Edward Bolingot Air Conditioning
Edward Bolingot Air Conditioning
Edward Bolingot Air Conditioning
by:
Edward Bolingot
ii
OVERVIEW
relative humidity, and air purity in indoor environments. This is a common approach for
ensure the proper maintenance of machinery or equipment that needs to run in a specific
atmosphere, or to carry out certain industrial processes that produce a lot of heat that needs to be
Controlling four essential variables: air temperature, humidity, movement, and quality, an
Many factors are taken into account while designing air-conditioning systems. The above-
mentioned self-contained unit serves a space directly. Ducts, part of the systems, are used to deliver
chilled air in more sophisticated systems, such as those found in tall buildings. Air is cooled once
at a central facility and then transported to individual units, where air is utilized to change the
This design aims to provide air-conditioning plan on all spaces except comfort rooms of a
3-room house in Purok 1, Maayongtubig, Dauin, Negros Oriental. The analysis comprises
calculating the overall cooling load while taking into account various aspects and selecting the
TABLE OF CONTENTS
Layout
Floor Plan
Note: All bedrooms are to be air-conditioned except for the comfort room outside the rooms.
2
Establishment Profile
Establishment: House
Location: Purok 1, Maayongtubig, Dauin, Negros Oriental
Walls: Concrete
Windows: Aluminum and Tinted Glass Casement Window
Ceiling: Hardiflex
Appliances
1. Room 1
Computer
LED Television
Electric Fan
Sound System (Surround)
2. Room 2
Computer
Electric Fan
Speakers (2.1 channel)
Laptop
3. Room 3
Electric Fan
Number of Occupants
1. Room 1
2 occupants (couple)
2. Room 2
2 occupants (daughter and son)
3. Room 3
Maximum of 3 (for guest)
3
FORMULA
Using formulas in heat transfer through plain walls.
where:
q = heat gained, W
k = thermal conductivity of the material, W/m-K
T= change in temperature, K
A = area of walls, m²
t = thickness, m
where:
where:
Room 1
Q = (2x150) = 300 watts
Room 2
Q = (2x150) = 300 watts
Room 3
Q = (3x70) = 210 watts
Assumed Temperature:
Outer = 32 ºC
Inner = 26 ºC
32 – 26 = 6 K
Using formulas in heat transfer through plain walls.
𝑘∆𝑇𝐴
𝑞= 𝑡
Where,
q = heat gained, W
A =area of walls, m²
t = thickness, m
5
t = 0.15 m
k = 1.28 W/m-k k (For General concrete thermal conductivity)
T = 6 K (change of temperature)
The area of the window and wall has different value of heat transfer; therefore, the heat transfer
to the window is calculated separately.
Room 2
Assumed Temperature:
Outer = 32 ºC
Inner = 26 ºC
32 – 26 = 6 K
Using formulas in heat transfer through plain walls.
𝑘∆𝑇𝐴
𝑞= 𝑡
Where,
q = heat gained, W
A =area of walls, m²
t = thickness, m
7
t = 0.15 m
k = 1.28 W/m-k k (For General concrete thermal conductivity)
T = 6 K (change of temperature)
t = 0.15 m
k = 1.28 W/m-k k (For General concrete thermal conductivity)
T = 6 K (change of temperature)
The area of the window and wall has different value of heat transfer; therefore, the heat transfer
to the window is calculated separately.
Room 3
t = 0.15 m
k = 1.28 W/m-k k (For General concrete thermal conductivity)
T = 6 K (change of temperature)
The area of the window and wall has different value of heat transfer; therefore, the heat transfer
to the window is calculated separately.
Room 1
The formula below is used to compute heat gained by solar energy through glass during the span
of time the wall is exposed to sunlight.
qsg = (A)(SHGF)(SC)(CLF)
where:
qsg = solar energy passing through window, W
A = area, m² exposed to sun
SHGF = solar heat gained factor for single sheet of clear glass, W/m-K
SC = shading coefficient
CLF = cooling load factor
Solution:
A = 3 m2
SHGF = 213 (see, appendix Table 6)
SC = 1.00 (Regular single glazing, appendix Table 7)
CLF = 0.53 (see, appendix Table 8)
qsg = (3) (213) (1) (0.53) = 338.67 W
*The Right (North-East) of the room is not exposed to sun during day time.
Room 2
The back side (South-East) of the room is exposed to sun during 7:00 am to 11:00 am.
The formula below is used to compute heat gained by solar energy through glass during the span
of time the wall is exposed to sunlight.
qsg = (A)(SHGF)(SC)(CLF)
where:
qsg = solar energy passing through window, W
A = area, m² exposed to sun
SHGF = solar heat gained factor for single sheet of clear glass, W/m-K
SC = shading coefficient
CLF = cooling load factor
Solution:
A = 1.8 m²
SHGF = 213 (see, appendix Table 6)
SC = 1.00 (Regular single glazing, appendix Table 7)
CLF = 0.53 (see, appendix Table 8)
qsg = (1.8) (213) (1) (0.53) = 203.202 W
11
*The Right (North-East) of the room is not exposed to sun during day time.
