the input board has been replaced or the calibration tampered with.
• Prior to attempting recalibration, test the analyzer's accuracy using suitably calibrated test equipment – see Sections 7.2 and
7.3.
✶ Note. Resistance boxes have an inherent residual resistance which may range from a few m up to 1 . This value must
be taken into account when simulating input levels, as should the overall tolerance of the resistors within the boxes.
7.2 Preparation
a) Switch off the supply and disconnect the conductivity cell(s), temperature compensator(s) and current output(s) from the
analyzer's terminal blocks.
b) Sensor A:
1) Link terminals B9 and B10.
2) Link terminal B12 to the Case Earth Stud – see Fig. 6.8.
3) Connect the 0 to 10k decade r esistance box to terminals B13 and B14 to simulate the conductivity cell. Connect the decade
box earth to the Case Earth Stud.
4) Connect the 0 to 1k decade r esistance box to terminals B11 and B9 to simulate the Pt100/Pt1000.
Temperature Conductivity
Simulator Cell Simulator
Earth
Terminal link
Fig. 7.1 Analyzer Terminal Links and Decade Resistance Box Connections
39
…7 CALIBRATION
Use the Sidescroll Key to scroll through the Pages within each Menu
Cal. Output 2 Cal. Output 3 Cal. Output 4 Load/Save Config Alter Fact.Code
O2: Adjust 4mA O3: Adjust 4mA O4: Adjust 4mA Factory Config.
O2: Adjust 20mA O3: Adjust 20mA O4: Adjust 20mA User Config.
Press To Set Press To Abort
Key
Available only if the
analog option board is fitted
40
7 CALIBRATION…
-----
FACTORY SETTINGS
Calibrate Sensor A
✶ Note. The values in the display lines for sensor calibration are shown only as
----- examples – the actual values obtained will differ.
Cal. Sensor A
Cal. Sensor B Dual input conductivity only – Sensor B calibration is identical to Sensor A
calibration.
0.230 Calib The display advances automatically to the next step once a stable and valid value is
A:Res.Zero (O/C) recorded.
✶ Note. The upper 6-segment display shows the measured input voltage. Once the
signal is within range the lower 6-segment display shows the same value and Calib is
displayed to indicate that calibration is in progress.
2.015 Calib The display advances automatically to the next step once a stable and valid value is
A:Res.Span (2K0) recorded.
0.230 Calib The display advances automatically to the next step once a stable and valid value is
A:Res.Zero (O/C) recorded.
41
…7 CALIBRATION
2.015 Calib The display advances automatically to the next step once a stable and valid value is
A:Res.Span(20R0) recorded.
2.020 Calib The display advances automatically to the next step once a stable and valid value is
A: Res.Vref recorded.
1.465 Calib The display advances automatically to the next step once a stable and valid value is
recorded.
A:T.Zero (100R)
2.068 Calib The display advances automatically to the next step once a stable and valid value is
recorded.
A:T.Span (150R)
1.548 Calib The display advances automatically to the next step once a stable and valid value is
A:T.Zero (1K0) recorded.
2.306 Calib The display returns automatically to Cal. Sensor A once a stable and valid value is recorded.
A:T.Span (1K5)
Cal. Sensor A
42
7 CALIBRATION…
Calibrate Output 1
✶ Note. When adjusting the 4 and 20mA outputs, the display reading is unimportant
----- and is used only to indicate that the output is changing when the and keys are
Cal. Output 1 pressed.
Adjust 4mA
Set the milliammeter reading to 4mA.
16000 ✶ Note. The analog output range selected in Configure Outputs (see Section 5.5) does
O1: Adjust 4mA not affect the reading.
Adjust 20mA
Set the milliammeter reading to 20mA.
7200 ✶ Note. The analog output range selected in Configure Outputs (see Section 5.5) does
O1: Adjust 20mA not affect the reading.
Cal. Output 1
Cal. Output 2 See below.
Calibrate Output 2
✶ Note. Output 2 (and outputs 3 and 4 if optional analog output board is fitted)
----- calibration is identical to Output 1 calibration.
