Module de communication LULC031 Table of Contents
Page
1 2 3 4
4-1 4-1-1 4-1-2 4-1-3 4-1-4 4-2 4-2-1 4-2-2
Introduction .........................................................................................................24 Description...........................................................................................................25 Installation............................................................................................................26 Control connections........................................................................................27
Network connections via an RS485 link ..........................................................27 RJ45 connector pin-out ....................................................................................27 Connection schematics (PLC <=> RJ45).........................................................27 Connection to the SCA type units.....................................................................28 Connection topology.........................................................................................28 Examples of electrical diagrams.........................................................................29 Association with an LUCA/B/C/D control unit ...................................................29 Association with an LUCM multifunction control unit........................................29 ENGLISH
5
5-1 5-2 5-2-1 5-2-2 5-2-3 5-2-4 5-2-4-1 5-2-4-2 5-2-4-3 5-3 5-4
Operation ..............................................................................................................30
To address and identify the control unit............................................................30 Implementation.....................................................................................................30 Programming example on a Micro or Premium TSX platform...........................31 Contingency modes if communication with the PLC is lost..............................32 Command for the programmable output LO1 ..................................................32 The registers .....................................................................................................32 The read/write zones ..................................................................................32 List of registers that can be read/write accessed in association with a LUCA/B/C/D control unit ..................................................................33 List of registers that can be read/write accessed in association with an LUCM multifunction control unit.....................................................37 Schematic diagram ..............................................................................................40 Description of the faults ......................................................................................40
6 7
Technical characteristics .............................................................................41 Connection capacities ...................................................................................41
05-2003
Table of Contents
LULC031 communication module
1 Introduction
The LULC031 communication module can be used to connect the TeSys model U starter unit to the Modbus network.
For further information about the Modbus protocol, please see the reference WEB site at the following address: www.Modbus.org. The protection and control information available depends on the control unit to which the module is associated. The module enables the following information and commands to be remotely accessed:
Control units
standard LUCA
advanced LUCB/CC/CD
multifunction LUCM
ENGLISH
States (ready, running, fault) Alarm Remote reset via the bus Motor load indication Fault differentiation Remote configuration and consultation of all the functions "Log" function "Monitoring" function On and off commands
The LULC031 module must only be used with LUC BL control units (24V DC).
WARNING
Improper communication port usage Use communication ports for transfer of non-critical data only, The data provided by monotoring contactor status and current levels is delayed by transmission time. Do not use this data for critical control decisions. Verify function settings before starting the motor. Do not use functions such as Run, Stop and Reverse for emergency or critical control applications. Improper use of Communication Ports can result in death, serious injury, or equipment damage.
05-2003
LULC031 communication module
2 Description
For the module to operate, power must be supplied via a 24V DC auxiliary source. For local control requirements, the LULC031 module incorporates a digital output 0.5A/24V DC. Modbus communication status LED
Module failure LED
RS 485 Modbus link RJ45 connector Connection for 24V DC auxiliary power supply for the module Digital output Connection for the 24V DC regulated power supply for outputs OA1, OA3 and LO1
Green "COM" LED
Flashing
Module is initializing or exchanging frames on the bus Communication fault not acknowledged Bus parameters are being initialized the Internal module fault 24 V voltage present on outputs OA1, OA3 and LO1
Red "ERR" LED
Flashing alone Flashing (alternately with "COM" LED) On
Green "24V =" LED
On
05-2003
ENGLISH
Outputs to control the Power base
LULC031 communication module
3 Installation
The Modbus LULC031 communication module is easily installed in the power base (LUB../LUS.. or LU2B../LU2S..) under the LUC...BL control unit that locks it into position. It must be assembled in the following order: 1) The starter control connector can be connected by wire using LU9BN11C cable (for LUB../LUS..) or LU9MR1C cable (for LU2B../LU2S..). NOTE: Direct wiring can be used, for example, to insert external stop control or a voltage interface. 2) install the Modbus LULC031 communication module. 3) install the LUC...BL control unit, NOTE: The control unit must be 24V DC
ENGLISH
Power base LUB.... LUS....
