1. General Description
SVP-917 type multi-function Protective Device is designed to measure single phase
two wire AC active energy and used in overvoltage protection, under voltage protection
and over-current protection . In case of over-voltage fault, under-voltage fault or
over-current fault in line, this product can instantly power off the load to prevent electrical
equipment from being burnt. The over-voltage, under-voltage and over-current values of
this product can all be set up by yourself and can be adjusted on the basis of local
practical condition .It is a long use-life product with the advantage of high stability , high
over load capability , low power loss and wide working voltage range .

2.Product features
2.1 LCD display with backlight , can display total active energy (kWh) , real time current
(A) , voltage(V) , active power (W) .
2.2 LCD display kWh (4 digital+1 decimal) , Bi-directional total active energy
measurement ,reverse active energy measure in the total active energy
2.3 Product self-design has function of lighting protection
2.4 Overvoltage protection, under voltage protection and over-current protection can
select auto-Reclosing mode or manual--Reclosing mode
2.5 In case of over-voltage fault, under-voltage fault or over current fault in single phase
line, the product can power off the line and can automatically restore connecting the line
over a time delay after voltage of the lien is recovered to normal condition.
2.6 In case of transient over voltage in line, the product can protect the equipment from
false operation.
2.7 In case that the line subjects to unstable voltage or sudden power-off and power-on
due to loosened connection and other fault, the product will disconnect the line.
2.8 When fault voltage of the line reaches the peak, the product itself will not be damaged.
2.9 Under over-current protection mode , you also can select Malignant load protection
(Pure Resistive Load limit) which is used for Apartments and Student Dormitories electric
safety
2.10 You can select the circuit output cycle switch on/off mode
2.11 Led indication of overvoltage protection, under voltage protection and over-current
protection
2.12 Diversified design for the protection , you can closed t any one of overvoltage
protection, under voltage protection and over-current protection in any time

3.Specification and Technical Parameters

Input working voltage 85~300V


Overvoltage protection value 85-300V ( default 270V)
SINOTIMER
Under voltage protection value 85-300V ( default 170V)
Over current protection value 1-63A ( default 40A)
1-80A( default 60A special
order)
Rated frequency 50/60Hz
Delay in switch on after power off 2-255V ( default 2s)
Voltage circuit power consumption ≤1W
Current circuit power consumption <1VA
Active energy display range 0~9999.9kWh
Voltage/current/active power +0.5%
accurate
Active energy accurate +1% (IEC62053-21)
Operating temperature -25℃~+70℃
Storage temperature -40℃~+80℃
Relative humidity ≤85%
Altitude ≤2500m
Electromagnetic Environment E2
Mechanical life ≥100000 cycles

4.LCD display and mode setting


4.1 Window sketch
SINOTIMER
4.2 Function mode and display code instruction
LCD Parameters setting
default Max. Min. Marking
Code
de Function mode 1 7 1
De1 Mode 1 overvoltage protection,
under voltage protection
and over-current protection
automatic switch off/on
De2 Mode 2 overvoltage protection,
under voltage protection
and over-current protection
automatic switch
off/manual switch on
De3 Mode 3 Close function of
overvoltage protection,
under voltage protection
and over-current
protection ,always keep the
output load switch off
De4 Mode 4 Close function of
overvoltage protection,
under voltage protection
and over-current
protection ,always keep the
output load switch on
De5 Mode 5 , unit: second 5 999 1 Close function of
De6 Mode 5 , unit: minute 5 999 1 overvoltage protection,
De7 Mode 5 , unit: hour under voltage protection
and over-current
5 999 1
protection , keep the output
load switch on /off in cycle
Bg Backlight mode Mode 1 means always
lighting , mode 2 means it
will lighting last 30s after
2 2 1
you push the button . it will
light out after 30s if no any
operation with button
SS Delay time in load It means switch on the
switch on after input output load after how many
2s 255s 2s
power on times when product input
power on again
Uo Overvoltage If the value exceed the
protection value 270V 300 V 85 V range , the LCD will display
off and closed this
SINOTIMER
protection function
UoH Overvoltage recovery This value must be smaller
value than overvoltage protection
265 V 300 V 85 V value. or it will default set
as overvoltage protection
value -5V when you save
UL Under voltage If the value exceed the
protection value range , the LCD will display
170 V 300 V 85 V
off and closed this
protection function
ULH Under voltage This value must be smaller
recovery value than under voltage
protection value. or it will
175 V 300 V 85 V
default set as under
voltage protection value
+5V when you save
SU overvoltage / under It means the fault must be
voltage fault judgment last how many times then it
time 3s 60s 0.1s will make output load
switch off when happen
fault
Io Over current If the value exceed the
protection value range , the LCD will display
40A 63 A 1A
off and closed this
protection function
Ic Malignant load If the value exceed the
protection value (Pure range , the LCD will display
0.5 A 5A 0.5 A
Resistive Load limit) off and closed this
protection function
SI Over current fault It means the fault must be
judgment time last how many times then it
3s 60s 0.1s will make output load
switch off when happen
fault
SH Delay time setting for It means the product must
recovery load after wait for how many times
output load switch off 60s 512s 1s then make the output
protection switch on again after
happen protection
op Delay time set for
cycle switch(under The time unit is different
5 999 1
function mode under mode5/6/7
5/6/7)
CL Delay time set for 5 999 1 The time unit is different
SINOTIMER
cycle switch on(under under mode5/6/7
function mode 5/6/7)
Er1 Last five records of
5 1
protection reason
Note 1: Under voltage protection value must be smaller than Overvoltage recovery value ,
or it will restore factory setting .
Note 2: Under the setting mode , mode 1 to 7 all can display the function mode ,
backlight mode , Delay time in load switch on after input power on , but the following
display will difference according to the function mode .

