4000 Series

Operator’s Non–Automatic Transfer Switches


Manual 4NTS, 4NCTS, 4NDTS

Refer to the outline and wiring drawings provided


Non–Automatic Manual Operation
with your 4000 Series N–ATS for all installation and The transfer switch does not transfer the electrical load
connection details and accessories. automatically if the connected source fails. The membrane
buttons must be pressed to transfer the load from one
source to the other source. See illustration below.
Refer to the Operator’s Manual provided with your 4000
Series non–automatic transfer switch for installation,
testing, and service. For electrical operation refer to the To connect the load to To connect the load to
illustration below for manual transfer control. the Normal source. the Emergency source

Refer to Group 5 Controller User’s Guide 381333–126 Push Transfer to Normal Push & hold* Transfer to
for ATS status display messages, time delays, pickup button. Emergency button.
& dropout settings, and adjustments.
Transfer Transfer to
to Normal Emergency

* Hold button 15 seconds or until


generator starts and runs.

press
these buttons

Transfer Transfer to
to Normal Emergency
If this light is on, the buttons will not work
Press for 15 Sec. until they are unlocked. See below.
observe If this light is blinking, the buttons are
these lights temporarily unlocked for 5 minutes.

Figure 1. Controls and indicators for non–automatic operation.

User Controls Locked How to temporarily unlock the user controls


If the User Controls Locked light is on, the Transfer Test and (if the User Controls Locked light is on)
Retransfer to Normal buttons will not work until you unlock Press up or down arrow keys on Transfer Control
them. Center (Group 5 Controller), enter the password, and
press Enter key. The user controls are now unlocked
To permanently unlock or lock the user controls refer to the for 5 minutes. During that time the light will blink.
Group 5 Controller User’s Guide 381333–126. Password
information and time delay settings are provided there.