TDU/TDF Universal Digital Room Sensor

For EVCB and EFCB Controllers

Models
Model # Temp RH CO2 PIR VOC Color
TDU00-100
TDF00-100

TDU00-101
TDF00-101
● ●
TDU00-102
TDF00-102
● ● ●
grey LCD,
TDU00-104
TDF00-104
● ● white
enclosure
TDU00-105
TDF00-105
● ● ●
TDU00-106
TDF00-106
● ● ● ●
TDU00-107
TDF00-107
● ● ● ● ●
TDU00 Series TDF00 Series

Model # Temp RH CO2 PIR VOC Color


TDU30-100
TDF30-100

TDU30-101
TDF30-101
● ●
TDU30-102
TDF30-102
● ● ●
black LCD,
TDU30-104
TDF30-104
● ● black
enclosure
TDU30-105
TDF30-105
● ● ●
TDU30-106
TDF30-106
● ● ● ●
TDU30-107
TDF30-107
● ● ● ● ●
TDU30 Series TDF30Series

Model # Temp RH CO2 PIR VOC Color


TDU60-100
TDF60-100

TDU60-101
TDF60-101
● ●
TDU60-102
TDF60-102
● ● ●
black LCD,
TDU60-104
TDF60-104
● ● white
enclosure
TDU60-105
TDF60-105
● ● ●
TDU60-106
TDF60-106
● ● ● ●
TDU60-107
TDF60-107
● ● ● ● ●
TDU60 Series TDF60 Series

Features Functions
• TDU series used to configure and operate the EVCB VAV
Onboard Sensors controllers
• TDF series used to configure and operate the EFCB Fan Coil
• Temperature sensor (°C/°F) controllers
• Humidity sensor (%RH), select models • Three wire connection between room sensor and controller
• Carbon dioxide sensor (CO2), select models • Elegant design
• PIR motion detection sensor, select models • Universal wall-mount design
• Volatile organic compounds (VOC), select models • Selectable Fahrenheit or Celsius scale
• Network service port via on-board mini USB connector
• Dimensions: 124mm x 83mm x 20mm (4.88” x 3.25” x 0.78”)
• Dimensions for models with CO2 sensor:
124mm x 83mm x 24mm (4.88” x 3.25” x 0.95”)

TDU-TDF00,30,60-190619 Page | 1
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers

Technical Specifications
Description TDU00 / TDU30 / TDU60 / TDF00 / TDF30 / TDF60 Series
Temperature Sensor
Setpoint Range 10ºC to 40ºC [50ºF to 104ºF]
Control Accuracy Temperature: ±0.4ºC [0.8ºF]
Display Resolution ±0.1ºC [0.2ºF]
Humidity Sensor (select models)
Setpoint Range (EFCB only) 10 to 65%RH
Control Accuracy (EFCB only) ±3.5% RH
Display Resolution 0.1%
CO2 Sensor (select models)
Operating Principle Self-calibrating, Non-Dispersive Infrared (NDIR)
Sensor Range 400 to 2000 ppm
Accuracy ±30 ppm ±3% of reading (Accuracy is defined after minimum 3 weeks of continuous operation)
Response Time 2 minutes by 90%
PIR Motion Sensor (select models)
Operating Principle Passive Infrared (PIR)
Detection Angle 100º
Detection Distance 4m [13ft]

4m
100º
Detection Area (13ft)

VOC Sensor (select models)


Operating Principle Self-calibrating, Non-Dispersive Infrared (NDIR)
Sensor Range 0-1000 ppb isobutylene equivalent tVOCs
Response Time < 5 seconds for tVOC
Start up Time 15 minutes
Other
Three wires to EVCB/EFCB controller and two wires to BACnet/Modbus network
Electrical connection
0.8 mm2 [18 AWG] minimum
Network service port Mini USB connector
Power supply 24Vac
Power consumption 1VA
Operating temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 to 95 % non-condensing
Degree of protection of housing IP 30 (EN 60529)
Weight 135 g. [0.30 lb]
Dimensions: C PIR Sensor
A = 4.88” | 124mm (Optional)
B = 3.25” | 83mm
C = 1.75” | 44mm D
D = 0.96” | 24mm
E = 2.07” | 53mm
F = 2.36” | 60mm
G = 3.28” | 83mm
H = 0.78” | 20mm (without CO2) E
0.95” | 24mm (with CO2) A G

B H

www.neptronic.com Page | 2
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers

Interface

AM PM Network Programming Mode


User Lock
Communication (Technician Setting)
Energy Saving Mode
Alarm Status AM PM Time
(NSB/OCC)
%RH °C ºC: Celsius Scale
CF °F ºF: Fahrenheit Scale A Automatic Mode Cooling
%RH %RH: Humidity
Humidify/
Heating Fan De-humidify
(EFCB only)

