#1.] A 400mm square tied interior column supports a dead load of 890KN and a
live load of 710KN. The column is reinforced with 8-25mm ⌀ bars. A square footing
is designed to support this load with its base at 1.5m below the ground surface.
Allowable soil pressure is 240KPA. Assume soil weighs 15.74KN/m3 and concrete to
be 23.5KN/m3, fc’= 20.7MPA , fy= 415MPA.
1.)Determine the dimension of the footing.
2.)Determine the reinforcement of the square footing.
3.)Determine the required Development length of the square footing.
Reinforcement location factor =1.3
Coating Factor B= 1.0
Reinforcing size factor= 1.0
Lightweight aggregate concrete factor= 1.0
Solution:
1. Dimension of the square footing. Assume total depth of 600mm with an
effective depth of
d = 600 – 75
d= 525mm
Effective Soil Pressure:
qeff = 240 - .60(23.5) – 15.74(0.9)
qeff = 211.73KPa
.645m d=.525m
Beam Shear:
Vu= 293.57(0.645)(2.74)
Vu= 518.83KN 2.74m
1
Vu= 6 ⌀ √fc’ bwd
0.75
518830= 6
√20.7 (2740) d
0.4m 40 + d = 2.74m
.925
40 + d = .925
2.74m
As Req’d
As = Pbd
= 0.033735(2740)(525) 1.17m
As = 4053mm2
Using 25mm ⌀
∏ 2
( 25 ) N = 4053 ; N= 8.26 say 9
4
C= 75mm
KTR= 0 ( no stirrups)
Ld Ld ( 4.15)(1.3)(1)(1)(1)
db = 1.1 α √ 20.7(2.5)
= 42.69
Ld As Req . 42.69(4053)
db
= As furnished =¿ =39.16
4418
Ld = 39.16(25)
Ld = 979mm (req’d Ld)
Solution:
1.) Required reinforcement for dowels.
Bearing strength of concrete at base of column.
F1 = ⌀(.85)fc’ A1
F1 = .65(.85)(34.6)(350)(350)
F1 = 2341771N
F1 = 2341.77KN < 3560KN (not safe)
F2 = .65(.85)(20.7)(350)2(2)
F2 = 2802004N
F2 = 2802.00KN < 3560KN
Excess load = 3560 – 2341.77
P = 1218.23KN
A s Fy = P
As (415) = 1218230
As = 2935mm2
Using 25mm⌀ dowels:
∏
(25)2 N = 2935
4
Ld = 570mm
Ld = .04 db fy
Ld = .04 (25)(415)
Ld = 415mm
Min. Ld = 200mm
Use Ld = 570mm
3.) Development Length of dowels into column.
.25 d bfy
Ld= '
√ fc
.25 d (25)(415)
Ld= = 440mm
√ 34.6
Ld = .04 dbfy
Ld = .04(25)(415) = 415mm
Min. Ld =200mm
Use Ld = 440mm.
#3.] Investigate the adequacy of the square footing using the strength design
method of the ACI code (318-83). The column has a dimension of 600mm x
600mm and carries an axial load of 1340KN (dead load) and 720KN(liveload).
Allowable soil pressure is 260KPa. There is a 0.60m earth overburden having a unit
weight of 15.7KN/m3 , fc’= 20.7MPa, fy = 276.5MPa.
517.5mm
62.5mm 37.5mm
70mm
3.0m
Vn = 1.36MPa.
2 1
(
V c= 1+ )
Bc 6
√ fc ’ > 1/3 √fc’
3.0m
Bc = 600/600 = 1
Vu = 344.44(3)(.6825) = 705KN
Vu 70500
Vn= =
⌀ bod .85 ( 300 ) ( 517.5 )
Vn = .53MPa
.6825m D= .5175m
1
Vc=
6
√ fc' = 16 √20.7
Vc = .76MPa > .53MPa (safe)
3.0m
4
Use P= .0037 ( 3 ¿=.0049 ACI code
∏
.02 abfy .02( ) ( 25 ) =(276.5)
Ld = √ fc = 4
√ 20.7
Ld = 596mm.
Min. Ld = .06 dbfy
Min. Ld = .06(25)(276.5)
Min. Ld = 415mm
Ld furnished = 1200-70 = 1300mm(ok)
Req’d Ld = 380mm
Min. Ld = 276.5mm
517.50-25 = 492.50mm
#4.] Design a square footing to support a 350mm x 350mm column carrying a dead
load of 320KN, live load of 560KN, a dead load moment of 12KN-m and a live load
moment of 18KN-m. Allowalbe soil pressure = 200KPa, fc’ =20MPa, fy= 350MPa .
Use ACI 318-83 code.
