9.b Level Switch

- The document describes a compact, plug-in type floatless level switch for use in pump panels or built into equipment. - It has a large switching capacity of 5A at 220VAC and easy DIN rail mounting for maintenance without rewiring. - Details are provided on model types for general purpose, long distance, high sensitivity, and low sensitivity applications with different operating voltages, resistances, and cable lengths.

Uploaded by

Naqib Fuad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views8 pages

9.b Level Switch

- The document describes a compact, plug-in type floatless level switch for use in pump panels or built into equipment. - It has a large switching capacity of 5A at 220VAC and easy DIN rail mounting for maintenance without rewiring. - Details are provided on model types for general purpose, long distance, high sensitivity, and low sensitivity applications with different operating voltages, resistances, and cable lengths.

Uploaded by

Naqib Fuad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Floatless Level Switch (Plug-in Type)

61F-G@P
CSM_61F-G_P_DS_E_3_2

Compact, Space-saving Plug-in Type Ideal


for Pump Panels or Building into Equipment.
• Large switching capacity: 5 A at 220 VAC (resistive load).
• Easy to handle with DIN rail mounting.
• Replace for maintenance without rewiring the socket.

Refer to Safety Precautions for Floatless Level 61F-G@P@ (110 VAC) in this catalog have been discontinued
Controllers. at the end of March 2018.

■ Model Number Legend


61F-@P@
1 2

1. Control Applications 2. Type


G1: Automatic water supply with idling prevention Blank: General-purpose
or water shortage alarm L 2KM: Long-distance (for 2 km)
G2: Automatic water supply and drainage with L 4KM: Long-distance (for 4 km)
abnormal water increase alarm
H: High-sensitivity
I: Liquid level indication and alarm
D: Low-sensitivity

■ Ordering Information
Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)
Model Model Model
G1 models 61F-G1P * 61F-G1PL 2K 61F-G1PL 4KM *

Type High-sensitivity Low-sensitivity


Model Model
G1 models 61F-G1PH * 61F-G1PD *

Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)


Model Model Model
G2 models 61F-G2P * 61F-G2PL 2KM * 61F-G2PL 4KM *

Type High-sensitivity Low-sensitivity


Model Model
G2 models 61F-G2PH * 61F-G2PD *

Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)


Model Model Model
I models 61F-IP * 61F-IPL 2KM * 61F-IPL 4KM *

Type High-sensitivity Low-sensitivity


Model Model
I models 61F-IPH * 61F-IPD *

Note: When ordering, specify the desired operating voltage at the end of the model number.
Example: 61F-G1P [110VAC]
Desired supply voltage
* 61F-G@P@ (110 VAC) in this catalog have been discontinued at the end of March 2018.
61F-G@P
■ Plug-in Models
Specifications
Item General-purpose Long-distance High-sensitivity Low-sensitivity
Controller Controllers Controllers Controller

61F-G1P 61F-G1PL 61F-G1PH 61F-G1PD


61F-G2P 61F-G2PL 61F-G2PH 61F-G2PD
61F-IP 61F-IPL 61F-IPH 61F-IPD
(see note 2) (see note 1, see note 6)
Controlling materials and For control of ordinary puri- For control of ordinary puri- For control of liquids with For control of liquids with
operating conditions fied water or sewage water fied water in cases where high specific resistance low specific resistance such
the distance between sew- such as distilled water as salt water, sewage water,
age pumps and water tanks acid chemicals, alkali chem-
or between receiver tanks icals
and supply tanks is long or
where remote control is re-
quired.
Supply voltage 100, 200, 220 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Interelectrode voltage 8 VAC 24 VAC 8 VAC
Interelectrode current Approx. 1 mA AC max. Approx. Approx. 1.2 mA AC max.
0.4 mA AC max.
Power consumption Approx. 6.4 VA max.
Interelectrode operate re- 0 to approx. 4 kΩ 0 to 1.8 kΩ (for 2 km) Approx. 15 kΩ to 0 to approx. 1.8 kΩ
sistance 0 to 0.7 kΩ (for 4 km) approx. 70 kΩ
(see note 5)
Interelectrode release re- Approx. 15 k to ∞ Ω 4 k to ∞ Ω (for 2 km) Approx. 300 k to ∞ Ω Approx. 5 k to ∞ Ω
sistance 2.5 k to ∞ Ω (for 4 km)
Response time Operate: 80 ms max.
Release: 160 ms max.
Cable length 1 km max. 2 km max. 50 m max. 1 km max.
(see note 3) 4 km max.
Control output 2 A, 200 VAC (Inductive load: cosφ = 0.4)
5 A, 200 VAC (Resistive load)
Ambient temperature Operating: –10 to 55°C
Ambient humidity Operating: 45% to 85% RH
Insulation resistance 100 MΩ min. (at 500 VDC)
(see note 4)
Dielectric strength 2000 VAC, 50/60 Hz for 1 min.
(see note 4)
Life expectancy Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min.
Weight Approx. 495 g
Note: 1. The relay in the 61F-G1H/-G2H/-IPH de-energizes when there is water present across the Electrodes, whereas the relay in the 61F-GP-
N8HY energizes when there is water present across the Electrodes.
2. Models are available for 2 km and 4 km.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as
the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers.
4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for
Floatless Level Controllers.
5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
6. High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-
nal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.
61F-G@P
Internal Circuit Diagrams
61F-G1P/-G1PL/-G1PD 61F-G1PH 61F-G2P/-G2PL/-G2PD
77 14
14 66 55 12
12 44 33 7 14 6 5 12 4 3 7 14 6 5 12 4 3
U2
U1 U1
U2 U2 U1
U1 U1 U1
24 V Control circuit 24 V Control circuit 24 V Control circuit
Power Power Power
supply 24 V Control circuit U2 supply 24 V Control circuit U2 supply 24 V Control circuit U2
8V 24 V 8V
U2 U1 U2 U1

