Imeter 7 English User Manual V1.0 20191205
Imeter 7 English User Manual V1.0 20191205
Imeter 7 English User Manual V1.0 20191205
Standards Compliance
DANGER
This symbol indicates the presence of danger that may result in severe injury or death and permanent
equipment damage if proper precautions are not taken during the installation, operation or
maintenance of the device.
CAUTION
This symbol indicates the potential of personal injury or equipment damage if proper precautions are
not taken during the installation, operation or maintenance of the device.
DANGER
Failure to observe the following instructions may result in severe injury or
death and/or equipment damage.
Installation, operation and maintenance of the meter should only be
performed by qualified, competent personnel that have the appropriate
training and experience with high voltage and current devices. The meter must
be installed in accordance with all local and national electrical codes.
Ensure that all incoming AC power and other power sources are turned OFF
before performing any work on the meter.
Before connecting the meter to the power source, check the label on top of
the meter to ensure that it is equipped with the appropriate power supply, and
the correct voltage and current input specifications for your application.
During normal operation of the meter, hazardous voltages are present on its
terminal strips and throughout the connected potential transformers (PT) and
current transformers (CT). PT and CT secondary circuits are capable of
generating lethal voltages and currents with their primary circuits energized.
Follow standard safety precautions while performing any installation or service
work (i.e. removing PT fuses, shorting CT secondaries, …etc).
Do not use the meter for primary protection functions where failure of the
device can cause fire, injury or death. The meter should only be used for
shadow protection if needed.
Under no circumstances should the meter be connected to a power source if it
is damaged.
To prevent potential fire or shock hazard, do not expose the meter to rain or
moisture.
Setup procedures must be performed only by qualified personnel familiar with
the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
Limited warranty
CET Electric Technology (CET) offers the customer a minimum of 12-month
functional warranty on the meter for faulty parts or workmanship from the date
of dispatch from the distributor. This warranty is on a return to factory for repair
basis.
CET does not accept liability for any damage caused by meter malfunctions. CET
accepts no responsibility for the suitability of the meter to the application for
which it was purchased.
Failure to install, set up or operate the meter according to the instructions herein
will void the warranty.
Only CET’s duly authorized representative may open your meter. The unit should
only be opened in a fully anti-static environment. Failure to do so may damage the
electronic components and will void the warranty.
CET Electric Technology
Table of Contents
Chapter 1 Introduction ........................................................................................................................................... 1
1.1 Overview ................................................................................................................................................... 1
1.2 Features .................................................................................................................................................... 1
1.3 iMeter 7’s application in Power Quality Monitoring and Energy Management Systems ......................... 6
1.4 Getting more information ......................................................................................................................... 6
Chapter 2 Installation ............................................................................................................................................. 7
2.1 Appearance ............................................................................................................................................... 7
2.2 Unit Dimensions........................................................................................................................................ 8
2.3 Terminal Dimensions ................................................................................................................................ 8
2.4 Mounting .................................................................................................................................................. 9
2.5 Wiring Connections .................................................................................................................................. 9
2.5.1 3-Phase 4-Wire Wye Direct Connection with 4CTs ...................................................................... 10
2.5.2 3-Phase 4-Wire Wye with 3PTs and 4CTs ..................................................................................... 10
2.5.3 3-Phase 3-Wire Grounded Wye with no PTs & 3CTs .................................................................... 11
2.5.4 3-Phase 3-Wire Grounded Wye with 3PTs & 3CTs ....................................................................... 11
2.5.5 3-Phase 3-Wire Direct Delta Connection with 3CTs ..................................................................... 12
2.5.6 3-Phase 3-Wire Open Delta with 2PTs & 3CTs ............................................................................. 12
2.5.7 3-Phase 3-Wire Open Delta with 2PTs & 2CTs ............................................................................. 13
2.6 Communications Wiring ......................................................................................................................... 13
2.6.1 Ethernet Port (10/100BaseT) ....................................................................................................... 13
2.6.2 RS485 Port ................................................................................................................................... 13
2.7 Chassis Ground Wiring ............................................................................................................................ 13
2.8 Digital Input Wiring ................................................................................................................................. 14
2.9 GPS 1PPS Input wiring............................................................................................................................. 14
2.10 Relay Output Wiring ............................................................................................................................. 14
2.11 Pulse Output Wiring ............................................................................................................................. 14
2.12 Power Supply Wiring............................................................................................................................. 14
Chapter 3 User Interface....................................................................................................................................... 15
3.1 Front Panel Interface .............................................................................................................................. 15
3.1.1 Front Panel Buttons ..................................................................................................................... 15
3.1.2 Front Panel Data Display .............................................................................................................. 15
3.2 On-board Web Interface ......................................................................................................................... 34
3.2.1 Setting PC's IP Address ................................................................................................................. 34
3.2.2 Configure iMeter 7’s IP Address ................................................................................................... 35
3.2.3 Accessing Web Interface .............................................................................................................. 35
Chapter 4 Applications.......................................................................................................................................... 80
4.1 Inputs and Outputs ................................................................................................................................. 80
4.1.1 Digital Inputs ................................................................................................................................ 80
4.1.2 Relay Outputs............................................................................................................................... 80
4.1.3 Energy Pulse Outputs ................................................................................................................... 81
4.2 Power, Energy and Demand .................................................................................................................... 82
4.2.1 Basic Measurements .................................................................................................................... 82
4.2.2 High-Speed Measurements ......................................................................................................... 82
4.2.3 Energy Measurements ................................................................................................................. 82
4.2.4 Demands ...................................................................................................................................... 82
4.3 Power Quality Parameters ...................................................................................................................... 83
4.3.1 Power Frequency and Freq. Deviation ......................................................................................... 83
4.3.2 Magnitude of the Supply Voltage ................................................................................................ 83
4.3.3 Flicker ........................................................................................................................................... 84
4.3.4 Supply Voltage Dips/Swells .......................................................................................................... 84
4.3.5 Voltage Interruptions ................................................................................................................... 87
4.3.6 Transient Voltages ........................................................................................................................ 87
4.3.7 Supply Voltage and Current Unbalance ....................................................................................... 88
4.3.8 Harmonics and Interharmonics ................................................................................................... 88
4.3.9 MSV (Mains Signalling Voltage) ................................................................................................... 89
4.3.10 RVC (Rapid Voltage Change) ...................................................................................................... 90
4.3.11 Underdeviation and Overdeviation............................................................................................ 91
4.3.12 Flagging Concept........................................................................................................................ 91
4.3.13 Inrush Current ............................................................................................................................ 92
4.3.14 EN50160 Compliance Report ..................................................................................................... 93
4.3.15 ITIC/SEMI F47 Curve .................................................................................................................. 93
4.3.16 Disturbance Direction Indicator ................................................................................................. 94
4.4 Motor Startup ......................................................................................................................................... 94
4.5 Setpoints ................................................................................................................................................. 95
4.6 Data Logging ........................................................................................................................................... 96
4.6.1 IER/AER ........................................................................................................................................ 96
4.6.2 WFR (Waveform Recorder) .......................................................................................................... 96
4.6.3 DWR (Disturbance Waveform Recorder) ..................................................................................... 97
4.6.4 RMSR (RMS Recorder) ................................................................................................................. 98
4.6.5 Pst Log .......................................................................................................................................... 98
4.6.6 Plt Log .......................................................................................................................................... 98
4.6.7 SDR (Statistical Data Recorder) .................................................................................................... 98
4.6.8 Max./Min. Recorder ..................................................................................................................... 99
4.6.9 Max. Demand Recorder (Peak Demand)...................................................................................... 99
4.6.10 SOE Log & Device Log ................................................................................................................ 99
4.6.11 PQ Counters ............................................................................................................................. 100
4.7 Time of Use (TOU) ................................................................................................................................. 100
4.8 Time Synchronization............................................................................................................................ 101
4.8.1 RTC ............................................................................................................................................. 101
4.8.2 GPS ............................................................................................................................................. 101
4.8.3 IRIG-B ......................................................................................................................................... 101
4.8.4 SNTP ........................................................................................................................................... 102
4.8.5 PecStar iEMS .............................................................................................................................. 102
4.9 Alarm Email ........................................................................................................................................... 102
4.10 Ethernet Gateway ............................................................................................................................... 105
Chapter 5 Modbus Map ...................................................................................................................................... 107
5.1 Basic Measurements ............................................................................................................................. 107
5.2 Energy Measurements .......................................................................................................................... 109
5.2.1 Energy Measurement (INT64) .................................................................................................... 109
5.2.2 Energy Measurement (INT32) .................................................................................................... 109
5.3 DI Pulse Counter ................................................................................................................................... 110
5.4 PQ Measurements ................................................................................................................................ 110
5.5 Harmonic Measurements ..................................................................................................................... 111
5.5.1 Harmonic Distortion .................................................................................................................. 111
5.5.2 Harmonic RMS Measurements .................................................................................................. 112
5.5.3 Total Power Individual Harmonics ............................................................................................. 113
5.5.4 Phase A/B/C Power Individual Harmonics ................................................................................. 113
5.5.5 Harmonic Angles ........................................................................................................................ 114
5.5.6 Harmonic Energy........................................................................................................................ 114
5.6 Interharmonic Measurements .............................................................................................................. 115
5.6.1 Interharmonic Distortion ........................................................................................................... 115
5.6.2 Interharmonic RMS Measurements ........................................................................................... 115
5.7 Demand ................................................................................................................................................ 116
5.7.1 Present Demand ........................................................................................................................ 116
5.7.2 Predicted Demand ..................................................................................................................... 118
5.7.3 Max. Demand Log ...................................................................................................................... 119
5.8 Real-time IER & AER .............................................................................................................................. 119
5.9 Data Logging ......................................................................................................................................... 120
5.9.1 SOE Log Buffer ........................................................................................................................... 120
5.9.2 PQ Log Buffer ............................................................................................................................. 120
5.9.3 SDR Log ...................................................................................................................................... 121
5.9.4 MM Log (Max/Min Log) ............................................................................................................. 121
II
5.9.5 Pst/Plt Log .................................................................................................................................. 122
5.9.6 IER & AER Log............................................................................................................................. 123
5.9.7 EN50160 Log .............................................................................................................................. 124
5.9.8 TOU Log...................................................................................................................................... 129
5.10 Real-time WFR Register ...................................................................................................................... 130
5.11 Setup Parameters................................................................................................................................ 131
5.11.1 Communication Setup ............................................................................................................. 131
5.11.2 DI Setup ................................................................................................................................... 131
5.11.3 RO Setup .................................................................................................................................. 132
5.11.4 System Setup ........................................................................................................................... 132
5.11.5 SMTP Setup .............................................................................................................................. 133
5.11.6 Basic Setup Parameters............................................................................................................ 134
5.11.7 PQ Setup .................................................................................................................................. 135
5.11.8 Demand Setup ......................................................................................................................... 136
5.11.9 WFR Setup ............................................................................................................................... 136
5.11.10 Energy Pulse Setup ................................................................................................................ 137
5.11.11 Standard Setpoint Setup ........................................................................................................ 138
5.11.12 High-Speed Setpoint Setup .................................................................................................... 140
5.11.13 SDR Setup............................................................................................................................... 141
5.11.14 Max./Min. Recorder (MMR) Setup ........................................................................................ 149
5.11.15 IER & AER Setup ..................................................................................................................... 151
5.11.16 EN50160 Setup ...................................................................................................................... 151
5.11.17 TOU Setup .............................................................................................................................. 152
5.12 Control Setup ...................................................................................................................................... 155
5.12.1 RO Control................................................................................................................................ 155
5.12.2 Clear/Reset Control.................................................................................................................. 155
5.13 Time Registers ..................................................................................................................................... 157
5.14 Information ......................................................................................................................................... 157
5.14.1 Meter Information ................................................................................................................... 157
5.14.2 Substation Information ............................................................................................................ 158
5.14.3 Site Information ....................................................................................................................... 158
Appendix A – Source Parameters for SDR and Max./Min. Recorders ................................................................. 160
Appendix B – Modbus SOE Classification ........................................................................................................... 164
Appendix C – PQ Log Classification ..................................................................................................................... 167
Appendix D – Technical Specification ................................................................................................................. 168
Appendix E – Accuracy Specification .................................................................................................................. 169
Appendix F – Standard Compliance .................................................................................................................... 170
Appendix G – Ordering Guide ............................................................................................................................. 171
Contact us .......................................................................................................................................................... 172
III
CET Electric Technology
Chapter 1 Introduction
This manual explains how to use the iMeter 7 Advanced Power Quality Analyzer. Throughout the manual, the
term “meter” generally refers to all models.
This chapter provides an overview of the iMeter 7 and summarizes many of its key features.
1.1 Overview
The iMeter 7 is one of CET’s latest Advanced PQ Analyzer designed for the compliance monitoring market as it
offers unsurpassed functionality by combining Class 0.2S Accuracy and advanced PQ Features in a compact DIN
144 form factor with a stunning, high resolution, color TFT LCD display. The iMeter 7 satisfies such standards as
IEC 62053-22 Class 0.2S, IEC 61000-4-30 Class A Edition 2, IEC-61000-4-15, IEC-61000-4-7, EN 50160 and optional
IEC 61850 for Smart Grid applications. Further, the iMeter 7 offers 2GB on-board memory, extensive I/O with
8xDIs, 4xROs, 2xSS Pulse Outputs, multiple Time Sync. methods, one 100BaseT Ethernet and two RS-485 ports.
These features likely make the iMeter 7 one of the most advanced PQ Analyzers for an intelligent Power Quality
Monitoring System.
