1. Install the ASIMON360 software and follow the on-screen instructions to complete installation. 2. Connect the Safety Basic Monitor, ASi Safety 4I/2O module, and Light Button Module hardware. Configure the PC network settings. 3. In ASIMON360, create a new workspace and add the devices. Configure the inputs and outputs, enabling the global error unlock. Drag inputs to the monitored start and restart locations.

Uploaded by

GUILLEM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
472 views1 page

En Quick Start Guide ASIMON Configuration Safety Basic Monitor

1. Install the ASIMON360 software and follow the on-screen instructions to complete installation. 2. Connect the Safety Basic Monitor, ASi Safety 4I/2O module, and Light Button Module hardware. Configure the PC network settings. 3. In ASIMON360, create a new workspace and add the devices. Configure the inputs and outputs, enabling the global error unlock. Drag inputs to the monitored start and restart locations.

Uploaded by

GUILLEM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ASIMON360 Safety Basic Monitor Configuration

using the example of BWU2852

1 Installation ASIMON360
1.2After
1.2 Nachinstallation
erfolgreicher Installationyou
is completed voncan
1.1 Run the command "Install" from
the "ASIMON360" software and follow start commissioning the hardware or
the screen instructions. directly continue with the device
configuration.

Hardware preparation and presetting the PC


2
2.1 For this Quick Start Guide we use a 2.2 Connect the Safety Basic Monitor
subset of the Small Starter Kit Safe Link to your PC using the Ethernet interface
(BW3000). and connect the power supply to ASI
PWR. Then open menu item 'Network
This consists of the Safety Basic and Enabling Center' in the Control
Monitor (BWU2852), the ASi Safety Panel.
4I/2O module (BWU2314, with E-STOP
on S11/12/21/22) as well as the
Light Button Module (BW2528) (see
fig., from left to right).
2.3 Click on "Change 2.4 Open the properties for 2.5 Fill in as follows
adapter Settings". the LAN connection and (example):
click on "Internet protocol IP-Address:
Version 4 (TCP/IPv4)". 192.168.42.1
Subnet mask:
255.255.255.0
Standard gateway:
192.168.42.200

Creating the device configuration


3

3.1 Start ASIMON360 and select "New workspace" 3.2 The hardware configuration opens. Select the 3.3 Set the local inputs and outputs. An E-STOP 3.4 Enable the global error unlock for the slave 1A
and click on "Create". Safety Basic Monitor (BWU2852). is connected to terminals S11/12/21/22. by selecting the "Service" tab, checking the field
"Global error unlock" and selecting address 1-1A.
Confirm with OK.

3.5 Click on "Add Slave" and select the connected 3.6 Use the menu point "Add Slave" to select 3.7 Go to "Safe outputs" and disable the output 3.8 All devices are now added. Now click on
Light Button Module (BW2528) and and use the ASi Safety 4I/2O Module (BWU2314). 2.14. "OK". ASIMON360 creates a basic
"Standard I/Os" to assign a standard input to the Deactivate all safe inputs except for configuration.
lower and upper button. S11/12/21/22. An E-STOP is connected here.

3.9 Global error unlock and error unlock use the 3.10 Drag the device "1-1A Upper button 3.11 Drag the device "1-3 S11/S12/21/22 E-STOP" of 3.12 Start the commissioning wizard to address
same input. Select in the catalog section the standard input." to the Monitored start on the AS-i safety 4E/2A module (BWU2314) into the the slaves and load the configuration into the
device "1-1A Lower button standard input" and OSSD1 and OSSD3. &-device in OSSD1 and into the &-device in OSSD3. Safety Basic Monitor (BWU2852). Connect the
drag it using drag&drop into the restart in OSSD3. Gateway (BWU2852) and follow the steps in the
commissioning wizard.

3.13 Change the interface of the Safety Basic 3.14 After completing the steps of the 3.15 The ASIMON diagnostics becomes visible. 3.16 Push the E-STOP on the ASi Safety 4I/2O-
Monitor as follows (example): commissioning wizard confirm the protocols You can monitor and test your configuration. Module (BWU2314) and release it again. Initiating
IP-Address:192.168.42.3 and click on "Finish". Operating the upper button activates the monitored the monitored start again restarts the OSSDs.
Subnet mask: 255.255.255.0 start and the safe input switches to green. The
Standard gateway: 192.168.42.4 pressed lower button triggers the error unlock and
the restart.

Important Note Bihl+Wiedemann GmbH


4 Flosswoerthstr. 41
This document is intended solely as an aid for the users of safety monitored equipment. 68199 Mannheim
It does not relieve the user of responsibility for proper testing. Please refer to the safety
instructions in the user manual.