Reinforced Concrete Design by Professor Anthony Kwame Danso
Reinforced Concrete Design by Professor Anthony Kwame Danso
Reinforced Concrete Design by Professor Anthony Kwame Danso
CHAPTER ONE
REINFORCED CONCRETE
1.1 Introduction
One of the greatest engineering achievements over the years is the discovery of reinforced concrete as a
construction material. Reinforced concrete is a composite material consisting of concrete and steel.
Table 1.1 presents a summary of the strength properties of the two materials.
Table 1.1 reveals that the strengths of the two materials are complimentary. While concrete is strong in
compression but weak in tension, steel is strong in both tension and compression. The tensile strength of
concrete is in fact about 10 per cent of its compressive strength. In view of this, the two materials are
combined to form a composite material so as to take advantage of their strengths. Moreover, the
coefficient of thermal expansion of steel and concrete are so close (i.e. 10 x per for steel and 7-12
x per for concrete) that there exist sufficient bond between the two materials despite differential
expansion over normal temperature ranges.
1.2 Concrete
As we learnt in BT 351: Concrete Technology, concrete is a mixture of cement, aggregates (coarse and
fine aggregates) and water. The water reacts with the cement which hardens and binds the aggregates into
the concrete matrix. Concrete can be specified in two ways: (a) By volume or mix (e.g. 1:2:3−1 part of
cement: 2 part of fine aggregate: 3parts of coarse aggregate) (b) by stating the compressive strength.
Engineers usually specify the strength of the concrete rather than the mix. The onus lies on the site
engineer to come out with an appropriate mix ratio that will give the specified strength.
1
Design of Reinforced Concrete Elements
The compressive strength of concrete is determined by casting concrete cubes of 150mm or 100mm. The
cubes are allowed to harden and after 28 days they are crushed to determine what we call the cube
strength (denoted by ). Another approach is to form cylindrical shape (150mm diameter by 300mm
high). This gives us the cylinder strength (denoted by ). The cylinder strength is normally used by the
Americans whereas in most parts of Europe, they describe concrete using the cube strength. In Ghana, the
cube strength is normally used. Research has shown that given the same mix, the cylinder strength is
about 78% of the cube strength. A concrete with the specification means it has cube strength of
30N/ and cylinder strength of 24N/ . The higher value is always the cube strength. For more
information refer to BS1881:1983: Methods of Testing Concrete.
1.3. Steel
Steel reinforcement bars are produced in two grades: hot rolled mild steel bars with a yield strength of
250 N/ ; hot rolled or cold worked high yield steel bars having yield strength of 460 N/ . There
is also steel fabric made from cold drawn steel wires welded to form a mesh; it has yield strength of 460
N/ .Mild steel bars are produced as smooth round bar whereas High yield bars are produced as
deformed bars to increase bond stress. Reinforcing bars are produced in the following diameters: 6, 8, 10,
12, 16, 20, 25, 32, 50, and 60mm.
In structural detailing, the symbols R and Y are used to denote mild steel and high yield reinforcement
bars respectively.
1. Concrete has a very low tensile strength and hence require the use of tensile reinforcing.
2
Design of Reinforced Concrete Elements
2. Forms and sometimes shoring are required to hold the concrete in place until it hardens sufficiently.
Formwork is very expensive.
3. Concrete has low strength per unit weight leading to heavy members. This becomes an increasingly
important matter for long – span structures where concrete’s large dead weight has a great effect on
bending moment.
4. The properties of concrete vary widely due to variations in its proportioning and mixing.
Furthermore, the placing and curing of concrete in not a carefully controlled as in the production of
other materials such as structural steel.
3
Design of Reinforced Concrete Elements
CHAPTER TWO
PRINCIPLES OF DESIGN
2.1. Introduction
In this chapter we will discuss the various principles underlining the design of reinforced concrete. This
will include the Limit state design concept, the Elastic and Ultimate strength method of design, Factor of
safety, Type of loads in buildings among others.
4
Design of Reinforced Concrete Elements
construction. There are two categories of limit states: (a) the Ultimate limit state (ULS) and (b) the
Serviceability limit state.
2.3.2 Ultimate limit state
An ultimate limit state is reached when the structure (or part of it) collapses. Collapse may arise from the
rapture, yielding or buckling of some critical sections, loss of stability as a rigid body (overturning), etc.
That is to say the building should have adequate strength, should be stable and robust. To ensure adequate
strength, the loads are combined in such a way that the structure can carry the worst loading condition.
Moreover, safety factors are applied to the loads and material strengths to allow for the uncertainties in
the estimation of loads and in the performance of materials. For stability and robustness the code specifies
that shear walls, ties (peripheral ties, internal ties and horizontal ties) etc should be introduced in the
building.
There are two (2) methods use in reinforced concrete design: (a) the Elastic method also known as the
Modular ratio method and (b) the Ultimate or Load factor method of design and analysis. The elastic
method was the first to be used before the ultimate strength method was introduced.
The Elastic method is concerned with setting a limit on the amount of stresses which should be allowed to
occur in a structure. The building is then designed to ensure that those permissible stresses are not
reached. Usually the yield strength of the material is divided by a factor of safety to arrive at the
permissible stresses. For example, if the yield strength of a material is say 256N/mm2, an appropriate
factor of safety is selected (say 1.6) and the yield strength is then divided by this factor
(i.e. 250/1.6 = 160N/mm2). This 160N/mm2 becomes the maximum amount of stress which will be
allowed to occur in the structure. As stated earlier on the factor of safety is intended to provide allowance
for the imperfection of the material among reasons.
Another important principle upon which the elastic method operates is the assumption that the
Stress – Strain curve of both steel and concrete is linear. That is, the materials act within the Elastic range
(Fig 2.1). Remember, our studies in BT153: Introduction to Strength of Materials revealed that within the
5
Design of Reinforced Concrete Elements
elastic range, a material will regain its shape once the applied load is removed. At this stage the stress
and strain in the material are proportional and the stress – strain curve is linear as shown in Fig 2.1.
A Strain (ε)
Elastic Range
Plastic Range
Moreover, the modulus of elasticity (E) for the material is constant. In view of this it can be said that there
will be a fixed ratio between the E value for concrete and steel. This ratio is referred to as the Modular
ratio and it is used to determine the magnitude of the stress in concrete and steel.
1) Singly reinforced section: This is a section with only design reinforcement at the tension zone
only. This reinforcement is referred to as tension reinforcement
2) Doubly reinforced section: This is a beam or section with reinforcements design to take up tension
at the tension zone as well as compression at the compression zone. The reinforcement design to
take the compressive stresses is referred to as compression reinforcement.
3) Balanced section: This is the section were the stresses in the steel and concrete reach their
permissible values simultaneously. In practice this section is difficult to achieve.
4) Over– reinforced section: This is a section that contains more reinforcement than is required to
give a balance section. In this case the concrete reaches its permissible stress first before the stress
in the reinforcement develops to its full value. The moment of resistance of this section is based on
the force in the concrete. Failure of this occurs through the crushing of the concrete
6
Design of Reinforced Concrete Elements
5) Under– reinforced section: This is a section that contains too little reinforcement to permit the
balanced section to be developed. In this case the steel yield first before the stress in the concrete
develops to its full value. The moment of resistance of this section is based on the force in the steel.
Now let us look at the analysis of the section. The analysis is based on the following assumptions:
Consider the rectangular concrete beam in Fig 2.2 & 2.3 with breadth b, and depth D reinforced at the
bottom.
LOAD
Neutral axis
Steel taking up tensile stresses
Fig 2.2
Area in compression = b dn
b εc fc
dn Fc
d
D la = d –
Fs
εs fs
7
Design of Reinforced Concrete Elements
d = the depth to the centroid of the steel reinforcement referred to as the effective depth
From Fig 2.3b, because of the assumption that the steel and concrete are each acting within the elastic
range, the strain have a triangular distribution varying from zero at the neutral axis to a maximum of
As explained earlier on, ES/Ec = the modular ratio = e. For ordinary reinforced concrete, e usually
e. =
Total compression force in concrete = area in compression x average compressive stress in concrete
8
Design of Reinforced Concrete Elements
FC = (b )x( x )= b
Total tension force in steel = area of steel in tension x tensile stress in steel
FS =
Example 1: A reinforced concrete rectangular beam has a breadth of 225mm and depth of 400mm and
reinforced with 4No 20mm diameter mild steel bars. If the beam has cover of 25mm, determine (a) the
depth to the neutral axis and (b) the moment of resistance of the section. The permissible stress in the
steel and concrete are 125N/mm2 and 10N/mm2. Take the modular ratio as 15.
b = 225mm
(a) Depth to the neutral axis ( )
From eqn 2, =
D = 400mm d
9
Design of Reinforced Concrete Elements
From the values obtained above, the moment of resistance of the section is 46.92kNm (the smaller of the
two values). In view of this, the beam should be designed in such a way that the maximum moment due to
the load does not exceed 49.kNm.