Following is a list of typical applications for the iMeter 7:
• PQ monitoring at HV, MV and LV Utility Substations
• Data Centers, Semiconductor Fabs, Heavy Industries
• 7x24 Automated Manufacturing Facilities
• Dips/Swells/Interruptions, Transients, Flickers & Harmonics Monitoring
• Mains and Critical feeder monitoring
• Optional IEC 61850 support for Smart Grid
Contact CET Technical Support should you require further assistance with your application.
1.2 Features
Basic Features
IEC 62053-22 Class 0.2S kWh metering with Multi-Tariff TOU
True RMS @ 1024 samples/cycle sampling
2GB on-board log memory
Industrial-grade, 5.7”, high-resolution Color TFT LCD @ 640x480
8xDigital Inputs, 4xRelay Outputs & 2xSS Pulse Outputs
Time Sync. via SNTP, GPS 1PPS or IRIG-B inputs
16 High-speed and 24 Standard Setpoints
Standard 100BaseT Ethernet and two RS-485 ports
Power Quality Features
IEC 61000-4-30 Edition 2 Class A Certified
IEC 61000-4-15, IEC 61000-4-7 and EN 50160 Reporting
Dips, Swells, Interruptions, Transients, Rapid Voltage Change, Inrush Current, Mains Signal Voltage and Flicker
monitoring
Real-time Waveform Capture (WFC), Waveform Recording (WFR) & Disturbance WF Recording (DWR)
Disturbance Direction Indicator
Harmonic and Interharmonic analysis up to 63rd
Waveform recording in COMTRADE file format
Front Panel Display and Web Interface
True RMS Real-time, Harmonics, Power and Energy measurements
Demands and Multi-Tariff TOU
Max. & Min. Logs
Sequence & Unbalance
Real-time WFC of 3Ø U & I @ 128 samples/cycle x 4 cycles
Event Waveforms and ITIC/SEMI F47 Curves
Harmonics & Interhamonics Histogram and Phasor Diagrams
Device and SOE Logs, PQ Counters and I/O Status
Device Configuration and Diagnostics
1
CET Electric Technology
PQ Event Counters
Dip, Swell, Interruption, Transient, Rapid Voltage Change, Inrush Current, Mains Signalling Voltages and Total
PQ Event Counters
Real-Time Waveform and Waveform Recorder (WFR)
Real-time WFC @ 128 samples/cycle x 4 cycles via Front Panel and Web Interface
WFR with max. 128 entries
Simultaneous capture of 3-phase Voltage and Current Inputs
No. of Cycles x Samples/Cycles with programmable pre-fault cycles: 10x1024, 20x512, 40x256, 80x128,
160x64, 320x32, 640x16
COMTRADE file format, downloadable from the on-board Web Server or FTP Server
2
CET Electric Technology
Metering
Basic Measurements (1-second update)
3-phase U, I, P, Q, S, PF, Phase Angles as well as U4, I4 and Frequency
kWh, kvarh Import/Export/Net/Total and kVAh Total
High-speed Measurements
3-phase U, I, P, Q, S and PF as well as U4 and I4 @ ½ cycle
Frequency @ 5 cycles
Demands
Present and Predicted Demand for 3-phase U, I, P, Q, S, PF as well as U4, I4 and Frequency
Present Demand of 4-phase U & I THD/TOHD/TEHD, 4-phase Current K-factor, U2/U0 & I2/I0 Unbalance, Over
& Under Deviation of Voltage and Frequency, 4-phase Fundamental Current
Max. Demand for This Month and Last Month (or Before the Last Reset and Since the Last Reset)
Demand Synchronization with DI
3
CET Electric Technology
Device Log
1024 FIFO entries time-stamped to ± 1ms resolution
Power On/Off, Setup changes, Time Sync., Device Operations and Self-diagnostics
Setpoints
PQ Setpoints
Transients, Dips, Swells, Interruptions
Rapid Voltage Change
Inrush Current
Trigger RO, SOE Log, WFR, DWR, RMSR and Alarm Email
Control Setpoints
16 High-speed (½ cycle) Setpoint and 24 Standard (1s) Setpoint
Extensive monitoring sources including U, I, P, Q, S, Demands, Harmonics, Unbalances, Deviations, Flickers,
Phase Reversal, etc.
Configurable thresholds and time delays
Trigger RO, SOE Log, WFR, DWR, RMSR and Alarm Email
Digital Outputs
Standard 6 channels for control, alarming and pulsing applications
RO1-RO4: Form A Mechanical Relay
DO1+/DO1-, DO2+/DO2-: Optically isolated Solid State Relay
Communications
RS-485 (P1, P2)
Dual optically isolated RS-485 ports with baud rate from 1.2kbps to 38.4 kbps
Protocol supported: Modbus RTU, Ethernet Gateway
Time Sync. via P1 with GPS 1PPS or IRIG-B outputs
4
CET Electric Technology
System Integration
PecStar iEMS
The iMeter 7 is supported by CET’s PecStar iEMS.
In addition, the iMeter 7 can be easily integrated into other 3rd party systems because of its support of
multiple communications ports as well as different industry standard protocols such as Modbus and IEC
61850
Diagsys
Display of Real-time measurements, PQ Events, Waveforms and Statistical Trend Charts
Export of IER, AER and SDR as well as EN50160
Generation and Export of self-defined PQ Analysis Reports
5
CET Electric Technology
1.3 iMeter 7’s application in Power Quality Monitoring and Energy Management Systems
The iMeter 7 can be used to monitor 3P4W or 3P3W connected power system. Modbus communications allow
real-time data, events, DI status, DR Logs, WFR Logs and other information to be transmitted to an Integrated
Energy Management System such as PecStar® iEMS.
6
CET Electric Technology
Chapter 2 Installation
Caution
Installation of the iMeter 7 should only be performed by qualified, competent personnel that have the
appropriate training and experience with high voltage and current devices. The meter must be installed in
accordance with all local and national electrical codes.
During the operation of the meter, hazardous voltages are present at the input terminals. Failure to observe
precautions can result in serious or even fatal injury and equipment damage.
2.1 Appearance
7
CET Electric Technology
Unit: mm
8
CET Electric Technology
2.4 Mounting
The iMeter 7 should be installed in a dry environment with no dust and kept away from heat, radiation and
electrical noise sources.
Installation steps:
Remove the mounting slide bars from the meter
Fit the meter through a 138mm x 138mm cutout as shown in Figure 2-4
Re-install the mounting slide bars and tighten the screws against the panel to secure the meter
Unit: mm
Caution
Under no circumstances should the PT secondary be shorted.
Under no circumstances should the CT secondary be open when the CT primary is energized. CT shorting blocks
should be installed to allow for easy maintenance.
9
CET Electric Technology
10
CET Electric Technology
Figure 2-7 3-Phase 3-Wire Grounded Wye with no PTs & 3CTs
Figure 2-8 3-Phase 3-Wire Grounded Wye with 3PTs & 3CTs
11
CET Electric Technology
Figure 2-10 3-Phase 3-Wire Open Delta with 2PTs & 3CTs
12
CET Electric Technology
Figure 2-11 3-Phase 3-Wire Open Delta with 2PTs & 2CTs
13
CET Electric Technology
Figure 2-17 Pulse Output (Solid State Relay) Connections for Energy Pulsing
14
CET Electric Technology
15
CET Electric Technology
The following figure provides an overview of the Front Panel User Interface.
16
CET Electric Technology
3.1.2.1.2 RMS
Enter the RMS sub-menu and the following screen appears which displays the 3Φ and Tot/Avg. RMS measurements
updated @1s for Uln, Ull, I, P, Q, S and PF as well as 3Φ U Angle, 3Φ I Angle, U4, I4 and Frequency.
Press < > to pause or refresh the display. Press <> & < > simultaneously to enter the large font display and then
use <> or <> to scroll between the different screens. Press <> & < > simultaneously again to return to the
summary screen.
17
CET Electric Technology
3.1.2.1.5 Energy
Enter the Energy sub-menu and the following screens are available which provides the measurements for kWh,
kvarh Import/Export/Total/Net and kVA Total.
Press <> or <> button to scroll among RMS, Fund. and Tot. Harm. Measurements.
18
CET Electric Technology
3.1.2.1.6 Demand
Enter the Demand sub-menu and the following screens are available which display the Present Demand, Predicted
Demand, This Max. and Last Max. for P Total Imp/Exp, Q Total Imp/Exp, S and 3Φ Currents. Use <> or <> button
to scroll among Present (including Present & Predicted Demand), This Max. and Last Max. with their timestamps.
Depending on the setting of the Self-Read Time, This Max. and Last Max. could mean the Max. Demand of This
Month/Last Month or Since/Before the Last Reset.
19
CET Electric Technology
At the Present TOU Summary screen, press <> & < > together to enter the large font display and use <> or <>
to scroll between the different screens. Press <> & < > simultaneously again to return to the summary screen.
20
CET Electric Technology
3.1.2.1.9 Min.
Enter the Min. sub-menu and the following screen is available which displays the Min. measurements with timestamps.
Press <> or <> to scroll among the 4 Max. Recorders and then Use < > to scroll to the different parameters.
21
CET Electric Technology
22
CET Electric Technology
At the Voltage and Current Interharmonics screens, press < > to view the %IHD and RMS measurements for 4Φ
Voltages and Currents from IH01 to IH63.
23
CET Electric Technology
3.1.2.2.6 EN50160
Enter the EN50160 sub-menu to show the EN50160 Summary Report where indicates a positive conclusion while
indicates a negative conclusion.
24
CET Electric Technology
• Flicker Severity
25
CET Electric Technology
26
CET Electric Technology
• Transient Overvoltages
27
CET Electric Technology
28
CET Electric Technology
29
CET Electric Technology
3.1.2.5.1 Basic
Enter the Basic sub-menu and the following screen appears. Use <>, <>, <>, <> to scroll through the different
parameters. Press < > to select and modify the desired parameter. The Front Panel Password is required for any
setup changes. Please refer to Table 3-4 for the range and default values of the different parameters.
30
CET Electric Technology
3.1.2.5.4 Comm.
Enter the Comm. Sub-menu to display the configuration for RS-485 (P1), RS-485 (P2) and Ethernet (P3) ports. Please
refer to Table 3-5 Comm. Parameters for more information about the different parameters.
31
CET Electric Technology
3.1.2.5.8 Record
Enter the Record sub-menu to display the settings for WFR, DWR, and RMSR. Please refer to Section 4.6.1 , Section
4.6.3 and Section 4.6.4 for more information about the different parameters.
32
CET Electric Technology
3.1.2.5.12 Maintenance
Enter the Maintenance sub-menu and the following screen appears which allows the manual control of RO and reset
of the different groups of parameters.
33
CET Electric Technology
Click Network & Internet, select the Change adapter options and then find the appropriate Ethernet connection.
34
CET Electric Technology
35
CET Electric Technology
4) The iMeter 7’s Web Interface appears after login. There are five items at the Title Bar – PQ Insight, Metering,
Power Quality, Events and Setup.
3.2.3.1 PQ Insight
The Waveform under PQ Insight menu is the first page displayed upon user login and includes the following
information and operations:
36
CET Electric Technology
3.2.3.2 Metering
Click Metering at the Title Bar and its sub-menus appear on the left-hand pane which includes Phasor, Basic, Demand,
Energy, TOU, Max./Min. and I/O. The following sections provide an overview of these sub-menus.
3.2.3.2.1 Phase
Click Phasor on the left-hand pane and the following screen appears which displays the Magnitude and Phase
information for Ua/Ub/Uc (3P4W) or Uab/Ubc/Uca (3P3W) and Ia/Ib/Ic as well as Frequency. Click Export to save the
Phasor data to a .csv file at the default Download folder for the Web Browser.
37
CET Electric Technology
3.2.3.2.3 Demand
Click Demand on the left-hand pane and the following screen appears which shows the readings for Demand (Present
Demand), Predicted (Predicted Demand), This Max and Last Max. Depending on the setting of the Self-Read Time,
This Max. and Last Max. could mean the Max. Demand of This Month / Last Month or Since / Before Last Reset.
Move the mouse pointer over the readings for This Max. and Last Max. to show the corresponding timestamp.
Click Export to save the Demand data on this page to .csv file at the default Download folder.
Click Reset This Max. (only accessible for Operator) to manually reset the Max. Demand of This Month or Since Last
Reset. It should be noted that it’s not possible to manually reset the Last Max., which is the Max. Demand of Last
Month or Before Last Reset.
38
CET Electric Technology
Click Individual Harmonics and the following pages are available which display the Harmonic Energy in spectrum or
table format for kWh, kvarh Import/Export by selecting Spectrum or Table from the top left drop-down list.
• Spectrum Move the mouse pointer over a particular histogram to show its harmonic order and value.
Click on the kWh Imp., kWh Exp., kvarh Imp., kvarh Exp. tab at the top to view the
respective Harmonic Energy spectrum.
39
CET Electric Technology
40
CET Electric Technology
41
CET Electric Technology
3.2.3.2.6 Max./Min.
Click Max./Min. on the left-hand pane and the following screen appears which displays the 4 Max./Min. Recorders.
Move the mouse pointer over the readings for This Max. and Last Max. to show the corresponding timestamp.
Click Export to save the specific group of Max. or Min. data displayed on the current page to a .csv file at the default
Download folder.
42
CET Electric Technology
3.2.3.3.1 Harmonics
Click Harmonics on the left-hand pane and the following screen appears which displays the Spectrum for up to 63rd
harmonics and the following parameters: THD, TOHD, TEHD, Crest Factor, K-Factor, TDD, TDD Odd and TDD Even.
Click Ua, Ub, Uc, U4, Ia, Ib, Ic or I4 at the top of the page to view the respective Harmonics data. Move the mouse
pointer over a particular histogram to show its harmonic order and value.
43
CET Electric Technology
• Click Harmonic Power at the bottom of the page to display the individual harmonic measurements for 3-Ø P, Q,
S and PF in Table format.
