Data sheet 3RW5072-6TB04

SIRIUS soft starter 200-480 V 210 A, 24 V AC/DC Screw terminals


Thermistor input

product brand name SIRIUS


product category Hybrid switching devices
product designation Soft starter
product type designation 3RW50
manufacturer's article number
● of standard HMI module usable 3RW5980-0HS01
● of high feature HMI module usable 3RW5980-0HF00
● of communication module PROFINET standard 3RW5980-0CS00
usable
● of communication module PROFIBUS usable 3RW5980-0CP00
● of communication module Modbus TCP usable 3RW5980-0CT00
● of communication module Modbus RTU usable 3RW5980-0CR00
● of communication module Ethernet/IP 3RW5980-0CE00
● of circuit breaker usable at 400 V 3VA2440-7MN32-0AA0; Type of assignment 1, Iq = 65 kA
● of circuit breaker usable at 500 V 3VA2440-7MN32-0AA0; Type of assignment 1, Iq = 65 kA
● of the gG fuse usable up to 690 V 2x3NA3354-6; Type of coordination 1, Iq = 65 kA
● of full range R fuse link for semiconductor protection 3NE1 230-2; Type of coordination 2, Iq = 65 kA
usable up to 690 V
● of back-up R fuse link for semiconductor protection 3NE3 333; Type of coordination 2, Iq = 65 kA
usable up to 690 V
● of line contactor usable up to 480 V 3RT1064
● of line contactor usable up to 690 V 3RT1064
General technical data
starting voltage [%] 30 ... 100 %
stopping voltage [%] 50 %; non-adjustable
start-up ramp time of soft starter 0 ... 20 s
ramp-down time of soft starter 0 ... 20 s
current limiting value [%] adjustable 130 ... 700 %
accuracy class according to IEC 61557-12 5%
certificate of suitability
● CE marking Yes
● UL approval Yes
● CSA approval Yes
product component
● HMI-High Feature No
● is supported HMI-Standard Yes
● is supported HMI-High Feature Yes
product feature integrated bypass contact system Yes
number of controlled phases 2

3RW50726TB04 Subject to change without notice


8/28/2022
Page 1/9 © Copyright Siemens
trip class CLASS 10A / 10E (preset) / 20E; acc. to IEC 60947-4-2
buffering time in the event of power failure
● for main current circuit 100 ms
● for control circuit 100 ms
insulation voltage rated value 600 V
degree of pollution 3, acc. to IEC 60947-4-2
impulse voltage rated value 6 kV
blocking voltage of the thyristor maximum 1 600 V
service factor 1
surge voltage resistance rated value 6 kV
maximum permissible voltage for protective
separation
● between main and auxiliary circuit 600 V
shock resistance 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
vibration resistance 15 mm to 6 Hz; 2g to 500 Hz
utilization category according to IEC 60947-4-2 AC-53a
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 09/23/2019
product function
● ramp-up (soft starting) Yes
● ramp-down (soft stop) Yes
● Soft Torque Yes
● adjustable current limitation Yes
● pump ramp down Yes
● intrinsic device protection Yes
● motor overload protection Yes; Full motor protection (thermistor motor protection and electronic
motor overload protection)
● evaluation of thermistor motor protection Yes; Type A PTC or Klixon / Thermoclick
● auto-RESET Yes
● manual RESET Yes
● remote reset Yes; By turning off the control supply voltage
● communication function Yes
● operating measured value display Yes; Only in conjunction with special accessories
● error logbook Yes; Only in conjunction with special accessories
● via software parameterizable No
● via software configurable Yes
● PROFIenergy Yes; in connection with the PROFINET Standard communication
module
● voltage ramp Yes
● torque control No
● analog output No
Power Electronics
operational current
● at 40 °C rated value 210 A
● at 50 °C rated value 186 A
● at 60 °C rated value 170 A
operating voltage
● rated value 200 ... 480 V
relative negative tolerance of the operating voltage -15 %
relative positive tolerance of the operating voltage 10 %
operating power for 3-phase motors
● at 230 V at 40 °C rated value 55 kW
● at 400 V at 40 °C rated value 110 kW
Operating frequency 1 rated value 50 Hz
Operating frequency 2 rated value 60 Hz
relative negative tolerance of the operating frequency -10 %
relative positive tolerance of the operating frequency 10 %
adjustable motor current
● at rotary coding switch on switch position 1 90 A
● at rotary coding switch on switch position 2 98 A
● at rotary coding switch on switch position 3 106 A

