Mindanao Journal of Science and Technology Vol.

19 (1) (2021) 163-177

Concrete Hollow Block Production Using Fine


Aggregates of Polyvinyl Chloride and Polystyrene
Roberto L. Rodriguez, Jr.1, 2* and Johnny A. Ching2
1Senior High School Department
FEU Cavite
Silang, Cavite 4118 Philippines
*[email protected]

2University
Research Office
De La Salle University – Dasmariñas
City of Dasmariñas, 4114 Philippines

Date received: September 26, 2020


Revision accepted: February 8, 2021

Abstract
Population concurrently grows with demand for food and infrastructure, which are
associated with plastic waste mismanagement and concrete hollow block (CHB)
consumption, respectively. However, there is a dearth in the utilization of plastic
pellets using polyvinyl chloride (PVC) and polystyrene (PS) in CHBs. Hence, this study
aimed to characterize PVC and PS pellets, and evaluate and compare their potentials
when incorporated as fine aggregates in CHBs in terms of workability and compressive
strength. The pellets were characterized and used as a substitute to sand resulting in
four batches of CHB specimen with 0, 10, 20, and 30% by volume of each pellet. Results
revealed that PVC absorbed more and sank in the water while PS absorbed less and
floated in water. The workability of both experimental groups increased as the
substitution of pellets was increased. The compressive strengths of the PVC group
dropped linearly with increasing pellet substitution and less than the minimum
acceptable value. The batch with 30% PS pellets resulted in the highest compressive
strength of 3.66 MPa among the experimental groups and greater than the minimum
acceptable value of 3.45 MPa. Results implied that the incorporation of PS pellets in
CHBs can be a promising solution to the plastic waste mismanagement and demand
for stronger CHBs.

Keywords: plastic utensil, wire cable insulation, slump value, compressive load, mass
concrete

1. Introduction

The effects brought about by exponential population growth have been


ubiquitous worldwide. One effect is the growing statistics in the demand and
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

consumption of the fundamental needs of human beings such as food and


shelter. However, the processes underlying food production and materials for
infrastructure as well as their preservation greatly contribute to a multifold and
alarming increase in waste products.

The utilization of plastic materials in manufacturing, storing, and preserving


foods are evident. Plastic materials are present in these processes in various
forms and types. The benefits of using plastic in these processes come with
the alarming effects on the environment (Sharma and Bansal, 2015). One of
which is the staggering report on plastic debris in the ocean which was
recorded to be 5.25 trillion pieces already (Parker, 2015) with a rate of 8
million trashes from 192 coastal countries (Dunham, 2015; Parker, 2015).

The Philippines ranked third in the list of coastal countries intensely


contributing to plastic pollution around the globe (Dunham, 2015; Ocean
Crusaders, 2020). The country dumps 125, 000 bags of plastics each day
(Arkin, 2015) aggregating to 1.88 million tons of plastic wastes each year
(Agence France-Presse, 2017). This was represented by the weekly
Greenpeace Coastal Clean Up in September 2017 at the Manila Bay wherein
54, 200 pieces of plastic waste – materials from products sold by
conglomerates like bags, bottle labels, sachet, and straws which were relevant
to three identified companies – were recovered (Agence France-Presse, 2017).
The country’s current battle with plastic mismanagement urged various
organizations and local government units (LGUs) to set forth policies and
projects to put this to an end (Arkin, 2015). Some LGUs act by implementing
policies in partnership with different companies and organizations (R. D. L.
Peneyra, personal communication, November 3, 2018).

Aside from food, the exponential demand for shelter and infrastructure entails
the rise in the need for construction materials with sufficient fresh and strength
parameters to withstand any topographical and environmental risks and
disasters such as typhoons and earthquakes. According to Reddy and Kolasani
(2015), water and concrete hollow blocks (CHB) are the top two of the most
consumed substances on earth. These materials are in great demand
particularly in the industrial sector for infrastructural projects.

Innovations have been established to replace the aggregates of different


materials and improve the parameters of CHB such as compressive strength,
workability, tensile strength, and flexural strength among others (Gardner et
al., 2015; Senhadji et al., 2015; Manjunath, 2016; Pešić et al., 2016;

164
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

Gregorova et al., 2017; Hama and Hilal, 2017; Khalil and Khalaf, 2017; Lasco
et al., 2017; Patel and Dala, 2017; De Jesus et al., 2018; Nguyen et al., 2018;
Hameed and Ahmed, 2019). Generally, fresh and strength parameters of
concrete increase almost linearly as the percentage of replacement increases
(Sharma and Bansal, 2015; Babafemi et al., 2018). The studies have
established the fact that the replacement of concrete constituents affects the
concrete’s fresh and strength parameters.