4.3 Key operation instruction


4.3.1 Press and hold on the “set” key for 3s, entering into setting status and if go on hold
the “set” key , it can select different function mode . then you can set different value by
pressing the “up” key or “down” key to increase or decrease the detailed value. if you hold
“up” key or “down” key at all , the value will increase or decrease at all .
4.3.2 Under the function mode , hold on the “set” key for 3s , it will save and exit to normal
display status . if you have no any operation more than 30s , it will also exit to normal
display status . if you press the he “up” key or “down” in the meantime ,all data will restore
factory setting
4.3.4 Under the normal display status , you can display voltage/current/active
energy/active power step by step by pressing the “up” key or “down” . the LCD will
display step by step automatically
4.3.5 Under the function mode 2 , you can press the he “up” key or “down” in the
meantime to make the output load switch on after happen protection /switch off
4.3.6 Under the function mode 1 and 2 , it the press the “down” key to check the last five
records of protection reason(Er1 ~ Er5 ) .under the display firstly layer is Er1 , the
second layer number : 1 means the overvoltage protection, 2 means under voltage
protection , 3 means over-current protection
4.3.7 Under the function mode 3 and 4 , all protection function will be closed . the product
is only as normal switch for keep the output load is switch on/off
4.3.8 Under the function mode 5/6/7 , all protection function will be closed . the product is
only as normal switch for keep the output load is switch on/off in cycle .

4.4 LCD display instruction


4.4.1 normal working status LCD display
SINOTIMER
4.4.2 Under function mode setting and value setting LCD display

4.4.3 Under function mode s5/6/7 LCD display

5.Usage
5.1The product can be installed on 35 mm din rail ,it should be install in the water proof box
indoor or outdoor . The product should be install fully in accordance with connection diagram on
the terminal cover, it is better to use copper as the leading wire for connection. All screws should
be tightened.
5.2 installation dimension
SINOTIMER

5.3 Connection diagram

Wire connection must connect as sequence of the above 2 type diagram

6.Note
6.1 The input and output shall be corrected connected on the basis of the product marking.
(Wherein, the load current shall be less than protective current of the product. )
6.2 Neutral line N cannot be improperly connected and shall be reliably wired; otherwise,
the protector may not work normally.
6.3 Before powering on, please carefully check whether the wiring is correct, whether the
load matches with protective current of the product and whether the binding screw is
tightened; otherwise, the product may be damaged.
6.4 After powering on the product, don’t touch any live part to avoid electric shock.
SINOTIMER
6.5 This product shall be combined with micro circuit breaker to play a role of short-circuit
protection; otherwise, the product may not be able to realize load limit protection in case
that input or load end of the product appears short circuit.
6.6 As the product has automatic reset function, after the product plays the role of
protection and acts, it is necessary to remove the load (electric appliance) and check the
circuit; otherwise the product will be frequently connected and disconnected to the load.
Finally, the product or its circuit may be burnt due to frequent overload connection and
disconnection for long time.

6.Warranty
Within 12 months from the day of selling and provided that users operate correctly according to
the requirement of the user’s manual , if the product doesn’t reach its technical specification. It
can be repaired or replaced in free f charge by the manufacturer .