Solution:
941,6
Required Area = 200 = 4.708m2
B2 = 4.708
m
e= p
12+18 30
e= 320+ 560 = 880 =0.034
941.6
q= 2.30
(1+.0887)
47.4 6 (.339)
E= 2.3 (1+ 2.3
¿ = .0339
1400 6 (.0339)
qult. = 2.3 [1+ 2.3
]
√ 20
Vc = (3) 6 = 2.234 MPa
1
Vc= 3 √20 = 1.49 MPa (allowable)(use)
288+ 241
Ave. q ult. = =264.5 MPa
2
Vu= 1400 – 264.5(.35+d)2KN
bod= (.35+d)(4)(d)
1400−264.5 ( .35+d )
Vn= =1.49(1000)
.85(.35+ d)(4)(d )
1400-264.5(.1225+.7d+d2)=1773.1d+5066d2
5330.5d2 + 1958.25d-1367.6=0
d2+.367d-.256=0
d= .355m
d=355mm
Vc= .745MPA(allowable)
y 47
= ; y=12.67KPa
.62 2.3
1
Vu= 288(.62)(2.3)- 2 (12.67)(.62)(2.3)
Vu=401.65KN
401.65(1000)
Vn= .85 (2300)(355)
From bending:
V 47
= ;V =19.92 KPa
.975 2.3
.975 1 .975
Mu= 288(.975)(2.3)( 2
¿ -
2 ( )
( 19.92 )( .975 ) ( 2.3 )
3
Mu= 307.6 KN-m
307.6(1000)2= .90(20)(2300)(355)2w(1-.59w)
.59w2-w+.059=0
W=.0612
.0612(20)
P= 350
; p=.004
As=Pbd=.004(2300)(355)
As=3266mm2
= 905mm>491mm (ok)
=56.67KN<61.8KN(ok)
#5.]Check the adequacy of the 3.5m square footing .5m thick with respect to
punching shear or two way shear. The footing is to support a 300x500mm column
loaded with 700KN DL and 450KN LL.
Dave= 400mm
Fc’=21MPa
Solution:
Pu= 1.2DL+1.6LL
=1.2(700)+1.6(450)
300+400 = 700mm
Pu=1560KN
Pu 1560
qnet= A = ( 3.5 ) =127.347 KPa
Punching Shear:
Vup = Pu –qnet(A)
=1560-127.347KN/m2 (.70x.90)
Vup=1479.77KN
#6.] A square footing supports a 350mm x 350mm column carrying a dead load of
300KN and live load of 500KN. The footing is subjected to an axial moment
produced by the effect of dead load, live and earthquake. The unfactored moments
are tabulated below.
MDx= 50KN-m MLx=60KN-m MEx=36KN-m
MDy=30KN-m MLy=50KN-m MEy=29KN-m
Thickness of footing is 460mm with and effective depth of 360mm. The bottom of
the footing is 1.20m. below the ground surface. Unit weight of soil = 15.7KN/m3 ,
Concrete= 23.5KN/m3 . use 2001 NSCP Specs.
1.) Which of the following gives the dimension of the square footing.
2.) Which of the following gives the punching stress at critical section.
3.) Which of the following gives the number of 20mm ⌀ reinforcing bars in
both ways for the footing.
P= 300KN
P= 500KN/800KN
.74m
.36m .46m
Solution:
1.) Dimension of the square footing:
P= 300+500 =800
Mx= 50+60 +36
Mx= 146KN.m
My=30+50+29
My=109KN.m
L=b=d
P 6 Mx 6 My
Fa= A + bd
+
db
P 6 Mx 6 My
fA= L + L + L
try L= 2.3m
fA=261.57KPa
fB= 395.61KPa
1270 6 ( 179.49 ) 6 ( 135.9 )
fC= (2.3 )( 2.3 ) + 2.3
+
2.3 ( 2.3 ) 2.3
fc= 218.58KPa
1270 6 ( 179.49 ) 6 ( 135.9 )
fD= (2.3 )( 2.3 ) + 2.3(2.3)(2.3) + 2.3 ( 2.3 ) 2.3
fD=84.55KPa
1148980
Vp= .85 (710)( 360)(4)
√ fc'
Vp=1.32Mpa < 3 =1.52MPa(safe)
W= (1-0.59w) = .077
W2 -1.69w + .131=0
W=0.081 1m
2.3m
.081( 21)
P= 414
; P=.0041
1.4
Pmin = 414 =.00338 .975m
As=Pbd
.35m
As=.0041(1000)(360)
As=1476mm2
∏❑ 1000
(20)2 =1476
4 S
S=212.85mm O.C
S= 210mm o.c
No. of bars:
2300
N= 210 +1
#7.] A square footing supports 450mm square column supporting a service dead load
of 1784KN and a service live load of 1204KN. The column is built of fc’=34.6MPa
and has 8-28mm RSB with fy=414.7MPa. Design a square footing to be constructed
using fc’=20.7MPa, fy= 414.7MPa. The top of the footing will be covered with
150mm of fill with a density of 18880 N/m3 and a 150mm of concrete basement
floor. The allowable bearing pressure of soil is 288KPa.