44
CET Electric Technology
Click Individual Interharmonics at the bottom of the page to view the data in a Table format.
45
CET Electric Technology
46
CET Electric Technology
3.2.3.3.6 EN50160
Click EN50160 on the left-hand pane and the following screen appears. Click on the drop-down list on the top left to
select the period for the desired EN50160 Summary Report. As shown in Figure 3-96, denotes the positive
evaluation while denotes the negative evaluation for the parameter. Click on a particular parameter to view the
report details. Click Export to download the en50160Report.xls file for the currently selected period.
47
CET Electric Technology
Flicker Severity
48
CET Electric Technology
Interharmonic Voltages
49
CET Electric Technology
50
CET Electric Technology
3.2.3.4 Events
Click Events at the Title Bar and its sub-menus appear on the left-hand pane which includes SOE, Device Log and PQ
Counters. The following sections provide a quick overview of these web pages.
3.2.3.4.1 SOE
Click SOE on the left-hand pane to display the SOE Log on the right-hand pane starting with the most recent events.
The interface supports the following filtering mechanisms.
Search Period: Use the drop-down box on the left to select a specific period.
Event Type: Use the drop-down box in the middle to select a particular event type such as Dip/Swell,
Transient, RVC, MSV, Inrush Current, Setpoint, I/O, Manual Trigger WFR and Motor Startup.
Keyword Search: Enter a keyword in the text box on the right to search for events that contain the keyword.
Click on a specific event to display the event details.
Click Export to save all SOE events to a .csv file at the default Download folder.
51
CET Electric Technology
52
CET Electric Technology
53
CET Electric Technology
3.2.3.4.3 PQ Counters
Click PQ Counters on the left-hand pane to display on the right-hand pane the different PQ Counters such as Dips,
Swells, Interruptions, Transients, RVC, Inrush Current and MSV.
54
CET Electric Technology
• PT/CT. Please refer to Table 3-4 Basic Parameters for more information.
55
CET Electric Technology
The following sections describe the Setup sub-menus which include Basic, PQ, Dmd. & Energy, Record, Setpoint, I/O,
HMI, Others and Diagnostics.
3.2.3.5.1 Basic
Click Basic on the left-hand pane and the following screen appears which has four tabs: Basic, Comm., Time and
Others.
3.2.3.5.1.1 Basic > Basic Settings
56
CET Electric Technology
57
CET Electric Technology
The following table illustrates the range for Time parameters where * indicates the default value.
Parameter Range/Default* Parameter Range/Default*
Date Time Sync.
Date 2000-01-01* to 2037-12-31 Clock Source RTC*, SNTP, GPS, IRIG-B~,
Time Zone GMT-12:00 to GMT+13:00; GMT+8:00* SNTP Server IP 192.168.101.2*
Time 00:00:00* to 23:59:59 IRIG-B Time Zone~ GMT-12 to GMT+13; GMT+8*
Date Format YY/MM/DD, MM/DD/YY, DD/MM/YY, SNTP Interval 1 to 1440 min, 60 min*
YY-MM-DD*, MM-DD-YY, DD-MM-YY
~ To set the IRIG-B as the Time Source and its time zone, the meter should be equipped with the corresponding module.
Table 3-6 Date and Time Parameters
3.2.3.5.1.4 Basic > Others
This web page allows the users to setup Language, Delimiter and the different parameters under Algorithm.
58
CET Electric Technology
59
CET Electric Technology
60
CET Electric Technology
Figure 3-136 Default Limits of the EN50160 Parameters for Low Voltage
61
CET Electric Technology
62
CET Electric Technology
• Energy Log Please refer to Section 4.6.1 for a detailed description of the parameters below.
63
CET Electric Technology
• Basic
64
CET Electric Technology
65
CET Electric Technology
Click to add a new Alternate Day or to clear the setting for the current Alternate Day.
66
CET Electric Technology
67
CET Electric Technology
3.2.3.5.4.3 Max./Min.
The iMeter 7 supports 4 Max./Min Recorders of 20 parameters each. Please refer to Section 4.6.8 for the explanation
of the Self-Read Time.
69
CET Electric Technology
3.2.3.5.5 Setpoint
Click Setpoint on the left-hand pane to configure the setup parameters for Setpoint (Standard Setpoint) and HSSP
(High-Speed Setpoint).
• Standard Setpoint
70
CET Electric Technology
Click on a particular Setpoint and the Setpoint Settings dialog box appears.
71
CET Electric Technology
• RO
Click the RO tab at the top of the page and the following screen appears. Please refer to Section 4.1.2 for more
information.
• Counters
Click the Counters tab at the top of the page and the following screen appears.
72
CET Electric Technology
Click More >> to open the Trigger Source dialog box and then select the event type that would trigger an alarm email.
73
CET Electric Technology
74
CET Electric Technology
The following table illustrates the range and default values of the Advanced parameters. Please refer to 5.11.4 for
more information.
Parameter Range/Default* Parameter Range/Default*
Time Format Flagged Data
COMTRADE Local*, UTC SDR Keep*, Remove
Modbus Local*, UTC EN 50160 Keep*, Remove
COMTRADE Diagsys
# of Sampling Rates 0*, No. of Sampling Rates Enable Yes*, No
Custom Label Port 60001
Dips/Swells FTP
D/S RMS Update 1-cycle*, ½-cycle Enable Yes*, No
Interruption Mode Single Phase, Three Phase* Port 1~65535, 21*
D/S Filter Disable*, Enable Username operator*
D/S Max. Duration 1~600s, 60s* Password abcd1234-
Swell Max. Magnitude 101~500 (%), 180* Anonymous Access Disable*, Enable
Front Panel Web
HMI Security Enable*, Disable Enable Yes*, No
Analog Display U Range 1~1,000,000V, 100* Port 1~65535, 80*
Analog Display I Range 1~1,000,000A, 5A* Login Timeout 0~1440min, 5min*
Aggregation Interval Modbus TCP
50/60-cycle, 150/180-cycle*,
Parameter Magnitudes 10-min, 2-hour Enable Yes*, No
Frequency 1s*, 3s, 10s Port 1~65535, 502*
Table 3-8 Advanced Settings Range
3.2.3.5.8 Diagnostics
Click Diagnostics on the left-hand pane to expand its sub-menu which consists of Device & Site Info., User
Management and Maintenance.
3.2.3.5.8.1 Device & Site Info.
• Device
75
CET Electric Technology
• Site
76
CET Electric Technology
3.2.3.5.8.3 Maintenance
Click Maintenance on the left-hand pane and the following screen appears which provides the options for RO Control,
Clear, Imp. /Exp. (Import/Export), OEM, Upgrade and Restart.
RO Control Perform Manual RO Control and Reset all DOs to Normal.
77
CET Electric Technology
78
CET Electric Technology
79
CET Electric Technology
Chapter 4 Applications
4.1 Inputs and Outputs
4.1.1 Digital Inputs
The iMeter 7 comes standard with 8 self-excited Digital Inputs that are internally wetted at 24 VDC with a sampling
frequency of 1000Hz and programmable debounce. The iMeter 7 provides the following programmable functions for
its Digital Inputs:
1) Status Input Status Inputs are typically used for status monitoring which can help prevent
equipment damage, improve maintenance and track security breaches. The real-
time statuses of the Digital Inputs are available on the Front Panel LCD Display,
Web Interface as well as through communications. Changes in Digital Input status
are stored as events in the SOE Log in 1 ms resolution.
2) Pulse Counting Pulse counting facilitates WAGES (Water, Air, Gas, Electricity and Steam)
information collection with a fixed incremental value of 1 for each pulse received.
3) Demand Sync Pulse One of the Digital Inputs can be programmed to receive Demand Sync Pulse. Only
one DI can be programmed as DMD Sync. For example, to set DI4 as Demand
Sync Input, DI1 to DI3 must not be programmed as a DMD Sync input.
4) Tariff Switching Up to 3 Digital Inputs may be used to select to which of the 8 Tariffs the energy
consumption should be accumulated. The 3 Digital Inputs (DI1 to DI3) represent
3 binary digits where Tariff 1=000, Tariff 2=001, …, Tariff 8=111 where DI1
represents the least significant digit and DI3 represents the most significant digit.
The DI1 Function setup register must first be programmed as a Tariff Switch
before configuring DI2 with the same function. In other words, if DI1 is configured
as a Status Input or Pulse Counter and DI2 is configured as a Tariff Switch, the
TOU will continue to function based on the TOU Schedule.
The following table describes the DI’s setup parameters:
Parameter Definition Options/*Default
0=Status Input*
DIx Function Each DI can be configured as a Status Input, Pulse Counter or DMD SYNC 1=Pulse Counter
DI. Only DI1 to DI3 can be configured as Tariff Switch. 2=DMD Sync
3=Tariff Switch
Specifies the minimum duration the DI must remain in the Active or 1 to 9999 (ms)
DIx Debounce Inactive state before a state change is considered to be valid. (Default=20ms)
DIx Setpoint Specifies the transition edge, whether it’s positive, negative or any, for a Any Edge*,
Type1 DI Setpoint to become active. The DI Setpoint Type is only used when a DI Positive, Negative
is configured as a Status Input.
Specifies what output action a DI Setpoint will take when it becomes RO1/RO2/RO3/RO4
DIx Trigger active. DI Setpoint is only valid when a DI is configured as a Status Input. /WFR/DWR/RMSR
Table 4-1 DI Setup Parameters
Note:
1. The DIx Setpoint Type only affects which edge would trigger the Waveform Recorder if configured.
80
CET Electric Technology
5) Transient Setpoint: Transient setpoint can be programmed to trigger RO, WFR/DWR/RMSR or Alarm
Email upon becoming active. Please refer to Section 4.3.6 for a detailed description.
6) RVC Setpoint RVC setpoint can be programmed to trigger RO, WFR/DWR/RMSR or Alarm Email
upon becoming active. Please refer to Section 4.3.10 for a detailed description.
7) Inrush Setpoint Inrush Setpoint can be programmed to trigger RO, WFR/DWR/RMSR or Alarm Email
upon becoming active. Please refer to Section 4.3.13 for a detailed description.
8) Motor Startup Setpoint Motor Startup Setpoint can be programmed to trigger RO and WFR/DWR/RMSR
upon becoming active. Please refer to Section 4.4 for a detailed description.
ROs on the iMeter 7 has the following setup parameters:
Parameter Definition Options/Default*
Arm Before Execute Enable or disable the Arm Before Execute feature for the RO 0=Disabled,
1=Enabled*
Specifies the duration for which the relay output will be active when a
ROx (x=1 to 4) Remote Operate or Setpoint Trigger command is received to operate 0 to 6000 (x 0.1s),
Pulse Width 0 (Latch Mode)*
it.
Table 4-2 DO Setup Parameters
Since there are multiple ways to trigger the Relay Outputs on the iMeter 7, a prioritized scheme has been developed
to avoid conflicts between different applications. In general, Front Panel Control has the highest priority and can
override other applications. Remote Control, Control Setpoint, Dip/Swell/Interruption Setpoint, Transient Setpoint,
RVC Setpoint and Inrush Current Setpoint share the same priority, meaning that they can all be programmed to control
the same Relay Output. This scheme is equivalent to having an implicit Logical OR operation for the control of a Relay
Output and may be useful in providing a generic alarm output signal. However, the sharing of a Relay Output is not
recommended if the user intends to generate a control signal in response to a specific setpoint condition.
4.1.3 Energy Pulse Outputs
The iMeter 7 comes with two Solid State Relay Outputs for energy pulsing as well as two front panel LED for kWh and
kvarh pulsing. Energy Pulse Outputs are typically used for accuracy testing. Energy pulsing can be configured from the
Front Panel (please refer to Section 3.1.2.5.3 ) or via the Web Interface (please refer to Section 3.2.3.5.3.2 ).
The following table illustrates the ranges and default values for the Energy Pulse parameters.
Parameters Options/Default* Parameters Options/Default*
Pulse Constant2 1000*, 3200, 5000, 6400, 12800 kWh LED 1, 4 and 7 in Table 4-4, N/A*
DO1/DO2 See Table 4-4, N/A* kvarh LED 10, 13 and 16 in Table 4-4, N/A*
Table 4-3 Energy Pulse Parameters
Notes:
1. The following table illustrates the available options for the Energy Pulse parameters.
ID Parameter ID Parameter ID Parameter
1 kWh Total 7 kWh Total TH 13 kvarh Total Fund.
2 kWh Imp. 8 kWh Imp. TH 14 kvarh Imp. Fund.
3 kWh Exp. 9 kWh Exp. TH 15 kvarh Exp. Fund.
4 kWh Total Fund. 10 kvarh Total 16 kvarh Total TH
5 kWh Imp. Fund. 11 kvarh Imp. 17 kvarh Imp. TH
6 kWh Exp. Fund. 12 kvarh Exp. 18 kvarh Exp. TH
Table 4-4 Available options for Energy Pulse
2. The Pulse Constant can be configured as 1000/3200/5000/6400/12800 impulses per kWh or kvarh. It's important
to understand that energy pulsing is always based on the secondary ratings as it would be impossible to generate
the required number or pulses based on the primary ratings. The following table illustrates the recommended
settings for the Pulse Constant based on Z = Vnominal x Inominal x 2, where Vnominal and Inominal are the secondary nominal
Voltage and Current ratings, respectively. In general, one would use a higher Pulse Constant for a smaller Z value
(i.e. a smaller Vnominal and Inominal) in an accuracy testing situation to reduce the test time.
