Sepam Series 10 - Proteccion 50-51
Sepam Series 10 - Proteccion 50-51
Sepam Series 10 - Proteccion 50-51
Description
Phase overcurrent protection is used to detect overcurrents due to phase-to-phase faults. It uses the
measurement of the fundamental component of the currents produced by 2 or 3 phase CTs, with 1 A or
5 A secondary rating.
3 independent set points (I>, I>> and I>>>) can be set to offer optimum discrimination:
The first two 2 set points (I> and I>>) have either a definite time (DT) or inverse definite minimum time
(IDMT) setting with different types of standardized curve (IEC, IEEE, RI).
The third set point (I>>>) only has a definite time (DT) setting. The minimum setting can be used to
obtain instantaneous operation (ANSI 50 function).
These set points can be used:
In all cases, to detect phase-to-phase ground faults with 1 or 2 set points depending on the protection
plan adopted (see example 1).
In the case of a protection located at the connection point to the distributor network, to provide current
limiting and thus comply with the maximum subscribed demand defined in the contract for connection
to the distributor network. If the distributor imposes this limiting, this can be performed by the first I>
set point with an IDMT curve (see example 2).
Example 1: Example of typical application: Protection curve with a first IDMT I> set point and a second
DT I>> set point
I> I>>
Non tripping zone
Tripping zone
SEPED307003 03/2009 81
Sepam Series 10 - Functions and Parameters
Additional Functions
Sepam integrates functions that complement phase overcurrent protection:
Reset time:
With an IDMT setting, the set point parameters are set in order to activate an IDMT reset time. This
enables coordination with electromechanical relays. By default, the reset time is not active. Refer to
Reset Time, page 93.
Cold Load Pick-Up I (Cold Load Pick-Up I or CLPU I):
Operation of all 3 I>, I>> and I>>> set points can be associated with the CLPU I function, which is used
to avoid nuisance tripping of the protection when the installation is energized. By default, the CLPU I
function is not active. Refer to Phase Overcurrent Cold Load Pick-Up (Cold Load Pick-Up I), page 102
Logic discrimination:
Sepam can be integrated in the logic discrimination system. This system can be used when the
installation requires the fault to be cleared within a short time. It is used to bypass the time interval
between the protection stages, imposed by time discrimination. By default, on the Sepam series 10 A,
output relay O5 is assigned to the logic discrimination blocking output. Refer to Logic Discrimination
(ANSI 68), page 121.
Block Diagram
IA I>
T 0
IB I> delayed output
IC
I>>
T 0
I>> delayed output
I>>>
T 0
I>>> delayed output
Standard Operation
If the 3 phase overcurrents exceed the I>, I>> or I>>> set point:
The I fault LED flashes quickly.
The corresponding pick-up output changes state.
The 3 pick-up outputs are used by the logic discrimination function to send a logic discrimination
blocking order: refer to Logic Discrimination (ANSI 68), page 121.
The state of these 3 outputs is available via the communication: refer to Communication, page 169.
After the time delay associated with the I>, I>> or I>>> set point has elapsed:
The I LED flashes slowly.
Output relays O1, O2, O3 change state.
The fault screen is displayed with the tripping current values.
If all 3 phase currents drop back below the I>, I>> or I>>> set points, then output relays O1, O2, O3 and
the display remain in the same state (latching function).
Pressing the Reset key deactivates the latching function (refer to Fault Acknowledgement, page 146):
The I LED goes out.
The output relays return to their initial state.
The fault screen is replaced by the screen displayed prior to appearance of the fault.
NOTE: If the I>>> set point time delay is set to INST (instantaneous), the I>>> delayed output is the same
as the I>>> pick-up output.
82 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
Customization Option
Sepam's custom mode can be used to modify standard operation:
Latching of the I LED can be disabled.
Assignment of the I>, I>> and I>>> set points to output relays O1, O2, O3 can be modified.
