Neptronic Thermostat TDU-TDF00,30,60-190619
Neptronic Thermostat TDU-TDF00,30,60-190619
Neptronic Thermostat TDU-TDF00,30,60-190619
Models
Model # Temp RH CO2 PIR VOC Color
TDU00-100
TDF00-100
●
TDU00-101
TDF00-101
● ●
TDU00-102
TDF00-102
● ● ●
grey LCD,
TDU00-104
TDF00-104
● ● white
enclosure
TDU00-105
TDF00-105
● ● ●
TDU00-106
TDF00-106
● ● ● ●
TDU00-107
TDF00-107
● ● ● ● ●
TDU00 Series TDF00 Series
Features Functions
• TDU series used to configure and operate the EVCB VAV
Onboard Sensors controllers
• TDF series used to configure and operate the EFCB Fan Coil
• Temperature sensor (°C/°F) controllers
• Humidity sensor (%RH), select models • Three wire connection between room sensor and controller
• Carbon dioxide sensor (CO2), select models • Elegant design
• PIR motion detection sensor, select models • Universal wall-mount design
• Volatile organic compounds (VOC), select models • Selectable Fahrenheit or Celsius scale
• Network service port via on-board mini USB connector
• Dimensions: 124mm x 83mm x 20mm (4.88” x 3.25” x 0.78”)
• Dimensions for models with CO2 sensor:
124mm x 83mm x 24mm (4.88” x 3.25” x 0.95”)
TDU-TDF00,30,60-190619 Page | 1
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers
Technical Specifications
Description TDU00 / TDU30 / TDU60 / TDF00 / TDF30 / TDF60 Series
Temperature Sensor
Setpoint Range 10ºC to 40ºC [50ºF to 104ºF]
Control Accuracy Temperature: ±0.4ºC [0.8ºF]
Display Resolution ±0.1ºC [0.2ºF]
Humidity Sensor (select models)
Setpoint Range (EFCB only) 10 to 65%RH
Control Accuracy (EFCB only) ±3.5% RH
Display Resolution 0.1%
CO2 Sensor (select models)
Operating Principle Self-calibrating, Non-Dispersive Infrared (NDIR)
Sensor Range 400 to 2000 ppm
Accuracy ±30 ppm ±3% of reading (Accuracy is defined after minimum 3 weeks of continuous operation)
Response Time 2 minutes by 90%
PIR Motion Sensor (select models)
Operating Principle Passive Infrared (PIR)
Detection Angle 100º
Detection Distance 4m [13ft]
4m
100º
Detection Area (13ft)
B H
www.neptronic.com Page | 2
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers
Interface
Wiring
We strongly recommend that all Neptronic products be wired to a
separate grounded transformer and that transformer shall
service only Neptronic products. This precaution will prevent
Avoid touching the CO2 and VOC interference with, and/or possible damage to incompatible
sensors as this may cause
incorrect readings. equipment.
Mode Selection (JP1)
CO2 sensor
TB1
RUN:
1 COM
2 PWR
Connect to
EVCB/EFCB
Digital Room Sensor is in Operation Mode.
3
4
DATA Digital Room Sensor must be set in this mode to operate
5 properly. If not locked, following setpoint and control mode
A+ Optional: connect to
6
7 B-
BACnet network to options can be modified by the end user:
enable service port
JP1
• Heating and Cooling ON
RUN
• Cooling only ON
•
VOC sensor
Heating only ON
PGM
• OFF
Mode Selector Jumper
JP1
RUN
(EFCB only)
RUN = Operation Mode
PGM = Programming Mode
PGM • Fan ON
• Humidify and De-humidify ON
•
Temperature and
Humidity sensors Humidify only ON
• Dehumidify only ON
BACnet
service port JP1
RUN PGM:
Digital Room Sensor is set in Programming Mode.
PGM
Mounting Instructions
CAUTION: Remove power to avoid a risk of malfunction.
A. Remove the captive screw that’s holding the base and the front cover of the unit together.
B. Lift the front cover of the unit to separate it from the base.
C. Pull all wires through the holes in the base.
D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
E. Mount the control module on the base and secure using the screw.
A B C D E
www.neptronic.com Page | 3
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers
Access to Menus
The menus and options are the same for both the TDU and TDF Digital Room Sensors. However, the action button or the button
used to access the menus and save changes is different for each Digital Room Sensor.
Operation Mode
The Mode Selector Jumper JP1 must be set to the RUN position (Operation Mode). Refer to the Wiring section on page 3.
EVCB
CO2 reading in ppm
(CO2 display option must be
Appears if in Night Set Back (NSB) enabled in programming mode)
or Occupancy (OCC) mode. Flashes
if overridden by user.
Press twice to
Press for 5 sec. display setpoint
to display air flow Press once to display C
(if using pressure sensors) control mode
Press to toggle
between °C and °F
Actual demand
Appears if setpoint
adjustment is locked
Fan icon appears in fan-powered box applications only
%RH
Setpoint value
EFCB
Appears if in Night Set Back (NSB) or CO2 reading in ppm
Occupancy (OCC) mode. Flashes if (CO2 display option must be
overridden by user. enabled in programming mode)
Press twice to
display setpoint
Press for 5 sec. to display Press once to display Press both keys for 3 sec. to
C toggle between °C and °F
Humidity Setpoint Mode Fan Speed Mode Press once to display
control mode
- LOW - Off
www.neptronic.com Page | 4
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers
Power Up
Upon power up, the LCD illuminates and all segments appear for 2 seconds. The Digital Room Sensor then displays its current
version for 2 seconds followed by the current version of the controller for 2 seconds. Pressing any key on the Digital Room Sensor
illuminates the LCD for 4 seconds.
Humidity Setpoint Display and Adjustment (Digital Room Sensor with Humidity Option)
If enabled via the configuration menu for the EVCB and in a humidity mode other than OFF for the EFCB, the Digital Room Sensor
displays the temperature reading for 8 seconds and then displays the humidity reading for 2 seconds. If the sensor is disconnected
or short circuited, then the unit displays the sensor's limit.
To access the humidity setpoint (EFCB only), press the key for 5 seconds. The humidity setpoint will be displayed for 5 seconds.
To adjust the setpoint press the and keys while the setpoint is displayed. The unit will return to normal mode if you do not press
any key for 3 seconds. The changed values will be saved automatically.
Control Mode
To access the Control Mode, press the key on the TDU or on the TDF. The Control Mode appears for 5 seconds. Press
the (TDU) or (TDF) key to scroll through the following control modes. These options can vary depending on the options
configured by the installer.
• Auto (Automatic Cooling or Heating)
• Cooling only (on, with cooling symbol)
• Heating only (on, with heating symbol)
• OFF (if it is not disabled in Programming Mode)
Occupancy Mode
This function is only available if enabled by your installer. If the appropriate digital input contact is triggered, the Digital Room
Sensor enters Occupancy Mode (the symbol appears) and uses the NoOcc setpoints defined in program mode. If not locked, no
occupancy mode can be overridden for a period by pressing the ( ) button. Each time you press the ( ) button, 15
minutes are added to the override (up to a maximum defined in program mode). Press the fan ( ) button until “0” is displayed
to disable the override. The icon will flash and the remaining override time will be displayed in minutes.
www.neptronic.com Page | 5
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers
Programming Mode
To access the programming mode, the Mode Selector Jumper (JP1) must be set to the PGM (Programming Mode) position and
terminal 3 (Data) must be disconnected from the Digital Room Sensor. Refer to the Wiring section on page 3 for more details.
www.neptronic.com Page | 6
Notes
Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic
authorized distributor, please consult www.neptronic.com.