One of the main criticisms of the elastic method is the assumption of the elastic behavior of the materials.
In the case of steel, if the maximum stress is limited to a value below the yield stress, the assumption
above is accurate. However, for concrete under compression, a linear stress – strain curve can be assumed
provided the stress does not exceed about half of the ultimate compressive strength. Even with this, the
effect of creep does not allow the concrete to truly exhibit the elastic or linear behaviour. In view of this,
CP 114 applies a factor of one – third to the ultimate cube stress to obtain the permissible stress for
concrete under flexure so that the behaviour of concrete gets close to the assumed linear elastic state.
Moreover, the permissible stress in the steel is usually related to the yield stress by a factor of 1.8. The
strain in the reinforcement at this stress is several times that which might be considered as being the
ultimate tensile strain of the concrete surrounding the reinforcement, so that development of the full
permissible stress in the reinforcement implies cracking of the concrete in the tension zone. In order to
control this (i.e. width of the crack), the permissible tensile stress in the steel reinforcement is limited to a
maximum value of 230N/mm2 irrespective of the yield strength of the steel.
Furthermore, the factor of safety used in design is expected to provide a constant ratio between the
working loads and the loads that would cause the collapse of the structure. It has been found that, this is
not true in practice, meaning the design will either have too high a factor of safety, resulting in an
uneconomical structure or one that is too low, resulting in a potentially dangerous structure.
Despite the above, the Code of Practice, CP 114: 1957 is guided by this principle and some designs, e.g.
water retaining structures are still carried out using this method. Today this method is considered as an
alternative method.
10
Design of Reinforced Concrete Elements
In the ultimate or load factor method, the section is analyzed up to the point of failure. The method takes
into account non – linearity in the behaviour of the steel and concrete. This presents the true state of
affairs of the materials’ behaviour than that of the elastic method. With this method, the actual strength of
a section is related to the load causing the failure, with the latter being determined by applying a factor to
the design load. Moreover, the ultimate strength (Fig 2.1) of the materials is used in the calculation.
The deficiency with this method is that, since the technique is concerned with the behaviour of the section
at ultimate load, it is unable to make any assessment of the behaviour of the structure under working load.
For this reason, it cannot be used for the serviceability states of deflection and cracking.
The ultimate strength method from the British Standard 8110 (BS 8110) is based on the limit state design
philosophy discussed in section 2.3. This method is meant to overcome many of the weakness or
disadvantages of the methods discussed previously. With this method the working loads are multiplied by
partial factor of safety to obtain the ultimate design load. The ultimate strength of the materials is also
divided by partial factor of safety. After this, each structural element (e.g. beams, columns, slabs etc) are
designed for the ultimate limit state (ULS) and checked for the serviceability limit state (SLS).
2.6.2. Section analysis using the Ultimate Strength method (BS 8110)
The analysis is based on the following assumptions (Section 3.4.4.1 of BS 8110 –1: 1997)
b εc k1fcu
k2x
x Fc
d
εs fs
(a) Cross section (b) Strain diagram (c) Parabolic stress block
11
Fig 2.4: Strain and stress distribution at failure (From first principles)
Design of Reinforced Concrete Elements
Fig 2.5 shows the strain and stress distribution within the plastic range (see Fig 2.1). At this stage the
distribution of stress in the concrete is no more linear as used in the Elastic method of analysis but rather a
parabolic curve. At failure, the value of the maximum stress in the concrete is taken to as k1fcu and the
force in the concrete (Fc) is assumed to act at a distance of k2x from the top of the section (Fig 2.4c). K1 is
the ratio of the average compressive stress in the concrete to the characteristic strength of the concrete
(fcu) and k2 is the ratio of the depth of the centroid of the stress block to the neutral axis depth(x). Due to
the shape of the stress block, it is difficult to develop design equations for the section and hence many
suggestions have been made for an equivalent stress distribution. Among these equivalent stress
distribution is the rectangular stress block from BS 8110 (Fig 2.5).
BS 8110 uses a simplified rectangular stress block of intensity 0.67 extending from the compression
face to a depth of 0.9x. The partial safety factor γm is taken as 1.5 for concrete and 1.05 for steel. The
strain in the concrete is 0.0035.
0.67
b εc = 0.0035
0.9x 0.45x
x Fc
d
Z = (d – 0.45x)
Fs
εs
(a) Cross section (b) Strain diagram (c) Simplified rectangular stress block
Fig 2.5: Stress block at the ultimate limit state (BS 8110)
BS8110 ensures that the reinforcement yields before the concrete crushes. In view of this, the maximum
moment that the section can carry is governed by the force in the concrete. Now
12
Design of Reinforced Concrete Elements
MC = Force in concrete (FC) x lever arm (Z) = 0.402x b (d – 0.45x) ……………. (5)
The code further specifies that the neutral axis depth x, should not exceed 0.5d. This means that from eqn
(5), the ultimate moment of resistance of the single reinforced section in terms of the concrete stress is
given by
From equation 6, the effective depth of section required to take any moment (M) is given by
FS = = 0.95
For the section to be in equilibrium under an external moment M, the internal moment of resistant of the
section (Ms) should be equal to the externally applied moment (M).
13
Design of Reinforced Concrete Elements
Depending on the value of the applied moment, the lever arm Z, should calculated using the formula
Z = d {0.5 + } ………………… (10) But Z should not be taken more than 0.95d
K= ………………………………. (11)
If the applied bending moment M, from the load exceeds the ultimate moment capacity M u, the excess
moment (M – ) is to be resisted by using an area of compression reinforcement (Fig 2.6) such
that the neutral axis depth remains at the maximum permitted value of 0.5d
0.67
b
=
0.9x Fc = (0.9x b) (0.67 )
d
(d – )
=
Moment of resistance of the compression reinforcement = Force in compression steel ( ) x lever arm
= x (d – ) = 0.95 (d – )
14
Design of Reinforced Concrete Elements
Equating the above additional resistant moment to the excess moment, we have
0.95 (d – ) = (M – )
But from eqn (6) = bd2 where = 0.156. Similarly, let us write M = K bd2
» 0.95 (d – ) = (K b – b )
0.95 (d – ) = (K – ) b
= + ……….…………….. (13)
Where, = 0.156.
NB: All the formulas (equations 6–13) can also be found at section 3.4.4.4 of BS8110 – 1:1997
2.7. Characteristic loads
These are the basic loads that may be applied to a particular member or structure. They are
15
Design of Reinforced Concrete Elements
a) Characteristic dead load, This is the weight of the structure complete with finishes, permanent
fixtures and partition. The word ―characteristic‖ means that the value of the load has an acceptable
probability of not being exceeded during the life of the structure. For instance if the for a certain
slab is 15kN/m2. It means that if the building will last for say 100yeras, we are 95% sure that the
value of the dead load will not exceed 15kN/m2.
b) Characteristic imposed load, This is the load of the occupant or users of the building and other
non permanent fixture on the building. Taking our classroom for instance, the imposed load
comprises of the weight of the students, the tables and chairs, lighting fittings and fixtures, air
conditioners etc.
c) Characteristic wind load, This is the wind load acting on the structure.
Below is a schedule of weight of some materials
Table 2.1: Weight of building materials
(based on BS 648 :1964)
Material description Weight
Asphalt— Roofing 2 layers (19mm thick) 0.412 kN/m²
Damp – proofing (19mm thick) 0.412 kN/m²
Bitumen and roofing felts – Mineral surfaced 0.034 kN/m²
bitumen per layer
Blockwork – Solid per 25mm thick, stone 0.539 kN/m²
aggregate
Aerated per 25mm thick 0.147 kN/m²
Brickwork– Clay, solid per 25mm thick 0.539 kN/m²
Concrete, solid per 25mm thick 0.578 kN/m²
Concrete–Natural aggregate 24 kN/m³
Lightweight aggregate 17.248 kN/m³
Reinforced concrete 24 kN/m³
Rendering (Cement : sand (1:3) 13mm thick) 0.294 kN/m²
Screeding (Cement : sand (1:3) 13mm thick) 0.294 kN/m²
Plastics sheeting (corrugated) 0.044 kN/m²
Terrazzo (25mm thick) 0.529 kN/m²
Plywood (per mm thick) 0.007 kN/m²
Timber – Softwood 5.782kN/m³
Hardwood 12.25 kN/m³
Water 9.82kN/m³
Steel (corrugated roofing sheet per mm thick) 0.098 kN/m²
16
Design of Reinforced Concrete Elements
The loads discussed above can be combined in various ways for design purpose to obtain the ultimate
design load. This can be found on Table 2.1 of BS 8110 – 1:1997 reproduced in this manual as Table 2.2
Table 2.2– Load combinations and values of for the ultimate limit state (Table 2.1: BS 8110 – 1:1997)
Load combination Dead load Imposed load Earth and Wind
Adverse Beneficial Adverse Beneficial water Load
pressure
1. Dead and imposed (and 1.4 1.0 1.6 0 1.4 —
earth and water pressure)
2. Dead and wind (and 1.4 1.0 — — 1.4 1.4
earth and water pressure)
3.Dead and imposed and 1.2 1.2 1.2 1.2 1.2 1.2
wind (and earth and water
pressure)
CHAPTER THREE
SLABS
3.1 Introduction
A slab is a horizontal plate element forming floors and roofs in a frame structure which normally
carry uniformly distributed loads. Slabs may be simply supported or continuous over one or more
supports. They are designed like other structural elements to carry their self weight and other loads
imposed on them. Slabs can be classified into three types:
(a) Flat slabs: These are slabs carried on columns and edge beams or walls with no interior beams.