Among the innovations in CHB production, replacing fine aggregates with


plastic waste materials abound in the scientific society to solve both the need
for stronger CHB and solutions for recycling plastic wastes. The replacement
of fine aggregate with polypropylene pellets (PP) is the only local study that
maximized pellet materials in the Philippines using nominal size CHB 4” x 8”
x 16” and following the standards for CHB in the country (Lasco et al., 2017).
However, studies that maximize the use of other types of plastic materials like
low-density polyethylene (LDPE), high-density polyethylene (HDPE),
polyvinyl chloride (PVC), and polystyrene (PS) (Lasco et al., 2017) are scant.
As recommended by Lasco et al. (2017), extensive investigation on the use of
different types of plastic wastes aside from PP and measurement of other
strength parameters should be carried out. Thus, the present study
characterized PVC and PS pellets as CHB reinforcement; determined the
effects of varying percentage replacement of fine aggregate with PVC and PS
pellets on the fresh and strength parameters of CHB such as workability and
compressive strength; and compared the PVC- and PS-blended CHBs’ fresh
and strength parameters.

2. Methodology

The study used an experimental research design. Materials were acquired from
the local hardware in Silang, Cavite, Philippines. The materials were prepared
based on the characterization and computed amount of each material before
mixing. The mixing of each material for each batch was done in a construction
site in Silang, Cavite. The fresh parameter of each batch was tested in situ after
acquiring a wet mixture. The specimens were then cured in preparation for the
measurement of strength parameter done at the laboratories of the College of
Engineering, Architecture, and Technology (CEAT) of De La Salle University
– Dasmariñas (DLSU-D).

165
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

2.1 Materials Preparation

The raw materials used were water, cement, white sand, PVC pellets, and PS
pellets. Commonly used for mixing and curing, the clean tap water was from
the CHB manufacturing site in Silang, Cavite. The specific gravity was taken
as 1.00. The cement used was Type 1 Portland cement purchased from a local
supplier. White sand as the fine aggregate was characterized and prepared
until a saturated surface dry condition was achieved. The PVC pellets were
thermoplastic pellets previously used as wire cable insulation obtained from a
junk shop in Silang, Cavite, wherein ground residual wastes from electronics
companies in the place are received. The PS pellets were in the form of plastic
cutlery wastes from the same junk shop. These cutleries were ground in a
grinding machine to achieve pellet size. These pellets in Figure 1 underwent
sieve analysis using American Society for Testing and Materials (ASTM)
E11-20 (2020) sieve plate number 04 with an aperture of 4.75 mm (Milano,
Italy). Pellets with sizes larger than 4.75 mm (> 4.75 mm) were excluded as it
may affect the strength parameters of the specimen (Lasco et al., 2017). These
materials were characterized in terms of density and specific gravity using
Archimedes’ Principle (Lasco et al., 2017), bulk density following ASTM
D1895-17 (2017), and absorption for 24 h following ASTM D570-98 (2018),
which became the bases for mixing. The fluid used in the characterization of
PVC pellets was distilled water while isopropyl alcohol was utilized for PS
pellets due to the difference in specific gravity.

(a) (b)

Figure 1. PVC pellets from wire cable insulation (a) and PS pellets from plastic
utensils (b) ground using grinding machineries

166
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

The materials were mixed to form the test specimens. Four batches each were
prepared for PVC- and PS-blended CHBs: batch 1 (0%), batch 2 (10%), batch
3 (20%), and batch 4 (30%) (Lasco et al., 2017). Batch 1 served as the
reference group wherein all other batches were compared with. The
distribution and measurement of each raw material based on the
characterization for each batch are shown in Table 1.

Table 1. Masses (kg) of each CHB constituent per cubic meter (m3) corresponding to
a mixed proportion (adapted from Lasco et al., 2017)

Mix proportion by volume per batch of PVC and PS concretes


Material
1 (0%) 2 (10%) 3 (20%) 4 (30%)

PVC Fine Aggregates


Water 91.65 82.50 73.30 64.15
Cement 197.61 177.88 158.05 138.32
Sand 1132.91 1019.68 906.33 793.10
PVC 0 123.31 246.61 369.99
PS Fine Aggregates
Water 91.65 82.50 73.30 64.15
Cement 197.61 177.88 158.05 138.32
Sand 1132.91 1019.68 906.33 793.10
PS 0 95.72 191.44 287.22

For each batch, five test specimens were made to maintain objectivity and
attain precision. This resulted in a total of 35 test specimens. The materials
were mixed with the cement to the sand ratio of 1:5 by volume and water-
cement ratio of 0.50 by volume. The test specimen mixtures were molded into
a 4” x 8” x 16” nominal size of CHBs (Lasco et al., 2017) using a molder.
Overestimation of materials was done with the help of the owner and expert
in CHB manufacturing from Silang, Cavite to account for spillage during the
mixing process.

2.2 Test of Specimens

The workability was tested following standard test method for slump of
hydraulic cement concrete conforming to ASTM C143/C143M-20 (2020).
Compressive strength was tested using the universal testing machine (UTM)
for the standard test for sampling and testing concrete masonry units and
related units following ASTM C140/C140M-20a (2020). The compressive
strength test was done under the supervision of the technical support personnel
and laboratory technician of CEAT in DLSU-D. The results were reviewed
and certified by a civil engineer specializing in structural engineering.

167
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

The data gathered for the parameters from batches 2 to 4 were compared with
batch 1. The data analyses were focused on determining if at least one batch
was different from the reference group using one-way analysis of variance
(ANOVA). Pairwise mean comparison was then utilized to determine which
pairs of data were significantly different. All statistical analyses were done at
a 5% probability level.

3. Results and Discussion

3.1 Characterization of Fine Aggregates

The sand and plastic concrete reinforcements in CHBs were compared in


terms of their physical characteristics (density, specific gravity, bulk density,
and absorption rate). Table 2 shows the result of the characterization of the
fine aggregate. These values were used in the mixing of the constituents of
CHBs and bases for the justifications in the workability and compressive
strength.

Table 2. Physical properties characterization of sand and


plastic concrete reinforcements

Bulk Density Absorption


Material Density (g/cm3) Specific Gravity
(kg/m3) (%)
Sand 2.43 2.43 1236.13 1.00*
PVC 1.35 1.35 1345.40 0.91
PS 0.96 0.96 958.23 0.09
*
characterization of average water absorption of white sand from (Mishra, 2020)

As shown in Table 2, white sand and PVC aggregates sank in the water while
PS aggregates floated otherwise. Moreover, the PVC had a greater absorption
ability than PS which were both lower than that of the white sand. This means
that when the pellets were mixed with two different concrete mixtures, there
was more water available in the PS mixture than the PVC mixture for
hydration. Furthermore, the specific gravity of the PVC and PS pellets was
higher than that of the cited literature which used PP pellets with 0.89 (Lasco
et al., 2017). Meanwhile, the same as the sand, PVC pellets sank in the water.
These, in turn, justified the fact that whether the plastic pellet sinks or floats
in water, it can be a fine aggregate substitute for CHB mixture.

168
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

3.2 Workability

Table 3 shows the average measured workability or slump values (mm) of wet
concrete mixtures with PVC and PS plastic as fine aggregates. Based on the
results, the control group obtained the lowest slump value, and batch 4 of both
plastic-blended concretes attained the highest slump values. It can also be
observed that workability increased as the percentage of plastic pellets was
increased (Figure 2). Moreover, the mean slump values of the concretes with
PS pellets were slower than that of the PVC pellets.

Table 3. Workability (mm) of PVC- and PS- blended CHBs following the slump test
(ASTM C143/C143M-20, 2020)

Workability (mm)
Batches Degree of Workability
PVC PS
1 (0%) 10.30A 10.30A
2 (10%) 14.60BX 12.60BY Very low
3 (20%) 16.30CX 14.70BY (0 – 25 mm)
4 (30%) 21.90DX 21.10CY
ABCD
– Treatment within each type of plastic (batches); XY – the type of plastic pellets (PVC versus PS).
Different letters indicate a significant difference at the 0.05 level.

This set of data and observations confirmed the study of Choi et al. (2009) as
cited by Khalil and Khalaf (2017), Patel and Dala (2017) and Babafemi et al.
(2018). This trend was attributed to the lower absorption of the pellets (Table
2) resulting in a greater amount of water for the hydration of the mixture when
the amount of the natural fine aggregates was reduced (Babafemi et al., 2018).
Conversely, this result contradicts the study of Rai et al. (2012) as cited by
Babafemi et al. (2018). It can be inferred that concrete mixtures with PVC
pellets had greater slump values than that of the concrete mixtures with PS
pellets. Such result is in contrast with the idea that if the supplement has low
absorption (Babafemi et al., 2018), there is more amount of water available
for hydration since PVC had greater absorption than PS. This can be attributed
to the fact that the absorption test of PS pellets was done using isopropyl
alcohol compared with PVC pellets which were immersed in distilled water.

The values from batch 1 to 4 were within the very dry mixture classification
between 0 to 25 mm (The Constructor, 2018). This implies that the types of
concrete formed were suitable for the roads vibrated by power-operated
machines and can be compacted by hand-operated machines. Moreover, batch
4 of both plastic-blended concretes with PVC and PS pellets were in the range
of 20 to 40 mm for a mixture that can be maximized for road construction.
The same batch for plastic-blended concretes can be classified as a mixture
for mass concrete with a workability value ranged from 20 to 50 mm (The

169
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

Constructor, 2018). Hence, the mixtures can be utilized in various massive


structures such as dams, bridge piers, and canal locks among others (Kulkarni
and Oluwafisayo, 2017).

25.00

20.00
Workability (mm)

15.00 PVC
PS
10.00

5.00

0.00
1 (0%) 2 (10%) 3 (20%) 4 (30%)
Batches

Figure 2. Workability of plastic-blended concrete with PVC and PS pellet aggregates

3.3 Compressive Strength

The compressive strength values (MPa) of plastic-blended CHBs are


presented in Table 4 following ASTM C140/C140M-20a (2020). These values
show the maximum pressure or strength that the test specimen can withstand.

Table 4. Compressive strength (MPa) of PVC- and PS-blended CHBs following


C140/C140M-20a (2020)

Compressive Strength (MPa)


Batches
PVC PS
1 (0%) 3.78A 3.78A
2 (10%) 3.08BX 3.46AY
3 (20%) 2.58BCX 3.28AY
4 (30%) 2.20CX 3.66AY
ABCD
– Treatment within each type of plastic (batches); XY – the type of plastic pellets (PVC versus PS).
Different letters indicate a significant difference at the 0.05 level.

Based on the results, it can be seen that batch 1 attained the maximum
compressive strength. For CHBs with plastic pellets, batch 4 (30% PVC
pellets) and batch 3 (20% PS pellets) attained the weakest compressive

170
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

strengths within their respective experimental groups. Meanwhile, batch 2


(10% PVC pellets) and batch 4 (30% PS pellets) obtained the strongest
compressive strength within their respective experimental groups. It can also
be observed that the compressive strength dropped almost linearly from batch
1 to 4 of PVC-blended CHBs and minimal differences between the
compressive strength of PS-blended CHBs compared with the control group
(Figure 3). Thus, with these results, it is worth noting that the sets of data can
be analyzed separately.

4.00

3.50
Compressive Strength (MPa)

3.00

2.50

2.00
PVC
1.50
PS
1.00

0.50

0.00
1 (0%) 2 (10%) 3 (20%) 4 (30%)
Batches

Figure 3. Compressive strength of plastic-blended concrete with


PVC and PS pellet aggregates

Statistically, there was a significant difference (p < 0.05) between the


compressive strengths of the treatments on the PVC-blended CHBs. Among
the experimental group, batch 2 (10% PVC pellets) was able to withstand the
maximum pressure which confirmed the work of Lasco et al. (2017). This is
ascribed to the minimal amount of incorporated plastic which can still resist
the compressive load.

The compressive strength of CHBs partially replaced with PVC pellets


generally dropped from batch 1 to 4 nearly linear. This suggests that the
probability of localized cracking of the specimens increased as the percentage
replacement was increased up to 30%. This trend of findings is in agreement
with Khalil and Khalaf (2017) and Patel and Dala (2017). Meanwhile, this
result reversed the trend observed in other studies (Rahmani et al., 2013; Yang
et al., 2015; Azhdarpour et al., 2016) in which it was contended that the

171
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

increase of the compressive strength can only be observed if there is a small


amount of partial replacement of plastic aggregate in the CHB mixture.

The dropped trend of the compressive strength or the localized cracking of the
test specimens after being subjected to UTM was attributed to three common
reasons. First, there is a decrease in the adhesive force between the surface of
the waste plastic and cement paste (Lasco et al., 2017). Second, it is the nature
of plastic to be hydrophobic which can restrict the flow of water which in turn
made the curing period of the CHBs less effective. Third, the aforementioned
reasons result in lower strength in the interfacial transition zone (ITZ) of the
CHBs (Sharma and Bansal, 2015) and greater probability of having an
increase in the matrix porosity; thus, decreasing the specimen density and
compressive strength (Senhadji et al., 2015).

Meanwhile, there was no significant difference (p > 0.05) between the


compressive strengths of the PS-blended and the locally manufactured CHBs.
Hence, it can be inferred that the PS-blended CHBs were at par with the
control group in terms of strength. The CHBs with the maximum percentage
of plastic pellets incorporated were able to resist the maximum load among
the experimental group it belonged to. This result contradicted the findings
from PVC pellets experimental group whose maximum load was withstood by
batch 1 (10% PVC pellets). This is also in contrast with the results of Lasco et
al. (2017). Thus, PS pellets from plastic utensils can be utilized in a greater
percentage suggesting that a possible solution in solving problems in plastic
waste mismanagement of PS type of plastic and the demand for stronger CHB
in the infrastructure industry.

Lastly, the compressive strengths achieved by both experimental groups were


less than the control group with a mean value of 3.78 MPa. Such value was
greater than the minimum acceptable value of 3.45 MPa set by ASTM
C140/C140M-20a (2020) (Lasco et al., 2017).

4. Conclusion and Recommendation

The fine aggregates used to partially replace the sand as natural aggregate
were characterized in terms of density, specific gravity, bulk density, and
absorption. PVC had a greater absorption ability than PS which both were
lower than that of the white sand. PVC pellets absorbed more than PS pellets.

172
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

Hence, the PS-concrete mixture had more water for hydration than the PVC-
concrete mixture.

The study also revealed that the workability in terms of slump values of fresh
concrete mixtures increased linearly as the percentage replacements of both
PVC and PS pellets increased. This observation is linked to the pellet
absorption that resulted in more water for plastic-blended mixtures hydration.
Both slump values of PVC- and PS-blended CHBs are qualified for roads
vibrated by power-operated machines and can be compacted by hand-operated
machines. Further, both batch 4 of plastic-blended CHBs are apt for massive
structure utilization such as dams, bridge piers, and canal locks among others.

The experimental groups yielded different results in terms of compressive


strength. The compressive strength in the experimental group with PVC
pellets decreased as the percentage replacement of plastic aggregate increased.
Meanwhile, the compressive strengths of CHBs incorporated with PS pellets
were statistically equal to that of the control group. This implies that the PS-
blended CHBs were at par with the locally manufactured CHBs in terms of
maximum compressive strength. The maximum compressive strength in the
experimental group with PS pellets was obtained by batch 4 (30% PS pellets).
The said batch attained the maximum compressive strength among the
experimental groups which was less than the compressive strength of the
control group and greater than the minimum acceptable compressive strength
for 4” x 8” x 16” nominal size of CHB in the country. This suggests that
incorporation of PS pellets in greater percentage to concrete mixtures can
suffice the need for a solution for plastic waste management of PS type of
plastic in its cutlery form and the demand for stronger CHBs in the
infrastructure industry.

Based on the results, the following recommendations were drawn. First,


further investigation on the effect of small increment of percentage
replacement of plastic aggregates can be done to identify whether the large
leap from 0% is a factor to take into account. Additionally, increasing the
amount of plastic to greater than 30% may also be considered. Second, effects
of varying water to cement ratio and mix design using either PVC or PS pellets
at their best mixes for workability and/or compressive strength can be
examined to identify whether these affect such parameters. Third, it is
recommended to test the absorption of PS pellets in distilled water using
sinkers due to the difference in specific gravity of water and PS pellets. This
will help in validating the contradicting results of the cited literature and the
present study. Fourth, PVC and PS in other forms and grain sizes such as fiber

173
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

and flakes can also be utilized to determine if there is a significant difference


in the workability and compressive strength. Fifth, other types of plastic
wastes or residual wastes can be further maximized to solve plastic waste
management and provide potential solutions for the demand for stronger
CHBs in the country. Lastly, the effects of using plastic as fine and/or coarse
aggregates and investigating its effect on other physical and mechanical
properties and fresh and strength parameters of the CHBs (bulk density,
porosity, tensile strength, and flexural strength) may be carried out.

