Calculation Pressure Drop by Alarm Valve

The document compares 4 options for calculating pump head pressure for a fire sprinkler system. Option 1 uses a formula and resistance values from a Vietnamese standard. Option 2 uses a different author's formula and resistance values. Options 3 and 4 use specified pressure drops from Viking brand valve catalogues. An example calculation is shown for a 150A alarm check valve with 6500 L/min flow. Option 1 gives the highest friction loss at 42.9m. Option 2 gives 10.1m loss. Options 3 and 4 specify 9m and 6m losses respectively. The estimation department chooses Option 2 as it provides an acceptable friction loss without difficulties in valve selection.

Uploaded by

Phuong Nguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
211 views10 pages

Calculation Pressure Drop by Alarm Valve

The document compares 4 options for calculating pump head pressure for a fire sprinkler system. Option 1 uses a formula and resistance values from a Vietnamese standard. Option 2 uses a different author's formula and resistance values. Options 3 and 4 use specified pressure drops from Viking brand valve catalogues. An example calculation is shown for a 150A alarm check valve with 6500 L/min flow. Option 1 gives the highest friction loss at 42.9m. Option 2 gives 10.1m loss. Options 3 and 4 specify 9m and 6m losses respectively. The estimation department chooses Option 2 as it provides an acceptable friction loss without difficulties in valve selection.

Uploaded by

Phuong Nguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

LOGO

FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 1:
 Pressure drop after through Alarm Valve.
Follow Table 7, point 10.6 Standard 7336:2003
We calculator as formular:
hb  Sb  qb  qb
qb : Water flow through Alarm Valve (l/s)
Sb: Resistance values of Alarm Valve

Alarm Valve Sb
Type
100A 0.00302
150A 0.00368

1
LOGO
FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 2:
 Pressure drop after through Alarm Valve.
Follow “Water supply & Drainage Water” of author Tran
Hieu Nhue
We calculator as formular:
hb  Sb  qb  qb
qb : Water flow through Alarm Valve (l/s)
Sb: Resistance values of Alarm Valve

Alarm Valve Sb
Type
100A 0.00302
150A 0.000869

2
LOGO
FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 3: Follow catalouge Viking ( Deluge Valve Type FSX-A )

3
LOGO
FIRE SPRINKLER SYSTEM

* PUMP HEAD
OPTION 4: Follow catalouge Viking ( Alarm Check Valve Model J1 )

4
LOGO
FIRE SPRINKLER SYSTEM

* COMPARE WITH 4 OPTION:


Example with Alarm Check Valve 150A ( 6 inches ), water
flow 6500 l/min:
OPTION 1:
Follow Table 7, point 10.6 Standard 7336:2003
 Pressure drop after through Alarm Valve

hb  Sb  qb  qb
 0.00368 108 108  42.9(m)

5
LOGO
FIRE SPRINKLER SYSTEM

* COMPARE WITH 4 OPTION:


Example with Alarm Check Valve 150A ( 6 inches ), water flow
6500 l/min:
OPTION 2:
Follow “Water supply & Drainage Water” of author Tran Hieu Nhue
 Pressure drop after through Alarm Valve

hb  Sb  qb  qb
 0.000869 108 108  10.1(m)

6
LOGO
FIRE SPRINKLER SYSTEM
OPTION 3: Follow catalouge Viking ( Deluge Valve Type FSX-A )

Pressure
drop
through
Alarm
Valve:
0.6 bar
= 6(m)

7
LOGO
FIRE SPRINKLER SYSTEM

OPTION 4: Follow catalouge Viking ( Alarm Check Valve Model J1 )

Pressure
drop
through
Alarm
Valve:
6m

8
LOGO
FIRE SPRINKLER SYSTEM

* COMPARE WITH 4 OPTION:


Example with Alarm Check Valve 150A ( 6 inches ), water
flow 6500 l/min:
Option 1 2 3 4
Total 42.9 10.1 9.0 6.0
Friction
loss (m)

1- Use Option 1, Total friction loss is too big (but follow VN


Standard)
2- Use Option 3 & 4 (follow catalouge) Total friction loss
can be smaller, but many type of Alarm Check Valve, so
difficult to choose for Calculation.
3- Use Option 2, Total friction loss isn’t too big, same
Option 3,4. Now Estimation Department follow this Option.