BS8110: Part 1, clause 1.2.2.1; also define it as a slab with or without drops, supported
generally without beams by columns with or without column heads. The slab may be solid or
have recesses formed on the soffit to give a waffle slab. Example can be found at the old
Main library of KNUST (the part of the library close to the Royal Parade ground).
17
Design of Reinforced Concrete Elements
Fig 3.1: (a) Slab without drop panel; (b) slab with drop panel and flared column head.
(b) Waffle or Ribbed slabs: These slabs have recesses formed on the soffit. This creates ribs which run
either in one or two directions. The first floor slab (near Focus FM) of the Great Hall of KNUST is a
typical example.
(c) Solid slab: Solid slabs have uniform thickness and are carried on beams (edge and interior)
18
Design of Reinforced Concrete Elements
The analysis of any of the slabs discussed above may be carried out using any of the following methods.
1. Elastic analysis. This covers three techniques:
i. Idealization into strips of beams of 1m width spanning one way or a grid with the strips spanning
two ways
ii. Elastic plate analysis
iii. Finite element analysis − the best method for irregularly shaped slabs or slabs with non-uniform
loads
2. Method of design coefficients. With this, use is made of moment and shear coefficients given in the
Code of Practice (e.g. Table 3.14 of BS 8110 – 1) and
3. The yield line and Hillerborg strip methods
In this manual, we focus on the design of solid slabs.
Fig 3.4
19
Design of Reinforced Concrete Elements
i. One – way slabs: When the ratio of the long span and short span (i.e. / ) is more than 2, the
panel is classified as One –way slab. The implication is that, the slab is designed to span between the
short span (Fig 3.6 b). Thus the main reinforcement bars are placed in the short span. The slab
enclosed by gridlines A – B and 1− 3 in Fig 3.4 above is an example of one –way slab.
= 2m
Distribution bars
(Top bar)
= 8m
Main reinforcement
(Bottom bar)
Fig 3.5
The ratio, = = 4 > 2. The slab is designed as strips of rectangular beams of 1m width and spanning
between the beams on gridline A and B (Fig 3.6b). The moment resulting from this analysis is used to
determine the spacing of the main bars. Minimum reinforcement is provided for the long span as
distribution
bars.
20
Design of Reinforced Concrete Elements
ii. Two – way slabs: This is where the ratio of the long span and short span (i.e. / ) is less than or
equal to 2. In this case, the strips are designed to span in both direction (Fig 3.6a). Reinforcement has
to be designed to take up the moments from both spans. Taking the slab enclosed by gridlines C – D
and 1− 2 (Fig 3.4) the ratio, = = 1.25 < 2; this makes it a Two – way slab. Reinforcements have to
21
Design of Reinforced Concrete Elements
9. Four edges discontinuous: e.g. panel K. In our domestic homes, the slab of most of the polytank
Stand has all the four edges discontinuous.
Fig 3.7
22
Design of Reinforced Concrete Elements
Fig 3.8
3. Load Estimation
All the dead loads ( ) and imposed loads ( ) the slab is likely to be subjected to during its life span are
calculated. As discussed in section 2.7, dead load comprises of the self weight of the slab complete with
finishes, permanent fixtures and partitions. The imposed load on the other hand is the weight of the
occupants of the building and all live (non permanent) load on the slab. A factor of safety of 1.4 and 1.6
are applied to the dead and imposed loads respectively to serve as allowance for the degree of uncertainty
in the analysis, material imperfection, extra loading and the quality of construction.
23
Design of Reinforced Concrete Elements
Table 3.12……………. Moment and shear for one – way spanning slabs
Table 3.14 and 3.15 …… Moment and shear co –efficient for two – way spanning slabs
5. Adequacy of section
As this stage check if the trial depth of the slab selected at step 2 above can take the maximum moment.
The effective depth of slab required to take up the maximum moment is given by
If the depth required ( ) is more than the initial effective depth, the design has to be revised by using
6. Calculate the area of steel required to take the moment using the following formulas
K= ………………………. (4)
and = 0.156.
24
Design of Reinforced Concrete Elements
7. Detailing
The output of the design calculations are presented in a detailed drawing giving the general
arrangement and overall layout of the structure. The drawing must show the sizes, arrangement,
spacing, and cut-off points for the reinforcing bars at the various sections of the elements. The
Bending schedule should also be prepared.
8. Checks
Check the section against Deflection, shear, cracking among others.
25
Design of Reinforced Concrete Elements
For moment and shear force analysis, a two – way slab (panel) is divided into four (4) strips (Fig 3.9 of
BS 8110 –1: 1997)
4 1, 3 4
Strip 1 and 3 are middle strips. These two strips are subjected to positive bending and reinforced at the
bottom. Strips 2 and 4 are edge strips and would be subjected to negative bending. They are reinforced at
the top. The reinforcements at the various strips are usually given the following names:
Strip 1: Short span midspan reinforcement; Strip 2: Short span continuous edge reinforcement;
Strip 3: Long span midspan reinforcement; Strip 4: Long span continuous edge reinforcement;
Bar mark 4 is placed over the support (i.e. where the beam is) and it should extend at least 0.75m from the
centre of the beam into the slab on both ends. In view of this, the total length of the bar should be a
minimum of 1.5m (i.e. 0.75 + 0.75 = 1.5m). Similarly, bar mark 2 should extend 0.5m both ways giving a
total length of 1.0m. The moments at the various strips are calculated using the formulas below:
Where and are the short span and load span moment coefficients obtained from table 3.14 of BS
8110. n= the total design ultimate load per unit area (1.4 + 1.6 )
26
Design of Reinforced Concrete Elements
= 6m
2 0.5m
4 3 1 4 3m
= 4m
2 0.5m
Plan
Negative bending at support
4 4
3
1 1
1
Beam
Bar mark 4 is placed over the support (i.e. where the beam is) and it should extend at least 0.75m from the
centre of the beam into the slab on both ends. In view of this, the total length of the bar should be a
minimum of 1.5m (i.e. 0.75 + 0.75 = 1.5m). Similarly, bar mark 2 should extend 0.5m both ways giving a
total length of 1.0m. The moments at the various strips are calculated using the formulas below:
Where and are the short span and load span moment coefficients obtained from table 3.14 of BS
8110. n= the total design ultimate load per unit area (1.4 + 1.6 ).
27
Design of Reinforced Concrete Elements
= n ……………… (1)
= n ……………… (2)
Where and are the short span and load span shear coefficients obtained from table 3.15 of
BS 8110.
Example: Fig 3.11 shows the first floor plan of a proposed 3storey office building. Using the ultimate
strength method (BS 8110), design and detail the slabs enclosed by gridlines A− B and 1− 3. The beams
lie on the main gridlines. Use steel grade 250 and concrete grade 30.
Solution
28
Design of Reinforced Concrete Elements
5200
X Y
4400 4800
Fig 3. 12a
The panels have been labeled X and Y. Each of them is a two− way slab. From Table 3.14 of
BS 8110 − 1, Panel X = Two adjacent edges discontinuous (i.e. the side on gridlines A and 1 are not
bordered by slab) Panel Y = One short edge discontinuous (i.e. the short side on gridline A is not
bordered by slab)
We shall use the following data to design the panels:
Cover to reinforcement = 25mm
Diameter of bars = 12mm
Concrete grade, = 30N/
Comment: The choice of cover depends on factors such as, (a) the degree of exposure of the
reinforcement to moisture (b) the expected duration of fire resistance (c) the location of the element,
whether below or above ground level etc.
Effective depth, d ≥
The panels are continuous and hence from table 2.1 (or Table 2.9 of the Code) the ratio is 26. The span of
a slab refers to its short dimension. In view of this, the span of panel X and Y are 4.4m and 4.8m
respectively. Moreover, despite the fact that their spans are not the same, they must have uniform
thickness. To do this, we use the panel with the longest span (i.e. panel Y) to determine the depth.