Cal. Output 2
Cal. Output 3 If optional analog output board is fitted.
Load/Save Config Optional analog output board not fitted – see page 44.
7200
O1: Adjust 20mA
Cal. Output 2
Cal. Output 3 If optional analog output board is fitted.
Load/Save Config Optional analog output board not fitted – see page 44.
43
…7 CALIBRATION
Load/Save Configuration
Select whether a configuration is to be loaded or saved.
Yes
-----No ✶ Note. If No is selected, pressing the key has no effect.
Load/Save Config
✶ Notes.
1) Load User Config. is displayed only if a User Configuration has been saved previously.
-----
Press To Set. 2) Press to Set and Press to Abort are displayed alternately on the lower display line.
Press To Abort
0000
Alter Fact. Code
44
8 SIMPLE FAULT FINDING
8.1 Error Messages b) If the response in a) is correct, reconnect the conductivity cell
If erroneous or unexpected results are obtained the fault may be cable and connect the resistance box to the cell end.
indicated by an error message – see Table 8.1. However, some Check the analyzer displays the correct values as set on the
faults may cause problems with analyzer calibration or give resistance box in this configuration.
discrepancies when compared with independent laboratory
If the analyzer passes check a) but fails check b), check the
measurements.
cable connections and condition. If the response for both
checks is correct, replace the conductivity cell.
Error Message Possible Cause
Temperature compensator/associated Cell Constant (K)
A: FAULTY Pt100
connections for Sensor A are either open
A: FAULTY Pt1000 0.05 0.1 1.0
circuit or short circuit. Conductivity
µS cm–1 (G) Resistance (R)
Temperature compensator/associated
B: FAULTY Pt100
B: FAULTY Pt1000
connections for Sensor B are either open 0.055 909.091kΩ – –
circuit or short circuit.
0.1 500kΩ 1MΩ –
The conductivity value before the cation
BEFORE CAT. HIGH 0.5 100kΩ 200kΩ –
exchange unit has exceeded 10µS/cm.
1 50kΩ 100kΩ 1MΩ
The conductivity value after the cation
AFTER CAT. HIGH exchange unit has exceeded the 5 10kΩ 20kΩ 200kΩ
programmed limit.
10 5kΩ 10kΩ 100kΩ
Table 8.1 Error Messages 50 1kΩ 2kΩ 20kΩ
100 500Ω 1kΩ 10kΩ
8.2 No Response to Conductivity Changes
500 100Ω 200Ω 2kΩ
The majority of problems are associated with the conductivity
cell which must be cleaned as an initial check. It is also important 1000 – 100Ω 1kΩ
that all program parameters have been set correctly and have 5000 – – 200Ω
not been altered inadvertently – see Section 5.
10000 – – 100Ω
If the above checks do not resolve the fault:
Table 8.2 Conductivity Readings for Resistance Inputs
a) Check the analyzer responds to a resistance input.
Disconnect the conductivity cell cable and connect a 8.3 Checking the Temperature Input
suitable resistance box directly to the analyzer input – see Check the analyzer responds to a temperature input.
Section 6.4. Select the CONFIG. SENSORS page and and set Disconnect the Pt100/Pt1000 leads and connect a suitable
Temp.Comp. to None – see Section 5.3. Check the analyzer
resistance box directly to the analyzer inputs – see Section 6.4.
displays the correct values as set on the resistance box – see Check the analyzer displays the correct values as set on the
Table 8.2 or use the expression: resistance box – see Table 8.3.
K x 106
R = Incorrect readings usually indicate an electrical calibration
G problem. Re-calibrate the analyzer as detailed in Section 7.3.
