CCC pioneered and is the world's most experienced supplier of such technologies. Series 3++ Antisurge Controllers calculate proximity-to-surge using a multivariable application function. Fast disturbances elicit a derivative response that increases the safety margin.

Uploaded by

Damian Wahlig
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views2 pages

CCC Antisurge

CCC pioneered and is the world's most experienced supplier of such technologies. Series 3++ Antisurge Controllers calculate proximity-to-surge using a multivariable application function. Fast disturbances elicit a derivative response that increases the safety margin.

Uploaded by

Damian Wahlig
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PB3301.

Series 3++ Antisurge Controllerproduct bulletin

Antisurge Controller
for Centrifugal and Axial Compressors

.000
SP
ALT LIMIT 2

DEV

9.3
LIMIT 3

OUT

PID

Every centrifugal or axial compressor has a characteristic combination of maximum head and minimum ow beyond which it will surge. Preventing that damaging phenomenon is one of a control systems most important tasks. The Series 3++ Antisurge Controller is the ideal candidate for the job. The only way to prevent surge is to recycle or blow-off enough flow to keep the compressor away from its surge limit, but compressing that extra flow is costly. To maintain an adequate but not excessive flow rate, a controller must accurately determine how close the compressor is to surging and tailor its response to the size and speed of any disturbances. CCC pioneered and is the worlds most experienced supplier of such technologies.

Antisurge Controller

Fault Alarm

M d o e R N U A/D TtB1. ol=03 Sgn=0 rCt01


ACK MENU SCROLL

RT

AUTO

MAN

SURGE RESET

Pioneering Surge Protection


A compressors surge limit is not xed with respect to any one measurable variable, such as compression ratio or the pressure drop across a ow meter. Instead, its a complex function that also depends on gas composition, temperatures and pressures, rotational speed, and guide vane angle. So Series 3++ Antisurge Controllers calculate proximity-to-surge using a multivariable application function that is invariant to all such changes. Because the best function for your process depends on which conditions are xed and the available measurements, an easily-selectable variety of such eld-proven fA modes is provided. A surge control system should also tailor its response to the size of each disturbance, in order to prevent surge without upsetting the process or requiring a large, energy-wasting margin of safety. To that end, the Series 3++ Antisurge Controller applies a combination of open and closed-loop control algorithms: For small disturbances, proportional-integral control is used with provisions for preventing reset windup . Fast disturbances elicit a derivative response that increases the safety margin, thus accelerating the PI control response. If that combination proves insufficient, our adaptive open-loop Recycle Trip response steps opens the antisurge valve even further, using step sizes based on the instantaneous rate of approach to surge. This provides just enough added flow to prevent surge without unnecessary process disruption. Finally, if unanticipated circumstances do trigger surging, our Safety On response redefines the safety margin to stop it after a single cycle, then remains in effect to prevent future surges.
PB3301 (1.0) May 2007

POC Tracking Limit Balance

TEST ENTER

RAM Stop

Fallback

PB3301 (1.0)

May 2007

A
Features:
selectable proximity-to-surge functions adapt controller to changing process conditions combined open and closed-loop control responses provide maximum protection and optimal process efciency integrated loop decoupling prevents interacting loops from destabilizing your process limiting control of any two single-input variables coordinated start-up and shut-down sequencing bumpless transfer between manual and automatic operating modes manual override prevents inadvertent compressor damage due to operator error fallback strategies keep your compressor online in the event of input failures optional, automatic switching to redundant controllers in the event of critical failures standard hardware simplies maintenance and parts stocking Modbus RTU or TCP interface for DCS/SCADA communication

Fast, Dedicated Hardware


Surge protection is further complicated by the speed at which surge develops. It can take only a small fraction of a second for the compressor to move from a relatively safe operating point to one where surge is inevitable. The Series 3++ Antisurge Controllers purpose-built hardware adjusts its outputs 25 times every second, based on measurements made every 5.0 milliseconds. In contrast, general-purpose controllers are just too slow for this task.

Integrated Loop Decoupling


Process protection, efciency and precision can be further improved by combining Series 3++ Antisurge Controllers with companion Performance Controllers (see PB3302). Independent control loops often interact to create pressure and flow oscillations that degrade performance and impair antisurge protection. In contrast, Series 3++ Systems feature built-in loopdecoupling algorithms that can prevent adverse interactions. As a result, their control loops can be tuned faster to achieve more precise control without sacrificing process stability.

Benets
Series 3++ Antisurge Controllers offer benets you cant get from general-purpose controllers, including: More economical operation of your compressor because our surge control methods allow the compressor to safely operate closer to its surge limit without unnecessary recycling More precise control of your process because the built-in loop decoupling algorithms allow companion Performance and Antisurge Controllers to be tuned faster and to counteract the potentially disruptive effects of antisurge control actions Less downtime because our control algorithms eliminate unnecessary process trips due to surge or overload conditions Lower compressor repair costs because elimination of damaging surges reduces the frequency of major repairs More reliable operation because fall-back strategies permit continued surge protection even after transmitter failures Simplied operation because our Recycle Trip and Safety On control responses minimize operator involvement Lower engineering costs because the Series 3++ Antisurge Controller is designed specically for compressor applications, thus eliminating custom software design and debugging costs and reducing startup expenses Lower capital costs because our surge and overload protection features prolong the life of your compressor.