29
Design of Reinforced Concrete Elements
d D
Overall depth, D ≥ d + (bar size) + Cover
Fig 3.13b
That is from above the overall depth of the slab should be 216mm. In slabs, the reinforcement offers more
additional resistance to deflection it is therefore always advisable to reduce the thickness obtained above.
Therefore select the overall depth, D = 150mm.
Dead load
Comment: If there is any other load you deem necessary, it can be added. Moreover, the load is always
estimated per unit area (i.e. kN/ ) for two – way slabs and kN/m for one – way slabs and beams.
Moment: The moments at the various strips are calculated using the formulas below:
30
Design of Reinforced Concrete Elements
Where and are the short span and long span moment coefficients obtained from Table 3.14 of
BS 8110. n = the total design ultimate load per unit area (1.4 + 1.6 ) = 14.48kN/
How to pick the coefficients: The moment coefficients are in bold. For each panel calculate the ratio
.This is used to select the coefficients for the short span. Starting with panel Y, the ratio gives us 1.1.
Go to Table 3.14 of BS 8110 – 1 and read under the ratio 1.1. You will find two values: 0.044 and 0.033.
Fig 3.14
The top value (i.e. 0.044) is the short span coefficient for the continuous edge which is negative. The
other value, 0.033 is the midspan (positive) coefficient. When you trace each of the rows to the right, you
31
Design of Reinforced Concrete Elements
would find their corresponding long span coefficients (0.037 and 0.028) at the last column of the table.
Now multiply each coefficient by the ultimate design load, n =14.48kN/ and the square of the short
span. Follow the same procedure and calculate the moments for panel X
Shear: The shear coefficients can be obtained from Table 3.15 of BS8110 and used to determine the
shear force as follows:
Short span, = n Long span, = n
One short edge Short span 0.39 x 14.48 x 4.8 0 x 14.48 x 4.8
discontinuous (Y) = 27.11kN =0
The depth of slab required to take the maximum moment (17.66kNm) from Table 3.3 is given by
as mentioned earlier on, slabs are designed as strips of rectangular beams of 1m (1000mm) width.
= = = 61.43mm
We require just 92.43mm depth of slab to take the maximum moment; however at the initial stage, we
selected 150mm which is more than the required. This implies that our initial overall depth of 160mm is
ok or satisfactory in terms of deflection and moment.
32
Design of Reinforced Concrete Elements
D = 150mm
Fig 3.16
=depth to the centroid of the short span reinforcement (i.e. the main bars)
=depth to the centroid of the long span reinforcement (i.e. the distribution bars)
Let us take each panel and moment, one after the other:
Panel X: Short Span: Moment for the continuous edge, M = − 17.66kNm (Table 2.2). The negative
moment means that the concrete at the top of the section is under tension and hence the reinforcement
should be placed at this position.
K= = = 0.042
Since K < (0.042< 0.156), there is no need to put reinforcement at the compression side of the section
Always remember not to take Z more than 0.95d. Z = 0.95d = 0.95 x 119 = 113.05mm
For steel grade 250 (i.e. mild steel) in slab, the minimum area of steel that has to be provided is given by
33
Design of Reinforced Concrete Elements
= 0.24% b D = x (1000 x 150) = 375 /m. (See Table 3.25 of the Code for more details)
Now, from the steel chart (Table 2.2a), read under bar size 12 and select an area of steel which is slightly
more than the area of steel required (i.e. 657.74 /m). That area is 754 /m. The bar spacing which
corresponds with this area is 150mm. See the illustration below.
12 754
Fig 3.17
At the continuous edge R12 bars @ 150mm spacing ( = 754 /m) at the top of the section.
The meaning of this statement is that, if you pick 1m of the slab at the continuous edge, the total cross
sectional area of all the bars should be at least 754 . To achieve this, the bars should be spaced at
150mm giving a total of about 7 bars
150 mm
175 175
1m
Fig 2.18
For the other sections take the lever arm to be 0.95d.
The area of steel required and provided for the other sections are shown in Table 3.5.
34
Design of Reinforced Concrete Elements
NB: All the area of steel provided, should be more than the minimum requirement
(i.e. 375 /m). The area to select is a matter of choice. However as much as possible try to maintain
uniformity in the spacing of the bars to speed up construction. From above all the top bars are spaced at
150mm whereas the bottom bars are at 200mm centres.
Step 7: Checks
35
Design of Reinforced Concrete Elements
From Fig 3.19, Clear distance = 200 – 2 ( x bar size) = 200 – 2 ( x 12) = 188mm
36
Design of Reinforced Concrete Elements
(c) Deflection
Check deflection for only the short span. Moreover, since the short span of panel Y has the higher value
(i.e. 4.8m) we shall perform the check on that span.
The tension reinforcement at the short span (midspan) offers additional resistance to deflection. In view of
this we always modify the basic span to depth ratio (i.e. 26) with a factor to arrive at the allowable
deflection.
Allowable deflection = 26 x 2 = 52
Since the actual deflection (40.34) is less than the allowable deflection (52), deflection is satisfactory.
3.3. Detailing
The important stage of the structural engineer’s design process is the detailing. This is where the outputs
of the design calculations are presented in a detail drawing giving the general arrangement and overall
layout of the reinforcement in the slab. It is important to note that any mistake at this stage renders the
whole design process useless. The contractor uses to this drawing to construct the building; slightest
mistake will result in the collapse of the building.
37
Design of Reinforced Concrete Elements
In this section, we will look at some principles regarding detailing, how to prepare Bending Schedule
among other things. We will use Fig 2.16 to explain the concepts.
The following are some key points to take note when detailing:
1. The letter R and Y are used to denote mild steel and high yield reinforcement bars respectively.
2. The description should indicate the bar type, bars size, the spacing and the number of bars. It should
also state whether it is a top or bottom bar. If a bar has the description: 30 R1202@150 . It
means the total number of such a bar is 30. The R12 stand for mild steel bar of 12mm diameter. Each
bar is given a number. For this bar, the 02 after the R12 is the bar number. Sometimes the bar number
is written in a circle as used in Fig 2.16. Moreover, it is spaced at 150mm centres. means it is the
first bottom (B) bar. T is used for top bar and TD means top down bar. In other words, when counting
from the top, it is the second bar.
3. Arrows are used to demarcate the position of each bar on the slab and the number of bars in each
range is written. For instance bar mark 3 has the description 22 + 24−R12@ 200 . This means
that at a spacing of 200mm, there be 22 number of bars arranged between gridlines 1and 2. Similarly,
24 bars will be arranged between gridlines 2 and 3. This gives a total of 46 bars.
4. Normally, at the discontinuous edge of a slab, the bars are bent to serve as top and bottom bar.
Example is bar mark 1 and 3
5. The standard length of reinforcement bars in the market is 9m. In view of this no single bar should
have a total length in excess of 9m. The detailing should try as much as possible to reduce cutting
waste during construction.
Bending schedule
It is always required of the designer to prepare a bending schedule for the bars. It schedule identifies the
various bar sizes, their shape and length, the total number etc. This facilitates the cutting on site. A typical
bending schedule has the format of Table 3.6.
CHAPTER FOUR
STAIRCASE
4.1 Introduction
A staircase is a set of steps or flights (including the surrounding structure) leading from one floor to
another. It is the most common means of access between the floors of a storey building. It is constructed
with materials such as timber, concrete (reinforced), steel etc. In this chapter, we will look at the design of
reinforced concrete stair.
39
Design of Reinforced Concrete Elements
Fig 4.1
There are various types of stair. Their choice in a structure is influenced by factors such as (a)
1. Straight Flight Stair: This is a stair with a single flight spanning between the two floors to be
assessed without intermediate landing.
2. Half – turn (180) Stair: The stair has two flights between the two floors with an intermediate
landing known as half landing. The stair is also known as dogleg stair. The stair to the office of the
College of Architecture and planning is an example
3. Quarter – turn (open well) Stair: The stair has three (3) flights between the two floors with two
intervening landing. An opening is created between the first and third flights hence the name open
well stair. An example is the stair leading to our Building Technology department office.
4. Free Standing or Scissor Stair: This is similar to half– turn but the landing is suspended. The
landing of this stair gets its support from the two flights. A typical example is the staircase leading to
Focus FM at the Great Hall of KNUST where the Moslems normally pray.
5. Helical stair: It has a single flight which turns as it rises into a helix shape from floor to floor. This
type of stair occur less space than straight flight.
6. Cantilever Stair: In this type of stair, there is a central reinforced concrete spine wall where each of
the steps cantilevers out of it. The various landings are designed as cantilever about a beam that in
40
Design of Reinforced Concrete Elements
turn cantilevers out of the central spine wall. Examples include the external stair of the Studio Block
(i.e. the location of the Exhibition Hall and BT classroom) and The New Block (i.e. the Architecture
Block) of College of Architecture and Planning (CAP). Others include the eternal stair of the
Examination Hall (near the Shuttle ranch) of KNUST.