Where: R = resistance
K = cell constant Input Resistance (Ω)
Temperature °C
G = conductivity Pt100 Pt1000
Failure to respond to the input indicates a fault with the analyzer 0 100.00 1000.00
which must be returned to the Company for repair. A response, 10 103.90 1039.00
but with incorrect readings, usually indicates an electrical
20 107.79 1077.90
calibration problem. Re-calibrate the analyzer as detailed in
Section 7.3. 25 109.73 1097.30
30 111.67 1116.70
40 115.54 1155.40
50 119.40 1194.00
60 123.24 1232.40
70 127.07 1270.70
80 130.89 1308.90
90 134.70 1347.00
100 138.50 1385.00
130.5 150.00 1500.00
45
APPENDIX A
A1 Automatic Temperature Compensation At high purity water conductivity levels, the conductivity/
The conductivities of electrolytic solutions are influenced temperature relationship is made up of two components: the
considerably by temperature variations. Thus, when significant first component, due to the impurities present, generally has a
temperature fluctuations occur, it is general practice to correct temperature coefficient of approximately 0.02/°C; and the
automatically the measured, prevailing conductivity to the value second, which arises from the effect of the H+ and OH– ions,
that would apply if the solution temperature were 25°C, the becomes predominant as the ultra-pure water level is
internationally accepted standard. approached.
Most commonplace, weak aqueous solutions have Consequently, to achieve full automatic temperature
temperature coefficients of conductance of the order of 2% per compensation, the above two components must be
°C (i.e. the conductivities of the solutions increase compensated for separately according to the following
progressively by 2% per °C rise in temperature); at higher expression:
concentrations the coefficient tends to become less.
Gt – Gupw
G25 = + 0.055
At low conductivity levels, approaching that of ultra-pure water, [1 + ∝ (t – 25)]
dissociation of the H2O molecule takes place and it separates
Where: Gt = conductivity at temperature t°C
into the ions H+ and OH–. Since conduction occurs only in the
presence of ions, there is a theoretical conductivity level for ultra- Gupw = ultra-pure water conductivity at
pure water which can be calculated mathematically. In practice, temperature t°C
correlation between the calculated and actual measured
∝ = impurity temperature coefficient
conductivity of ultra-pure water is very good.
0.055 = conductivity in µS cm–1 of ultra-pure
Fig. A1 shows the relationship between the theoretical
water at 25°C
conductivity for ultra-pure water and that of high purity water
(ultra-pure water with a slight impurity), when plotted against The expression is simplified as follows:
temperature. The figure also illustrates how a small temperature Gimp
variation considerably changes the conductivity. Subsequently, G25 = + 0.055
[1 + ∝ (t – 25)]
it is essential that this temperature effect is eliminated at
conductivities approaching that of ultra-pure water, in order to
ascertain whether a conductivity variation is due to a change in Where: Gimp = impurity conductivity at temperature t°C
impurity level or in temperature.
For conductivity levels above 1µS cm–1, the generally accepted The conductivity analyzer utilizes the computational ability of a
expression relating conductivity and temperature is: microprocessor to achieve ultra-pure water temperature
Gt = G25 [1 + ∝ (t – 25)] compensation using only a single platinum resistance
thermometer and mathematically calculating the temperature
Where: Gt = conductivity at the temperature t°C compensation required to give the correct conductivity at the
G25 = conductivity at the standard temperature reference temperature.
(25°C)
∝ = temperature coefficient per °C
At conductivities between 1µS cm–1 and 1,000µS cm–1, ∝ lies
generally between 0.015/°C and 0.025/°C. When making
temperature compensated measurements, a conductivity
analyzer must carry out the following computation to obtain G25:
Gt
G25 =
[1 + ∝ (t – 25)]
46
APPENDIX A…
µS cm–1
One of these measurements could be made at the ambient
0.4 temperature and the other obtained by heating the sample.
Temperature coefficient (%/°C) = ∝ x 100.
0.3 For ultra pure water applications the temperature compensation
equation becomes,
Gimp1 – Gimp2
0.2 ∝=
[Gimp2 (t1 – 25) – Gimp1 (t2 – 25)]
Where: Gimp1 = Gt1 – Gupw1
0.1 Gimp2 = Gt2 – Gupw2
B
A
0.0
0 10 20 30 40 50 60 70 80 90 100 A2 Relationship Between Conductivity and
Temperature ºC Total Dissolved Solids (TDS) Measurement
The TDS factor (i.e. the relationship between conductivity
Curve 'A' – Theoretical ultra pure water conductivity
(µS cm –1 ) and TDS in p.p.m.) is totally dependent on the
Curve 'B' – High purity water conductivity
(ultra pure water with slight impurity) properties of the solution being measured.