Z Energy Pulse Constant Default
≤1000 1000/3200/5000/6400/12800 5000
≤2000 1000/3200/5000/6400 5000
≤2600 3200/5000/6400 5000
≤4000 5000/6400 5000
>13000 5000 5000
Table 4-5 Recommended Settings for Energy Pulse Constant
81
CET Electric Technology
4.2.4 Demands
Demand is defined as the average power consumption over a fixed interval (usually 15 minutes).
iMeter 7 provides the predicted demand for pre-alarming and helps users to reduce demand consumption by
predicting the demand at the end of the present period based on the current real-time power consumption.
iMeter 7 also provides the Max. Demand of This/Last Month or Since/Before Last Reset according to the Self-Read
Time setup parameter. The Max. Demand of This Month (or Since Last Reset) is transferred to the Max. Demand of
Last Month (Before Last Reset) and then reset each month at the Self-Read Time or after a manual reset.
The iMeter 7 provides the following Present Demand and Predicted Demand parameters:
82
CET Electric Technology
83
CET Electric Technology
4.3.3 Flicker
The iMeter 7 provides the Flicker measurements in accordance with Section 5.3 of IEC 61000-4-30 Ed.2 Standard for
Class A performance (where IEC 61000-4-15 Standard applies). The Nominal Frequency (50Hz or 60Hz) and the Flicker
Curve (120V or 230V) setup parameters, programmable via the Web Server or Communications, determine which
model would be used for the following Flicker measurements.
Short-term flicker severity (Pst) measured over a 10-minute interval
Long-term flicker severity (Plt) calculated from a sequence of 12 Pst according to the following formula:
The Pst and Plt measurements can be accessed through Front Panel (refer to Section 3.1.2.2.5 ), On-board Web Server
(refer to Section 3.2.3.3.5 ) or through Communications.
4.3.4 Supply Voltage Dips/Swells
The iMeter 7 supports the detection of the Supply Voltage Dips and Swells using a method that is in accordance with
Section 5.4 of IEC 61000-4-30 Ed. 2 Standard for Class A performance.
The iMeter 7 provides Dips/Swells detection for voltage quality monitoring on a per phase basis, which support
multiple triggers at the same time, including WFR/DFR/RMSR, RO, SOE and Alarm Email. The timestamp, duration
and Magnitudes of per phase voltage of each Dip/Swell would be recorded by the iMeter 7.
4.3.4.1 Dips/Swells Detection
As per IEC 61000-4-30 Ed.2:
Voltage Swells Detection
On polyphase systems a Swell begins when the Urms(1/2) voltage of one or more channels rises above the Swell
Threshold and ends when the Urms(1/2) voltage on all measured channels is equal to or below the Swell Threshold
minus the Hysteresis voltage.
Voltage Dips Detection
On polyphase systems a Dip begins when the Urms(1/2) voltage of one or more channels is below the Dip Threshold
and ends when the Urms(1/2) voltage on all measured channels is equal to or above the Dip Threshold plus the
Hysteresis voltage.
PQ Disturbance Settings
The PQ Disturbance setup parameters can be programmed over the Web Interface or via Communications. The Dip
Threshold, Swell Threshold, Voltage Interruption Threshold (See Section 4.3.5.1 ) and Dip/Swell Hysteresis should
be configured to meet the following criteria:
a) The Voltage Interruption Threshold (please see Section 4.3.5.1 ) shall be set below the Dip Threshold.
b) The Dip/Swell Hysteresis must be less than the Dip/Swell Thresholds.
c) The Rapid Voltage Changes (RVC) Threshold must be less than the Dip and Swell Thresholds.
d) Regardless of whether Dip/Swell is enabled, the conditions for a), b) and c) must always be met.
The following table illustrates the ranges and default values for the PQ Disturbance parameters on the iMeter 7.
Parameter Options/Range, Default* Parameter Options/Range, Default*
PQD Enable Yes*, No Dip Threshold 1% to 99% (x Udin/Usr), 90%*
Reference Voltage Udin*, Usr Dip Hysteresis 1% to 100% (x Udin/Usr), 2%*
PQD Trigger WFR, DWR*, RMSR Dip Trigger RO1, RO2, RO3, RO4
Swell Threshold 101% to 200% (x Udin/Usr), 110%* Interruption Threshold 0% to 50% (x Udin/Usr), 5%*
Swell Hysteresis 1% to 100% (x Udin/Usr), 2%* Interruption Hysteresis 1% to 100% (x Udin/Usr), 2%*
Swell Trigger RO1, RO2, RO3, RO4 Interruption Trigger RO1, RO2, RO3, RO4
Table 4-8 PQ Disturbance Parameters
84
CET Electric Technology
85
CET Electric Technology
86
CET Electric Technology
87
CET Electric Technology
∑U
K =1
K
2
Ik
Current Kth Harmonic/Interharmonic Distortion = X100% where the denominator is the RMS
∞
∑I
K =1
K
2
88
CET Electric Technology
The iMeter 7 provides measurements for Voltage Harmonics, Current Harmonics, K-Factor, Crest Factor (for Current
only), Power Harmonics and Energy Harmonics.
K-Factor
K-factor is defined as the weighted sum of the harmonic load currents according to their effects on transformer
heating, as derived from ANSI/IEEE C57.110. A K-Factor of 1.0 indicates a linear load (no harmonics). The higher K-
Factor, the greater the harmonic heating effects.
x rms
89
CET Electric Technology
The iMeter 7 can simultaneously detect three different frequencies for Mains Signalling Voltage. The emission
signalling will trigger an event in SOE, recording the Trigger Channel and Max. Volt. of three-phase voltages.
90
CET Electric Technology
∑ 𝑛𝑛 𝑈𝑈 2 ∑ 𝑛𝑛 𝑢𝑢 2
𝑈𝑈𝑑𝑑𝑑𝑑𝑑𝑑 −� 𝑖𝑖=1 𝑟𝑟𝑟𝑟𝑟𝑟−𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢,𝑖𝑖 � 𝑖𝑖=1 𝑟𝑟𝑟𝑟𝑟𝑟−𝑜𝑜𝑜𝑜𝑜𝑜𝑜𝑜,𝑖𝑖−𝑈𝑈
𝑑𝑑𝑑𝑑𝑑𝑑
𝑛𝑛 𝑛𝑛
Uunder = 𝑈𝑈𝑑𝑑𝑑𝑑𝑑𝑑
Uover = 𝑈𝑈𝑑𝑑𝑑𝑑𝑑𝑑
Where
n = the number of 10/12 cycle RMS values for under or overdeviation
and
Urms-under, i /Urms-over, i is the ith 10/12-cycle RMS value.
The iMeter 7 is capable of measuring Voltage with an accuracy of 0.1% and monitoring Voltage Deviation on line. In
addition, the Voltage Deviation is supported by the Setpoint function. Please refer to Chapter 3 User Interface for the
Deviation parameters on the Front Panel and Web Interface.
4.3.12 Flagging Concept
The iMeter 7 supports the Flagging Concept as per Section 4.7 of IEC 61000-4-30 Ed.2 Standard:
During a dip, swell, or interruption, the measurement algorithm for other parameters (for example, frequency
measurement) might produce an unreliable value. The flagging concept therefore avoids counting single event
more than once in different parameters (for example, counting a single dip as both a dip and a frequency variation)
and indicates that an aggregated value might be unreliable.
Flagging is only triggered by dips, swells and interruptions*. The detection of dips and swells is dependent on the
threshold selected by the user and this selection will influence which data are "flagged".
The flagging concept is applicable for Class A measurement performance during measurement of power frequency,
voltage magnitude, flicker, supply voltage unbalance, voltage harmonics, voltage interharmonics, mains signalling
and measurement of underdeviation and overdeviation parameters.
If during a given time interval any value is flagged, the aggregate value indicating that value shall also be flagged.
The flagged value shall be stored and also included in the aggregation process, for example, if during a given time
interval any value is flagged the aggregated value that includes this value shall also be flagged and stored.
*Besides, flagging will be triggered by the detection of I > 2In on iMeter 7.
The Flagging Status register (0080) indicates if a certain group of data has been flagged with a bit value of 1 meaning
flagged and 0 meaning not flagged. The following table illustrates the details of the Flagging Status register for real-
time data.
91
CET Electric Technology
92
CET Electric Technology
93
CET Electric Technology
94
CET Electric Technology
4.5 Setpoints
The iMeter 7 comes with 24 Standard Setpoints and 15 High-speed Setpoints which allow users to initiate an action in
response to a specific condition. Typical setpoint applications include alarming, control and power quality monitoring.
Under Limit Specify the value that the setpoint parameter must go below for Over Setpoint 0*
or exceed for Under Setpoint for the setpoint to becomes inactive.
Specify the minimum duration that the setpoint condition must be met before
Active the setpoint becomes active. An event will be generated and stored in the SOE
Delay Log. The range of the Setpoint Active Delay is 0 to 9,999 seconds for Standard 0* to 9999
Setpoints and 0 to 9,999 cycles for HS Setpoints.
Specify the minimum duration that the setpoint return condition must be met
Inactive before the setpoint becomes inactive. An event will be generated and stored
Delay in the SOE Log. The range of the Setpoint Inactive Delay is 0 to 9,999 seconds 0* to 9999
for Standard Setpoints and 0 to 9,999 cycles for HS Setpoints.
None*, RO1, RO2,
Trigger Specify what action a setpoint can take when it becomes active. DWR, WFR, RMSR,
Alarm Email
Table 4-20 Description for Setpoint Parameters
95
CET Electric Technology
The iMeter 7 provides the following Setpoint parameters, Standard Setpoint can monitor all parameters while the HS
Setpoint only can monitor parameters 1 to 10.
Key Parameter Key Parameter Key Parameter
0 Null 27 I TOHD 54 Q Total Imp. Pred. Demand
1 Uln 28 I TEHD 55 P Total Exp. Pred. Demand
2 Ull 29 U TIHD 56 Q Total Exp. Pred. Demand
3 U4 30 U TOIHD 57 S Total Pred. Demand
4 I 31 U TEIHD 58 PF Total Pred. Demand
5 I41 32 I TIHD 59 Pst
6 Reserved 33 I TOIHD 60 Plt
7 kW Total 34 I TEIHD 61 Reserved
8 kvar Total 35 U TH RMS 62 Phase Loss
9 kVA Total 36 U TOH RMS 0x0200 U HD02
10 PF 37 U TEH RMS … …
11 U2 Unbalance 38 I TH RMS 0x3F0000 U HD63
12 U0 Unbalance 39 I TOH RMS 0x400000 U H02 RMS
13 I2 Unbalance 40 I TEH RMS … …
14 I0 Unbalance 41 U TIH RMS 0x7D0000 U H63 RMS
15 U Fund. 42 U TOIH RMS 0x810000 U IHD01
16 I Fund. 43 U TEIH RMS … …
17 Voltage Deviation 44 I TIH RMS 0xBF0000 U IHD63
18 Voltage over Dev. 45 I TOIH RMS 0x20000000 I H02 RMS
19 Voltage Under Dev. 46 I TEIH RMS … …
20 Frequency 47 P Total Imp. Demand 0x3F000000 I H63 RMS
21 Freq. Deviation 48 Q Total Imp. Demand 0x40000000 I HD02
22 Phase Reversal 49 P Total Exp. Demand … …
23 U THD 50 Q Total Exp. Demand 0x7D000000 I HD63
24 U TOHD 51 S Total Demand 0x81000000 I IH01 RMS
25 U TEHD 52 PF Total Demand … …
26 I THD 53 P Total Imp. Pred. Demand 0xBF000000 I IH63 RMS
Table 4-21 Setpoint Parameters
96
CET Electric Technology
The WFR log can be viewed directly on the Front Panel and Web Interface as well as downloaded from the on-board
FTP/Web Server or via communications. The programming of the WFR is supported via the Front Panel (Please refer
to Section 3.1.2.5.8 ), Web Interface (Please refer to Section 3.2.3.5.4.1 ) or communications.
The following table illustrates the ranges and default values of the WFR parameters.
Parameter Range/Default* Parameter Range/Default*
Format See Table 4-25, 256 x 40* Pre. Fault Cycles See Table 4-25, 4*
WF Bust Recording 1-7, 1*
Table 4-24 WFR Setup Parameters
Format (samples x cycles) Pre-Fault Range Format (samples x cycles) Pre-Fault Range
16 x 640 2-384 32 x 320 2-192
64 x 160 2-96 128 x 80 2-48
256 x 40 2-24 512 x 20 2-12
1024 x 20 2-6
Table 4-25 WFR Format & Pre-Fault Range
The iMeter 7 also provides the following settings for Schedule WFR to trigger the WFR on the hour as pre-configured.
The programming of the Scheduled WFR is supported via the Web Interface or Communications.
Parameter Options/Value, Default* Parameter Options/Value, Default*
Enable Yes, No* Interval 1 to 960 h, 24 h*
Recording Interval Start Date 2000-01-01*
0 to 1000, 1*
(Repetition) Start Time 00:00:00*
Table 4-26 Scheduled WFR Setup Parameters
97
CET Electric Technology
Notes:
1) The data for Stages A, B, D and E are always recorded.
2) For stages C and D:
If C < 150 cycles, then D would be 0.
If C = 150 cycles, then the data for stage D will be recorded.
If D = 18,000 cycles, the recording of the stage D data ends even if the disturbance is not finished.
2) The following figure shows an example of Disturbance Waveform Recording.
98
CET Electric Technology
99
CET Electric Technology
100
CET Electric Technology
Each TOU schedule has the following setup parameters and can be programmed via the Web Server (Please refer to
Section 3.2.3.5.3.4 ) or communications:
Parameters Definition Options
Specify a daily rate schedule which can be divided into a maximum starts atthe
1 to 20, first period
00:00 and the
Daily Profile # of 12 periods in 15-min intervals.
Up to 20 Daily Profiles can be programmed for each TOU schedule. last period ends at
24:00.