LUC...BL control unit
Power base LU2B.... LU2S....
LULC031
LU9BN11C
LU9MR1C
05-2003
LULC031 communication module
4
4-1 4-1-1
Control connections
Network connections via an RS485 link RJ45 connector pin-out
The module is connected to the Modbus network via an RJ45 connector by respecting the following wiring: RJ45 connector pin-out
1 2 3 4
Signal Do not connect Do not connect Do not connect
D(B)
RJ45 connector pin-out
5 6 7 8 D(A)
Signal
Do not connect Do not connect
0 V.L
4-1-2
Connection schematics (PLC <=> RJ45)
PCMCIA / TSXSCP114 board (channel 1)
470 W 0V Tx 18 10 12
RJ45 of the LULC031 module Wiring direction for the RJ45 connector
1 8
D(A) D(B)
Tx + 11 9 470 W 5V Rx Rx + 20 1 2 5 13 16
D(B) D(A)
4 5
0 V.L
TSXSCY21601 coupler (channel 0)
SUB D 25 pins 470 W 0V 5V 470 W 6 24 Tx Tx + 21 9
RJ45 of the LULC031 module
D(A) D(B)
D(B) D(A)
4 5
11 150 W 0V 23 13
nc nc
0 V.L
Shielding NOTE: ensure that the 470 resistors are connected to the 0 V and 5 V polarities. NOTE: Schneider references for cables used to link the modules RJ45 connector to the coupler: (coupler)TSX SCP 114 <------> (cable) TSX SCP CX4030 <------> RJ45. (coupler)TSX SCY 21601 <------> (cable) TSX SCX CM6030 : Stripped wires <------> RJ45. 05-2003 7
ENGLISH
LULC031 communication module
4-1-3
Connection to the SCA type units
Unit
SCA 50 SCA 62
Commercial reference
VW3 A8 306 D30 VW3 A8 306
Ends of the cable
RJ45 RJ45
Free wires
SUBD15
4-1-4
Connection topology
Connecting accessories exist, such as: - T-couplings: to connect several LULC031 modules on the bus LULC031
1 - LULC031 communication module
ENGLISH
2 - T-coupling VW3A8306TF 3 - VW3A8306R D wire 4 - VW3A8306R line termination NOTE: We recommend placing a line end termination at each end of the bus to avoid malfunctions on the communication bus. This means that a T-coupling must not have a free RJ45 connector. Either it is connected to a slave or the master, or there is a line end termination.
PLC
- Distribution units: to connect several LULC031 modules in star connection.
1 - LULC031 communication module
3
2 - VW3A8306R connection cable with 1 RJ45 connector on each end 3 - LU9GC3 Modbus distribution unit with channel connection on the PLC side and starter-controller side via RJ45 connectors
1 1
Line termination To the PLC
05-2003
LULC031 communication module
4-2
4-2-1
Examples of electrical diagrams Association with an LUCA/B/C/D control unit
+24V DC
LULC031
OUTPUT COM OA1 OA3 COM 24V + LO1
QF1 Modbus module
24V AUX + D(B) D(A) 0 V.L
0V
4 5 8
QF1 A2 A1 V1
Modbus
24V DC
Control by Modbus communication module without coil pre-wiring and with emergency stop
S1
4-2-2
Association with an LUCM multifunction control unit
LUCM
24V AUX + -
Multifunction Control Unit
D(B) D(A) 0 V.L
4 5 8 +
24V DC
LULC031
OUTPUT COM OA1 OA3 COM 24V + LO1
QF1 Modbus module
24V AUX + D(B) D(A) 0 V.L
Control by Modbus communication module without coil pre-wiring and with emergency stop
4 5 8
+24V DC QF1 A2 A1 V1 LUB/LU2B LUS/LU2S S1
Modbus
0V
24V DC
NOTE: 24V DC auxiliary power supplies are compulsory for fault-free operation.