Wiring
We strongly recommend that all Neptronic products be wired to a
separate grounded transformer and that transformer shall
service only Neptronic products. This precaution will prevent
Avoid touching the CO2 and VOC interference with, and/or possible damage to incompatible
sensors as this may cause
incorrect readings. equipment.
Mode Selection (JP1)
CO2 sensor
TB1
RUN:
1 COM
2 PWR
Connect to
EVCB/EFCB
Digital Room Sensor is in Operation Mode.
3
4
DATA Digital Room Sensor must be set in this mode to operate
5 properly. If not locked, following setpoint and control mode
A+ Optional: connect to
6
7 B-
BACnet network to options can be modified by the end user:
enable service port
JP1
• Heating and Cooling ON
RUN
• Cooling only ON

VOC sensor
Heating only ON
PGM
• OFF
Mode Selector Jumper
JP1
RUN
(EFCB only)
RUN = Operation Mode
PGM = Programming Mode
PGM • Fan ON
• Humidify and De-humidify ON

Temperature and
Humidity sensors Humidify only ON
• Dehumidify only ON
BACnet
service port JP1
RUN PGM:
Digital Room Sensor is set in Programming Mode.
PGM

Mounting Instructions
CAUTION: Remove power to avoid a risk of malfunction.

A. Remove the captive screw that’s holding the base and the front cover of the unit together.
B. Lift the front cover of the unit to separate it from the base.
C. Pull all wires through the holes in the base.
D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
E. Mount the control module on the base and secure using the screw.

A B C D E

www.neptronic.com Page | 3
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers

Access to Menus
The menus and options are the same for both the TDU and TDF Digital Room Sensors. However, the action button or the button
used to access the menus and save changes is different for each Digital Room Sensor.

Action Buttons on Digital Room Sensor


Action Button
TDU TDF

Operation Mode
The Mode Selector Jumper JP1 must be set to the RUN position (Operation Mode). Refer to the Wiring section on page 3.

EVCB
CO2 reading in ppm
(CO2 display option must be
Appears if in Night Set Back (NSB) enabled in programming mode)
or Occupancy (OCC) mode. Flashes
if overridden by user.

Press twice to
Press for 5 sec. display setpoint
to display air flow Press once to display C
(if using pressure sensors) control mode
Press to toggle
between °C and °F

Actual demand
Appears if setpoint
adjustment is locked
Fan icon appears in fan-powered box applications only

Change setpoint value


Room temperature C

%RH
Setpoint value

Alternates between room temperature for


Exits after 5 sec. Exits after 5 sec. 8 sec and then room humidity for 2 sec.
Exits after 3 sec.
(requires Humidity sensor thermostats,
Scroll through the following values: Press to change mode:
and Humidity Mode must not be OFF)
“Airflow”*
“Airflow Setpoint”* - Auto
“Actual Damper Pos Percent”
“Air Supply Temp” † - Off

* appears only in pressure independent mode - Cool only


† appears only if “AST” is selected for the
Analog Input Signal Type - Heat only

EFCB
Appears if in Night Set Back (NSB) or CO2 reading in ppm
Occupancy (OCC) mode. Flashes if (CO2 display option must be
overridden by user. enabled in programming mode)

Press twice to
display setpoint
Press for 5 sec. to display Press once to display Press both keys for 3 sec. to
C toggle between °C and °F
Humidity Setpoint Mode Fan Speed Mode Press once to display
control mode

Appears if setpoint Actual demand


Appears if setpoint
adjustment is locked adjustment is locked

%RH Change setpoint


value Change setpoint value
C

Setpoint value Room temperature Setpoint value


%RH

Exits after 5 sec. Exits after 5 sec. Exits after 5 sec.


Alternates between room temperature for Exits after 3 sec.
Press to change mode: Press to change mode: 8 sec and then room humidity for 2 sec.
(requires Humidity sensor thermostats,
- Auto - Auto and Humidity Mode must not be OFF)

- LOW - Off

- MEDIUM - Cool only

- HIGH - Heat only

www.neptronic.com Page | 4
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers

Power Up
Upon power up, the LCD illuminates and all segments appear for 2 seconds. The Digital Room Sensor then displays its current
version for 2 seconds followed by the current version of the controller for 2 seconds. Pressing any key on the Digital Room Sensor
illuminates the LCD for 4 seconds.