88 99 15
15 10
10 11 11
11 22 8 9 15 10 1 11 2 8 9 15 10 U2 1 11 2

61F-G2PH 61F-IP/-IPL/-IPD 61F-IPH


7 14 6 5 12 4 3 7 14 6 5 12 4 3
7 14 6 5 12 4 3
U2

U1 U1 U1
U1 U2 U2 U1 U2 U2 U1
24 V Control circuit
U1 U1
Power 24 V Control circuit 24 V Control circuit
supply 24 V Control circuit U2 Power Power
supply 24 V Control circuit U2 supply 24 V Control circuit U2
8V
8V 24 V

8 9 15 10 U2 1 11 2
8 9 15 10 1 11 2 8 9 15 10 1 11 2

Note: The 61F-G@PH High-sensitivity Controller uses advanced operation. The internal relay will operate on the NO contact side when power is
supplied and then will operate according to the liquid level.
61F-G@P
■ Connections
Automatic Water Supply Control with Pump Plug-in Type
Idling Prevention and Abnormal Water 61F-G1P
Shortage Alarm
Dimensions:
Page 7

Automatic Water Supply Control with Pump Idling Prevention Automatic Water Supply Control with Abnormal Water Shortage Alarm

Connections Connections
Commercial Voltage B Alarm Commercial Voltage
R S T
61F-G1P
R S T B Alarm

MCCB
7 14 6 5 12 4 3 MCCB
7 14 6 5 12 4 3
U1 U1
U2 U2
Control U1 Control U1
0V 24 V circuit 0V 24 V
circuit

Control U2 Control U2
24 V 24 V circuit
circuit
Power Power
8V 8V
supply U2 U1 supply U2 U1

8 9 15 10 1 11 2 8 9 15 10 1 11 2
Pushbutton switch
Pushbutton
switch

(See note.)
Contactor Contac-
(See note.) PS-3S tor PS-4S

Motor Motor
protection Water protection Water supply Water
relay E1 relay source tank E1
Water tank E2 E2
E3
E3 E4
supply
source
E1'
E2'
E3
M P M P

Note: Be sure to ground the common Electrode E3 (the Note: Be sure to ground the common Electrode E3 (the
longest Electrode). longest Electrode).
Connection Sockets
14PFA (Front-connecting)
• Insert a pushbutton switch between terminals 11 and 15 as PL15 (Rear-connecting)
shown by the dotted lines. • Insert a pushbutton switch between terminals 11 and 15 as
• Do not press the pushbutton if the low-water alarm sounds and shown by the dotted lines.
the pump stops during normal operation (water below E2'). • If the pump stops when the pushbutton switch is released,
press it again.
Test Operation/Recovering from Power Interruptions
Test Operation/Recovering from Power Interruptions
If the supply water level is below E1' when starting operation or
when recovering from a power interruption, press the pushbutton If the supply water level is below E4 when starting operation or
to momentarily close the circuit to start the pump. when recovering from a power interruption, press the pushbutton
to momentarily close the circuit to start the pump.