Another form of a cantilever stair is that cantilevering from a central spine beam. The spine beam is
stepped and the steps (usually precast) are bolted to the horizontal surface (treads) of the spine beam.
Examples can be found at the following halls of KNUST: Independence Hall, University Hall
(Katanga), Republic Hall and Queens Hall. The stairs lead to the Administrative offices of each hall.
7. Spiral Stair: This stair is the most economical in terms of space utilization and cost. It consists of
several cantilever steps jotting out like leaves from a central circular column. Each of the steps is
designed as a cantilever and usually the steps taper at the end (i.e. it becomes wider at the free end).
The steps are precast with a central hole of the same diameter (with some clearance) as the central
column. The steps are arranged to form a spiral around the central column. The final landing is
designed to span the central column and the adjoining walls. Example of this stair can be found at the
Studio Block of CAP, KNUST.
41
Design of Reinforced Concrete Elements
Fig 4.2
The flight of the stair may span between two beams, two landings (or floors) or a beam and landing. The
effective span (L) is given by (section 3.10.1.3 BS 8110 – 1: 1997)
42
Design of Reinforced Concrete Elements
L= + + ……………………………….. (1)
= the breadth (width) of the supporting member at one end or 1.8m, whichever is lesser,
= the breadth (width) of the supporting member at other end or 1.8m, whichever is lesser.
≤ 1.8m ≤ 1.8m
Landing or Floor
Moment, M =
Landing or Floor
(a)Flight supported by two landings (floors)
Landing or floor
Moment, M =
Ground Floor (GF)
GF Beam ≤ 1.8m
Floor Beam
Moment, M =
Ground Floor (GF)
GF Beam L 43
(c)Flight supported by two beams
Design of Reinforced Concrete Elements
When the flight spans between two beams (Fig 4.3c) or a beam and landing (Fig 4.3b), the moment is
calculated as M = 0.125 and when it spans between two landings designed orthogonal ( ) to the
direction of the flights (Fig. 4.3a), M = 0.1 , where w is the load of the flight and L, the effective span.
In the load estimation, any incline load (e.g. waist of flight and its finishes) should be multiply by the
slope factor, F = , where R is the rise and T the going. This is aimed at converting the inclined
In traverse design, each step is designed separately. Stairs in this category include spiral stair, cantilever
stair and steps spanning between beams or walls. The step is designed as a rectangular beam with width, b
equal to the going of the step and depth, D equal to the waist. Where the steps are disjointed as in
cantilever steps, the rise may be taken as the depth, D
Example 1: Half –turn stair where the landing is continuous with the stair flight
With reference to Fig 4.4 design and detail the stair enclosed by gridlines E – F and 2 – 3. Use concrete
grade C30 and steel grade 250. The room height is 3m.
Solution
44
Design of Reinforced Concrete Elements
Because the flight and the landing span in the same direction, the design of the flight is deem to include
the landing.
E F
10 Equal treads @ 300mm
= 3000mm
2 2
2000 1200
100
2300
1100
3 3
9 Equal treads @ 300mm = 2700mm
6425
E F
Dead load
i. Step: (0.15m x 24kN/ ) = 1.8kN/ …… … (0.15m is the rise)
45
Design of Reinforced Concrete Elements
Imposed load:
W = 12.06 kN/
Fig 4.5 (a): The load of the flight is taken to
be the same as the landing and distributed
3.3m
across the whole span.
Midspan of
landing
Ground beam
W =12.06kN/
Fig 4.5 (b): The load of the flight and landing
( ) are treated separately. The 2.7m is the
2.7m 0.6m
span of the flight only and the 0.6m is half of
Midspan of the landing width.
landing
Ground beam
.
Fig 4.5a & b present two ways of distributing the load on the span. If one wish to carry out the design as
accurate as possible Fig 4.5b should be used. However, for the sake of time and since the maximum
moment in the two cases does not vary significantly, one can always use Fig 4.5a.
From Fig 4.5a, maximum moment, M = ……………because, it is supported by a beam and landing
46
Design of Reinforced Concrete Elements
Assuming 12mm diameter bars and 25mm cover, effective depth d = 150 – (0.5x12 + 25) = 119mm. By
inspection the lever arm will be more than 0.95d.
Distribution bars: Minimum area of steel = 0.24% b D = 0.24% (1000 x 150) = 360 /m. Therefore
provide R10 bars at 200mm ( = 393 /m) as distribution bars
Since the actual deflection (29.2) is less than the allowable deflection (29.4), the 150mm waist is ok.
Note: the floor width of 2.0m exceeds the limit of 1.8m; hence the width is taken as 1.8m.
47
Design of Reinforced Concrete Elements
Provide R16 bars at 175mm ( = 1149 /m) as main bars. For distribution bars use the say
Step 3: Detailing
48
Design of Reinforced Concrete Elements
Example 2: Half –turn stair where the landing spans orthogonal to the flight
2 2
2000 1200
100
2400
1100
Landing
3 3
6425
E F
Fig 4.7
This time from Fig 4.7 the landing will be designed separately from the flights. The landing spans
between (receive its support from) the beams on gridlines (2) and (3). The flights in turn receive part of
their support from the landing (i.e. the flights transfer part of their load to the landing). We will use the
same information for question 1.
49
Design of Reinforced Concrete Elements
(a) Load Estimation : From question (1) the ultimate design load, w = 12.06kN/
This time, the load of the flight covers only the 2.7m span because the landing is not continuous with the
flight. Calculating for the reactions,
This means that the flight will transfer 13.32kN of its load to the landing and 19.24kN to the ground
beam.
W =12.06kN/
Fig 4.8b
x
= 19.24kN = 13.32kN
From Fig 4.8b, let the maximum moment occur at a distance x from B. At this point shear force is equal
to zero. After going through the calculations,
x= = 1.60m …………… (Please take your time to do the calculations and confirm this answer)
50
Design of Reinforced Concrete Elements
Note, when detailing the stair at the landing area, these bars should lie on top of the main bars for the
landing so as to transfer the 13.32kN load to the landing.
Distribution bars: Minimum area of steel = 0.24% b D = 0.24% (1000 x 150) = 360 /m. Therefore
provide R10 bars at 200mm ( = 393 /m) as distribution bars
(c) Deflection check: Please follow example 1 and check for deflection.
W = 12.06kN/
0.9m 3m 0.6m
Fig 4.9a
4.5m
is the load transferred from the flight to the 1st floor and is that received by the landing.
Hence 16.88kN of load is transferred to the 1st floor and 19.30kN to the landing.
W = 12.06kN/
= 16.88kN = 19.30kN
Maximum deflection occurs a few distance (x) into the span of the distributed load. Again at this point
shear force is equal to zero. By inspection,
x= = 1.40m …………… (Please take your time to do the calculations and confirm this answer)
51
Design of Reinforced Concrete Elements
This means that maximum deflection occurs at = 0.9 + 1.4 = 2.3m from . At this point
Provide R16 bars at 175mm ( = 1149 /m) as main bars. For distribution bars use the say
Dead load
Note: the 1st and 2nd flights transferred 13.32kN and 19.3kN of their load respectively to the landing. In
design we use the higher value and add it to the load per meter width of the landing.
52
Design of Reinforced Concrete Elements
W = 26.13 kN/m
Fig 4.10
2.4m
M= = 18.81kNm
Assuming 12mm diameter bars and 25mm cover, effective depth d = 150 – (0.5x12 + 25) = 119mm. By
inspection the lever arm will be more than 0.95d.
Distribution bars: Provide minimum area of steel. That is, R10 bars at 200mm
Note: It is a good practice to limit the minimum bar size (main bars) to 12mm at a maximum spacing of
200mm
(d) Detailing
The detailing of the stair is similar to that of example 1 (Fig 4.6). However, this time at the landing area,
the main bars for the flights (i.e. bar marks 2, 8 & 7) will be the second bottom bar. Bar mark 3 will be the
first bottom bar. This way, the flights will receive their support partly from the landing as the design
calculations were carried out.
53
Design of Reinforced Concrete Elements
With reference to Fig 4.12, design and detail the stair enclosed by gridlines F− G and 7−8. Use steel grade
250 and concrete C30. Rise = 250mm, waist = 150mm
SOLUTION
The proportioning of the stair is shown in Fig 4.11.
Note: The 1st flight spans between the ground beam and the beam on gridline 8
The 3rd flight spans between the beam on gridline 8 and the landing at the first floor level.