Temperature Display and Setpoint


The Digital Room Sensor displays the temperature reading. If the sensor is disconnected or short circuited, the unit displays the
sensor's limits. To toggle the temperature scale between ºC and ºF, press the key on the TDU or both the and keys for 3
seconds on the TDF.
To display the setpoint, press the or key twice. The setpoint appears for 5 seconds. To adjust the setpoint, press the arrow
keys while the temperature is displayed. If the setpoint adjustment has been locked, the lock symbol appears.

CO2 (Digital Room Sensor with CO2 Option)


If enabled via the configuration menu, the Digital Room Sensor displays the CO2 reading on the first line above the temperature
reading. If CO2 display is enabled, the time will not be displayed.

Humidity Setpoint Display and Adjustment (Digital Room Sensor with Humidity Option)
If enabled via the configuration menu for the EVCB and in a humidity mode other than OFF for the EFCB, the Digital Room Sensor
displays the temperature reading for 8 seconds and then displays the humidity reading for 2 seconds. If the sensor is disconnected
or short circuited, then the unit displays the sensor's limit.
To access the humidity setpoint (EFCB only), press the key for 5 seconds. The humidity setpoint will be displayed for 5 seconds.
To adjust the setpoint press the and keys while the setpoint is displayed. The unit will return to normal mode if you do not press
any key for 3 seconds. The changed values will be saved automatically.

Control Mode
To access the Control Mode, press the key on the TDU or on the TDF. The Control Mode appears for 5 seconds. Press
the (TDU) or (TDF) key to scroll through the following control modes. These options can vary depending on the options
configured by the installer.
• Auto (Automatic Cooling or Heating)
• Cooling only (on, with cooling symbol)
• Heating only (on, with heating symbol)
• OFF (if it is not disabled in Programming Mode)

Fan Speed Selection Mode (EFCB Only)


To access the Fan Speed selection mode, press the key. The mode appears for 5 seconds. These options can vary depending
on the fan speed signal and auto mode settings. If in No Occupancy mode, the button now serves as the override button.
• Automatic speed. Available only if enabled by the installer.
• Low speed
• Medium speed
• High speed

Night Set Back (NSB)


This function is only available if enabled by your installer. If the appropriate digital input contact is triggered, the Digital Room Sensor
enters NSB Mode (the symbol appears) and uses the NSB setpoints defined in program mode. Press any key to override NSB for
the delay defined in program mode (default: 120 minutes). The symbol flashes to indicate that the NSB mode is overridden (during
this time the standard setpoints are used). If the NSB Mode was set to OFF, all outputs will be off for the duration of the period and
cannot be overridden.

Occupancy Mode
This function is only available if enabled by your installer. If the appropriate digital input contact is triggered, the Digital Room
Sensor enters Occupancy Mode (the symbol appears) and uses the NoOcc setpoints defined in program mode. If not locked, no
occupancy mode can be overridden for a period by pressing the ( ) button. Each time you press the ( ) button, 15
minutes are added to the override (up to a maximum defined in program mode). Press the fan ( ) button until “0” is displayed
to disable the override. The icon will flash and the remaining override time will be displayed in minutes.

www.neptronic.com Page | 5
TDU/TDF Universal Digital Room Sensor
For EVCB and EFCB Controllers

Set Time and Date


1. Press and hold the ( ) button for 5 seconds
2. Use the arrow keys to set the desired value. Press the ( ) button to save and go to the next step. Press the ( )
button to go to the previous step without saving.

= select / set value Local Time Local Time Local Date

Set Time Display format Hours Minutes Year


24 (24-hour format) 12 (0-23 or 1-12 am/pm) 00 (00-59) 15 (15-99)
12 (AM/PM format)
Exits and returns to
Month Day RUN mode.
1 (1-12) 1 (1-31)
Local Date Local Date

*** To save any changes, press on TRL and on TDU ***


Airflow
*** To the and Airstep
previous Supply Temperature
without saving, press on TRL and TDU ***
Press and hold the ( ) button for 5 seconds and use the arrow keys to view the “airflow”, “airflow Setpnt", “actual damper
pos percent” and “air Supply Temp”. After 5 seconds without any action, the Digital Room Sensor returns to operation mode. The
air supply temperature appears only if analog input AI1 or AI2 are configured with the AST option.

Programming Mode
To access the programming mode, the Mode Selector Jumper (JP1) must be set to the PGM (Programming Mode) position and
terminal 3 (Data) must be disconnected from the Digital Room Sensor. Refer to the Wiring section on page 3 for more details.

Backlight and Contrast Level Adjustment


In programming mode, for models with the grey LCD screen, the backlight level can be adjusted. For models with the black LCD
screen, the contrast level can be adjusted. Use the and keys to adjust the backlight or contrast level. Press the ( ) key
to save any changes.

www.neptronic.com Page | 6
Notes
Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic