Duct Design: ME 425 - Air Distribution & ASHRAE Outlet Selection

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

1

1
ME 425 - Air Distribution & ASHRAE Outlet Selection
ME 425
Keith E. Elder, P.E.
Duct Design
Duct Design
The purpose of air conditioning ductwork is to deliver air from
the fan to the diffusers which distribute the air to the room.
Air Moves Through the Ductwork in Response to a Pressure
Difference Created by the Fan
The necessary pressure difference will be a function of the way
the ductwork is laid out and sized.
The objective of duct design is to size the duct so as to
minimize the pressure drop through the duct, while keeping the
size (and cost) of the ductwork to a minimum.
Proper duct design requires a knowledge of the factors that
effect pressure drop and velocity in the duct.
2
2
ME 425 - Air Distribution & ASHRAE Outlet Selection
Duct System Pressure
Total Pressure, TP, is Related to the Energy in the Air
Stream, and is equal to:
TP = Static Pressure + Velocity Pressure
Static pressure and velocity pressure increase and
decrease as the air proceeds through the ductwork,
depending on the cross-sectional area of the flow.
The total pressure of the airstream decreases as the
air proceeds through the the ductwork due to the
conversion of mechanical energy to heat caused by
friction
Duct System Pressure
3
3
ME 425 - Air Distribution & ASHRAE Outlet Selection
Velocity Pressure
Where:
VP = Velocity Pressure, inches H
2
O
V = Velocity, feet per minute
VP
V
=
|
\

|
.
|
4005
2
Static Pressure Losses
Frictional Losses
Due to fluid viscosity and turbulence in the flow through the
ductwork, and occur along the entire length of the ductwork
Dynamic Losses
Result from flow disturbances caused by fittings that change
the airflow direction or area.
4
4
ME 425 - Air Distribution & ASHRAE Outlet Selection
Frictional Loss Calculation
Velocity Reduction Method
Velocity at the fan discharge is pre-selected. The duct
system is designed to provide progressively lower duct
velocities as the air proceeds from the main duct to the
branches.
Static Regain Method
The ducts are sized so the increase in static pressure at
each take-off offsets the pressure loss of the succeeding
section of ductwork.
Equal Friction Method
The duct is sized to result in a constant pressure loss per
unit length of duct.
Equal Friction Method
Frictional Losses, Ap, can be approximated:
Rectangular Ductwork is converted to round:
Ap f
L
d
V
=
|
\

|
.
|
|
\

|
.
| 0 03
1000
1 22
1 82
.
.
.
( )
( )
D
ab
a b
e
=
+
130
0 625
0 25
.
.
.
5
5
ME 425 - Air Distribution & ASHRAE Outlet Selection
Equal Friction Chart
6
6
ME 425 - Air Distribution & ASHRAE Outlet Selection
Maximum Duct Velocity
Controlling Factor Controlling Factor - Duct Friction
Application Noise Generation Main Ducts Branch Ducts
Main Ducts Supply Return Supply Return
Residences 600 1000 800 600 600
Apartments
Hotel Bedrooms 1000 1500 1300 1200 1000
Hospital Bedrooms
Private Offices
Directors Rooms 1200 2000 1500 1600 1200
Libraries
Theatres 800 1300 1100 1000 800
Auditoriums
General Offices
High Class Restaurants 1500 2000 1500 1600 1200
High Class Stores
Banks
Average Stores 1800 2000 1500 1600 1200
Cafeterias
Industrial 2500 3000 1800 2200 1500
* From Carrier Air System Design Manual
Approximate Ductwork Cost
Dimension Gauge
*
lb/SF
Up to 12 26 0.906
13 to 30 24 1.156
31 TO 54 22 1.406
55 TO 84 20 1.656
84 and Over 18 2.156
Galvanized Steel = $8.25 per lb
**
* Source: Uniform Mechanical Code
**
Source: Recent bids includes fittings & everything
7
7
ME 425 - Air Distribution & ASHRAE Outlet Selection
Economical Duct Design
Minimize aspect ratio (a/b)
Minimize total pounds of sheet metal and
Minimize number of reductions (2-inch rule)
Duct Sizing Exercise
An office space has a sensible peak cooling load of
29,400 Btu/hr. The inside design temperature is 78 F
and the supply air temperature is 60F. The duct must
be lined and yet fit under the beam shown below and
not exceed a friction loss of 0.10 inches per 100 feet.
Determine the
most economical
duct size.
8
8
ME 425 - Air Distribution & ASHRAE Outlet Selection
Dynamic Loss Calculation
Ap
f
= C
o
p
v,o
Fitting Loss Exercise
1000 CFM is flowing through
a 16 x 12 rectangular duct.
400 CFM flows through an
8 x 12 branch to another room, and the remaining
600 CFM continues along the 12 x 12 main duct.
What is the pressure drop, in inches of water,
through the branch?
9
9
ME 425 - Air Distribution & ASHRAE Outlet Selection
Homework
Read 05F35.1-25
The ductwork shown below will serve several open
office spaces. Size the ductwork and calculate the
maximum pressure drop. The maximum vertical
space is 12 inches and the branch fittings are of the
same type as the example in the handout.
1200 CFM
900 CFM
750 CFM
FROM
FAN
1200 FPM
70 ft
30 ft
40 ft
80 ft
40 ft
30 ft
30 ft