A year can be divided into a maximum of 12 seasons. Each season 1 to 12, starts from
Season # is specified with a Start Date and ends with the next season’s Start
Date. January 1st
Alternate Days # A day can be defined as an Alternate Day, such as May 1st. Each 1 to 90.
Alternate Day is assigned a Daily Profile.
Specify the day type of the week. Each day of a week can be Weekday1, Weekday2,
Day Types assigned a day type such as Weekday1, Weekday2, Weekday3 and Weekday3 and
Alternate Days. The Alternate Day has the highest priority. Alternate Days
Specify when to switch from one TOU schedule to another. Writing Format: YYYYMMDDHH
Switching Time 0xFFFFFFFF to this parameter disables switching between TOU Default=0xFFFFFFFF
schedules.
Table 4-35 TOU Setup Parameters
For each of the 8 Tariff Rates, the iMeter 7 provides the following measurements: kWh Import/Export, kvarh Import/
Export, kVAh, P/Q/S Max. Demand with their timestamps. All these data are available via the Front Panel (See Section
3.1.2.1.7 ), Web Interface (See Section 3.2.3.2.5 ) and communications.
101
CET Electric Technology
4.8.4 SNTP
SNTP (Simple Network Time Protocol) can be used to synchronize the iMeter 7's clock with an external SNTP Server
through its Ethernet port providing that the network has been properly configured. The programming of the SNTP
setup parameters is supported via the Front Panel (See Section 3.1.2.5.10 ), Web Server (See Section 3.2.3.5.1.3 ) or
communications.
Parameters Option
0= RTC, 1=GPS, 2=SNTP, 3=IRIG-B
Clock Source Set Clock Source=2
GMT-12:00 / GMT-11:00 / GMT-10:00 / GMT-9:00 / GMT-8:00 / GMT-7:00 / GMT-6:00 /
GMT-5:00 / GMT-4:00 / GMT-3:30 / GMT-3:00 / GMT-2:00 / GMT-1:00 / GMT-0:00 /
Time Zone GMT+1:00 / GMT+2:00 / GMT+3:00 / GMT+3:30 / GMT+4:00 / GMT+4:30/ GMT+5:00 /
GMT+5:30 / GMT+5:45 / GMT+6:00 / GMT+6:30 / GMT+7:00 / GMT+8:00 (default)/
GMT+9:00 / GMT+9:30 / GMT+10:00 / GMT+11:00 / GMT+12:00 / GMT+13:00
Time Sync. Interval 10 to 1440 minutes, default=60
SNTP Server IP Default=192.168.101.2
Table 4-37 SNTP Setup Parameters
102
CET Electric Technology
103
CET Electric Technology
2. Click on Setup-> Others-> Alarm Email-> Settings as shown below. Please note that all the SMTP information
should be entered correctly (please log into the Sender Email account to confirm the SMTP settings). Click Save
to store the configuration in the iMeter 7. The message “Saved Succeeded” will appear if the configuration is
accepted by the meter.
104
CET Electric Technology
4. If the Receiver receives the test email successfully, please return to Alarm Email Settings and click on “More >>”
to open the Trigger Source dialog box. Check the Setpoint selection box and click OK to confirm the changes. Click
Save to keep the changes.
105
CET Electric Technology
106
CET Electric Technology
107
CET Electric Technology
108
CET Electric Technology
109
CET Electric Technology
5.4 PQ Measurements
Register Property Description Format Unit
0700 RO Ua Deviation1 Float
0702 RO Ub Deviation1 Float
0704 RO Uc Deviation1 Float
0706 RO Uab Deviation Float
0708 RO Ubc Deviation Float
0710 RO Uca Deviation Float
0712 RO Ua Over Deviation1 Float
0714 RO Ub Over Deviation1 Float
0716 RO Uc Over Deviation1 Float
--
0718 RO Uab Over Deviation Float
0720 RO Ubc Over Deviation Float
0722 RO Uca Over Deviation Float
0724 RO Ua Under Deviation1 Float
0726 RO Ub Under Deviation1 Float
0728 RO Uc Under Deviation1 Float
0730 RO Uab Under Deviation Float
0732 RO Ubc Under Deviation Float
0734 RO Uca Under Deviation Float
0736 RO Freq. Deviation Float Hz
0738~0748 -- Reserved --
0750 RO U0 Unbal. Float
0752 RO U2 Unbal. Float --
0754 RO I0 Unbal. Float
0756 RO I2 Unbal. Float
0758 RO U0 Float V
0760 RO U1 Float V
0762 RO U2 Float V
0764 RO I0 Float A
0766 RO I1 Float A
0768 RO I2 Float A
0770 RO Ua / Uab Pst.2 Float
0772 RO Ub / Ubc Pst. 2 Float
0774 RO Uc / Uca Pst. 2 Float
--
0776 RO Ua / Uab Plt. 2 Float
0778 RO Ub / Ubc Plt. 2 Float
0780 RO Uc / Uca Plt. 2 Float
110
CET Electric Technology
0782 -- Reserved --
0784 RO Ia TDD Float
0786 RO Ib TDD Float
0788 RO Ic TDD Float
0790 RO I4 TDD Float
0792 -- Reserved --
0794 RO Ia TDD Odd Float
0796 RO Ib TDD Odd Float
0798 RO Ic TDD Odd Float
0800 RO I4 TDD Odd Float
0802 -- Reserved --
0804 RO Ia TDD Even Float
0806 RO Ib TDD Even Float
0808 RO Ic TDD Even Float
0810 RO I4 TDD Even Float
0812 -- Reserved --
0814 RO Ia K-Factor Float
0816 RO Ib K-Factor Float
0818 RO Ic K-Factor Float
0820 RO I4 K-Factor Float
0822 -- Reserved --
0824 RO Ia Crest Factor Float
0826 RO Ib Crest Factor Float
0828 RO Ic Crest Factor Float
0830 RO I4 Crest Factor Float
0832 -- Reserved --
0834 RO Ua Crest Factor Float
0836 RO Ub Crest Factor Float
0838 RO Uc Crest Factor Float
0840 RO U4 Crest Factor Float
Table 5-9 PQ Measurements
Notes:
1. When the Wiring Mode is 3P3W, the 3Φ Uln Deviations have no meaning and their registers are reserved.
2. When the Wiring Mode is 3P3W, the phase A/B/C Voltage Pst. and Plt. mean phase AB/BC/CA Voltage Pst. and Plt.
111
CET Electric Technology
112
CET Electric Technology
113
CET Electric Technology
114
CET Electric Technology
115
CET Electric Technology
5.7 Demand
5.7.1 Present Demand
Register Property Description Format Unit
3600 RO Ua1 Float V
3602 RO Ub1 Float V
3604 RO Uc1 Float V
3606 RO ULN Avg1 Float V
3608 RO U4 Float V
3610 RO Uab Float V
3612 RO Ubc Float V
3614 RO Uca Float V
116
CET Electric Technology
117
CET Electric Technology
118
CET Electric Technology
119
CET Electric Technology
120
CET Electric Technology
121
CET Electric Technology
122
CET Electric Technology
123
CET Electric Technology
124
CET Electric Technology
1 week
24754 RO Uc H02 Max. Float
24756~24886 RO ······ Float ······
24888 RO Ua H25 Max. Float
24890 RO Ub H25 Max. Float Maximum 25 harmonics on 3-phase over
th
1 week
24892 RO Uc H25 Max. Float
24894~24904 -- Reserved -- --
24906 RO Ua H02 Min. Float
24908 RO Ub H02 Min. Float Minimum 2 harmonics on 3-phase over
nd
1 week
24910 RO Uc H02 Min. Float
24912~25042 RO ······ Float ······
25044 RO Ua H25 Min. Float Minimum 25th harmonics on 3-phase over
125
CET Electric Technology
126
CET Electric Technology
127
CET Electric Technology
128
CET Electric Technology
129
CET Electric Technology
130
CET Electric Technology
5.11.2 DI Setup
Register Property Description Format Range, Default*
40100 RW DI1 Mode 1
UINT16 0=Status Input*, 1=Pulse Counter
2=DMD Sync, 3= Tariff Switch
40101 RW DI1 Debounce UINT16 1 to 9999 (ms), 20ms*
40102 -- Reserved -- --
40104 RW DI1 Setpoint Type2 UINT16 0=Any *, 1=Positive, 2=Negative
40105 RW DI1 Trigger3 UINT32 0*
40107~40108 -- Reserved -- --
… RW … … …
0=Normal* (Status Input), 1=Pulse Counter
40163 RW DI8 Mode1 UINT16 2=DMD Sync, 3= Tariff Switch
40164 RW DI8 Debounce UINT16 1 to 9999 (ms), 20ms*
40165 -- Reserved -- --
40239 RW DI8 Setpoint Type2 UINT16 0=Any Transition*, 1=Positive, 2=Negative
40240 RW DI8 Trigger3 UINT32 0*
Table 5-56 DI Setup Parameters
Notes:
1. Only one DI should be programmed as the DMD Sync. Input. To use a different DI for Demand Sync., the existing DI must first be reset back to
Normal (Status Input) before programming the new DI for Demand Sync. Otherwise the configuration will be unsuccessful. Only DI1 to DI3
can be set as Tariff Switch.
2. The DIx Setpoint Type only affects which edge would trigger the Waveform Recorder if configured.
3. The table below provides a list of DIx’s Setpoint Trigger, with a value of “1” meaning active and “0” meaning inactive.
Bit Trigger Bit Trigger Bit Trigger Bit Trigger
B0 RO1 B2 RO3 B4 to B26 Reserved B28 WFR
B1 RO2 B3 RO4 B27 DWR B29 RMSR
Table 5-57 DIx Trigger
131
CET Electric Technology
5.11.3 RO Setup
Register Property Description Format Range, Default*
40301 RW Arm Before Execute1 UINT16 0=Disabled, 1=Enabled*
40302 RW RO Pulse Width2 UINT16
40303 RW RO Pulse Width2 UINT16
0 to 6000 (x0.1s), 0*
40304 RW RO Pulse Width2 UINT16
40305 RW RO Pulse Width2 UINT16
Table 5-58 RO Setup Parameters
Notes:
1. Arm Before Execute setup register is used to specify if the relays need to be armed before they can be operated on.
2. The RO Pulse Width specifies the duration for which the relay output will be active when a Remote Operate or Setpoint Trigger command is
received to operate it.
5.11.4 System Setup
Register Property Description Format Range / Options
40751 RW Dip/Swell RMS Update1 UINT16 0=1-cycle*, 1= ½ -cycle
40752 RW Interruption Mode2 UINT16 0=Single Phase, 1=Three Phase*
40753 RW Dip/Swell Filter3 UINT16 0=Disable*, 1=Enable
40754 RW Dip/Swell Max. Duration3 UINT16 1~600s, 60s*
40755 RW Swell Max. Magnitude3 UINT16 101~500 (%), 500*
40756~40798 -- Reserved -- --
40799 RW Delimiter 4 UINT16 0=Option 1*, 1=Option 2
40800 RW Clock Source5 UINT16 0=RTC*, 1=SNTP, 2=GPS, 3=IRIG-B
40801 RW Time Zone6 UINT16 0 to 32, 26*
40802 RW IRIG-B Time Zone6 UINT16 0 to 32, 26*
40803 RW Language UINT16 0=English*, 1=Simplified Chinese,
2=Traditional Chinese
0=YYMMDD*, 1=MMDDYY
40804 RW Date Format UINT16 2=DDMMYY, 3=YYYY-MM-DD
4=MM-DD-YYYY, 5=DD-MM-YYYY
40805 -- Reserved -- --
40806 RW Backlight Timeout UINT16 0 to 60 min (0 means disabled), 5*
40807 RW LCD Contrast (%) UINT16 50 to 100 (%), 90%
40808 RW Phase A Color UINT16 See Note 7, 1*
40809 RW Phase B Color UINT16 See Note 7, 4*
40810 RW Phase C Color UINT16 See Note 7, 8*
40811 RW Phase N Color UINT16 See Note 7, 13*
40812 RW Earth Wire Color UINT16 0=Green,1=Yellow-Green*
40813 RW Set Password UINT32 0~999999, 1*
40815~40817 -- Reserved -- --
40819 RW Time Format8 UINT16 See Note, 0*
40820 RW PQ Curve UINT16 0=ITIC*, 1=SEMI F47
40821 RW Aggregation Interval9 UINT16 0=50/60-cycle, 1=150/180-cycle*
2=10-min, 3=2-hour
40822 RW Freq. Interval UINT16 0=1s*, 1=3s, 2=10s
40823 -- Reserved -- --
40824 RW Sampling Rates in CFG File10 UINT16 0=0*, 1=Actual Sampling
40825 RW Keep/Remove Flagged Data11 UINT16 0=Keep*, 1=Remove
40826~40833 RW FTP User Name CHAR See Note 12, operator*
40834~40841 RW FTP User Password CHAR See Note 12, abcd1234-*
40842 RW FTP Anonymous Logon UINT16 0=Enabled, 1=Disabled*
40843 RW FTP Enable UINT16 0=Enable*, 1=Disable
40844 RW TELNET Visible UINT16 0=Enable*, 1=Disable
40845 RW Analog Display Voltage Scale UNIT32 1~1,000,000 (V), 415*
40847 RW Analog Display Current Scale UNIT32 1~1,000,000 (A), 5A*
40849~40856 -- Reserved -- --
40857 RW Web Enable UINT16 0=Disabled, 1=Enabled*
40858 -- Reserved -- --
40859 RW WEB Port UINT16 1 to 65535, 80*
40860 RW FTP Port UINT16 1 to 65535, 21*
40861 RW TELNET Port UINT16 1 to 65535, 23*
40862 RW Diagsys Enable13 UINT16 0=Disabled, 1=Enabled*
40863 RW Diagsys Port UINT16 1 to 65535, 60001*
40864 RW Modbus TCP Enable14 UINT16 0=Disabled, 1=Enabled*
40865 RW Modbus TCP Port UINT16 1 to 65535, 502*
40866 RW HMI Security Enable UINT16 0=Disabled, 1=Enabled*
132
CET Electric Technology
40867~40894 -- Reserved -- --
40895 RW Web Login Timeout UNIT16 0~1440 min (0 means disabled), 5 min*
Table 5-59 System Setup Parameters
Notes:
1. The Dip/Swell RMS Update register determines if the Urms is computed every cycle and then shifted by ½ cycle (register value = 0) or if the
Urms is computed every ½ cycle and then shifted by ½ cycle (register value = 1).