05-2003
ENGLISH
LULC031 communication module
5
5-1
Operation
To address and identify the control unit
The Modbus communication module address is defined by the micro switches which can be accessed in the lower part of the module. Values from 1 to 31 are accepted. Address encoding is in binary with the least significant bit on the left. The module is supplied factory-set with address 1. Address 0 (used by the Master for a broadcast request) is not taken into account by the module.
On
1 On
Ex : address 5
ENGLISH
Register 690 is used to identify the control unit that is present. This register is read/write accessible and can contain 3 values written by the user: - Value 0 ==> Auto-identification function (by default). The LULC031 module automatically identifies the type of control unit at power up, - Value 1 ==> The control unit is the "standard" type (LUCA) or "upgradable" (LUCB/C/D), - Value 2 ==> The control unit is the "multifunction" type (LUCM), Addressing is only taken into account when the communication module is switched on to the power supply.
5-2
Implementation
Communication is based on Modbus RTU slave protocol. The data format is the following: 1 start bit 8 data bits 1 parity bit 1 stop bit
1) When 24V DC aux is supplied, the LULC031 module initializes 2) At the end of the initialization phase, the LULC031 module will automatically identify the configuration parameters for the RS 485 link. To do this, a certain amount of traffic is obviously required on the network. The LULC031 module recognizes the speed and parity of the Master after analyzing a maximum of 40 frames for the lowest speed (1200 baud). The magnitudes recognized are: - Speed: 1200, 2400, 4800, 9600 and 19200 baud - Parity: even, odd, no parity (parity bit deleted). NOTE: These parameters are factory preset to 19200 baud, no parity and 1 bit stop. The recognized Modbus requests are: - Code 03 (03 hex) (read multiple register), - Code 06 (06 hex) (write single register), - Code 16 (10 hex) (write multiple register). - Code 43 (2B hex) (read device identification) to identify the module. NOTE: The "Broadcast" function is supported for request codes 06 and 16 using address 00. The "exception" codes supported are: - Code 01 - Illegal function, - Code 02 - Illegal data address, - Code 03 - Illegal data value (write command not completed). 10 05-2003
LULC031 communication module
NOTE: The detailed format of these requests is explained on the site www.Modbus.org NOTE: When combined with the LUCM multifunction control unit, you must ensure that you do not supply 24V DC power to the LULC031 module before suppling 24V DC power to LUCM control unit. Otherwise, a communication fault will be generated at the LULC031 module (red LED On). This fault can only be cancelled by turning the LULC031 module off.
5-2-1
Programming example on a Micro or Premium TSX platform
The applications for Micro and Premium logic controllers are designed and implemented using PL7 software. The READ_VAR or WRITE_VAR requests respectively read or write the value of one or more consecutive objects of the same type (bit, word) in PL7 language. Index of the first object to be read
! (* read the states of the motor feed at address 4 contained in the internal word MWO *) IF %MO AND NOT %MW100:X0 THEN READ_VAR(ADD#3.0.4,%MW,455,1,%MW0:1,%MW100:4):RESET %M0; EN_IF;
Word table containing the value of the objects read
Recipient address
Nature of the PL7 objects to be read: internal word MW
Number of objects to be
Read report
Index of the first object to write
!
Word table containing the value of the objects to be sent
(* motor feed commands by transmitting the contents of the internal word MW 502 *) IF %M10 AND NOT %MW200:X0 THEN WRITE_VAR(ADD#3.0.4,%MW,704,1,%502:1,%MW1000:4):RESET %M10; EN_IF;
Recipient address
Nature of the PL7 objects to write: internal word MW
Number of objects to write
Write report
For more details on programming Modbus communication on a TSX platform, please refer to the PL7 on-line help, under the heading Communication fields Volume 2/ Communication via Modbus .
05-2003
11
ENGLISH
LULC031 communication module
5-2-2
Contingency modes if communication with the PLC is lost
The following commands only affect the operation of OA1 and OA3 modes if communication with the PLC is lost. These contingency modes are selected by writing 1 in the bits of register 682 according to the following allocation: Without contingency mode: - Value 0 ==> Contingency mode disabled (default setting), With contingency mode: - Value 1 ==> Held in same state (outputs OA1 and OA3 remain in the same state as before the loss of communication regardless of the commands written in register 704), - Value 2 ==> Forced stop, - Value 3 ==> Unchanged (signals a Time Out fault, the command states in register 704 are copied to outputs OA1 and OA3), - Value 4 ==> forced running in direction 1 (OA1 output = 1 and OA3 output = 0), - Value 5 ==> forced running in direction 2 (OA3 output = 1 and OA1 output = 0).
ENGLISH
5-2-3
Command for the programmable output LO1
It is possible to allocate a default command to the digital output of the LULC031 module. This provides a fault output on the communication module. This is allocated by writing 1 to the bits in register 685. - Value 0 ==> LO1 port always on 0 (zero), - Value 1 ==> LO1 port always on 0 1, - Value 2 ==> No allocation, output LO1 is not used, - Value 3 ==> A thermal overload fault will cause output LO1 to close (452.3 = 1). - Value 4 ==> A thermal overload warning will cause output LO1 to close (461.3 = 1). - Value 5 ==> Rotary button set to the ready position will cause output LO1 to close (457.0 = 1). - Value 6 ==> The mechanical system tripping (rotary button set to the Trip position) due to an over-current or short-circuit fault will set output LO1 to 1 (457.1 = 1), - Value 7 ==> Close down of the power Base poles will cause output LO1 to close (457.2 = 1).
5-2-4
The registers
The number and content of the registers that can be accessed differs according to the type of control unit to which the module is associated.
5-2-4-1
The read/write zones
The memory zone from 0 to 19999 can be accessed by the client. - Reading the zone of a "Reserved" register (or non-set) causes a correct response (value "0"). - Writing to the zone of a "Reserved" register causes a correct response (value "0"). NOTE: The write operation is not taken into account and the contents remain equal to (0). - Writing to the zone of a "Read only" register causes a response with an exception code (code 03). The memory zone = 20000 is private and therefore reading/writing is not authorised. NOTE: All accesses will be signalled by an exception code (code 02).
12
05-2003
LULC031 communication module
5-2-4-2
List of registers that can be read/write accessed in association with a LUCA/B/C/D control unit
From 50 to 80, identification registers, read only 16-bit register 50 to 54 Bit Range ASCII Unit Default LUCA value only 0 Information Module commercial reference msb = charactere 1 msb = charactere 3 msb = charactere 5 msb = charactere 7 msb = charactere 9 61 62 63 75 2 4 0-1 0-1 Off/On Off/On 0 0 0 - 149 0-65535 0-65535 0 0 0 lsb = charactere 2 lsb = charactere 4 lsb = charactere 6 lsb = charactere 8 lsb = charactere 10
Module firmware revision x100 (example: the value 100 corresponds to version V1.0) Module parameter compatibility version x100 Identification register: Control unit LUCA/B/C/D Multifunction control unit LUCM
From 451 to 473, command registers, read only 16-bit register 451 Bit Range Unit Default LUCA value only 0 Information Fault number register*
0-65535 None
Description of the fault (register 451) Short-circuit fault Magnetic fault Thermal overload fault Control unit internal fault LULC031 Module internal fault LULC031 Module loss of communication 452 0 1 2 3 4 to 10 11 12 0-1 0-1 0-1 0-1 0-1 0-1 0-1 Off/On Off/On Off/On Off/On Off/On Off/On Off/On 0 0 0 0 0 0 0 1 2 4 54 100, 101, 102, 104 109 Short-circuit fault Magnetic fault Reserved Thermal overload fault Reserved Control unit internal fault Reserved
05-2003
13
ENGLISH
Module identification module = 100)
code
(LULC031
LULC031 communication module
From 451 to 473, command registers, read only 16-bit register (452) Bit 13 14 15 455 0 1 2 Range 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-63 Unit Off/On Off/On Off/On Off/On Off/On Off/On Off/On Off/On Off/On Off/On Off/On 3.125 %IR Default LUCA value only 0 0 0 0 0 0 0 0 0 0 0 0 0 Information Module internal fault Reserved Reserved
Ready. Rotary knob set to
and no fault.