Solution:
Ass. Total depth = 1 to 2 times the width of column
Total depth = 1.7(450) =765 say 800mm
Effective Soil Pressure
qe = 288 - .15(2.4)(9.81)-.15(18.88)-0.8(2.4)(9.81)
qe = 262.80KPa
DL +¿
Area required = qe
1784 +1204
L2 = 262.80
L2 = 11.37
L = 3.37m say 3.4m
DL = 1784KN
LL = 1204KN
150mm
800mm
Try 28mm⌀
d= 800-70-1.5⌀ (reinforcement is in both directions)
d= 800-70-1.5(28)
d= 688mm
Check for punching shear at a distance d/2 from face of column:
1.4 DL+1.7≪ ¿ 1.4 (1784 ) +1.7(1204 )
qu = Area = 3.4 (3.4)
¿
qu = 393.11KPa
Pu= 1.4(1784) + 1.7(1204)
Pu= 4544.4KN
Vu= Pu – qu (1.138)2
Vu= 4544 – 393.11(1.138)2
Vu= 4035.31KN
d/2
bod = 11388(4)(688)
3.4m 450mm
2
bod = 3131776mm d/2
4035310
Vp= .85 ( 3131776 )
Vp= 1.5158MPa
3.4m
3.4m
3.4m
Bending:
1.475
Mu= 393.11(3.4)(1.475)( 2
¿
Mu = 1454 KN-m
1454x106=.90(20.7)(3400)(6880)2w(1-.59w)
W(1-.59w)=.048
W2-1.69+.081=0
1.69+.081
W= 2 ; w=.0495
.0495 (20.7)
P= 414.7
; P=.00247
1.4
Pmin= 414.7 =.00338
Reinforcement :
As=Pbd = .00338(3400)(688)
As= 7906mm2
Using 28mm ⌀
∏ 2
( 28 ) N = 7906
4
Req Ld = 1122mm
Ld. Furnished = 1475-70
Ld furnished = 1405 >1122(ok)
Fb= .70(.85)(20.7)(450)(450)(2)
Fb= 4988182N
Fb= 4988 KN > 4544.4KN (safe)
A2 = [450 + 4(688)]2
A2 = 10252804
A2 10252804
√ A
=√
450( 450) = 7.1 > 2
Use 2
Bearing strength of column at the base of footing:
F = ⌀ 0.85 fc’ A1
F = .70 (.85)(34.6)(450)(450)
F = 4168867.5 N
F = 4169KN
Excess load = 4544.4 – 4169
Excess load = 375.4KN (to be transferred by dowels)
T= ⌀ Asfy
375400 = .70 As(414.7)
As= 1294mm3
ACI code:
Min. As = .005 area of contact
As= .005(450)(450)
As = 1012.5mm2
Use As=1293mm2
(using 25mm ⌀ dowels)
∏ ❑ ( 25 ) 2
(4) = As
4
Wall Footing
#1.] A wall footing is to support a 300mm wide reinforced concrete wall with a dead
load of 290 KN/m and a live load of 220 KN/m. The bottom of the footing is
1.20m. below the final grade. Assume the soil weighs 15.74 KN/m3 and the allowable
soil pressure is 193 Kpa. Fc’= 20.7MPa, fy = 415 MPa . Use 75mm as steel
covering. Conrete weighs 23.5 KN/m3.
1.) Compute the width and depth of footing.
2.) Compute the spacing of 22mm main bars and 16mm longitudinal temp.
and shrinkage steel
3.) Compute the development length required if :
Bar Location Factor= 1.0
Coating Factor = 1.0
Size Factor = 1.0
Normal Weight Concrete = 1.0
.3m
700mm
500mm
3m
Solution:
1.) Width and depth of footing . Try 500mm thick of footing.
