AURORA MODEL FIRE PUMPS Section 917 Page 115

DIESEL ENGINE DATA Date July 2001


Supersedes Section 917 Page 115
Dated December 1992

CATERPILLAR MODEL 3208-DINA (175)


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-8 24V NEG. 636 1720 (2) 2-1/2” NPT 1-1/4” NPT 75 120/240 VOLT
GROUND (10.4) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20. BTU/MIN GPM @ °90F
1460 101 4.8 225 459 657 34.0 569 12 GPM
1750 121 5.8 272 600 750 34.0 626 12 GPM
2100 141 7.0 318 724 784 34.0 739 12 GPM
2300 150 7.7 343 794 810 34.0 796 12 GPM
3000 160 9.7 416 1069 980 34.0 905 13 GPM

CATERPILLAR MODEL 3208-DINA (210)


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-8 24V NEG. 636 1720 (2) 2-1/2” NPT 1-1/4” NPT 75 120/240 VOLT
GROUND (10.4) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20. BTU/MIN GPM @ °90F
1460 122 5.8 220 530 829 34.0 626 12 GPM
1750 141 6.8 270 653 871 34.0 739 12 GPM
2100 165 8.3 320 794 907 34.0 739 12 GPM
2300 176 9.0 340 883 943 34.0 853 12 GPM
3000 185 11.2 409 1144 1095 34.0 984 13 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
Section 917 Page 116 AURORA MODEL FIRE PUMPS
Date July 2001 DIESEL ENGINE DATA
Supersedes Section 917 Page 116
Dated December 1992

CATERPILLAR MODEL 3208-DIT


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-8 24V NEG. 636 1780 6” NPT 1-1/4” NPT 75 120/240 VOLT
GROUND (10.4) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1460 145 7.9 261 567 718 54.0 215 12 GPM
1750 196 10.4 335 805 835 54.0 682 14 GPM
2100 235 12.0 453 1088 842 54.0 853 16 GPM
2300 251 13.0 521 1203 800 54.0 910 18 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
AURORA MODEL FIRE PUMPS Section 917 Page 117
DIESEL ENGINE DATA Date July 2001
Supersedes Section 917 Page 117
Dated December 1992

CATERPILLER MODEL 3306B-DIT


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
I-6 24V NEG. 638 2600 5” NPT 1-1/2” NPT 75 120/240 VOLT
GROUND (10.5) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20. BTU/MIN GPM @ °90F
1460 195 10.0 349 989 1139 27.0 1820 30 GPM
1750 231 11.9 459 1236 1080 27.0 1990 30 GPM
2100 267 14.2 646 1624 979 27.0 2161 30 GPM
2300 272 14.5 739 1836 921 27.0 2275 30 GPM

CATERPILLER MODEL 3306B-DITA


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
I-6 24V NEG. 638 2540 5” NPT 1-1/2” NPT 75 120/240 VOLT
GROUND (10.5) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20. BTU/MIN GPM @ °90F
1460 245 12.1 438 1236 1134 27.0 1990 35 GPM
1750 266 13.1 534 1377 1026 27.0 2047 40 GPM
2100 287 14.7 688 1642 981 27.0 2218 60 GPM
2300 284 19.8 798 1766 1022 27.0 2161 65 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
Section 917 Page 118 AURORA MODEL FIRE PUMPS
Date July 2001 DIESEL ENGINE DATA
Supersedes Section 917 Page 119
Dated December 1992

CATERPILLER MODEL 3406B-DIT PHASE 0


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
I-6 24V NEG. 893 2960 6” NPT 2” NPT 75 120/240 VOLT
GROUND (14.6) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20. BTU/MIN GPM @ °90F
1460 247* 12.4 458 1098 840 27.0 1299 35 GPM
1750 292 14.8 578 1367 828 27.0 1366 35 GPM
2100 330 17.2 750 1704 774 27.0 1401 35 GPM

This rating is not listed or approved by ULI or FM, but is available and meets
the same standards as listed and approved ratings

CATERPILLAR MODEL 3406B-DIT PHASE 1


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
I-6 24V NEG. 893 2960 6” SPL 2” NPT 75 120/240 VOLT
GROUND (14.6) CAT FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20. BTU/MIN GPM @ °90F
1460 325 16.1 625 1801 1078 34.0 1820 25 GPM
1750 370 18.3 823 2218 988 34.0 1820 29 GPM
2100 375 18.6 1006 2440 847 34.0 1820 31 GPM
2300 350 17.8 1084 2458 766 34.0 1820 30 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
AURORA MODEL FIRE PUMPS Section 917 Page 119
DIESEL ENGINE DATA Date July 2001
Supersedes Section 917 Page 120
Dated December 1992