2. The Interruption Mode register determines if an Interruption event should start when the Urms of all 3 phases (register value = 1) or when the
Urms of any 1 phase (register value = 0) fall below the Interruption Threshold.
3. The Dip/Swell Filter determines if a Dip/Swell event should be recorded when the Dip/Swell duration exceeds the preset value of Dip/Swell
Max. Duration register or if a Swell event should be recorded if the Urms exceeds the preset value of Swell Max. Magnitude register. The
Dip/Swell Max. Duration and Swell Max. Magnitude registers are disregarded if the Dip/Swell Filter is disabled.
4. The Delimiter setup register supports two options, 1 and 2:
Option 1: “,” is used as the x1000 delimiter and “.” as the decimal point (e.g. 123,456,789.0).
Option 2: “ ” is used as the x1000 delimiter and “,” as the decimal point (e.g. 123 456 789,0).
5. When Clock Source is set to GPS or IRIG-B, P1 (RS485) port will be automatically used for the respective Time Sync signal. Please refer to Section
4.8 for a detailed description.
6. The following table lists the Codes for different Time Zones. The IRIG-B Time Zone parameter should be configured when Clock Source is set to
IRIG-B.
Code Time Zone Code Time Zone Code Time Zone
0 GMT-12:00 11 GMT-2:00 22 GMT+5:45
1 GMT-11:00 12 GMT-1:00 23 GMT+6:00
2 GMT-10:00 13 GMT-0:00 24 GMT+6:30
3 GMT-9:00 14 GMT+1:00 25 GMT+7:00
4 GMT-8:00 15 GMT+2:00 26 GMT+8:00
5 GMT-7:00 16 GMT+3:00 27 GMT+9:00
6 GMT-6:00 17 GMT+3:30 28 GMT+9:30
7 GMT-5:00 18 GMT+4:00 29 GMT+10:00
8 GMT-4:00 19 GMT+4:30 30 GMT+11:00
9 GMT-3:30 20 GMT+5:00 31 GMT+12:00
10 GMT-3:00 21 GMT+5:30 32 GMT+13:00
Table 5-60 Time Zones
7. The following table lists the Color options for different wires.
No. Color (R, G, B) No. Color (R, G, B) No. Color (R, G, B) No. Color (R, G, B)
0 Brown (153,51,0) 4 Yellow (255,216,0) 8 Blue (0,0,255) 12 White (255,255,255)
1 Red (255,0,0) 5 Turquoise (0,162,132) 9 Violet (112,48,160) 13 Black (0,0,0)
2 Pink (255,173,177) 6 Green (0,255,36) 10 Grey (159,159,159)
3 Orange (255,102,0) 7 Light-blue (79,204,246) 11 Neutral Grey (193,193,193)
Table 5-61 Wire Color Options
8. The timestamp for different data is programmable by writing the “Time Format” register, with the bit value of “0” meaning LOCAL time, while
“1” meaning UTC time. The following table illustrates the details of this register.
BIT Description Note
Timestamp of retrieved Data logs via Modbus: Real-time measurement, SOE, PQ LOG, SDR,
B0 MODBUS
Max./Min. Log, Plt/Pst, EN50160 Log, TOU Log, IER and AER Log.
B1 COMTRADE Timestamp of COMTRADE file including the first/trigger point in .cfg file
Table 5-62 Time Format Register
9. The basic measurement interval shall be a 10-cycle period for 50 Hz power system and a 12-cycle period for 60 Hz power system. The 10/12-
cycle measurement are then aggregated over 4 additional intervals: 50/60-cycle, 150/180-cycle, 10 min, 2-hour.
10. “0” means the DWR file in COMTRADE format doesn’t include any sampling section information.
11. For Keep/Remove Flagged Data register, the bit value of “0” means Keep Flagged Data in the log while “1” means remove. The following table
illustrates the details of this register.
Bit4~Bit15 Bit3 Bit2 Bit1 Bit0
Reserved EN50160 Log Min. Log Max. Log SDR Log
Table 5-63 Keep/Remove Flagged Data Register
12. The FTP Username and Password should not exceed 16 characters.
13. Modification written to this register requires a Device Reboot to take effect.
14. Modification written to this register will take effect at once.
5.11.5 SMTP Setup
Register Property Description Format Range/Options
40900 RW SMTP Event Classification Bitmap Note 1
40902 RW SMTP Port UINT16 1 to 65535 (Default=25)
40903 RW SMTP Server Address UINT32 Note 2
40905 RW Sender Address CHAR Note 3
40925 RW Sender Username CHAR Note 4
133
CET Electric Technology
134
CET Electric Technology
5.11.7 PQ Setup
Register Property Description Format Range, Default*
41100 RW Dip/Swell Enable UINT16 0=Disabled, 1=Enabled*
41101 RW Dip/Swell Reference Voltage UINT16 0=Udin*, 1=Usr
41102 RW Swell Threshold1 UINT16 101 to 200 (x0.01Udin/Usr), 110*
41103 RW Dip Threshold1 UINT16 1 to 99 (x0.01 Udin/Usr), 90*
41104 RW Interruption Threshold1 UINT16 0 to 50 (x0.01 Udin/Usr), 10*
41105 RW Swell Hysteresis1 UINT16
41106 RW Dip Hysteresis1 UINT16 1 to 1000 (x0.001 Udin/Usr), 20*
41107 RW Interruption Hysteresis1 UINT16
41108 RW PQD Trigger2 UINT32 0x800000000(DWR) *
41110 RW Dip/Swell Trigger3 UINT32
41112 RW Transient Enable UINT16 0=Disabled*, 1=Enabled
41113 RW Transient Threshold UINT16 5 to 500 (%), 55*
41114 RW Transient Trigger4 UINT32 0x10000000 (WFR)*
41116~41119 -- Reserved -- --
41120 RW Inrush Current Enable UINT16 0=Disabled*, 1=Enabled
41121 RW Inrush Current Threshold UINT16 100 to 500 (%), 120*
41122 RW Inrush Current Hysteresis UINT16 1 to 1000 (0.1% to 100%), 5*
41123 RW Inrush Current Trigger4 UINT32 0x10000000 (WFR)*
41125~41127 -- Reserved -- --
41128 RW RVC Enable UINT16 0=Disabled*, 1=Enabled
41129 RW RVC Threshold UINT32 2 to 100 (0.2% to 10%Un), 50*
41131 RW RVC Hysteresis UINT32 1 to 50 (0.1% to 5%Un), 25*
41133 RW RVC Trigger4 UINT32 0*
41135~41153 -- Reserved -- --
41154 RW MSV #1 Enable UINT16 0=Disabled*, 1=Enabled
41155 RW MSV #1 Frequency UINT16 See Note 5, 10000*
41156 RW MSV #1 Threshold UINT16 3 to 1000 (x0.001Un), 50*
41157 RW MSV #1 Signalling Time UINT16 1 to 120s, 60s*
41158~41159 -- Reserved -- --
41160 RW MSV #2 Enable UINT16 0=Disabled*, 1=Enabled
41161 RW MSV #2 Frequency UINT16 See Note 5, 20000*
41162 RW MSV #2 Threshold UINT16 3 to 1000 (x0.001Un), 50*
41163 RW MSV #2 Signalling Time UINT16 1 to 120s, 60s*
41164~41165 -- Reserved -- --
41166 RW MSV #3 Enable UINT16 0=Disabled*, 1=Enabled
41167 RW MSV #3 Frequency UINT16 3 to 1000 (x0.001Un), 50*
41168 RW MSV #3 Threshold UINT16 See Note 5, 30000*
41169 RW MSV #3 Signalling Time UINT16 1 to 120s, 60s*
41170~41171 -- Reserved -- --
41172 RW Flicker Mode UINT16 0=120V, 1=230V*
Table 5-69 PQ Setup
135
CET Electric Technology
Notes:
1. The values for the Dip Threshold, Swell Threshold, Voltage Interruption Threshold and Dip/Swell Hysteresis should be configured to meet the
following criteria:
a) The Voltage Interruption Threshold shall be set below Dip Threshold.
b) The Dip/Swell Hysteresis must be less than the Dip/Swell Thresholds.
c) The Rapid Voltage Changes (RVC) Threshold must be less than the Dip and Swell Thresholds.
d) Regardless of whether Dip/Swell is enabled, the conditions for a), b) and c) must always be met.
2. The following table illustrates the details of the PQD Trigger register with a bit value of “1” meaning Active while “0” meaning Inactive.
Bit Trigger Bit Trigger Bit Trigger Bit Trigger
B0 to B26 Reserved B27 DWR B28 WFR B29 RMSR
Table 5-70 PQD Trigger Register
3. The following table illustrates the details for Dip/Swell Trigger register with a bit value of “1” meaning Active while “0” meaning Inactive.
Bit Trigger Event Type Bit Trigger Event Type Bit Trigger Event Type
B0 RO1 B8 RO1 B16 RO1
B1 RO2 B9 RO2 B17 RO2
Dip Swell Interruption
B2 RO3 B10 RO3 B18 RO3
B3 RO4 B11 RO4 B19 RO4
Table 5-71 Dip/Swell Trigger Register
4. The following table illustrates the details for Transient/Inrush Current/RVC Trigger register with a bit value of “1” meaning Active while “0”
meaning Inactive.
Bit Trigger Bit Trigger Bit Trigger Bit Trigger
B0 RO1 B2 RO3 B4 to B26 Reserved B28 WFR
B1 RO2 B3 RO4 B27 DWR B29 RMSR
Table 5-72 Transient/Inrush Current/RVC Trigger Register
5. The MSV Frequency Range is 600 to 30000 (x0.1Hz) for 50Hz power system or 700 to 30000 (x0.1Hz) for 60Hz power system.
5.11.8 Demand Setup
Register Property Description Format Range, Default*
41250 RW Sync. Mode UINT16 0=SLD*, 1=SYNC DI
41251 RW Demand Period UINT16 1 to 60minutes, 15*
41252 RW Number of Sliding Windows UINT16 1* to 15
41253 RW Self-read Time1 UINT16 Default = 0xFFFF
41254 RW Predicated Response UINT16 70* to 99
Table 5-73 Demand Setup
Notes:
1. The Self-Read Time allows the user to specify the time and day of the month for the Peak Demand Self-Read operation. The Self-Read Time
supports three options:
• A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
• A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read Time = Day * 100 +
Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15th
day of each month.
• A 0xFFFF value will disable the Self-Read operation and replace it with manual operation. A manual reset will cause the Max. Demand of
This Month to be transferred to the Max. Demand of Last Month and then reset. The terms This Month and Last Month will become Since
Last Reset and Before Last Reset.
136
CET Electric Technology
137
CET Electric Technology
138
CET Electric Technology
139
CET Electric Technology
140
CET Electric Technology
141
CET Electric Technology
142
CET Electric Technology
143
CET Electric Technology
5.11.13.4 SDR #4
Register Property Description Format Range/Options Default
46000 RW Recording Interval UINT16 0 to 60 min (0 means disabled) 10
46001 RW Recording Mode UINT16 0=Stop-When-Full, 1=First-In-First-Out 1
46002 RW # of Parameters UINT16 0 to 64 (0 means disabled) 63
46003 RW Parameter #1 UINT16 Ua TH RMS 11076
46004 RW Parameter #2 UINT16 Ub TH RMS 11077
46005 RW Parameter #3 UINT16 Uc TH RMS 11078
46006 RW Parameter #4 UINT16 U4 TH RMS 11079
46007 RW Parameter #5 UINT16 Ia TH RMS 11088
46008 RW Parameter #6 UINT16 Ib TH RMS 11089
46009 RW Parameter #7 UINT16 Ic TH RMS 11090
46010 RW Parameter #8 UINT16 I4 TH RMS 11091
46011 RW Parameter #9 UINT16 Pa TH 11679
46012 RW Parameter #10 UINT16 Pb TH 11680
46013 RW Parameter #11 UINT16 Pc TH 11681
46014 RW Parameter #12 UINT16 P Total TH 11715
46015 RW Parameter #13 UINT16 Qa TH 11682
46016 RW Parameter #14 UINT16 Qb TH 11683
46017 RW Parameter #15 UINT16 Qc TH 11684
46018 RW Parameter #16 UINT16 Q Total TH 11716
46019 RW Parameter #17 UINT16 Sa TH 11685
46020 RW Parameter #18 UINT16 Sb TH 11686
46021 RW Parameter #19 UINT16 Sc TH 11687
46022 RW Parameter #20 UINT16 S Total TH 11717
46023 RW Parameter #21 UINT16 PFa TH 11688
46024 RW Parameter #22 UINT16 PFb TH 11689
46025 RW Parameter #23 UINT16 PFc TH 11690
46026 RW Parameter #24 UINT16 PF TH 11718
46027 RW Parameter #25 UINT16 Ua DC Component 11103
46028 RW Parameter #26 UINT16 Ub DC Component 11104
46029 RW Parameter #27 UINT16 Uc DC Component 11105
46030 RW Parameter #28 UINT16 U4 DC Component 11106
46031 RW Parameter #29 UINT16 Uab DC Component 15000
46032 RW Parameter #30 UINT16 Ubc DC Component 15001
46033 RW Parameter #31 UINT16 Uca DC Component 15002
46034 RW Parameter #32 UINT16 Ia DC Component 11359
46035 RW Parameter #33 UINT16 Ib DC Component 11360
46036 RW Parameter #34 UINT16 Ic DC Component 11361
46037 RW Parameter #35 UINT16 I4 DC Component 11362
46038 RW Parameter #36 UINT16 Ua HD01 10504
46039 RW Parameter #37 UINT16 Ub HD01 10505
46040 RW Parameter #38 UINT16 Uc HD01 10506
46041 RW Parameter #39 UINT16 U4 HD01 10507
46042 RW Parameter #40 UINT16 Ua HD03 10512
46043 RW Parameter #41 UINT16 Ub HD03 10513
46044 RW Parameter #42 UINT16 Uc HD03 10514
46045 RW Parameter #43 UINT16 U4 HD03 10515
46046 RW Parameter #44 UINT16 Ua HD05 10520
46047 RW Parameter #45 UINT16 Ub HD05 10521
46048 RW Parameter #46 UINT16 Uc HD05 10522
46049 RW Parameter #47 UINT16 U4 HD05 10523
46050 RW Parameter #48 UINT16 Ua HD07 10528
46051 RW Parameter #49 UINT16 Ub HD07 10529
46052 RW Parameter #50 UINT16 Uc HD07 10530
46053 RW Parameter #51 UINT16 U4 HD07 10531
46054 RW Parameter #52 UINT16 Ua HD09 10536
46055 RW Parameter #53 UINT16 Ub HD09 10537
46056 RW Parameter #54 UINT16 Uc HD09 10538
46057 RW Parameter #55 UINT16 U4 HD09 10539
46058 RW Parameter #56 UINT16 Ua HD11 10544
46059 RW Parameter #57 UINT16 Ub HD11 10545
46060 RW Parameter #58 UINT16 Uc HD11 10546
46061 RW Parameter #59 UINT16 U4 HD11 10547
46062 RW Parameter #60 UINT16 Ua HD13 10552
46063 RW Parameter #61 UINT16 Ub HD13 10553
144
CET Electric Technology
145
CET Electric Technology
146
CET Electric Technology
147
CET Electric Technology
148
CET Electric Technology
149
CET Electric Technology
5.11.14.3 MMR #3
Register
Property Description Format Range/Options Default
Max. Min.