3RW50726TB04 Subject to change without notice


8/28/2022
Page 2/9 © Copyright Siemens
● at rotary coding switch on switch position 4 114 A
● at rotary coding switch on switch position 5 122 A
● at rotary coding switch on switch position 6 130 A
● at rotary coding switch on switch position 7 138 A
● at rotary coding switch on switch position 8 146 A
● at rotary coding switch on switch position 9 154 A
● at rotary coding switch on switch position 10 162 A
● at rotary coding switch on switch position 11 170 A
● at rotary coding switch on switch position 12 178 A
● at rotary coding switch on switch position 13 186 A
● at rotary coding switch on switch position 14 194 A
● at rotary coding switch on switch position 15 202 A
● at rotary coding switch on switch position 16 210 A
● minimum 90 A
minimum load [%] 15 %; Relative to smallest settable Ie
power loss [W] for rated value of the current at AC
● at 40 °C after startup 16 W
● at 50 °C after startup 13 W
● at 60 °C after startup 11 W
power loss [W] at AC at current limitation 350 %
● at 40 °C during startup 2 237 W
● at 50 °C during startup 1 867 W
● at 60 °C during startup 1 637 W
type of the motor protection Electronic, tripping in the event of thermal overload of the motor
Control circuit/ Control
type of voltage of the control supply voltage AC/DC
control supply voltage at AC
● at 50 Hz rated value 24 V
● at 60 Hz rated value 24 V
relative negative tolerance of the control supply -20 %
voltage at AC at 50 Hz
relative positive tolerance of the control supply 20 %
voltage at AC at 50 Hz
relative negative tolerance of the control supply -20 %
voltage at AC at 60 Hz
relative positive tolerance of the control supply 20 %
voltage at AC at 60 Hz
control supply voltage frequency 50 ... 60 Hz
relative negative tolerance of the control supply -10 %
voltage frequency
relative positive tolerance of the control supply 10 %
voltage frequency
control supply voltage
● at DC rated value 24 V
relative negative tolerance of the control supply -20 %
voltage at DC
relative positive tolerance of the control supply 20 %
voltage at DC
control supply current in standby mode rated value 160 mA
holding current in bypass operation rated value 490 mA
locked-rotor current at close of bypass contact 7.6 A
maximum
inrush current peak at application of control supply voltage 3.3 A
maximum
duration of inrush current peak at application of control 12.1 ms
supply voltage
design of the overvoltage protection Varistor
design of short-circuit protection for control circuit 4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature
circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is
not part of scope of supply
Inputs/ Outputs
number of digital inputs 1
number of digital outputs 3

3RW50726TB04 Subject to change without notice


8/28/2022
Page 3/9 © Copyright Siemens
● not parameterizable 2
digital output version 2 normally-open contacts (NO) / 1 changeover contact (CO)
number of analog outputs 0
switching capacity current of the relay outputs
● at AC-15 at 250 V rated value 3A
● at DC-13 at 24 V rated value 1A
Installation/ mounting/ dimensions
mounting position with vertical mounting surface +/-90° rotatable, with vertical mounting
surface +/- 22.5° tiltable to the front and back
fastening method screw fixing
height 230 mm
width 160 mm
depth 282 mm
required spacing with side-by-side mounting
● forwards 10 mm
● backwards 0 mm
● upwards 100 mm
● downwards 75 mm
● at the side 5 mm
weight without packaging 7.3 kg
Connections/ Terminals
type of electrical connection
● for main current circuit busbar connection
● for control circuit screw-type terminals
width of connection bar maximum 35 mm; with connection cover 3RT1966-4EA1 maximum length 45 mm
wire length for thermistor connection
● with conductor cross-section = 0.5 mm² maximum 50 m
● with conductor cross-section = 1.5 mm² maximum 150 m
● with conductor cross-section = 2.5 mm² maximum 250 m
type of connectable conductor cross-sections
● for main contacts for box terminal using the front 95 ... 300 mm²
clamping point solid
● for main contacts for box terminal using the front 70 ... 240 mm²
clamping point finely stranded with core end
processing
● for main contacts for box terminal using the front 70 ... 240 mm²
clamping point finely stranded without core end
processing
● for main contacts for box terminal using the front 95 ... 300 mm²
clamping point stranded
● at AWG cables for main contacts for box terminal 3/0 ... 600 kcmil
using the front clamping point
● for main contacts for box terminal using the back 120 ... 240 mm²
clamping point solid
● at AWG cables for main contacts for box terminal 250 ... 500 kcmil
using the back clamping point
● for main contacts for box terminal using both min. 2x 70 mm², max. 2x 240 mm²
clamping points solid
● for main contacts for box terminal using both min. 2x 50 mm², max. 2x 185 mm²
clamping points finely stranded with core end
processing
● for main contacts for box terminal using both min. 2x 50 mm², max. 2x 185 mm²
clamping points finely stranded without core end
processing
● for main contacts for box terminal using both min. 2x 70 mm², max. 2x 240 mm²
clamping points stranded
● for main contacts for box terminal using the back 120 ... 185 mm²
clamping point finely stranded with core end
processing
● for main contacts for box terminal using the back 120 ... 185 mm²
clamping point finely stranded without core end
processing
● for main contacts for box terminal using the back 120 ... 240 mm²
clamping point stranded
type of connectable conductor cross-sections

3RW50726TB04 Subject to change without notice


8/28/2022
Page 4/9 © Copyright Siemens
● at AWG cables for main current circuit solid 2/0 ... 500 kcmil
● for DIN cable lug for main contacts stranded 50 ... 240 mm²
● for DIN cable lug for main contacts finely stranded 70 ... 240 mm²
type of connectable conductor cross-sections
● for control circuit solid 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● for control circuit finely stranded with core end 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
processing
● at AWG cables for control circuit solid 1x (20 ... 12), 2x (20 ... 14)
wire length
● between soft starter and motor maximum 800 m
● at the digital inputs at AC maximum 1 000 m
tightening torque
● for main contacts with screw-type terminals 14 ... 24 N·m
● for auxiliary and control contacts with screw-type 0.8 ... 1.2 N·m
terminals
tightening torque [lbf·in]
● for main contacts with screw-type terminals 124 ... 210 lbf·in
● for auxiliary and control contacts with screw-type 7 ... 10.3 lbf·in
terminals
Ambient conditions
installation altitude at height above sea level maximum 5 000 m; derating as of 1000 m, see Manual
ambient temperature
● during operation -25 ... +60 °C; Please observe derating at temperatures of 40 °C or
above
● during storage and transport -40 ... +80 °C
environmental category
● during operation according to IEC 60721 3K6 (no ice formation, only occasional condensation), 3C3 (no salt
mist), 3S2 (sand must not get into the devices), 3M6
● during storage according to IEC 60721 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must
not get inside the devices), 1M4
● during transport according to IEC 60721 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
EMC emitted interference acc. to IEC 60947-4-2: Class A
Communication/ Protocol
communication module is supported
● PROFINET standard Yes
● EtherNet/IP Yes
● Modbus RTU Yes
● Modbus TCP Yes
● PROFIBUS Yes
UL/CSA ratings
manufacturer's article number
● of circuit breaker
— usable for High Faults at 460/480 V according Siemens type: 3VA54, max. 600 A; Iq max = 65 kA
to UL
● of the fuse
— usable for Standard Faults up to 575/600 V Type: Class L, max. 700 A; Iq = 10 kA
according to UL
— usable for High Faults up to 575/600 V Type: Class L, max. 700 A; Iq = 100 kA
according to UL
operating power [hp] for 3-phase motors
● at 200/208 V at 50 °C rated value 60 hp
● at 220/230 V at 50 °C rated value 60 hp
● at 460/480 V at 50 °C rated value 150 hp
Safety related data
protection class IP on the front according to IEC IP00; IP20 with cover
60529
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front with cover
ATEX
certificate of suitability
● ATEX Yes
● IECEx Yes
hardware fault tolerance according to IEC 61508 0

3RW50726TB04 Subject to change without notice


8/28/2022
Page 5/9 © Copyright Siemens
relating to ATEX
PFDavg with low demand rate according to IEC 61508 0.09
relating to ATEX
PFHD with high demand rate according to EN 62061 9E-6 1/h
relating to ATEX
Safety Integrity Level (SIL) according to IEC 61508 SIL1
relating to ATEX
T1 value for proof test interval or service life 3y
according to IEC 61508 relating to ATEX
Certificates/ approvals
For use in hazard-
General Product Approval
ous locations

Confirmation

For use in hazard- Declaration of


Test Certificates Marine / Shipping
ous locations Conformity

Type Test Certific-


ates/Test Report

other

Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW5072-6TB04
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW5072-6TB04
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RW5072-6TB04
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RW5072-6TB04&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RW5072-6TB04/char
Characteristic: Installation altitude
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RW5072-6TB04&objecttype=14&gridview=view1
Simulation Tool for Soft Starters (STS)
https://support.industry.siemens.com/cs/ww/en/view/101494917

3RW50726TB04 Subject to change without notice


8/28/2022
Page 6/9 © Copyright Siemens
14/24
1/L1

3/L2

5/L3

A1

IN

95

-Q
BYPASSED
ON/RUN

>
A2

T11/21
T22
2/T1

4/T2

6/T3

T12
13 NO

23 NO

98 NO

96 NC

3RW50726TB04 Subject to change without notice


8/28/2022
Page 7/9 © Copyright Siemens
3RW50726TB04 Subject to change without notice
8/28/2022
Page 8/9 © Copyright Siemens
last modified: 4/11/2022

3RW50726TB04 Subject to change without notice


8/28/2022
Page 9/9 © Copyright Siemens