VALVE SPECIFICATIONS
Pressure/Temp. rating: 2500 kPa / -30°C to 120°C
Materials:
- Flow Optimizer: Glass Filled Polymer
- Cartridge: AISI Type 304 Stainless Steel
AISI Type 17-7 PH Stainless Steel Spring
- Body: Forged Brass ASTM B283
- End Connections: Brass
- Stem: Brass
- Stem Seals: EPDM O-Rings
- Ball Valve: Nickel-Plated Brass Ball
- Ball Seals: Teflon Seals with EPDM O-Rings
Flow Rate Range: 0.021 l/s – 7.192 l/s
40 Large 1 1/2"
Large 359.4 64 40 182.9 221.5 85.9 63.5 298.5 131.1 5.5
50 2"
NOTES:
1
Select appropriate Union Connection length and add to "A" dimension, Housing Length.
2
Select the Fixed End first and the Union End second. Mixing different size tailpieces will affect the Kv-value.
3
Tailpiece not available, threaded tailpiece used with an adapter.
1 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
CONTROL & BALANCE VALVE 15 – 50mm AUTOMIZER
ACTUATED BALL Kvs AND FLOW RATE TABLE (l/sec)
MODEL FLOWRATE (l/sec) @ Differential Pressure (kPa)*
FULL CLOSE
SIZE NO. Kvs
PORT OFF ∆P2
(Optimizer)
10 20 30 40 50 60 70 80 90 100 (m3/h)
F3AR1_1 0.030 0.043 0.053 0.061 0.068 0.074 0.080 0.086 0.091 0.096 0.345
F3AR1_2 0.053 0.075 0.092 0.106 0.119 0.130 0.140 0.150 0.159 0.168 0.603
F3AR1_3 0.098 0.139 0.171 0.197 0.220 0.241 0.260 0.278 0.295 0.311 1.121
15mm 900kPa
F3AR1_4 0.182 0.570 0.315 0.363 0.406 0.445 0.481 0.514 0.545 0.575 2.069
F3AR1_5 0.280 0.396 0.485 0.560 0.627 0.686 0.741 0.792 0.841 0.886 3.190
F3AR1_6 • 0.469 0.664 0.813 0.939 1.050 1.150 1.240 1.330 1.410 1.480 5.345
F3AR1_1 0.030 0.043 0.053 0.061 0.068 0.074 0.080 0.086 0.091 0.096 0.345
F3AR1_2 0.053 0.075 0.092 0.106 0.119 0.130 0.140 0.150 0.159 0.168 0.603
F3AR1_3 0.098 0.139 0.171 0.197 0.220 0.241 0.260 0.278 0.295 0.311 1.121
20mm 900kPa
F3AR1_4 0.197 0.278 0.341 0.394 0.440 0.482 0.521 0.557 0.591 0.623 2.241
F3AR1_5 0.326 0.460 0.564 0.651 0.728 0.798 0.862 0.921 0.977 1.030 3.707
F3AR1_6 • 0.560 0.792 0.971 1.120 1.250 1.370 1.480 1.580 1.680 1.770 6.379
F3AR1_1 0.023 0.032 0.039 0.045 0.051 0.056 0.060 0.064 0.068 0.072 0.259
F3AR1_2 0.045 0.064 0.079 0.091 0.102 0.111 0.120 0.129 0.136 0.144 0.517
25mm F3AR1_3 0.098 0.139 0.171 0.197 0.220 0.241 0.260 0.278 0.295 0.311 1.121
900kPa
small F3AR1_4 0174 0.246 0.302 0.348 0.389 0.427 0.461 0.493 0.523 0.551 1.983
F3AR1_5 0.288 0.407 0.498 0.576 0.643 0.705 0.761 0.814 0.863 0.910 3.276
F3AR1_6 • 0.523 0.739 0.905 1.050 1.170 1.280 1.380 1.480 1.570 1.650 5.948
F3AR2_3 0.318 0.450 0.551 0.636 0.711 0.779 0.841 0.900 0.954 1.010 3.621
25mm F3AR2_4 0.538 0.760 0.931 1.080 1.200 1.320 1.420 1.520 1.610 1.700 6.121
690kPa
large F3AR2_1 0.795 1.120 1.380 1.590 1.780 1.950 2.100 2.250 2.390 2.510 9.052
F3AR2_2 • 1.090 1.540 1.890 2.180 2.440 2.670 2.890 3.080 3.270 3.450 12.41
F3AR2_3 0.303 0.525 0.525 0.606 0.677 0.742 0.801 0.857 0.909 0.958 3.448
F3AR2_4 0.553 0.782 0.957 1.110 1.240 1.350 1.460 1.560 1.660 1.750 6.293
32mm 690kPa
F3AR2_1 0.788 1.110 1.360 1.580 1.760 1.930 2.080 2.230 2.360 2.490 8.966
F3AR2_2 • 1.110 1.560 1.910 2.210 2.470 2.710 2.930 3.130 3.320 3.500 12.59
F3AR2_3 0.303 0.428 0.525 0.606 0.677 0.742 0.801 0.857 0.909 0.958 3.448
40mm F3AR2_4 0.553 0.782 0.957 1.110 1.240 1.350 1.460 1.560 1.660 1.750 6.293
690kPa
small F3AR2_1 0.772 1.090 1.340 1.540 1.730 1.890 2.040 2.180 2.320 2.440 8.793