The 2nd flight spans between the beams on gridline line F and G
The landing is designed as part of the flight. The load of the landing is assumed be divided equally
between the intersecting flights. (E.g. the 1st and 2nd flight will share the load of the first landing)
F G
200
7
7
1100
Up 1500
Down
8 8
4 Equal treads @
300 = 1200mm
Fig 4.11
3600
F G
54
Design of Reinforced Concrete Elements
Flight: From example 1, the ultimate design load for flight, = 12.06kN/
Landing:
Dead load
Effective span, L = 2.1 + landing width + beam width = 2.1 + 1.1 + 0.5 (0.2) = 3.3m
NB: The flight spans between the centres of the ground beam and the beam on gridline 8
=12.06kN/
= 2.85kN/ Half of the landing load is
applied on the span.
2.1m 1.2m (I.e. x 5.69 = 2.85kN/ )
Fig 4.12a
=12.06kN/
= 2.85kN/
55
x
= 19.9kN = 8.85kN
Design of Reinforced Concrete Elements
Maximum deflection occurs at a distance say x from RGB where shear force is equal to zero. By inspection
x= = 1.65m. ……………………… You can draw the Shear force diagram to confirm the answer.
Alternatively, we can also assume the load of the flight to be distributed on the whole span so that the
maximum moment,
M= = = 16.42kNm. Since the two approaches give almost the same result, you can
adopt the second approach for the sake of time though the first approach is more accurate.
(c)Area of steel
Assuming 12mm diameter bars and 25mm cover, effective depth d = 150 – (0.5x12 + 25) = 119mm. By
inspection the lever arm will be more than 0.95d.
Distribution bars: Provide minimum area of steel. That is, R10 bars at 200mm
Effective span, L = beam width + 1.1 + 2.1 + (landing width) = (0.2) + 3.3 + (1.5) = 4.15m
NB: It spans between the centre of the beam on gridline 7 and the first floor. Assuming the load of the
flight is distributed on the whole span,
56
Design of Reinforced Concrete Elements
Provide R16 bars at 175mm ( = 1149 /m) as main bars and R10 bars at 200mm
Effective span, L = 3.6m (It spans between the centres of the beams on gridline F and G.
=12.06kN/
= 2.85kN/ = 2.85kN/
= 10.66kN = 10.66kN
Fig 4.13
The other half of the landing load is applied on the 2nd flight.
M = 10.66 (1.8) – (2.85 x 1.2) (0.6 + x 1.2) – (12.06 x 0.6) ( x 0.6) = 12.91kNm
Provide R12 bars at 200mm ( = 565 /m) as main bars and R10 bars at 200mm
57
Design of Reinforced Concrete Elements
(c) Detailing
Fig 4.14a
58
Design of Reinforced Concrete Elements
Fig 4.14b
Fig 4.14c
59
Design of Reinforced Concrete Elements
Fig 4.14d
6 4
Landing/
Floor
1900 300 mm concrete wall
800 1st
Landing
B B
9 Equal treads @
300 = 2700
6 4
Solution Fig 4. 15 a
This is an example of traverse design where each is designed in isolation. The main reinforcement for
each step which should be at least 2No of bars is placed at the top of the tread. Light mesh is provided at
the waist to serve as temperature reinforcement. The mains bars must be continued into the wall at least a
60
Design of Reinforced Concrete Elements
distance not less than the clear span of the step. The 1st landing is supported by a beam which cantilevers
from the spine wall.
Dead load
ii. Waist : (Rise x tread x Conc. Density = (0.15 x 0.3) x 24kN/ = 0.54kN/m
Imposed load:
Characteristic imposed load, = Imposed load constant x Tread = 1.5 kN/ x 0.3m = 0.45kN/m
Fig 4.15b
The step is designed as a rectangular beam with width b the going (i.e. 300mm) and Depth, D equal to the
waist (125mm). Using 12mm diameter bar and 25mm cover,
61
Design of Reinforced Concrete Elements
Provide 2−R12 bars ( = 226 ) as main bars and R10 bars at 175mm
( = 449 /m) as distribution bars at the top of the step. Moreover, provide mesh reinforcement
Step 4: Detailing
(a)
(b)
62
Design of Reinforced Concrete Elements
Fig 4.16
CHAPTER FIVE
BEAMS
5.1. Introduction
Beams form integral part of the structural framework of a building. Beams can be classified as either
flanged beam or rectangular beam. Flanged beams are those beams which are cast monolithically with the
floor or roof slab. The slab becomes the flange and the beam forms the web. Flange beam may have the
shape of Tee and hence refer to as T − beam or Lee which is also called L− beam.
Roof beams and lintels come under the category of rectangular beams. These beams are isolated from
slab. Beams are either simply supported or continuous over several supports.
Fig 5.1
63
Design of Reinforced Concrete Elements
64
Design of Reinforced Concrete Elements
Effective span = its length to the face of the support + half its effective depth = 1.8 + (0.24) = 1.92m
Fig 5.3b: Cantilever beam which forms the end of a continuous beam
Effective span = the length to the centre of the support = 1.9m.
65
Design of Reinforced Concrete Elements
Fig 5.5a illustrates the distribution of slab load among the supporting beams. An angle of is drawn at
all the corners of the panels. The area of slab load supported by each beam is determined from it.
A D E
1.9m
2.2m
4.4m
1.9m
0.8m
1.9m 2.2m 2.2m
B C F
3.8m 5.2m
Fig 5.5 a
Beam
4.4m
0.6m
D
1.9m 2.2m Fig 5.5 b
ABCD and CDEF are the panels (slabs) with the supporting beams at the edges. The following statements
are true:
(a) When the angle is drawn,
the corners at the short span meet first. If you take panel ABCD for instance, the angles drawn at A
and D will intersect whereas those of B and C also meet. A line is then drawn to link the two points.
(b) The closer corners intersect
at half of the short span. The angle at A and D intersect an x 3.8 = 1.9m.
66
Design of Reinforced Concrete Elements
(1.4 + 1.6 )
Fig 5.6a: All spans loaded with the maximum ultimate design load
Fig 5.6b: Alternate spans loaded with the maximum ultimate design load
As mentioned earlier on, the analysis of the moment and shear force in beams can be carried out using
any of the methods of structural analysis discussed in BT 353. These moments give more accurate values
of moment and shear at the various sections. However, as an alternative, the empirical formulas in Table
3.5 of the Code can be used to determine approximate values for moment and shear. Such a beam should
satisfy the following provisions:
(a) The characteristic imposed load may not exceed characteristic dead load ;
(b) The loads should be substantially uniformly distributed over three or more spans;
67
Design of Reinforced Concrete Elements
Interior spans
End span End span
A B C D E F
Fig 5.7: Moment and shear for continuous beams (Table 3.5 of BS8110 −1:1997)
Table 5.1 (Table 3.5 of BS 8110 −1: Ultimate bending moment and Shear forces for beams)
At outer Near middle of At first interior At middle of At interior
support end span support interior spans supports
Moment 0 0.09FL − 0.11FL 0.07FL − 0.08FL
Shear 0.45F — 0.6F — 0.55F
Steps:
(a) Calculate the design shear stress v = , where V = the Shear force at the section under
consideration. Check to ensure that v does not exceed the limit of 0.8 or 5 N/ , whichever is
the lesser,
(b) Calculate the Concrete shear stress ( ) from Table 3.8 of the Code. Alternatively you can use the
(c) Compare v to and decide on the form and area of the links from Table 3.7 of the code.
68
Design of Reinforced Concrete Elements
The design procedure is the same as the one discussed for slabs. However, for T− beam and L− beam the
ratio in Table 5.2 should be used in calculating the initial depth. Refer to Table 3.9 of the Code for more
details.
Example: With reference to Fig 3.11 (i.e. the drawing used for the slab design) design and detail the
continuous beam on gridline 2. Use steel grade 250 and concrete grade C35.
Solution
The beam is an interior beam (or T− beam) support by 5 columns located at gridlines A, B, C, D and E as
shown below.
A B C D E
Slab (flange)
150mm
= 0.7 x Effective span = 0.7 x 5.2 = 3.64m. The effective span is taken to be the longest center to
center dimension of the beam (Fig 5.8a). Moreover, we shall assumed the width of the web, = 225mm.
» Effective flange width, = + = 225 + = 953mm. This means that almost a metre of the
slab (i.e.0.953m) acts together with the web to form the T − beam.
The ratio = = 0.24 < 0.3. Therefore from Table 5.2 the ratio is 20.8
Overall depth, D ≥ d + (bar size) + Links + Cover. Assume bar size = 20mm, links = 8mm and a cover
of 25mm.
= 953
.