5. Acknowledgement

The advice, supervision, and guidance of Mrs. Teodora L. Rodriguez, Mr.


Roberto B. Rodriguez, Sr., and experts in the fields of engineering, who made
this study possible, are duly acknowledged.

6. References

Agence France-Presse. (2017). Greenpeace : PH is third worst plastic polluter of


oceans. Retrieved from https://newsinfo.inquirer.net/932739/greenpeace-environmen
t-water-pollution-polluter-manila-bay

American Society for Testing and Materials (ASTM) C140/C140M-20a. (2020).


Standard test methods for sampling and testing concrete masonry units and related
units. West Conshohocken, PA: ASTM International.

American Society for Testing and Materials (ASTM) C143/C143M-20. (2020).


Standard test method for slump of hydraulic-cement concrete. West Conshohocken,
PA: ASTM International.

American Society for Testing and Materials (ASTM) D1895-17. (2017). Standard test
methods for apparent density, bulk factor, and pourability of plastic materials. West
Conshohocken, PA: ASTM International.

American Society for Testing and Materials (ASTM) D570-98. (2018). Standard test
method for water absorption of plastics. West Conshohocken, PA: ASTM
International.

American Society for Testing and Materials (ASTM) E11-20. (2020). Standard
specification for woven wire test sieve cloth and test sieve. West Conshohocken, PA:
ASTM International.

174
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

Arkin, F. (2015). Asian states top global list of ocean plastic polluters. Retrieved from
https://www.scidev.net/asia-pacific/news/asian-states-top-global-list-of-ocean-plastic
-polluters/

Azhdarpour, A.M., Nikoudel, M.R., & Taheri, M. (2016). The effect of using
polyethylene terephthalate particles on physical and strength-related properties of
concrete: A laboratory evaluation. Construction and Building Materials, 109, 55-62.
https://doi.org/10.1016/j.conbuildmat.2016.01.056

Babafemi, A.J., Šavija, B., Paul, S.C., & Anggraini, V. (2018). Engineering properties
of concrete with waste recycled plastic: A Review. Sustainability, 10(3875).
https://doi.org/10.3390/su10113875

Choi, Y.W., Moon, D.J., Kim, Y.J., & Lachemi, M. (2009). Characteristics of mortar
and concrete containing fine aggregate manufactured from recycled waste
polyethylene terephthalate bottles. Construction and Building Materials, 23(8), 2829-
2835. https://doi.org/10.1016/j.conbuildmat.2009.02.036

De Jesus, R.M., Pelaez, E.B., & Caneca, M.C. (2018). Experimental study on
mechanical behaviour of concrete beams with shredded plastics. International Journal
of GEOMATE, 14(42), 71-75. https://doi.org/10.21660/2018.42.7172

Dunham, W. (2015). World’s oceans clogged by millions of tons of plastic trash.


Retrieved from https://www.scientificamerican.com/article/world-s-oceans-clogged-
by-millions-of-tons-of-plastic-trash/

Gardner, L.J., Bernal, S.A., Walling, S.A., Corkhill, C.L., Provis, J.L., & Hyatt, N.C.
(2015). Characterisation of magnesium potassium phosphate cements blended with fly
ash and ground granulated blast furnace slag. Cement and Concrete Research, 74, 78-
87. https://doi.org/10.1016/j.cemconres.2015.01.015

Gregorova, V., Ledererova, M., & Stefunkova, Z. (2017). Investigation of influence of


recycled plastics from cable, ethylene vinyl acetate and polystyrene waste on
lightweight concrete properties. Procedia Engineering, 195, 127-133. https://doi.org
/10.1016/j.proeng.2017.04.534

Hama, S.M., & Hilal, N.N. (2017). Fresh properties of self-compacting concrete with
plastic waste as partial replacement of sand. International Journal of Sustainable Built
Environment, 6(2), 299-308. https://doi.org/10.1016/j.ijsbe.2017.01.001

Hameed, A.M., & Ahmed, B.A.F. (2019). Employment the plastic waste to produce
the light weight concrete. Energy Procedia, 157, 30-38. https://doi.org/10.1016/j.egypr
o.2018.11.160

Khalil, W.I., & Khalaf, K.J. (2017). Eco-Friendly concrete containing pet plastic waste
aggregate. Diyala Journal of Engineering Sciences, 10(01), 92-105.