F3AR2_2 • 1.100 1.550 1.900 2.200 2.460 2.690 2.910 3.110 3.290 3.470 12.50
F3AR3_1 2.570 3.640 4.460 5.150 5.760 6.310 6.810 7.280 7.720 8.140 29.31
40mm
F3AR3_2 690kPa 3.940 5.570 6.820 7.880 8.800 9.650 10.40 11.10 11.80 12.50 44.83
large
F3AR3_3 • 5.150 7.280 8.920 10.30 11.50 12.60 13.60 14.60 15.40 16.30 58.62
F3AR3_1 2.570 3.640 4.460 5.150 5.760 6.310 6.810 7.280 7.720 8.140 29.31
50mm F3AR3_2 690kPa 3.940 5.570 6.820 7.880 8.800 9.650 10.40 11.10 11.80 12.50 44.83
F3AR3_3 • 5.150 7.280 8.920 10.30 11.50 12.60 13.60 14.60 15.40 16.30 58.61
NOTES:
2
Close-Off Pressures measured with 35 in-lb. actuator. The “Close Off Pressure” is the maximum allowable pressure drop across the valve body when the valve is
fully closed. Since the torque available from the actuator helps determine the close off pressure rating, higher pressure ratings can be achieved by using a larger
actuator.
2 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
CONTROL & BALANCE VALVE 15 – 50mm AUTOMIZER
3 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
CONTROL & BALANCE VALVE 15 – 50mm AUTOMIZER
CARTRIDGE FLOW RATES (+/-5%)
40 - 50mm, 1 1/2" - 2" (2" cartridge)
Range 1 Range 2 Range 4 Range 8
l/s GPM 10-95 22-210 40-390 90-880
kPaD kPaD kPaD kPaD
0.757 12.00 F3C2136
0.883 14.00 F3C2142
1.009 16.00 F3C2148
1.136 18.00 F3C2154 F3C2236
1.262 20.00 F3C2160
1.325 21.00 F3C2242
1.388 22.00 F3C2166
1.514 24.00 F3C2172 F3C2248 F3C2436
1.640 26.00 F3C2178
1.703 27.00 F3C2254
1.767 28.00 F3C2184 F3C2442
1.893 30.00 F3C2190 F3C2260
2.019 32.00 F3C2196 F3C2448
2.082 33.00 F3C2266
2.145 34.00 F3C21102
2.271 36.00 F3C21108 F3C2272 F3C2454 F3C2836
2.397 38.00 F3C21114
2.461 39.00 F3C2278
2.524 40.00 F3C2460
2.650 42.00 F3C2284 F3C2842
2.776 44.00 F3C2466
2.839 45.00 F3C2290
3.028 48.00 F3C2296 F3C2472 F3C2848
3.218 51.00 F3C22102
3.281 52.00 F3C2478
3.407 54.00 F3C22108 F3C2854
3.533 56.00 F3C2484
3.596 57.00 F3C22114
3.785 60.00 F3C2490 F3C2860
4.038 64.00 F3C2496
4.164 66.00 F3C2866
4.290 68.00 F3C24102
4.543 72.00 F3C24108 F3C2872
4.795 76.00 F3C24114
4.921 78.00 F3C2878
5.300 84.00 F3C2884
5.678 90.00 F3C2890
6.057 96.00 F3C2896
6.435 102.00 F3C28102
6.814 108.00 F3C28108
7.192 114.00 F3C28114
4 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
CONTROL & BALANCE VALVE 15 – 50mm AUTOMIZER
ACTUATOR SPECIFICATIONS
Control Signal: On/Off (On/Off Or 3-Point Floating), Modulating (Analog Or Pulse Width Modulation)
Power Supply: 24VAC + 20% 50/60Hz, 110VAC 60Hz, or 220 50Hz, 24VDC + 10%
Power Consumption: 2 – 10VA, dependent on speed selected
Transformer Sizing: 3 VA-Class 2 power source
Overload Protection: Electronic throughout 0 – 95° rotation
Torque: Min 35 in-lbs
Angle of Rotation: Max 95°, Electronically or Mechanically adjustable 20 – 100%
Position Indication: Built in indicator
Direction of Rotation: Reversible with switch - Clockwise/ Counter Clockwise
Manual Over-Ride: Push button
Humidity Rating: 5 to 95% RH, non condensating
Ambient Temperature: -30°C to +60°C (-22°F to +130°F)
Storage Temperature: -40°C to +80°C (-40°F to +176°F)
Auxiliary Switch: Adjustable 0° to 95° 6 A @ 24VAC, (Single pole double throw) (form C contact)
Zero and Span: Programmable zero and span adjustment
Fail-Safe: Spring Return, Power Caps or Enerdrive Capacitive, programmable fail-safe system.