150
d D = 450
300
= 225
Fig 5.9
70
Design of Reinforced Concrete Elements
D ≥ 250 + (20) + 8 + 25 = 293mm. Unlike slab, the resistance to deflection offered by the reinforcement
is not so significant to rely on. In view of this, the overall depth of the section obtained above should
always be increased. Select D = 450mm (see Fig 5.9)
First pick the longest span (in this case between gridlines A&B) and calculate the area of load on it as
shown in Fig 5.10. Draw at all the corners. You do not necessarily have to draw the panels to scale
but remember that always the corners at the short span will intersect first. They will intersect at the
midspan of the short span.
From Fig 5.10b, total area of slab load on beam = [ x 2.2 (0.8 + 5.2)] + [ x 2.4 (0.4 + 5.2)] = 13.32
A
2.2m 2.4m
2.2m 2.4m
B
4.4m 4.8m
Fig 5.10 a
2
Beam
5.2m
0.8m 0.4m
71
Design of Reinforced Concrete Elements
Dead load
1. Slab: From the slab design, the dead load of slab including finishes = 6.34kN/
Thus, the total load on the 5.2m span beam is 275.282kN. Using the empirical formulas in Table 3.5 of
the Code, approximate values for bending moment and shear force at the critical sections can be
determined. On the other hand, if one desires to carry on the design as accurate as possible, then the total
load should be converted to distributed load and spread on the entire span as shown in Fig 5.11. After
this, Moment distribution method or Slope deflection equation can be used to analyze the beam.
W= 52.94kN/m
A B C D E
Fig 5.11
Table 5.4
Moment Shear
(kNm) (kN)
At outer 0 0.45F = 0.45 x 275.28 = 123.88
Support (A & E)
72
Design of Reinforced Concrete Elements
The depth of beam required to take the maximum moment (157.46kNm) is given by
= = = 386.70mm
We require 429.7mm depth of beam to take the maximum moment; however at the initial stage, we
selected 450mm which is more than the required. This implies that the initial depth of 450mm is
satisfactory.
Effective depth, d = D – (Cover + bar size + link) = 450 – {25 + (20) + 8} = 407mm
K= = = 0.115
73
Design of Reinforced Concrete Elements
Since K < (0.115 < 0.156), there is no need to put reinforcement at the compression side of the section
Provide 5R20 bars ( = 1571 ) at the bottom of the beam and 2R20 bar at the top for the purpose
2R20
150
407
D = 450
Fig 5.12a
5R20
= 225
K= = = 0.141
Since K < (0.141 < 0.156), there is no need to put reinforcement at the compression side of the section
74
Design of Reinforced Concrete Elements
Provide 5R25 bars ( = 2454 ) at the top of the beam and 2R20 bar at the bottom for tying the
links.
5R25
150
407 D = 450
Fig 5.12b
2R20
= 225
K= = = 0.065
Since K < (0.065 < 0.156), there is no need to put reinforcement at the compression side of the section
Provide 3R20 bars ( = 942 ) at the bottom of the beam and 2R20 bar at the top for tying the
links. 2R20
150
407
D = 450
Fig 5.12c
3R20
75
Design of Reinforced Concrete Elements
K= = = 0.083
Since K < (0.083 < 0.156), there is no need to put reinforcement at the compression side of the section
Provide 4R20 bars ( = 1257 ) at the top of the beam and 2R20 bar at the bottom
4R20
150
407 D = 450
Fig 5.12d
2R20
= 225
Step 7: Checks
Where V = the Shear force at the section under consideration. We shall use the maximum shear force
from Table 5.4 (i.e. 165.168kN)
76
Design of Reinforced Concrete Elements
v= = = 1.80
Since the design shear, (1.80 ) is less than the allowable shear (4.38 N/ ) the depth of the
beam is ok.
= 0.79 x x x
(0.56 + 0.4) < 1.8 < 4.38. We shall provide links only and the spacing of the links is given by the
formula
Where = the total area of the two legs of the link. Using 10mm links,
It is always a good practice to select the diameter of the links and use the formula above to determine the
spacing.
≤ = = 134mm
77
Design of Reinforced Concrete Elements
Provide R 10 bars at 125 spacing around the first interior support and 200 centres at all the sections.
(b) Deflection
We shall check deflection at near middle of the end span where the span is longest.
= 0.55 + ( ) = 0.98
Since the actual deflection (12.78) is less than the allowable deflection (20.38), deflection is satisfactory.
Step 8 Detailing
78
Design of Reinforced Concrete Elements
Fig 5.13
CHAPTER SIX
COLUMNS
6.1. Introduction
Columns are vertical members which carry axial compressive load and sometimes bending moment one
or both axis. In this chapter, we will focus our studies on the design of reinforced concrete columns.
Columns can be classified based on their resistance to lateral loads as braced and unbraced columns. In
concrete framed building, the beams and columns may be designed to act together as a rigid frame in
transmitting the lateral forces down to the foundations. In such instance the columns are said to be
unbraced and must be designed to carry both the vertical (compressive) and lateral (bending) loads.
On the other hand, the lateral loads may be transferred through the roof and floors to a system of bracing
or shear walls, designed to transmit the loads to the foundations. In such a case the columns are said to be
braced and hence designed to carry only vertical loads.
BS 8110−1 further classify braced columns based on the ratio of their effective height to their lateral
dimensions as either Short or Slender column. Where neither of the ratios is more than 15, the column is
classified as short. It should otherwise be considered as slender.
The effective height about any axis is influenced by the degree of fixity at the end of the column. For
braced columns, the effective height is obtained by multiplying the clear height between the end restraints
( ) by an end condition factor from Table 3.21 of BS 8110 – 1 reproduced here as Table 6.1
Table 6.1 Values of for braced columns (Table 3.21 of BS 8110 – 1: 1997)
End Condition at
top End Condition at bottom
1 2 3
80
Design of Reinforced Concrete Elements
End condition
6.3 Bending Moment 2 Force in Columns
and Axial
The bending moment at the top and bottom of a column is calculated by considering a singly – storey
Subframe shown in Fig 6.2. The Subframe is loaded to give the maximum unbalanced moment at the top
and bottom of the column considered. To achieve this, the maximum load (1.4 + 1.6 ) be placed on
the beam – for column subframes at the corner of a building.
In the case of interior columns, the maximum load (1.4 + 1.6 ) should be placed on the longer of the
two spans and the other span loaded with the minimum load, 1.0
(a) Subframe for corner column at (c) Subframe for interior column at roof level
roof level.
81
Moment at foot
of upper column
= [ ] ………………… Corner column Fig 6.2 b
Moment at head
of lower column
= [ ] ………………… Corner column Fig 6.2 b
Where,
82
Design of Reinforced Concrete Elements
& = the stiffness of the beams on either side of the joint. The stiffness is halved.
= = the fixed end moment of the beam assuming both ends as fixed and w = 1.4 + 1.6
∆ = the difference in Fixed end moment for the beams on either side of an internal column
= − ; where = 1.4 + 1.6 (load on long span beam) and = 1.0 (load on short
span beam)
The design moment in a column either direction should not be less than N , where N is the design
ultimate axial load and is a minimum eccentricity equal to 0.05 times the overall Column depth in
the plane of bending, but not more than 20mm (section 3.8.2.4 of BS 8110 − 1: 1997)
The axial force in columns is calculated using any of the following two methods.
4.6m 4.8m
2.3m 2.4m
6m
3m
Column
2.5m
5m
From Fig 6.3, area of load on column = (2.3 +2 .4) x (3 + 2.5) = 25.85
83
Design of Reinforced Concrete Elements
In practice, it is unlikely that all the floors of a given structure will carry the ultimate load all times. This
means that when a single column carries several floors or when a large area floor is carried by a single
beam, BS 6399 −1 recommends a reduction to the total imposed loads on the floor (Table 6. 2)
For design purpose short columns are divided into four categories:
(a) Short braced columns carrying axial load only (moment is insignificant). Example is column B2
(Fig 6.4).The spans of the beams on opposite sides of the column are equal. The area of steel for such
a column is calculated from the following equation:
Where,
= the net cross sectional area of concrete in a column (excluding area of reinforcement)
5m
A2 B2 C2
2 84
5m
Design of Reinforced Concrete Elements
For columns in this category, the span of beams on adjacent sides of the column must not differ by more
than 15% of the longer span (see column C2 in Fig 6.4). Taking column C2, the difference in span
between the beams on gridline 2 (i.e. 5.2 − 4.5 = 0.7m) does not exceed 15 percent of the longer span (i.e.
15% x5.2 = 0.78m). The axial loading capacity obtained for axially loaded columns in equation 1 is
reduced to cater for the small moment that will be induced in this second category of columns. This gives
the axial load capacity as
(c) Short braced columns carrying axial load plus bending about one axis (uniaxial bending).
Where the beams spans on one gridline differ by more than 15 per cent of the longer, such a column
should be designed to carry vertical load in addition to bending moment about on axis. Examples include
column A2 and C3. Taking column C3, there will be bending of the column about gridline C since the
difference in the span of the beam (i.e. 6.2 − 5 = 1.2m) is more than 15 per cent of the longer span (i.e.