In simple solutions where only one electrolyte is present, the
conductivity/TDS ratio can easily be ascertained, e.g. 0.5 in the
Fig. A.1 Ultra-pure Water Temperature Compensation case of sodium chloride. However, in complex solutions where
more than one electrolyte is present, the ratio is not easily
calculated and can only be reliably determined by laboratory
testing (e.g. precipitation and weighing). The ratio in these cases
is found to vary between approximately 0.4 and 0.8, depending
on the chemical constituents, and is constant only when the
chemical ratios remain constant throughout a particular
process.
In cases where the TDS factor cannot be determined easily, refer
to the supplier of the particular chemical treatment being used.
47
…APPENDIX A
48
SPECIFICATION
Conductivity EMC
Range Emissions and immunity
Programmable 0 to 0.5 to 0 to 10000 µS/cm Meets requirements of:
(with various cell constants) EN61326 (for an industrial environment)
Units of measure EN50081-2
µS/cm, µS/m, mS/cm, mS/m, M -cm and TDS EN50082-2
Accuracy
Better than ±1% of reading Analog Retransmission
Number of signals
Operating temperature range
Two, fully-isolated outputs supplied as standard
–10 to 150°C (14 to 302°F)
Four, fully-isolated outputs when ordered with option card
Temperature compensation
Output current
–10 to 150°C (14 to 302°F)
0 to10mA, 0 to 20mA or 4 to 20mA
Temperature coefficient
Analog output programmable to any value between
Programmable 0 to 5%/°C and fixed temperature 0 and 22mA to indicate system failure
compensation curves (programmable) for acids, neutral
salts and ammonia Accuracy
±0.25% FSD, ±5% of reading
Temperature sensor
Programmable Pt100 /Pt1000 Resolution
0.1% at 10mA 0.05% at 20mA
Reference Temperature
25°C (77°F) Maximum load resistance
750 at 20mA
Display Configuration
Type Can be assigned to either measured variable or
Dual 5-digit, 7-segment backlit LCD either sample temperature
Information
16-character, single line dot-matrix
Environmental Data
Operating temperature limits
–20 to 65°C (–4 to 149°F)
Storage temperature limits
–25 to 75°C (–13 to 167°F)
Operating humidity limits
Up to 95%RH non condensing
49
…SPECIFICATION
Power supply
Voltage requirements
85 to 265V AC 50/60 Hz
24V AC or 12 to 30V DC (optional)
Power consumption
<10VA
Insulation
Mains to earth (line to ground) 2kV RMS
Safety
General safety
EN61010-1
Overvoltage Class II on inputs and outputs
Pollution category 2
50
NOTES
51
…NOTES
52
PRODUCTS & CUSTOMER SUPPORT
Products Customer Support
Automation Systems
• for the following industries: We provide a comprehensive after sales service via a Worldwide
– Chemical & Pharmaceutical Service Organization. Contact one of the following offices for
– Food & Beverage details on your nearest Service and Repair Centre.
– Manufacturing
– Metals and Minerals United Kingdom
– Oil, Gas & Petrochemical ABB Limited
– Pulp and Paper Tel: +44 (0)1453 826661
Fax: +44 (0)1453 827856
Drives and Motors
• AC and DC Drives, AC and DC Machines, AC motors to 1kV United States of America
• Drive systems ABB Inc.
• Force Measurement Tel: +1 (0) 755 883 4366
• Servo Drives Fax: +1 (0) 755 883 4373
• Electromagnetic Magnetic Flowmeters 2. Copies of operating and maintenance records relating to the
alleged faulty unit.
• Mass Flow Meters
• Turbine Flowmeters
• Wedge Flow Elements
Process Analytics
• Process Gas Analysis
• Systems Integration
Transmitters
• Pressure
• Temperature
• Level
• Interface Modules