Torque of 44 in-lb • • • •
Torque of 62 in-lb • •
Control Signal: On/Off
Control Signal: 3 Point • • •
Control Signal:
• • •
Modulating 0–10 Vdc
Power Supply 24 VAC • • • • • •
Speed: 108 sec
Speed: 90 sec • • • • • •
Built-In Auxiliary Switches • •
Fail Safe (Spring Return) • •
Torque of 35 in-lb • • • • • • • •
Torque of 70 in-lb •
Control Signal: On/Off • • • •
Control Signal: 3 Point • • •
Control Signal:
• •
Modulating 0–10 Vdc
Power Supply 24 Vac • • • • • • •
Power Supply 120 Vac • •
Speed: 90 sec • • • • • • • • •
Built-In Auxiliary Switch • • • •
Fail Safe (Spring Return) • • • • • • • •
5 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
CONTROL & BALANCE VALVE 15 – 50mm AUTOMIZER
ML6161D ML6174D ML7161A ML7174A ML6185A ML6185C ML8185A ML8185C ML7285A ML7285C
Honeywell 2006 2009 2008 2001 1000 1008 1008 1006 1007 1005
Torque of 35 in-lb • •
Torque of 50 in-lb • • • • • •
Torque of 70 in-lb • •
Control Signal: On/Off • •
Control Signal: 3 Point • • • •
Control Signal:
• • • •
Modulating 4–20 mA/2–10 Vdc
Power Supply 24 VAC • • • • • • • • • •
Speed: 90 sec • • • • • • • • • •
Built-In Auxiliary Switches • • • • •
Fail Safe (Spring Return) • • • • • •
Neptronic BBT-
24
BBT-
1000
BBT-
1060
BBT-
1021
BBT-
1080
BBTF-
1000
BBTF-
1060
BBTF-
1021
BBTF-
1080
BBTHV-
1100
BBTHV-
1160
BBTHV-
1120
BBTHV-
1180
BBM
2000A
BBM
2060A
Torque of 50 in-lb • • • • • • • • • • • • • • •
Control Signal: On/Off • • • • • • • • • • • • •
Control Signal: 3 Point • • • • • • • • • • • • •
Control Signal:
Modulating 2-10 Vdc, • •
4-20mA and PWM
Power Supply 24 VAC • • • • • • • • • • •
Power Supply 110 VAC • • • •
Speed: 90 sec • • • • •
Speed: 20-30 sec • • • • • • • • • •
Built-In Auxiliary
• • • • • •
Switches
Fail Safe
TM • • • • • • •
(Enerdrive System)
6 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
CONTROL & BALANCE VALVE 15 – 50mm AUTOMIZER
Belimo LM24 LM24S LF24 LF24S LF120 LF120S LF24-3 LF24-3S LM24SR LF24SR LF24SRS
Torque of 35 in-lb • • • • • • • • • • •
Control Signal: On-Off • • • • • •
Control Signal: 3-point • • • •
Control Signal: Modulating
2-10 VDC • • •
Power Supply: 24 VAC • • • • • • • • •
Power Supply: 120 VAC • •
Speed: 75 Second • • • •
Speed: 80-110 Second • • •
Speed: 150 Second • • • •
Built in Auxiliary Switch • • • • •
Fail Safe: Spring Return • • • • • • • •
7 10/2004
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.