CATERPILLAR MODEL 3406B-DITA PHASE 0


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
I-6 24V NEG. 893 3240 6” SPL 2” NPT 75 120/240 VOLT
GROUND (14.6) CAT FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1460 300 14.8 530 1289 865 27.0 1422 30 GPM
1750 420 20.5 855 1960 788 27.0 1422 35 GPM
2100 430 22.2 1117 2366 700 27.0 1479 40 GPM

CATERPILLAR MODEL 3406B-DITA PHASE 1


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
I-6 24V NEG. 893 3240 6” SPL 2” NPT 75 120/240 VOLT
GROUND (14.6) CAT FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1750 460 22.3 943 2532 979 34.0 3241 35 GPM
2100 482 23.6 1119 2825 892 34.0 2900 39 GPM
2350 455 22.5 1194 2832 801 34.0 2559 38 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
Section 917 Page 120 AURORA MODEL FIRE PUMPS
Date July 2001 DIESEL ENGINE DATA
Supersedes Section 917 Page 121
Dated December 1992

CATERPILLAR MODEL 3408B-DITA PHASE 0


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-8 24 V NEG. 1099 1175 6” NPT 2” NPT 75 120/240 VOLT
GROUND (18.0) 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1460 310 15.7 613 1414 797 27.0 1592 40 GPM
1750 481 24.1 1030 2259 738 27.0 1706 55 GPM
2100 507 26.2 1209 2542 691 27.0 1820 60 GPM

CATERPILLAR MODEL 3408B-DITA PHASE 1


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-8 24V NEG. 1099 3740 11” O.D. 2” NPT 75 120/240 VOLT
GROUND (18.0) SPL FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1750 510 26.8 1116 2966 959 34.0 4948 42 GPM
2100 525 29.0 1257 3341 964 34.0 4436 44 GPM
2350 510 29.4 1342 3507 941 34.0 4151 44 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
AURORA MODEL FIRE PUMPS Section 917 Page 121
DIESEL ENGINE DATA Date July 2001
Supersedes Section 917 Page 123
Dated December 1992

CATERPILLAR MODEL 3412-DIT PHASE 0


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-12 24V NEG. 1649 5020 11” O.D. 2” NPT 75 120/240 VOLT
GROUND (27.0) SPL FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1460 503* 25.7 1069 2381 754 27.0 1990 55 GPM
1750 538 29.4 1286 2737 705 27.0 2047 55 GPM
2100 572 32.5 1432 3019 694 27.0 2218 65 GPM

* This rating is not listed or approved by ULI or FM, but is available and
meets the same standards as listed or approved ratings

CATERPILLAR MODEL 3412-DIT PHASE 1


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-12 24V NEG. 1649 5020 11” O.D. 2” NPT 75 120/240 VOLT
GROUND (27.0) SPL FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1460 625 32.8 1229 3535 1069 34.0 5061 50 GPM
1750 660 34.2 1490 3938 955 34.0 4663 54 GPM
2100 700 37.6 1769 4496 903 34.0 4493 59 GPM
2350 625 35.7 1840 4496 856 34.0 4151 55 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.
Section 917 Page 122 AURORA MODEL FIRE PUMPS
Date July 2001 DIESEL ENGINE DATA
Supersedes Section 917 Page 124
Dated December 1992

CATERPILLAR MODEL 3412-DITA PHASE 0


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-12 24V NEG. 1649 5100 11” O.D. 2” NPT 75 120/240 VOLT
GROUND (27.0) SPL FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1460 503 25.6 963 2313 846 27.0 2161 65 GPM
1750 638 32.6 1306 2878 743 27.0 2218 75 GPM
2100 739 39.4 1649 3602 732 27.0 2275 90 GPM

CATERPILLAR MODEL 3412-DITA PHASE 1


MAXIMUM STANDARD
NUMBERS VOLTAGE DISPLACEMENT UNIT RAW WATER RAW WATER WATER JACKET
OF AND CU. IN. WEIGHT EXHAUST INLET P.S.I. HEATER SIZE
CYLINDERS POLARITY (L) LBS. CONNECTION SIZE PRESSURE VOLTS/WATT
V-12 24V NEG. 1649 5100 (2) 6” SPL 2” NPT 75 120/240 VOLT
GROUND (27.0) CAT FLANGE 3000 WATT

RATED EXHAUST MAXIMUM MINIMUM


HORSE- FUEL COMBUSTION FLOW EXHAUST ALLOWABLE RADIATED RAW WATER
POWER CONSUMPTION AIR REQ’D RATE TEMP. EXHAUST BACK HEAT FLOW
R.P.M. SEE NOTE 1 GAL/HOUR C.F.M. C.F.M. °F PRESSURE IN. H20 BTU/MIN GPM @ °90F
1750 800 39.8 1752 4640 961 34.0 6711 64 GPM
2100 860 44.0 2145 5347 883 34.0 6199 72 GPM
2350 870 45.2 2331 5661 849 34.0 5744 74 GPM

NOTES:
1. If UL and FM horsepower ratings differ, the lesser of the two ratings is shown.