Room 3
The back side (South-East) of the room is exposed to sun during 7:00 am to 11:00 am, the
same as Room 2.
The formula below is used to compute heat gained by solar energy through glass during the span
of time the wall is exposed to sunlight.
qsg = (A)(SHGF)(SC)(CLF)
where:
qsg = solar energy passing through window, W
A = area, m² exposed to sun
SHGF = solar heat gained factor for single sheet of clear glass, W/m-K
SC = shading coefficient
CLF = cooling load factor
Solution:
A = 1.8 m²
SHGF = 213 (see, appendix Table 6)
SC = 1.00 (Regular single glazing, appendix Table 7)
CLF = 0.53 (see, appendix Table 8)
qsg = (1.8) (213) (1) (0.53) = 203.202 W
Internal Heat Gain from Lights. Rooms 1, 2, and 3 have the same number of lights with the
same capacity
q = (lamp capacity) (Fu) (Fb) (CLC)
where:
Fu = utilization factor (fraction of installed lamps in use)
Fb = ballast factor of fluorescent lamps usually 1.2 for common fluorescent fixtures
CLF = cooling load factors for lightning
q = ((24 watts x 4) + (40 watts x 1)) (1.2) (0.82)
q = 133.824 watts
12
Room 2
Room 3
Room 1
Room 2
Room 3
Room 1
Room 2
Room 3
Room 1
Room 2
Room 3
Room 1
With a refrigerating capacity of 1.86 TR, it is advisable to use an air conditioning system that
can sustain this load assuming the area is packed with maximum people inside.
Room 2
With a refrigerating capacity of 1.56 TR, it is advisable to use an air conditioning system that
can sustain this load assuming the area is packed with maximum people inside.
15
Room 3
With a refrigerating capacity of 0.933 TR, it is advisable to use an air conditioning system that
can sustain this load assuming the area is packed with maximum people inside.
16
CONCLUSION
Room 1 and Room 2, with a refrigerating capacity of 1.86 TR and 1.56 TR
respectively, it is advisable to use an air conditioning system in each room that can sustain this
load assuming the area is packed with maximum people inside. The most suitable AC unit to be
used is:
Panasonic 2 Ton 4 Star Wi-Fi Twin-Cool Inverter Split Air Conditioner (Copper, Shield
Blu Anti-Corrosion Technology, nanoe-G Air Purification, 2021 Model, CS/CU-WU24XKYXF,
White
Features:
Wi-Fi Split AC with Twin Cool Inverter compressor: Variable Speed Inverter Compressor
which adjusts power depending on heat load. It is most energy efficient and has lowest-noise
operation | Seamless hands-free operation and Voice Control with Alexa and Google Assistant
Capacity: 2 Ton - Suitable for large sized rooms (181 sq ft to 260 sq. ft) | Equipped with
Powerful and Dry Mode for different cooling needs
Energy Star Rating: 4 Star | Annual Power Consumption: 1143.38 kWh | ISEER: 4.2
Manufacturer Warranty: 1 Year Comprehensive | 5 years on PCB |10 years on Compressor | 5
years on Outdoor Casing
Copper Condenser Coil with Shield Blu Technology: Anti Corrosion Blue Fin Technology |
Enhances durability in high humidity coastal areas
17
Features:
Appendix
Hours after lights are Fixture X, Hours of operation Fixture Y, Hours of operation
turned on 10 16 10 16
0 0.08 0.19 0.01 0.05
1 0.62 0.72 0.76 0.79
2 0.66 0.75 0.81 0.83
3 0.69 0.77 0.84 0.87
4 0.73 0.80 0.87 0.89
5 0.75 0.82 0.90 0.91
6 0.78 0.84 0.92 0.93
7 0.80 0.85 0.93 0.94
8 0.82 0.87 0.95 0.95
9 0.84 0.88 0.96 0.96
10 0.85 0.89 0.97 0.97
11 0.32 0.90 0.22 0.98
12 0.29 0.91 0.18 0.98
13 0.26 0.92 0.14 0.98
14 0.23 0.93 0.12 0.99
15 0.21 0.94 0.09 0.99
16 0.19 0.94 0.08 0.99
17 0.17 0.40 0.06 0.24
18 0.15 0.36 0.05 0.20
Fixture X: recessed lights, not vented, supply and return air registers below the ceiling of
through the ceiling space and griller.
Fixture Y: vented or free hanging lights; air registers below or through the ceilings, return air
registers around the fixtures and through the ceiling space.
Quality of Construction a b c
Table 8. Cooling Load Factors of Glass with Interior Shading (North Latitudes)
References
https://www.nationalglass.com.au/wp-content/uploads/2019/06/Glass-Data_v4-
Low-Res.pdf
http://www.chigo.ph/residential-ac/floor-mounted-air-conditioners/30tr-floor-
mounted-air-conditioner
https://www.wconline.com/blogs/14-walls-ceilings-blog/post/89661-comparing-
solar-heat-gaincoefficients-shgc-and-shading-coefficients-sc