Latching of output relays O1, O2, O3 can be disabled.
The activation logic of output relays O1 and O2 is configurable (contact closed or open on fault
detection).
Refer to Custom Operating Mode, page 147.
Settings
SEPED307003 03/2009 83
Sepam Series 10 - Functions and Parameters
I
extrait de CT192
t
I(t) = I(0).e t
Measurement of the Sepam currents is not affected by the presence of an aperiodic component (50 Hz
or 60 Hz), which permits a significant reduction in the ANSI 51 protection function setting.
In instantaneous protection (ANSI 50), the I>>> set point should be set to at least 37% of the peak value
of the inrush current stated by the transformer manufacturer.
With delayed protection (ANSI 51), the same rule applies, taking account of the current attenuation
according to the time constant stated by the transformer manufacturer.
84 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
Description
Earth fault protection is used to detect overcurrents due to phase-to-earth faults. It uses the measurement
of the earth fault current fundamental component according to several connection diagrams (see below).
This protection can be used in various application scenarios:
Incomer/feeder protection
Neutral point protection
Tank earth leakage protection
2 independent set points (Io> and Io>>) can be set to offer optimum discrimination:
The Io> set point has either a definite time (DT) or inverse definite minimum time (IDMT) setting with
different types of standardized curve (IEC, IEEE, RI).
The Io>> set point (Io) only has a definite time (DT) setting. The minimum setting can be used to obtain
instantaneous operation (ANSI 50N function).
Operation of both the Io> and Io>> set points can be associated with the Earth Fault Cold Load Pick-Up
(Cold Load Pick-Up Io) and Second Harmonic Restraint (see page 105) function, which is used to avoid
nuisance tripping of the protection when the installation is energized. In particular, the CLPU Io function
incorporates the option of activating restraint based on the detection of a second harmonic component in
the phase currents. Activation of this restraint is recommended on transformer applications, if the earth
fault current measurement is based on the sum of the 3 phase CTs. In this case, the aperiodic component
of the transformer inrush currents can cause transient saturation of the phase CTs and result in incorrect
earth fault current measurement likely to result in nuisance tripping of the earth fault protection. The
CLPU Io H2 restraint can be used to detect this incorrect residual current and inhibit the earth fault set
points during the transient currents linked to energizing.
Example: Curve for IDMT type Io> set point and DT type Io>> set point
t
Io > Io >>
Non tripping zone
Tripping zone
SEPED307003 03/2009 85
Sepam Series 10 - Functions and Parameters
Diagram 1 Diagram 2
Earth fault current measurement using the common Current measurement from an earth CT with 1 A or 5 A
point of the 3 phase CTs, with 1 A or 5 A secondary secondary rating.
rating.
The connection is as follows: The connection is as follows:
A
B A
C B
C
B
15
IA
B
25 15
14 25 IA
24 IB 14
13 24 IB
23 IC 13
23 IC
12
22 Io 12
CT Io
11 1A/5A 22
21 11
21
This version allows a minimum protection setting of 10% of the phase CT rating (diagram1) or the earth
CT rating (diagram2).
Sensitive earth fault protection - Sepam series 10 • •2•
The authorized connection diagrams are the same as the standard version. However, the minimum
protection setting is divided by 10 compared with the standard version. It is 1% of the phase CT rating
(diagram1) or the earth CT rating (diagram2).
However, if the protection set point needs to be set with low-level current values, use of an earth CT is
strongly recommended (diagram 2). In the case of diagram 1, precision errors in the 3 phase CTs can
result in incorrect earth fault current measurement. For set points below 10% CT In, this inaccuracy could
lead to nuisance tripping of the protection.
86 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
B
15
25 IA
14
24 IB
13
23 IC
12
Io
22 2-240 A
CSH120 11
Io
CSH200 21 0.2-24 A
GO110
This version of Sepam is particularly suited to application scenarios requiring low-level earth fault current
detection, wired as an alarm or as a trip.
Sepam has 2 sensitivity ranges, depending on the connection of the core balance CT to the Sepam relay:
0.2-24 A range (primary current)
2.0-240 A range (primary current)
For more information on connecting the core balance CT to Sepam, refer to Connecting a Core Balance
CT, page 40.
Additional Functions
Sepam integrates functions that complement earth fault protection:
Reset time:
With an IDMT setting, the set point parameters are set in order to activate an IDMT reset time. This
enables coordination with electromechanical relays. By default, the reset time is not active. Refer to
Reset Time, page 93.
Earth fault cold load pick-up (Cold Load Pick-Up Io or CLPU Io):
Operation of both the Io> and Io>> set points can be associated with the CLPU Io function, which is
used to avoid nuisance tripping of the protection when the installation is energized. By default, the
CLPU Io function is not active. Refer to Earth Fault Cold Load Pick-up (Cold Load Pick-Up Io) and
Second Harmonic Restraint, page 105.
Logic discrimination:
Sepam can be integrated in the logic discrimination system. This system can be used when the
installation requires the fault to be cleared within a short time. It is used to bypass the time interval
between the protection stages, imposed by time discrimination. By default, on the Sepam series 10 A,
output relay O5 is assigned to the logic discrimination blocking output. Refer to Logic Discrimination
(ANSI 68), page 121.
SEPED307003 03/2009 87
Sepam Series 10 - Functions and Parameters
Block Diagram
Standard Operation
If the earth fault current exceeds the Io> or Io>> set point:
The I fault LED flashes quickly.
The corresponding pick-up output changes state.
The 2 pick-up outputs are used by the logic discrimination function to send a logic discrimination
blocking order: refer to Logic Discrimination (ANSI 68), page 121.
The state of these 2 outputs is available via the communication: refer to Communication, page 169.
After expiry of the time delay associated with the Io> or Io>> set point:
The I fault LED flashes slowly.
Output relays O1, O2, O3 change state.
The fault screen is displayed, with the tripping current values.
If the earth fault current drops back below the Io> or Io>> set point, then output relays O1, O2, O3 and
the display remain in the same state (latching function). Pressing the Reset key deactivates the latching
function (refer to Fault Acknowledgement, page 146):
The I LED goes out.
The output relays return to their initial state.
The fault screen is replaced by the screen displayed prior to appearance of the fault.
NOTE: If the Io>> set point time delay is set to INST (instantaneous), the I>> delayed output is the same
as the I>> pick-up output.
Customization Option
Sepam's custom mode can be used to modify standard operation:
Latching of the I LED can be disabled.
Assignment of the Io> and Io>> set points to the O1, O2, O3 output relays can be modified.
Latching of output relays O1, O2, O3 can be disabled.
The activation logic of output relays O1 and O2 is configurable (contact closed or open on fault
detection).
Refer to Custom Operating Mode, page 147.
88 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
Settings
NOTE:
For standard and sensitive versions, Ino is the earth CT primary rated current.
For the very sensitive version, Ino is the primary rated current Ino for CSH200, CSH120 and GO110
core balance CTs, i.e. 470 A.
SEPED307003 03/2009 89
Sepam Series 10 - Functions and Parameters
90 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
Introduction
Phase or earth fault overcurrent protection can be delayed using the following types of tripping curve:
Definite time (DT): I>, I>>, I>>>, Io> and Io>> set points
IDMT: I>, I>> and Io> set points only
In the case of standardized IDMT curves (IEC and IEEE type only), a reset time can be activated. This
reset time enables Sepam's coordination with electromechanical relays, placed upstream.
IDMT Curve
In IDMT protection functions, the tripping time depends on the measured value (phase or earth fault
current), in accordance with standards IEC 60255-3 and IEEE C-37112.
Operation is represented by characteristic curves t = f(I/Is) or t = f(Io/Is) (where Is is the operating set
point), which look like this:
t
1 20 I/Is (Io/Is)
SEPED307003 03/2009 91
Sepam Series 10 - Functions and Parameters
In and Ino: phase CT primary rated current or earth CT primary rated current respectively
Characteristic Curve A p
IEC standard inverse time SIT/A 0.14 0.02
IEC very inverse time VIT/B 13.5 1
IEC long time inverse LTI/B 120 1
IEC extremely inverse time EIT/C 80 2
Characteristic Curve A B p
IEEE moderately inverse (MI) 0.0103 0.0228 0.02
IEEE very inverse (VI) 3.922 0.0982 2
IEEE extremely inverse (EI) 5.64 0.02434 2
92 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
Reset Time
When the I>, I>> and Io> set points use standardized IDMT curves (IEC or IEEE type), it is possible to
activate an IDMT reset time. This characteristic ensures coordination of a Sepam with an electrome-
chanical overcurrent relay, placed upstream.
Without a reset time, the tripping time delay counter is reset once the current drops back below the set
point (I < 95% Is).
With a reset time, when the current drops back below the set point, the time delay counter is decremented
in line with a curve that depends on the measured current value. The aim is to reproduce the operation
of the electromechanical relay disk. The reset time corresponds to the time it would take the disk to return
from its maximum position (fault current) to its off-position. This time depends on the current measured
by the Sepam relay.
The reset time curve is defined in standard IEEE C-37112.
It is defined by the following equation:
where:
Is: Tripping set point value
I (Io): Current measured by the protection function
TMS (or TD): Tripping curve setting
Tr, the value of the reset time for a zero current and TMS = 1, is defined in the table below:
Characteristic Curve Tr
IEC standard inverse time SIT/A 12.1
IEC very inverse time VIT/B 43.2
IEC long time inverse LTI/B 120
IEC extremely inverse time EIT/C 80
IEEE moderately inverse (MI) 0.97
IEEE very inverse (VI) 4.32
IEEE extremely inverse (EI) 5.82
TMS = 1
Tr
0 1 I/Is (Io/Is)
SEPED307003 03/2009 93
Sepam Series 10 - Functions and Parameters
Delayed
output
Pick-up output
Value of T
internal
time delay
counter
Tr
t(s)
100
10
TMS
1.5
1
0.8
0.6
1
0.4
0.3
0.2
0.1
0.05
0.1
0.02
0.01
1 10 I/Is
94 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
t(s)
1000
100
10
TMS
2
1 1.5
1
0.8
0.6
0.4
0.3
0.2
0.1
0.1
0.05
0.02
0.01
1 10 I/Is
SEPED307003 03/2009 95
Sepam Series 10 - Functions and Parameters
t(s)
10 000
1000
100
TMS
2
10 1.5
1
0.8
0.6
0.4
0.3
0.2
1
0.1
0.05
0.02
0.1
1 10 I/Is
96 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
t(s)
1000
100
10
TMS
2
1.5
1
0.8
0.6
0.1
0.4
0.3
0.2
0.1
SEPED307003 03/2009 97
Sepam Series 10 - Functions and Parameters
t(s)
100
10
TD
15
12
10
8
6
1 5
4
3
0.1
0.5
0.01
1 10 I/Is
98 SEPED307003 03/2009
Sepam Series 10 - Functions and Parameters
t(s)
1000
100
10
TD
15
12
1 10
8
6
5
4
3
0.1 1
0.5
0.01
1 10 I/Is
SEPED307003 03/2009 99
Sepam Series 10 - Functions and Parameters
t(s)
1000
100
10
1
TD
15
12
10
8
6
5
4
3
0.1
2
0.5
0.01
1 10 I/Is
RI Curve
t(s)
100
10
TMS
1.5
1
0.8
0.6
0.4
1 0.3
0.2
0.1
0.05
0.1
0.02
0.01
1 10 I/Is