Chafai 2013
Chafai 2013
net/publication/261345949
CITATIONS READS
8 871
5 authors, including:
16 PUBLICATIONS 53 CITATIONS
University M'Hamed Bougara of Boumerdes
146 PUBLICATIONS 620 CITATIONS
SEE PROFILE
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
ISOTAEP-ICAMCS 2017 : International Symposium on Optimization Techniques Applied to Engineering problems View project
All content following this page was uploaded by Hamid Bentarzi on 16 June 2020.
This type of test can be used in commissioning and operations, for the counting mechanism to return to
troubleshooting. the starting position. In an Auto-reclosing relay, the
reset time is the time following a successful closing
C. Transient Test: operation, measured from the instant the auto-reclose
Transient testing may be investigated by applying relay closing contacts make, which must elapse
simultaneously fundamental and non-fundamental frequency before the auto-reclose relay will initiate a new
components of voltage and current that represent real power reclosing sequence in the event of a further fault
system conditions. This type of test may be used for testing a incident
security of the protective relay. 3) Number of shots: is the predetermined number of
The signal that may be used in this type for testing may be attempt for the auto-reclosing to clear the faults being
obtained from digital fault recorders (DFR) or Simulator such sensed, there is no specific rule to select the number
as Simulink/Matlab or electromagnetic transient programs of shots but so often Auto-reclosers have three (3)
(EMTP). shots.
The increasing use of digital technology in devices such as Today almost all Auto-reclosers are designed based on IDMT
protection, oscillography, measurement, and control apparatus function. IDMT that is one type among the inverse time over
in electric power substations has created the potential for current relays fits very well this application because more is
severe the fault, faster it should be cleared to avoid damage to
accumulating large numbers of digital recording of power
the apparatus. The reclaim time of an Auto-Recloser
system transient events. In addition to these sources of digital
represents in fact the time delay of the IDMT which is based
data, analog and digital power system simulators may be used on the following equation:
to generate digital data. The users of these data are faced with Ǥଵସ
the problem of managing different file data formats used by ݐௗ௬ ൌ ( כ1)
ሺ ሻబǤబమ ିଵ
each system to generate, store, and transmit data [2].The
Where: t݈݀݁ܽ ݕ: relay operation time (time delay),
common standard format that has been used in the power
TMS: time multiplier setting,
system applications is IEEE Standard Common Format for
I : current detected by relay,
Transient Data Exchange “COMTRADE”. IS: current set-point.
II. AUTO-RECLOSER PRINCIPLE OPERATION The Auto-recloser can be tested using the developed tester for
different values of the input current amplitude under different
When a fault occurs, the auto-recloser detects an conditions such as transient fault and permanent fault [5].
overcurrent and breaks the circuit, instantaneously or after an
intentional time delay. After a first preset interval of time III. DISTANCE PROTECTION
(usually 1/3 sec) the recloser recloses (called first shot). If the
fault persists, the recloser again trips, and waits a second Protections based on distance relaying have been used in the
preset interval (usually 15 sec). It recloses again, only to trip if power grid generally and in transmission lines particularly in
the fault is still present (second shot). After a third open order to detect the fault rapidly and disconnect the faulted part
interval (usually 45 sec), the recloser closes one last time. If only. Transmission lines are usually protected by step distance
the fault persists, the recloser opens and locks out (third shot), protection using the mho or quadrilateral relay characteristic
requiring manual resetting. If any recloser is successful, the with three or four zones of protection. Each zone of protection
is based on a percentage of the line impedance, which varies
depending on the philosophy and criteria of each utility. This
maintains a reliable operation of the power system and ensures
continuity of power supply [6].
The basic principle governing the operation of a distance relay
is the ratio between the voltage V and the current I at the
relaying point. The ratio (V/I) represents the measured
impedance Z of the faulty line between the relay location and
the point of fault occurrence. Then, the measured impedance is
compared to the set impedance, and if this Z is within the
reach of the relay then the fault will be cleared. The relay
entire cycle is reset automatically (See Fig. 1) [4]. characteristics form different shapes in the R-X diagram that
Fig.1 Typical sequence for auto-recloser operation. can be used in different types of applications. The mho circle
is the most common type of relay characteristics. For a
Any Auto-recloser consists of three principle parameters transmission line considering three zones of protection, the
which are: mho characteristics for each zone are shown in Figure 2,
1) Dead time:is the time during the fault detection and where the diameter of each mho circle is based on the value of
the power line opening or the amount of time each zone of protection. However, zone-three relay may be
necessary for opening the circuit breaker (circuit affected by the power swing because its impedance enters the
breaker coil is energized ). characteristic of the relay and its time delay is longest. Faults
2) Reclaim time: is defined in IEEE Std. C37.100-1992 are permanently compared to power swings that are more
[3] as the time required, after one or more counting
Up Relay
AD 622 sampler Digital PWM Power LPF under
Filter stage test
ADC
Fig.8 Three phases voltage waveforms in the scope of the power system fault Fig.9 Three phases current waveforms in the scope of the power system
simulations using SIMULINK fault simulations using SIMULINK.