49100 49500 RW Self-read Time UINT16 See Note 1 0xFFFF
49101 49501 RW # of Parameters UINT16 0 to 20 18
49102 49502 RW Parameter #1 UINT16 Ua THD 10103
49103 49503 RW Parameter #2 UINT16 Ub THD 10104
49104 49504 RW Parameter #3 UINT16 Uc THD 10105
49105 49505 RW Parameter #4 UINT16 Ia THD 10115
49106 49506 RW Parameter #5 UINT16 Ib THD 10116
49107 49507 RW Parameter #6 UINT16 Ic THD 10117
49108 49508 RW Parameter #7 UINT16 Ia TDD 10065
49109 49509 RW Parameter #8 UINT16 Ib TDD 10066
49110 49510 RW Parameter #9 UINT16 Ic TDD 10067
49111 49511 RW Parameter #10 UINT16 Ia K-Factor 10080
49112 49512 RW Parameter #11 UINT16 Ib K-Factor 10081
49113 49513 RW Parameter #12 UINT16 Ic K-Factor 10082
49114 49514 RW Parameter #13 UINT16 Ua Crest Factor 10090
49115 49515 RW Parameter #14 UINT16 Ub Crest Factor 10091
49116 49516 RW Parameter #15 UINT16 Uc Crest Factor 10092
49117 49517 RW Parameter #16 UINT16 Ia Crest Factor 10085
49118 49518 RW Parameter #17 UINT16 Ib Crest Factor 10086
49119 49519 RW Parameter #18 UINT16 Ic Crest Factor 10087
49120~ 49520~ RW Parameter #19~ UINT16 Reserved 0
49121 49521 Parameter #20
Table 5-95 MMR #3 Setup
5.11.14.4 MMR #4
Register
Property Description Format Range/Options Default
Max. Min.
49200 49600 RW Self-read Time UINT16 See Note 1 0xFFFF
49201 49601 RW # of Parameters UINT16 0 to 20 20
49202 49602 RW Parameter #1 UINT16 U0 (Zero Sequence) 10059
49203 49603 RW Parameter #2 UINT16 U1 (+ve Sequence) 10061
49204 49604 RW Parameter #3 UINT16 U2 (-ve Sequence) 10060
49205 49605 RW Parameter #4 UINT16 I0 (Zero Sequence) 10062
49206 49606 RW Parameter #5 UINT16 I1 (+ve Sequence) 10064
49207 49607 RW Parameter #6 UINT16 I2 (-ve Sequence) 10063
49208 49608 RW Parameter #7 UINT16 Ua Pst 50001
49209 49609 RW Parameter #8 UINT16 Ub Pst 50002
49210 49610 RW Parameter #9 UINT16 Uc Pst 50003
49211 49611 RW Parameter #10 UINT16 Ua Plt 50004
49212 49612 RW Parameter #11 UINT16 Ub Plt 50005
49213 49613 RW Parameter #12 UINT16 Uc Plt 50006
49214 49614 RW Parameter #13 UINT16 Uab Deviation 10036
49215 49615 RW Parameter #14 UINT16 Ubc Deviation 10037
49216 49616 RW Parameter #15 UINT16 Uca Deviation 10038
49217 49617 RW Parameter #16 UINT16 Ua Deviation 10033
49218 49618 RW Parameter #17 UINT16 Ub Deviation 10034
49219 49619 RW Parameter #18 UINT16 Uc Deviation 10035
49220 49620 RW Parameter #19 UINT16 Freq. Dev. 10051
49221 49621 RW Parameter #20 UINT16 Reserved 0
Table 5-96 MMR #4 Setup
Note:
1. The Self-Read Time allows the user to specify the time and day of the month for the Peak Demand Self-Read operation. The Self-Read Time
supports three options:
• A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
• A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read Time = Day * 100 +
Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00pm on the
15th day of each month.
• A 0xFFFF value will disable the Self-Read operation and replace it with manual operation. A manual reset will cause the Max. Demand
of This Month to be transferred to the Max. Demand of Last Month and then reset. The terms This Month and Last Month will become
Since Last Reset and Before Last Reset.
150
CET Electric Technology
151
CET Electric Technology
152
CET Electric Technology
2. It is invalid when set Start Date as 0xFFFF. If one of season’s start time is set as 0xFFFF, then all the later seasons’ Start Date must be 0xFFFF
which means the valid period of last season is from Start Date to the end of this year.
3. The previous season must be earlier than the later season.
153
CET Electric Technology
154
CET Electric Technology
155
CET Electric Technology
156
CET Electric Technology
5.14 Information
5.14.1 Meter Information
Register Property Description Format Note
9800~9819 60200~60219 RO Meter Model1 CHAR See Note 1
e.g. 11005 shows
9820 60220 RO Firmware Version UINT16 the version is
V1.10.05
9821 60221 RO Modbus Version UINT16 e.g. 33 shows the
version is V3.3
e.g. 0107 means
the version is
V01.07
9822 60222 RO IEC 61850 Version UINT16 e.g. 0000 means
no 61850 support
or 61850 version
number error
e.g. 10 shows the
9823 60223 RO Hardware Version UINT16 version is V1.0
9824 60224 RO Firmware Update Date: Year-2000 UINT16 e.g. 1907012
9825 60225 RO Firmware Update Date: Month UINT16 means July 12,
9826 60226 RO Firmware Update Date: Day UINT16 2019
e.g. 1701030100
means the 100th
9827 60227 RO Serial Number UINT32 iMeter 7 that was
manufactured on
January 3rd, 2017
9829 60229 -- Reserved -- --
9830 60230 RO Feature Code2 UINT32
9832 60232 -- Reserved -- --
9833 60233 -- Reserved -- --
Bit0: System
Parameters Error
Bit1: Secret
9835 60235 RO ARM Diagnostic Info. UINT32 Parameters Error
Bit2: DSP Error
Bit3: Memory
Configuration Error
9837 60237 RO DSP Diagnostic Info. UINT32 Bit0: AD Error
157
CET Electric Technology
158
CET Electric Technology
159
CET Electric Technology
65 10065 20065 30065 Ia TDD 1973 11973 21973 31973 kWc Fund.
66 10066 20066 30066 Ib TDD 1974 11974 21974 31974 kvara Fund.
67 10067 20067 30067 Ic TDD 1975 11975 21975 31975 kvarb Fund.
68 10068 20068 30068 I4 TDD 1976 11976 21976 31976 kvarc Fund.
-- -- -- -- Reserved 1977 11977 21977 31977 kVAa Fund.
70 10070 20070 30070 Ia TDD Odd 1978 11978 21978 31978 kVAb Fund.
71 10071 20071 30071 Ib TDD Odd 1979 11979 21979 31979 kVAc Fund.
72 10072 20072 30072 Ic TDD Odd 1980 11980 21980 31980 dPFa
73 10073 20073 30073 I4 TDD Odd 1981 11981 21981 31981 dPFb
-- -- -- -- Reserved 1982 11982 21982 31982 dPFc
75 10075 20075 30075 Ia TDD Even 1983 11983 21983 31983 kWa H02
76 10076 20076 30076 Ib TDD Even 1984 11984 21984 31984 kWb H02
77 10077 20077 30077 Ic TDD Even 1985 11985 21985 31985 kWc H02
78 10078 20078 30078 I4 TDD Even 1986 11986 21986 31986 kvara H02
-- -- -- -- Reserved 1987 11987 21987 31987 kvarb H02
80 10080 20080 30080 Ia K-Factor 1988 11988 21988 31988 kvarc H02
81 10081 20081 30081 Ib K-Factor 1989 11989 21989 31989 kVAa H02
82 10082 20082 30082 Ic K-Factor 1990 11990 21990 31990 kVAb H02
83 10083 20083 30083 I4 K-Factor 1991 11991 21991 31991 kVAc H02
-- -- -- -- Reserved 1992 11992 21992 31992 PFa H02
85 10085 20085 30085 Ia Crest Factor 1993 11993 21993 31993 PFb H02
86 10086 20086 30086 Ib Crest Factor 1994 11994 21994 31994 PFc H02
87 10087 20087 30087 Ic Crest Factor … … … … …
88 10088 20088 30088 I4 Crest Factor 2715 12715 22715 32715 kWa H63
-- -- -- -- Reserved 2716 12716 22716 32716 kWb H63
90 10090 20090 30090 Ua Crest Factor 2717 12717 22717 32717 kWc H63
91 10091 20091 30091 Ub Crest Factor 2718 12718 22718 32718 kvara H63
92 10092 20092 30092 Uc Crest Factor 2719 12719 22719 32719 kvarb H63
93 10093 20093 30093 U4 Crest Factor 2720 12720 22720 32720 kvarc H63
94 10094 20094 30094 Ua MSV #1 2721 12721 22721 32721 kVAa H63
95 10095 20095 30095 Ub MSV #1 2722 12722 22722 32722 kVAb H63
96 10096 20096 30096 Uc MSV #1 2723 12723 22723 32723 kVAc H63
97 10097 20097 30097 Ua MSV #2 2724 12724 22724 32724 PFa H63
98 10098 20098 30098 Ub MSV #2 2725 12725 22725 32725 PFb H63
99 10099 20099 30099 Uc MSV #2 2726 12726 22726 32726 PFc H63
100 10100 20100 30100 Ua MSV #3 2727 12727 22727 32727 Ua TIHD
101 10101 20101 30101 Ub MSV #3 2728 12728 22728 32728 Ub TIHD
102 10102 20102 30102 Uc MSV #3 2729 12729 22729 32729 Uc TIHD
103 10103 20103 30103 Ua THD 2730 12730 22730 32730 U4 TIHD
104 10104 20104 30104 Ub THD 2731 12731 22731 32731 Ua TOIHD
105 10105 20105 30105 Uc THD 2732 12732 22732 32732 Ub TOIHD
106 10106 20106 30106 U4 THD 2733 12733 22733 32733 Uc TOIHD
107 10107 20107 30107 Ua TOHD 2734 12734 22734 32734 U4 TOIHD
108 10108 20108 30108 Ub TOHD 2735 12735 22735 32735 Ua TEIHD
109 10109 20109 30109 Uc TOHD 2736 12736 22736 32736 Ub TEIHD
110 10110 20110 30110 U4 TOHD 2737 12737 22737 32737 Uc TEIHD
111 10111 20111 30111 Ua TEHD 2738 12738 22738 32738 U4 TEIHD
112 10112 20112 30112 Ub TEHD 2739 12739 22739 32739 Ia TIHD
113 10113 20113 30113 Uc TEHD 2740 12740 22740 32740 Ib TIHD
114 10114 20114 30114 U4 TEHD 2741 12741 22741 32741 Ic TIHD
115 10115 20115 30115 Ia THD 2742 12742 22742 32742 I4 TIHD
116 10116 20116 30116 Ib THD -- -- -- -- Reserved
117 10117 20117 30117 Ic THD 2744 12744 22744 32744 Ia TOIHD
118 10118 20118 30118 I4 THD 2745 12745 22745 32745 Ib TOIHD
-- -- -- -- Reserved 2746 12746 22746 32746 Ic TOIHD
120 10120 20120 30120 Ia TOHD 2747 12747 22747 32747 I4 TOIHD
121 10121 20121 30121 Ib TOHD -- -- -- -- Reserved
122 10122 20122 30122 Ic TOHD 2749 12749 22749 32749 Ia TEIHD
123 10123 20123 30123 I4 TOHD 2750 12750 22750 32750 Ib TEIHD
-- -- -- -- Reserved 2751 12751 22751 32751 Ic TEIHD
125 10125 20125 30125 Ia TEHD 2752 12752 22752 32752 I4 TEIHD
126 10126 20126 30126 Ib TEHD -- -- -- -- Reserved
127 10127 20127 30127 Ic TEHD 2754 12754 22754 32754 Ua IHD00
128 10128 20128 30128 I4 TEHD 2755 12755 22755 32755 Ub IHD00
-- -- -- -- Reserved 2756 12756 22756 32756 Uc IHD00
130 10130 20130 30130 Uab Fund. 2757 12757 22757 32757 U4 IHD00
161
CET Electric Technology
131 10131 20131 30131 Ubc Fund. 2758 12758 22758 32758 Ua IHD01
