NEC Article 250
NEC Article 250
NEC Article 250
AND BONDING NATIONAL ELECTRICAL CODE ARTICLE 250 By Jim Biesterveld Some of the material is taken from Mike Holt and Soars presentaGons
NEC 250.1 Scope (1) Systems, circuits, and equipment require, permi=ed, or not permi=ed to be grounded (2) Circuits conductors to be grounded on grounded systems
(3) LocaBon of grounding connecBons (4) Type and size of grounding and bonding conductors and electrodes (5) Methods of grounding and bonding
(6) CondiBons under which guards, isolaBon, or insulaBon maybe subsBtuted for grounding The code has its deniBons and these need to be understood to properly understand and interpret the code requirements of the NEC and Wisconsin Comm 16
10
13
15
16
17
19
20
21
Supplemental electrodes
COMM 16 2-rods
No switching acBon in grounded conductor generator gets connected to system with neutral and grounds separate. Grounded conductor remains as a grounded conductor because it is grounded at service.
31
Equipment grounding conductor run underground to these locaBons must be insulated or covered copper See ArBcle 547 for specic Code secBons.
35
36
37
38
39
40