..
VI. CONCLUSION
The PC based relay testing system has been successfully
implemented. Simulator, that is used to generate three phase
voltages and currents, presented the actual power grid events
mainly the fault and other abnormal conditions such as power
swing to test the relay performance. In fact, implementation is
used to generate one of these signals and output them to
external environment using the acquisition card AD 622. User
Interface (GUI) has been developed to include some
parameters of the relay, to control the generated data of
waveform signals and to display the generated signals.
The tester has been used to generate the signal under
different abnormal conditions, such as power swing and line
fault. It can be noticed that the tester results are satisfactory
Fig.10Three voltage phases (above) and three current phases waveforms and this approach may be used for testing protective distance
(below) in the scope of the power system fault simulations using SIMULINK. relay as well as over-current relay even in a large power
network.
Moreover, it can be concluded that this proposed
Digital data that may represent the signals of all conditions
framework has the following advantages:
of power system such normal case, fault condition and
Firstly, this tester can be used to test the reliability of the
transient disturbance, have been produced by simulator
distance protection and overcurrent relay (also auto-recloser)
SIMULINK/MATLAB as shown in Fig.6. Then, the generated
during any abnormal conditions such as power swing and
signals with different waveforms that may be injected to the
faults.
relay under test have been displayed on the scope as shown in
Secondly, this scheme can be easily implemented on PC
Figs.8, 9, 10.
based protective relay tester.
V. PERFORMANCE EVALUATION OF THE TESTER
VII. REFERENCES
Test bench has been used to generate the faulted stimulus [1] A.Ouadi, H. Bentarzi, M. Chafai and A.Zitouni, “Microcontroller Based
waveforms using SIMULINK real-time workbench, and the Protective Relay Testing System” in Proceeding The 10th WSEAS
windows target application developed using SIMULINK International Conference on CIRCUITS, SYSTEMS, ELECTRONICS,
CONTROL & SIGNAL PROCESSING (CSECS '11), Montreux
HUMOSOFT driver and AD622 board. Real-time stimulus University, Switzerland, December, 29-31, 2011.
waveform signals that may be generated by simulator [2] Power Systems Relay Committee of the IEEE Power Engineering
programs have been displayed on the external scopes as shown Society ”IEEE Standard Common Format for Transient Data Exchange
for Power Systems” IEEEStd C37.111-1999,USA, 18 March 1999.
in Fig.11. [3] IEEE Std. C37.100-1992, IEEE Standard Definitions for Power
Switchgearn 1992.
[4] A.G. Phadke, T. Hlibka, M.Ibrahim, “A digital computer system for
EHV Substation: Analysis and Field Tests”, IEEE Trans. Power
Apparatus and System, Vol. PAS-95, pp. 291-301, 1976.
[5] H.Bentarzi, M.Chafai and A. Ouadi, “A New Computer Based Auto-
recloser Framework“, accepted to be presented in The 24th IEEE
international conference on Microelectronics, 17-20 December 2012,
Algiers, Algeria.
[6] H.Bentarzi, A. Ouadi, M. Chafai and A. Zitouni, “ Distance Protective
System Performance Enhancement Using Optimized Digital Filter”, in
Proc. CSECS '11 The 10th WSEAS International Conference on
CIRCUITS, SYSTEMS, ELECTRONICS, CONTROL & SIGNAL
PROCESSING, Montreux University, Switzerland, December, 29-31,
2011.
[7] Power System Relaying Committee Of the IEEE Power Engineering
Society, “Power Swing And Out-Of-Step Consideration On
Transmission Lines”, IEEE PSRC WG D6, 2005.
[8] K.C.A. Dierks “Relay Specific Computer Aided Testing for Protective
Relays” Eskom, Republic of South Africa, 2006.
[9] Internal report of CNEPRU, 2012.
Fig.11 The displayed signals on the scope under different conditions.