132 10132 20132 30132 Uca Fund. 2759 12759 22759 32759 Ub IHD01
-- -- -- -- Reserved 2760 12760 22760 32760 Uc IHD01
500 10500 20500 30500 Ua HD00 2761 12761 22761 32761 U4 IHD01
501 10501 20501 30501 Ub HD00 … … … … …
502 10502 20502 30502 Uc HD00 3006 13006 23006 33006 Ua IHD63
503 10503 20503 30503 U4 HD00 3007 13007 23007 33007 Ub IHD63
504 10504 20504 30504 Ua HD01 3008 13008 23008 33008 Uc IHD63
505 10505 20505 30505 Ub HD01 3009 13009 23009 33009 U4 IHD63
506 10506 20506 30506 Uc HD01 3010 13010 23010 33010 Ia IHD00
507 10507 20507 30507 U4 HD01 3011 13011 23011 33011 Ib IHD00
… … … … … 3012 13012 23012 33012 Ic IHD00
748 10748 20748 30748 Ua HD62 3013 13013 23013 33013 I4 IHD00
749 10749 20749 30749 Ub HD62 -- -- -- -- Reserved
750 10750 20750 30750 Uc HD62 3015 13015 23015 33015 Ia IHD01
751 10751 20751 30751 U4 HD62 3016 13016 23016 33016 Ib IHD01
752 10752 20752 30752 Ua HD63 3017 13017 23017 33017 Ic IHD01
753 10753 20753 30753 Ub HD63 3018 13018 23018 33018 I4 IHD01
754 10754 20754 30754 Uc HD63 -- -- -- -- Reserved
755 10755 20755 30755 U4 HD63 … … … … …
756 10756 20756 30756 Ia HD00 3325 13325 23325 33325 Ia IHD63
757 10757 20757 30757 Ib HD00 3326 13326 23326 33326 Ib IHD63
758 10758 20758 30758 Ic HD00 3327 13327 23327 33327 Ic IHD63
759 10759 20759 30759 I4 HD00 3328 13328 23328 33328 I4 IHD63
-- -- -- -- Reserved -- -- -- -- Reserved
761 10761 20761 30761 Ia HD01 3330 13330 23330 33330 Ua TIH RMS
762 10762 20762 30762 Ib HD01 3331 13331 23331 33331 Ub TIH RMS
763 10763 20763 30763 Ic HD01 3332 13332 23332 33332 Uc TIH RMS
764 10764 20764 30764 I4 HD01 3333 13333 23333 33333 U4 TIH RMS
-- -- -- -- Reserved 3334 13334 23334 33334 Ua TOIH RMS
… … … … … 3335 13335 23335 33335 Ub TOIH RMS
1066 11066 21066 31066 Ia HD62 3336 13336 23336 33336 Uc TOIH RMS
1067 11067 21067 31067 Ib HD62 3337 13337 23337 33337 U4 TOIH RMS
1068 11068 21068 31068 Ic HD62 3338 13338 23338 33338 Ua TEIH RMS
1069 11069 21069 31069 I4 HD62 3339 13339 23339 33339 Ub TEIH RMS
-- -- -- -- Reserved 3340 13340 23340 33340 Uc TEIH RMS
1071 11071 21071 31071 Ia HD63 3341 13341 23341 33341 U4 TEIH RMS
1072 11072 21072 31072 Ib HD63 3342 13342 23342 33342 Ia TIH RMS
1073 11073 21073 31073 Ic HD63 3343 13343 23343 33343 Ib TIH RMS
1074 11074 21074 31074 I4 HD63 3344 13344 23344 33344 Ic TIH RMS
-- -- -- -- Reserved 3345 13345 23345 33345 I4 TIH RMS
1076 11076 21076 31076 Ua TH RMS -- -- -- -- Reserved
1077 11077 21077 31077 Ub TH RMS 3347 13347 23347 33347 Ia TOIH RMS
1078 11078 21078 31078 Uc TH RMS 3348 13348 23348 33348 Ib TOIH RMS
1079 11079 21079 31079 U4 TH RMS 3349 13349 23349 33349 Ic TOIH RMS
1080 11080 21080 31080 Ua TOH RMS 3350 13350 23350 33350 I4 TOIH RMS
1081 11081 21081 31081 Ub TOH RMS -- -- -- -- Reserved
1082 11082 21082 31082 Uc TOH RMS 3352 13352 23352 33352 Ia TEIH RMS
1083 11083 21083 31083 U4 TOH RMS 3353 13353 23353 33353 Ib TEIH RMS
1084 11084 21084 31084 Ua TEH RMS 3354 13354 23354 33354 Ic TEIH RMS
1085 11085 21085 31085 Ub TEH RMS 3355 13355 23355 33355 I4 TEIH RMS
1086 11086 21086 31086 Uc TEH RMS -- -- -- -- Reserved
1087 11087 21087 31087 U4 TEH RMS 3357 13357 23357 33357 Ua IH00 RMS
1088 11088 21088 31088 Ia TH RMS 3358 13358 23358 33358 Ub IH00 RMS
1089 11089 21089 31089 Ib TH RMS 3359 13359 23359 33359 Uc IH00 RMS
1090 11090 21090 31090 Ic TH RMS 3360 13360 23360 33360 U4 IH00 RMS
1091 11091 21091 31091 I4 TH RMS 3361 13361 23361 33361 Ua IH01 RMS
-- -- -- -- Reserved 3362 13362 23362 33362 Ub IH01 RMS
1093 11093 21093 31093 Ia TOH RMS 3363 13363 23363 33363 Uc IH01 RMS
1094 11094 21094 31094 Ib TOH RMS 3364 13364 23364 33364 U4 IH01 RMS
1095 11095 21095 31095 Ic TOH RMS … … … … …
1096 11096 21096 31096 I4 TOH RMS 3609 13609 23609 33609 Ua IH63 RMS
-- -- -- -- Reserved 3610 13610 23610 33610 Ub IH63 RMS
1098 11098 21098 31098 Ia TEH RMS 3611 13611 23611 33611 Uc IH63 RMS
1099 11099 21099 31099 Ib TEH RMS 3612 13612 23612 33612 U4 IH63 RMS
1100 11100 21100 31100 Ic TEH RMS 3613 13613 23613 33613 Ia IH00 RMS
162
CET Electric Technology
1101 11101 21101 31101 I4 TEH RMS 3614 13614 23614 33614 Ib IH00 RMS
-- -- -- -- Reserved 3615 13615 23615 33615 Ic IH00 RMS
1103 11103 21103 31103 Ua DC Component 3616 13616 23616 33616 I4 IH00 RMS
1104 11104 21104 31104 Ub DC Component -- -- -- -- Reserved
1105 11105 21105 31105 Uc DC Component 3618 13618 23618 33618 Ia IH01 RMS
1106 11106 21106 31106 U4 DC Component 3619 13619 23619 33619 Ib IH01 RMS
1107 11107 21107 31107 Ua Fund. 3620 13620 23620 33620 Ic IH01 RMS
1108 11108 21108 31108 Ub Fund. 3621 13621 23621 33621 I4 IH01 RMS
1109 11109 21109 31109 Uc Fund. -- -- -- -- Reserved
1110 11110 21110 31110 U4 Fund. … … … … …
1111 11111 21111 31111 Ua H02 RMS 3928 13928 23928 33928 Ia IH63 RMS
1112 11112 21112 31112 Ub H02 RMS 3929 13929 23929 33929 Ib IH63 RMS
1113 11113 21113 31113 Uc H02 RMS 3930 13930 23930 33930 Ic IH63 RMS
1114 11114 21114 31114 U4 H02 RMS 3931 13931 23931 33931 I4 IH63 RMS
1115 11115 21115 31115 Ua H03 RMS -- -- -- -- Reserved
1116 11116 21116 31116 Ub H03 RMS 3933 13933 23933 33933 Ua Angle
1117 11117 21117 31117 Uc H03 RMS 3934 13934 23934 33934 Ub Angle
1118 11118 21118 31118 U4 H03 RMS 3935 13935 23935 33935 Uc Angle
… … … … … 3936 13936 23936 33936 U4 Angle
1351 11351 21351 31351 Ua H62 RMS 3937 13937 23937 33937 Ia Angle
1352 11352 21352 31352 Ub H62 RMS 3938 13938 23938 33938 Ib Angle
1353 11353 21353 31353 Uc H62 RMS 3939 13939 23939 33939 Ic Angle
1354 11354 21354 31354 U4 H62 RMS 3940 13940 23940 33940 I4 Angle
1355 11355 21355 31355 Ua H63 RMS -- -- -- -- Reserved
1356 11356 21356 31356 Ub H63 RMS 3942 13942 23942 33942 Ua Fund. Angle
1357 11357 21357 31357 Uc H63 RMS 3943 13943 23943 33943 Ub Fund. Angle
1358 11358 21358 31358 U4 H63 RMS 3944 13944 23944 33944 Uc Fund. Angle
1359 11359 21359 31359 Ia DC Component 3945 13945 23945 33945 U4 Fund. Angle
1360 11360 21360 31360 Ib DC Component 3946 13946 23946 33946 Ua H02 Angle
1361 11361 21361 31361 Ic DC Component 3947 13947 23947 33947 Ub H02 Angle
1362 11362 21362 31362 I4 DC Component 3948 13948 23948 33948 Uc H02 Angle
-- -- -- -- Reserved 3949 13949 23949 33949 U4 H02 Angle
1364 11364 21364 31364 Ia Fund. … … … … …
1365 11365 21365 31365 Ib Fund. 4190 14190 24190 34190 Ua H63 Angle
1366 11366 21366 31366 Ic Fund. 4191 14191 24191 34191 Ub H63 Angle
1367 11367 21367 31367 I4 Fund. 4192 14192 24192 34192 Uc H63 Angle
-- -- -- -- Reserved 4193 14193 24193 34193 U4 H63 Angle
1369 11369 21369 31369 Ia H02 RMS 4194 14194 24194 34194 Ia Fund. Angle
1370 11370 21370 31370 Ib H02 RMS 4195 14195 24195 34195 Ib Fund. Angle
1371 11371 21371 31371 Ic H02 RMS 4196 14196 24196 34196 Ic Fund. Angle
1372 11372 21372 31372 I4 H02 RMS 4197 14197 24197 34197 I4 Fund. Angle
-- -- -- -- Reserved -- -- -- -- Reserved
1374 11374 21374 31374 Ia H03 RMS 4199 14199 24199 34199 Ia H02 Angle
1375 11375 21375 31375 Ib H03 RMS 4200 14200 24200 34200 Ib H02 Angle
1376 11376 21376 31376 Ic H03 RMS 4201 14201 24201 34201 Ic H02 Angle
1377 11377 21377 31377 I4 H03 RMS 4202 14202 24202 34202 I4 H02 Angle
-- -- -- -- Reserved -- -- -- -- Reserved
… … … … … … … … … …
1669 11669 21669 31669 Ia H62 RMS 4504 14504 24504 34504 Ia H63 Angle
1670 11670 21670 31670 Ib H62 RMS 4505 14505 24505 34505 Ib H63 Angle
1671 11671 21671 31671 Ic H62 RMS 4506 14506 24506 34506 Ic H63 Angle
1672 11672 21672 31672 I4 H62 RMS 4507 14507 24507 34507 I4 H63 Angle
-- -- -- -- Reserved
Notes:
All the parameters’ values are single precision float type except energy parameters which are 32-bit signed integer type.
163
CET Electric Technology
165
CET Electric Technology
+4 UINT32 Setpoint Group # (0~23 represents Group 1 to 24 for Standard Setpoint, 0~15 for HS Setpoint)
+6 FP32 Max. Magnitude during Setpoint Duration
+8 UINT32 Duration
8. The following table illustrates the structure of RO Released by Impulse Control event value occupying 4 registers.
Offset Format Description
+0 UINT32 B0~B3 represents RO1 to RO4
+2 UINT32 Pulse Width (x0.1s)
9. The following table illustrates the structure of DI SP Active Return event value occupying 4 registers.
Offset Format Description
+0 UINT32 B0~B7 represents DI1 to DI8
+2 UINT32 Trigger (Please refer to Table 5-57 DIx Trigger)
10. The following table illustrates the structure of RO Operated/Released by Dip/Swell/Transient event value occupying 4 registers.
Offset Format Description
+0 UINT32 B0~B3 represents RO1 to RO4
+2 UINT32 Event Type (0=Transient, 1=Dip, 2=Swell, 3=Interruption)
11. The following table illustrates the structure of Motor Startup End event value occupying 6 registers.
Offset Format Description
+0 FP32 Imax
+2 FP32 Umin
+4 UINT32 Duration(ms)
166
CET Electric Technology
167
CET Electric Technology
168
CET Electric Technology
169
CET Electric Technology
170
CET Electric Technology
171
CET Electric Technology
Contact us
CET Electric Technology Inc.
Tel: +86.755.8341.5187
Fax: +86.755.8341.0291
Email: [email protected]
Web: www.cet-global.com
172