Kulkarni, R., & Oluwafisayo, O. (2017). Mass concrete – What is mass concrete &
where it is used? Retrieved from http://www.dailycivil.com/mass-concrete

Lasco, J.D.D., Madlangbayan, M.S., & Sundo, M.B. (2017). Compressive strength and
bulk density of concrete hollow blocks (CHB) with polypropylene (PP) pellets as

175
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

partial replacement for sand. Civil Engineering Journal, 3(10), 821-830.


https://doi.org/10.28991/cej-030917

Manjunath, B.T.A. (2016). Partial replacement of e-plastic waste as coarse-aggregate


in concrete. Procedia Environmental Sciences, 35, 731-739. https://doi.org/10.1016
/j.proenv.2016.07.079

Mishra, G. (2020). Properties of aggregates and its values for use construction.
Retrieved from https://bit.ly/37AFCzk

Nguyen, H., Carvelli, V., Adesanya, E., Kinnunen, P., & Illikainen, M. (2018). High-
performance cementitious composite from alkali-activated ladle slag reinforced with
polypropylene fibers. Cement and Concrete Composites, 90, 150-160. https://doi.org/1
0.1016/j.cemconcomp.2018.03.024

Ocean Crusaders. (2020). Plastics ain’t so fantastic. Retrieved from https://oceancrusad


ers.org/plastic-crusades/plastic-statistics/

Parker, L. (2015). Ocean trash: 5.25 trillion pieces and counting, but big questions
remain. Retrieved from https://www.nationalgeographic.com/news/2015/1/150109-
oceans-plastic-sea-trash-science-marine-debris/

Patel, H.G., & Dala, S.P. (2017). An experimental investigation on physical and
mechanical properties of concrete with the replacement of fine aggregate by poly vinyl
chloride and glass waste. Procedia Engineering, 173, 1666-1671.
https://doi.org/10.1016/j.proeng.2016.12.191

Pešić, N., Zivanovic, S., Garcia, R., & Papastergiou, P. (2016). Mechanical properties
of concrete reinforced with recycled HDPE plastic fibres HDPE plastic fibres.
Construction and Building Materials, 115, 362-270. https://doi.org/10.1016/j.conbuild
mat.2016.04.050

Rai, B., Rushad, S.T., Kr, B., & Duggal, S.K. (2012). Study of waste plastic mix
concrete with plasticizer. International Scholarly Research Notices, 2012.
https://doi.org/10.5402/2012/469272

Rahmani, E., Dehestani, M., Beygi, M.H.A., Allahyari, H., & Nikbin, I.M. (2013). On
the mechanical properties of concrete containing waste PET particles. Construction
and Building Materials, 47, 1302-1308. https://doi.org/10.1016/j.conbuildmat.2013.
06.041

Reddy, A.V., & Kolasani, D. (2015). Optimization of fly ash content in different grades
of magnetic water concrete. International Journal of Research in Engineering and
Technology, 04(13), 51-56.

Senhadji, Y., Escadeillas, G., Benosman, A. S., Mouli, M., Khelafi, H., & Ould Kaci,
S. (2015). Effect of incorporating PVC waste as aggregate on the physical, mechanical,
and chloride ion penetration behavior of concrete. Journal of Adhesion Science and
Technology, 29(7), 625-640. https://doi.org/10.1080/01694243.2014.1000773

176
R. L. Rodriguez, Jr. & J. A. Ching / Mindanao Journal of Science and Technology Vol. 19 (1) (2021) 163-177

Sharma, R., & Bansal, P.P. (2015). Use of different forms of waste plastic in concrete
– A review. Journal of Cleaner Production. https://doi.org/10.1016/j.jclepro.2015.08.0
42

The Constructor. (2018). Workability of concrete - types and effects on concrete


strength. Retrieve from. https://theconstructor.org/concrete/workability-of-concrete-
types-strength/11739/

Yang, S., Yue, X., Liu, X., & Tong, Y. (2015). Properties of self-compacting
lightweight concrete containing recycled plastic particles. Construction and Building
Materials, 84(2015), 444-453. https://doi.org/10.1016/j.conbuildmat.2015.03.038