The String Monitoring Unit monitors up to 16 DC current inputs and 1 voltage input from photovoltaic strings. It measures currents, voltages, temperature and receives digital and analog inputs. The unit communicates via RS485 and can be configured through its DIP switches or via Modbus protocol. It is housed in a DIN rail enclosure and operates from 22-27VDC.

Uploaded by

risqi rotbi
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views

DB String Monitoring Unit 1625 en

The String Monitoring Unit monitors up to 16 DC current inputs and 1 voltage input from photovoltaic strings. It measures currents, voltages, temperature and receives digital and analog inputs. The unit communicates via RS485 and can be configured through its DIP switches or via Modbus protocol. It is housed in a DIN rail enclosure and operates from 22-27VDC.

Uploaded by

risqi rotbi
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

STRING MONITORING

UNIT 1625 (SMU 1625)


Item No.: 421.927

DESCRIPTION OF FUNCTIONS The String Monitoring Unit was specially developed for multiple channel measurement of string
currents in PV systems. Regardless of the inverter used, the measurement unit monitors the
DC voltage sided strings of PV systems and enables quick identification of defects and
troubleshooting.

TECHNICAL DATA
Input current: Number: 16
Measuring range: 0 … 25 A DC
Precision: ≤ 0.5 %

Input voltage: Number: 1


Measuring range: 0 … 1,500 V DC
Precision: < 1.5 %

Input temperature: Number: 1


Type: PT100 as 3-wire circuit
Measuring range: 0 … 300 °C
Precision: < 1.5 %

Digital input: Number: 4


Type: PNP digital input, 24 V DC
Maximum input current: 24 V DC

Analog current input: Number: 1


Type: Current input
Measuring range: 0 … 20 mA
Precision: < 1.5 %

Analog voltage input: Number: 1


Type: Voltage input
Measuring range: 0 … 10 V

Supply: Supply voltage: 22 … 27 V DC


Power consumption: <3W

Communication interface: Standard: RS485


Data format: 8N1 (factory setting), 8E1, 8O1
Adjustable via Modbus
Protocols: Modbus RTU
Baud rate: 2.400 bps, 4.800 bps, 9.600 bps(factory setting), 19.200 bps
Bus address: Defined by DIP-switches

Information subject to change, errors and omissions excepted / As at 05-2016 1|2


Ambient conditions: Operating temperature: -20 °C … +80 °C
Working atmosphere: Without corrosive gas

Housing: Dimensions (W x H x D): 267 x 108 x 52 mm


Type of installation: DIN EN mounting rail
Weight: 795 g

SETTING OF MODBUS ADDRESS

Protocol = Modbus
Parity = none
Baud rate = 19200
Address = 2

Protocol = Modbus
Parity = none
Baud rate = 9600
Address = 55

meteocontrol GmbH | Spicherer Straße 48 | 86157 Augsburg | Germany | Telephone +49 (0)821 34666 - 0 | Fax +49 (0)821 34666 - 11
E-Mail [email protected] | Web www.meteocontrol.com

Information subject to change, errors and omissions excepted / As at 05-2016 2|2