Main
Range of product TeSys GV3
Complementary
Poles description 3P
Network type AC
[Ics] rated service short-circuit 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Tightening torque 5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
Height 132 mm
Width 55 mm
Depth 136 mm
Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
Packing Units
Unit Type of Package 1 PCE
2
Jun 22, 2022
Package 1 width 14.5 cm
Offer Sustainability
Sustainable offer status Green Premium product
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov
Contractual warranty
Warranty 18 months
4
Jun 22, 2022
1 Maximum peak current
2 70-80 A (GV3P80), 62-73 A (GV3P73)
3 48-65 A (GV3P65)
4 37-50 A (GV3P50)
5 30-40 A (GV3P40)
6 23-32 A (GV3P32)
7 17-25 A (GV3P25)
8 12-18 A (GV3P18)
9 9-13 A (GV3P13)
6
Jun 22, 2022
Product data sheet GV3P13
Dimensions Drawings
GVl3L, GV3P
Dimensions
GV3P••