On (= 1 contactor switched on) Fault (overload , magnetic, short-circuit, internal fault) Alarm (thermal overload and loss of communication) Tripped (Rotary handle = "Trip") Reset authorized Reserved Reserved Reserved
ENGLISH
3 4 5 6 7 8 to 13
LUCB Motor current on 6 bits LUCD 455.8 Isb 455.13 msb The value 32 is 100 % of I average/FLA LUCC Motor current on 6 bits 455.8 Isb 455.13 msb The value 21 is 100 % of I average/FLA Reserved
4.69 %IR
14 15
0-1
Off/On
NOTE: The information in register 455 is the result of logic equations that consider the mechanical states of the starter and the internal logic information (fault, running...) 457 0 1 2 3 4 to 15 0-1 0-1 0-1 0-1 0-1 Off/On Off/On Off/On Off/On Off/On 0 0 0 0 0
Rotary handle = ON Rotary handle = "Trip" State of the power terminals Vout powered, 24 V DC on the outputs Reserved voltage present
NOTE: The information in register 457 (bits 0 to2) corresponds to the mechanical states of the starter. Hence, bits 0 and 1 reflect the position of the rotary knob, while bit 2 corresponds to the logic information of the NO contact 13-14. 460 0-65535 None 0 Warning number = 4 thermal overload, = 109 loss of communication on external ModBus port
14
05-2003
LULC031 communication module
From 451 to 473, command registers, read only 16-bit register 461 Bit 0 to 2 3 4 to 15 466 Range 0-1 0-1 0-1 0-200 Unit Off/On Off/On Off/On %IR Default LUCA value only 0 0 0 Reserved Thermal overload warning Reserved I AV average current (accuracy 10%) Information
NOTA : (register 466) With an LUCC single-phase advanced control unit, the value 67% corresponds to nominal motor I instead of 100% in three-phase. 473 0-65535 None Checksum value of the module configuration
602, configuration register, read and write accessible if the starter is stopped 16-bit register 602 Bit 0 1 2 3 to 15 Range 0-1 0-1 0-1 0-1 Unit Off/On Off/On Off/On Off/On Default LUCA value only 1 0 0 0 Information Thermal overload failure must be reset manually Thermal overload remote reset Thermal overload fault auto reset Reserved
From 681 to 690, setting registers, read/write accessible 16-bit register Value Range Unit Default LUCA value only Information
Timeout on loss of external communication 681 0-65535 None 6000
Time out (time base 10 ms) NOTE: The zero value (0) represents zero time.
Configuration du mode de repli en cas de perte de communication externe 682 0 1 2 3 4 5 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0
Contingency mode disabled Outputs held is same state OA1 and OA3 outputs forced to 0 Outputs OA1 and 0A3 unchanged, signalling that a loss of communication exists OA1 output forced to 1 OA3 output forced to 1
05-2003
15
ENGLISH
LULC031 communication module
From 681 to 690, setting registers, read/write accessible 16-bit register Value Range Unit Default LUCA value only Information
Allocation and control of output LO1 685 0 1 2 3 4 5 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0-65535 None 0 LO1 output forced to 0 V LO1 output forced to 24 V Image print out of the 700 register status Thermal overload fault Thermal overload warning Rotary handle = ON Rotary handle = "Trip" Power Base poles state
ENGLISH
6 7
Identification of the control unit type 690 0 1 2 0-65535 None 0-65535 None 0-65535 None 0 Auto-identification of the control unit type Standard control unit LUCA Upgradable control unit LUCB/CC/CD Multifunction control unit LUCM
From 700 to 705, command registers, read/write accessible 16-bit register 700 701 702 703 3 Bit Range Unit Default LUCA value only 0 0 0 0 Information LO1 output (if 685 = 2) Reserved Reserved
0-65535 None 0-65535 None 0-65535 None
Alarm acknowledgement if communication is lost with the following contingency modes validated: unchanged, forced running in the direct direction, or forced running in the reverse direction, outputs OA1 and OA3 held when [682] = 1, 3, 4 or 5. Run (output OA1) Run (output OA3) Reserved
704
0 1 2
0 0 0
16
05-2003
LULC031 communication module
From 700 to 705, command registers, read/write accessible 16-bit register (704) Bit 3 Range Unit Default LUCA value only 0 Information 460 = 102 or 104 alarms reset 451 = 102 or 104 faults reset This action results in the restitution of the LULC031 modules default settings (factory settings) (see 5-4 Description of the faults, page 20) 0
Loss communication fault reset (if 682 = 2) Reset Reserved Return parameters to default value (factory setting).
4 to 15 705 0 0-1 Off/On
0 0
5-2-4-3
List of registers that can be read/write accessed in association with an LUCM multifunction control unit
This control unit satisfies the strictest motor protection requirements. These protection systems can be adjusted and configured locally via a display/keypad that is incorporated on the front panel and remotely by reading/writing to registers. It processes the following information: - diagnostics (type of faults, current values,) - operating (number of starts, operating time, number and type of trips,) - fault log (record the last 5 faults with the motor current at the moment the fault occurred) This information is provided in registers, the summary of which is the following (for more details, see the users manual for the multifunction control unit).
Identification
Registers 0 ... 99 75
Words / Bits Bit 4
Commercial reference, serial number, software versionof the module with the multifunction CU, the CU and the base Multifunction control unit LUCM
Log
Registers 100 ... 450 -
Words / Bits -
Fault log, Operating log, Log of the last 5 trips -
05-2003
17
ENGLISH
LULC031 communication module
States Registers 451 ... 464 451 452 Words / Bits Word Default n Bit 0 Bit 1 Bit 2 Short-circuit fault Magnetic fault Thermal overload fault Alarm signalling (bits) Fault signalling (bits)
Bit 3 to (see the operating manual for the multifunction control Bit 15 unit LUCM) 455 Bit 0 Bit 1 Ready. Rotary knob set to Power poles closed Fault Alarm Reserved Reset no allowed Reserved Reserved Motor current % (bit 0) Motor current % (bit 1)
ENGLISH
Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9
Bit 10 Motor current % (bit 2) (455) Bit 11 Motor current % (bit 3) Bit 12 Motor current % (bit 4) Bit 13 Motor current % (bit 5) Bit 14 Reserved Bit 15 Run start 460 461 word Bit 3 Warning number Thermal overload warning
Values
Registers 465 ... 471 465 466
Words
Ieff for phase1, phase 2, phase3 motor load, thermal state, earth leakage current, phase unbalance and phase missing Thermal capacity (Im/Ir) motor load
word word
Registers 472 ... 599 -
Words / Bits -
Reserved -
18
05-2003
LULC031 communication module
Configuration Registers 600 ... 699 601 Words / Bits Bit 2 Bit 3 Bit 4 Protection and alarm thresholds, contingency mode and rearming mode Power Base type (only significant when one of the bits 3 to 6 is set) = 1 Base size 12A LUB12 = 1 Base size 32A LUB32
Bit 13 3 phases load Bit 14 A phase load Bit 15 Aux fan cooled 602 Bit 0 Bit 1 Bit 2 Reset mode-manual
Thermal overload fault auto reset
Bit 3 to (see the operating manual for the multifunction control Bit 15 unit LUCM) 681 682 685 690 Value (see page 15) Value (see page 15) Value (see page 16) Value (see page 16)
Commands
Registers 700 ... 714 700 703 704
Words / Bits Bit 0 Bit 3 Bit 0 Bit 1 Bit 2 Bit 3
Commands LO1 output (if 685 = 2) Alarm acknowledgement "LULC031 Module loss of communication" OA1 output OA3 output Reserved 460 = 102 or 104 alarms reset 451 = 102 or 104 faults reset (see 5-4 Description of the faults, page 20)
Bit 4 Bit 5 Bit 6 to 15
Reserved Trip test Reserved
05-2003
19
ENGLISH
Thermal overload remote reset
LULC031 communication module
5-3
Schematic diagram
Advanced Control Unit (LUCB/CC/CD) or Multifunction Control Unit (LUCM)
Input Interface
LULC031
ON/OFF - TRIP - POLE
LED
address
D (B)
mP
ENGLISH
4 5 8
RS485
D (A) 0 V.L
Output Interface
AL1 AL2 power supply
24V
COM OA1 OA3 LO1 COM
24V Aux
5-4
Description of the faults
Fault Green "24V LED off " Causes 24V DC power missing on the 24V terminal Internal LULC031 module faults Corrective actions Check the connection between the power supply and the module If register 451 = 102 or 104 : ==> acknowledgement by setting bit 704.3 to 1 This action results in the restitution of the LULC031 modules default settings (factory settings) in respect of the following parameters : - Bus speed and parity, - Setting registers 681 to 690 -------------If register 451 102 or 104 : ==> cycle the LULC031 module off and on. Red "ERR" LED flashing Loss of communications If register 682=2 : on the Modbus network ==> acknowledgement by setting bit 704.3 to 1 If register 682=1,3 ,4 ou 5 : ==> acknowledgement by setting bit 703.3 to 1
Red "ERR" LED permanently on
20
05-2003
LULC031 communication module
6 Technical characteristics
Physical interface Protocol Max transmission speed Bit/s RS 485 Modbus RTU Auto-configuration up to 19200 10 with LUCA/B/C/D control units 200 with LUCM control unit Via switches: from 1 to 31 C V For operation 25+55 24 DC Limited to 500 3 including 2 dedicated to controlling the windings of the starter-controller 0.5A / 24V 10%
Maximum clear-to-send delay for a request ms Addressing Ambient air temperature Power supply for the outputs
Current consumed on the auxiliary 24V DC mA Number of outputs Commutation capacity of the outputs Accuracy on the Im/Ir values
NOTE: The clear-to-send delay corresponds to the time between the end of the question from the Master and the beginning of the response from the LULC031 module.
Connection capacities
Connectors 3 and 6 Pins - pitch: 3.81 Starter control and monitoring Connection: 1 connector - rigid conductor: ....................................... - flexible conductor:................................... - conductor size: ....................................... - flexible conductor with terminal end: - without insulated ferrule: .................... - with insulated ferrule: ......................... Multiple connection: (2 conductors with the same section) - 2 rigid conductors: .................................. - 2 flexible conductors:.............................. - 2 flexible conductors with terminal end: - without insulated ferrule: .................... - with insulated ferrule: ......................... Tightening torque: Flat-blade screwdriver: 0.25 to 0.34 mm2 0.75 mm2 (0.2 / 0.25 N.m) 1.79 / 2.23 Lb-in 2.5 mm (0.10 in) 0.14 to 0.5 mm2 0.14 to 0.75 mm2 0.25 to 1. mm2 0.25 to 0.5 mm2 0.14 to 1 mm2 0.14 to 1 mm2 AWG 28 to AWG 16