Effective Soil Pressure:
qeff = 193-.50(23.5)-15.74(.70)
qeff = 170.23KPa
Consider 1 meter strip of wall:
290+ 220
Width of footing = 170.23 = 3m
Vu = qu(.925)(1)
Vu= 233.33(.925)(1)
Vu = 215.83KN
Vu=⌀ .17 √fc’ bd
=.75 (.17)(1)√20.7(1000)(425)
Vu= 246538KN
Vu=246538 KN > 215.83(safe)
Total thickness of footing = 500mm
Width of footing =3m
2.) Spacing of 22mm ⌀ bars
1.35
Mu=233.33(1.35)(1)( 2
¿
Mu = 212.62KN-M
Mu=⌀ fc’ bd2w (1-0.59w)
212.62x106=.90(20.7)(1000)(425)2w (1-0.59w)
W(1-0.59w) = .06318
W2-1.6949w +.107093 = 0
P(415)
.0657= 20.7
; P=.00328
P 1.4
Pmin= 415 ; Pmin.00337
C=75(side cover)
KTR= 0 (no stirrups)
C + KTR 75+ 0
db
= 22
= 3.4 >2.5
Use 2.5
Ld ( 415)( 1)(1)(1)( 1)
=
db 1.1 √ 20.7(2.5)
Ld
=32.8
db
Ld= 32.8(22)
Ld= 721.6mm <1275mm (ok)
Development Required = 721.6mm
#2.] A 400mm thick bearing wall of a rigid frame building carries a vertical load of
300KN dead load and 300KN live load per linear meter, together with a moment of
90KN-m dead load and 90KN-m live load per linear meter of length. Design the
footing to support the bearing wall for a uniform soil pressure. Allowable soil
pressure = 300KPa Use fy=280MPa, fc’=20MPa. Use ACI 318-83 code.
Solution:
Consider 1m length of wall
Assume wt. of footing = 6% of service load
Wt. of footing = 0.06 (300+300) = 36KN
Total load = 300+300+36 = 636KN
636
Required Area = 300 = 2.12m2
L(1) =2.12
L= 2.12m say 2.2m
For uniform soil pressure, the centroid of the footing must coincide with the
equivalent eccentric load.
600KN
180
e= 600 = .30m
A B
L=2.2m
B = .30 + 1.1
B= 1.4m
A= L – B = 0.8m
Pu= 1.4(300) +1.7(300)
Pu= 930KN
Net ultimate soil pressure
930
qult = 2.2 = 422.7 KN/m
Vc = .745MPa (allowable)
Vu= (1.4-0.20-d) (422.70)
Vu= (1.2-d) (422.70)
Vu= (1.2 –d)(422.70)
1.498 d=1.2-d
d=0.48m
d=480mm
Assuming 25mm ⌀ reinforcing bars:
Total depth = 480 + 70 +12.5 = 562.5mm
Check weight of footing:
Wt. of footing = 2.2(1)(0.5625)(2.4)(9.81)
=29.14KN < 36KN (ok)
0.59w2 – w + 0.073 = 0
W=.076
.076 (20)
P= 280
; P=0.0054
1.4
Pmin = 260 = .005
Use P= .0054
As=Pbd = .0054(1000)(480)
As= 2592mm2
A25=490
490(1000)
Spacing = 2592
= 189mm say 185mm o.c
.02( 490)(380)
Ld= √ 20
= 614mm
Ld = .06dbfy =.06(25)(280)=420mm
Ld= 300mm
At heel:
As= .005(1000)(480)=2400mm2
=530mm <614
Use a standard 90 hook if the actual Ld is less than the required. Place temperature
bars perpendicular to main reinforcement
Ast = .002(480)(1000)
Ast = 950mm2
A16 = 200mm2
200 (1000)
Spacing = 960
= 208mm say 200mm O.C
The bottom two 16mm ⌀ bars will serve as support for the horizontal bars.
#3.] For the wall footing shown in the figure, which of the following ost nearly gives
the effective soil pressure if the allowable soil pressure is 200KPa. (The effective soil
pressure is the remaining soil pressure available to support the loads after the effects
of the soil and concrete weights are subtracted) fc’=28MPa , fy= 280MPa. Use 2001
NSCP Specs.
Unit Weight of concrete = 24KN/m3
PDL = 200KN/m
PL = 180KN/m
.74mm
1.2mm
.39mm
.46mm
-Which of the following most nearly gives the minimum width of footing rounded to
the nearest .10m such that the effective soil pressure will not be exceeded.
-Which of the following most nearly gives the ultimate shear due to factored loads
acting on the critical section.
Solution
1.) Effective Soil Pressure:
qe=200-24(0.46)-16(0.74)
qe =177.12KPa
P MC
Max = A
+
I
P 6M
Max = +
A bd
P 6M
Max= (L)( 1) + L
380 6(135)
177.12= L
+
LxL
P u 6 Mu
Max = L
+
LxL
586 6(202.50)
Max = 3.5
+
3.5 ( 3.5 )
Max= 266.62MPa
Pu 6 Mu
Min= L - L( L)
585 6 (202.50)
Min = 3.5
−
3.5(3.5)
Min = 68.24KPa
x 198.38
= ; x=135.24
2.386 3.5
P(203.48+266.62)
V= 2
(1.114)(1)
V=261.87KN