Principles of Operation Principles of Operation


Water supply source Water tank Water tank
Water
supply Water
supply
P P
E1 (U2 indicator ON)
Pump OFF E1
Pump
Water OFF
shortage E1' Pump ON
E2' (U2 indicator OFF)
B L Pump E2
ON E2 Water
shortage
E3 E3 (U1 indicator OFF)
B L E4

E3

• The pump starts when the water level in the tank drops below • The pump stops when the water level reaches E1 and starts
E2 and stops when the water level reaches E1. when the water level in the tank drops below E2.
• When the level of water supply source drops below E2', the • If the water level drops below E4 for any reason, the pump
pump stops. Pumping idling is prevented and the alarm stops and the alarm sounds.
sounds.
61F-G@P

Automatic Water Supply and Drainage Plug-in Type


Control with Abnormal Water Increase 61F-G2P
Alarm
Dimensions:
Page 7

Automatic Water Supply with Abnormal Water Increase Alarm Automatic Drainage Control with Abnormal Water Increase Alarm

Connections Connections
Commercial Voltage B Alarm Commercial Voltage B Alarm
R S T R S T
61F-G2P 61F-G2P

MCCB
7 14 6 5 12 4 3 MCCB
7 14 6 5 12 4 3
U2 U1 U2 U1
Control U1 Control U1
0V 24 V circuit 0V 24 V circuit

Control U2 Control U2
24 V circuit 24 V circuit

Power 8V Power 8V
supply U2 supply U2

8 9 15 10 1 11 2 8 9 15 10 1 11 2

(See note.)
Contac- Contac-
tor tor (See note.)
PS-4S
Motor Motor
protection protection PS-4S
relay Water supply source Water E4 relay
E1
tank E2 Wastewater
E3 tank E4
E1
M P M P E3 E2

Reservoir

Note: Be sure to ground the common Electrode E3 (the Note: Be sure to ground the common Electrode E3 (the
longest Electrode). longest Electrode).

Connection Sockets
14PFA (Front-connecting) Connection Sockets
PL15 (Rear-connecting) 14PFA (Front-connecting)
PL15 (Rear-connecting)

• Connect terminal 14 to power supply terminal 9. (Terminal 8 is • Connect terminal 8 to power supply terminal 9.
not connected.)
• The power supply depends on the specifications of the model.

Principles of Operation
Water L B B L
supply Upper Upper
P limit
(U1 indicator ON) limit
(U1 indicator ON)
E4 E4
Pump OFF (U2 indicator ON) (U2 indicator ON)
E1 Pump ON E1

Pump ON (U2 indicator OFF) Pump OFF (U2 indicator OFF)


E2 E2
E3 E3 P

Water drainage

• The pump starts when the water level drops below E2 and • The pump starts when the water level reaches E1 and stops
stops when the water level reaches E1. when the water level drops below E2.
• If the water level drops below E4 for any reason, the pump • If the water level drops below E4 for any reason, the pump
stops and the alarm sounds. stops and the alarm sounds.
61F-G@P

Liquid Level Indication and Alarm Plug-in Type


61F-IP

Dimensions:
Page 7

Liquid Level Indication and Alarm

Connections
Commercial Voltage
R S T

MCCB

Intermediate
Upper limit

Upper limit
Alarm
B PL PL PL
61F-IP

7 14 6 5 12 4 3

U2 U1 U1
U2

0V Control U1
24 V circuit

Control
24 V circuit U2

Power 8V
supply

8 9 15 10 1 11 2

(See note.) PS-3S


Upper alarm
Water supply Water E1 Intermediate
tank
source E2 Lower alarm
E3

M P

Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Connection Sockets
14PFA (Front-connecting)
PL15 (Rear-connecting)

Principles of Operation

Water tank
• When the water level drops E2, the lower-limit indicator turns ON
and the alarm sounds.
B Upper (U1 indicator ON)
• When the water level reaches E2, the indicator turns OFF and limit E1 (U1 indicator OFF)
the intermediate indicator turns ON.
• When the water level rises to E1, the upper-limit indicator turns Middle
ON and the alarm sounds. (U2 indicator ON)
Lower E2 (U2 indicator OFF)
B limit
E3
61F-G@P
Dimensions
Note: All units are in millimeters unless otherwise indicated.

61F-G1P, -G1PL, -G1PH, -G1PD


61F-G2P, -G2PL, -G2PH, -G2PD
61F-IP, -IPL, -IPH, -IPD

79 60
61F-G1P
61F-G2P
61F-IP 118

89
3.5
30 97.5
72
14PFA

■ Safety Precautions
Refer to Safety Precautions for All Level Controllers.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.


To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

In the interest of product improvement, specifications are subject to change without notice.