15% x 6.2 = 0.93m). For this group of columns, we design them using column design charts.
(d) Short braced columns carrying axial load plus bending about both axis (biaxial bending).
85
Design of Reinforced Concrete Elements
This often occurs in columns at the corner of buildings. Examples include column C4, E4, D3, E2 etc.
Taking column C4 for instance, it will bend about gridline C as well as 4. Column D3 will also bend
about gridline D since the difference in the beams span (i.e. 6.2 − 5= 1.2m) is more than 15 per cent of
the longer span (i.e. 15% x 6.2 = 0.93m). Similarly on gridline 3, the difference in span
(i.e. 5.2 – 3.2 = 2m) is more than 15 per cent of the longer span (i.e. 15% x 5.2 = 0.78m); therefore there
will be bending about gridline 3.
These columns are designed by increasing the moment about one axis as follows.
When ≥ , increase the moment about the x – x axis. The design moment becomes
= + ……………………… (4)
However, when < , increase the moment about the y – y axis. The design moment becomes
= + ……………………… (5)
h x x
Where,
86
Design of Reinforced Concrete Elements
After you have determined the increased moment about one of the axes of the column, the section can
then be designed to take up the vertical load (N) and the bending moment (M) using column design
charts.
Part 3 of BS 8110 presents design chart for symmetrically reinforced columns subject to vertical loads
and bending moment. There is a separate chart for each grade of concrete combined with high yield
reinforcement and individual ratios. The area of reinforcement can be found from the appropriate
chart using the and ratios for the column section being designed. See appendix A for
copies of these design charts.
To do this calculate the effective height and use it to calculate the slenderness ratio in both axes.
This stage is applicable only to columns subjected to axial load plus uniaxial or biaxial bending.
For columns subjected to axial load only, use equation 1. Equation 2 should be used for columns
supporting approximately symmetrical arrangement of beams. Design charts should however be used to
design columns subject to bending about one or both axis.
87
Design of Reinforced Concrete Elements
5. Detailing
Detail the column and show the arrangement of the links and the main bars.
Example 1: Fig 6.5 shows the plan and section of a proposed two storey residential building; using the
information given, design and detail column B2 from foundation to roof. Concrete grade: C30 and steel
grade: 250.
5m
A2 B2 C2
2
5m
C3 D3
3
X
6.2m
C4 E4
4
A B C D E
Design data:
Column size: 225 x 225mm Cross section area = 0.225 x 0.225 = 0.05
Solution
89
Design of Reinforced Concrete Elements
= 0.75 (End conditions: top = 1, bottom = 1). That is, at the top of the column, the depth of the roof
beam (350mm) is greater than the dimension of the column (225mm); hence end condition 1 applies.
Similarly, at the bottom of the column, the depth of the floor beam (i.e. 450mm) is greater that of the
column. In this case condition 1 also applies at the bottom. From table 3.21 of the code, = 0.75.
Clear distance between foundation and soffit of beam, = (3 + 0.1 +0.6) – 0.3 = 3.4m
= 0.90 (End conditions: top = 1, bottom = 3). NB: The column footing only provides nominal restraint
to the column; hence condition 3 applies at the bottom.
4.5m 4.5m
2.25m 2.25m
5m
Column B2 2.5m
2.5m
5m
90
Design of Reinforced Concrete Elements
Dead load
Imposed load
91
Design of Reinforced Concrete Elements
Looking at the arrangement of the beams, the column will carry only axial load (bending moment is
insignificant).
The axial load capacity of an axially loaded column from equation 1 is given by
= ………………….. (ii) Using this equation, the area of steel required ( ) and
The area of steel required, for each column is negative. This implies that theoretically steel
reinforcement is not required to carry the axial load. However, practically we have to provide minimum
reinforcement. Moreover, in rectangular columns there should be at least 4 number of bars.
92
Design of Reinforced Concrete Elements
Minimum area of steel, = 0.4% b h = 0.4% x (225 x 225) = 202.5 . Hence from the steel chart
select 4 number of bar of any diameter of your choice such that the total area is slightly more than
202.5 .
Links: Spacing = 12 x bar size = 12 x 16 = 192mm. Therefore provide R8 bars as links at 200mm
spacing.
Step 5: Detailing
Example 2: With reference to Fig 6.6, design and detail column A2. Use the design data for example 1.
From example 1
it was shown that
all the columns
are short.
Step 2: Axial
load (N) 4.5m
estimation
2.25m
Column A2
93
Design of Reinforced Concrete Elements
Dead load
94
Design of Reinforced Concrete Elements
Imposed load
95
Design of Reinforced Concrete Elements
Dead load
Ultimate design load, w = 1.4 + 1.6 = 1.4 (2.69) + 1.6 (1.5) = 6.17kN/m
Area of load on 4.5m beam = 10.125 (Refer to section 5.4 on how to determine area of load on a
beam)
Dead load
Ultimate design load, w = 1.4 + 1.6 = 1.4 (18.29) + 1.6 (7.88) = 38.21kN/m
96
Design of Reinforced Concrete Elements
Stiffness, K = = = 75 x
Stiffness, K = = = 63 x
Roof beam
I= = = 804 x K= = = 179 x
Floor beam
I= = = 1709 x K= = = 380 x
Moment in column
6.17kN/m
Moment at top
= [ ] B
= 179
C
of column
2.85m
= 75
Fixed end moment at B is given by
A
4.5m
= = = = 10.41kNm
Fig 6.10a. Subframe: Roof junction
Comment: we always use only half of the beam stiffness. Moreover, the formula above was derived using
the method of Moment Distribution we studied last semester in BT 353: Elementary Theory of Structures.
C
= = = = 64.48kNm = 75
38.21kN/m 2.85m
B D
= 380 97
3.4m
= 63
A
Design of Reinforced Concrete Elements
Moment at bottom
= [ ]
of upper column
= 64.48 x
= 14.74kNm
N is the axial load for the foundation to 1st floor column (the maximum value). See Table 6.5
Since 3.2kNm is smaller than any of the moments, the column design will be governed by the moments
obtained from the frame analysis. Thus we shall use 14.74kNm for 1st floor to roof column and
12.38kNm for foundation to 1st floor column.
98
Design of Reinforced Concrete Elements
Column Location
(N/ ) (N/ ) ( )
1st flr to roof 0.04 4R16 bars
(804 )
Fdn to 1st floor 4R16 bars
(804 )
Step 5: Detailing
CHAPTER SEVEN
FOUNDATIONS
99
Design of Reinforced Concrete Elements
7.1 Introduction
Foundation is the final destination of the loads from the roof, beams, slabs, walls and columns. There are
two types of foundations: Artificial foundation and natural foundation. The natural foundation refers to
the surrounding soil or earth upon which the structure is being built. The artificial foundation is
constructed to distribute the load of the structure evenly unto the natural foundation (Fig 7.1). Our studies
will focus on the design of artificial foundation.
Column or wall
Artificial foundation
Fig 7.1a
Distribution of load unto the natural foundation
100
Design of Reinforced Concrete Elements
This is one of the most common types of foundation for framed structures where a pad or footing (square,
rectangular, and trapezoidal etc) is constructed to support either a single column or several columns.
Isolated footing supports only one column, combined pad supports two footing and strip footing supports
several columns. Each and their method of design are described below.
This is the most common type of pad foundation. The pad is constructed to transmit the column load
evenly to the soil. The thickness of the footing is influence by the allowable bearing capacity of the soil.
The bearing capacity of a soil is the maximum amount of load it can sustain per square meter without
failure from soil test. Table 7.1 shows value for some soils.
Below is the procedure for the analysis and design of isolated pad foundation.
1. Determine the size of the pad on plan using the safe bearing capacity of the soil and the loading at
the serviceability limit state
2. Calculate the bearing pressure at the base of the footing using the ultimate design load
3. Moment analysis and Area of steel to resist the moment
4. Check for Punching shear
5. Check for shear at some critical sections
6. Detailing
Example 1: Design a suitable isolated pad foundation to safely transfer from a 300 x 300mm square
column with characteristic dead load, = 720kN and imposed load = 300kN. The allowable bearing
capacity of the soil is 200kN/m2. Use concrete grade C30 and steel grade 250.
101
Design of Reinforced Concrete Elements
Solution
The dead load given above excludes the self weight of the footing so an allowance has to be made for it.
Let us assume this to be 80kN.
A=
Column
= = 5.5
Pad Fig 7.1b
Using a square pad, the length
2.5m
If we assume the pad to be 500mm thick, its self weight = (2.5x 2.5 x 0.5) x 24kN/ = 75kN. Since
this value is less than the 80kN assumed in step 1, we may either continue to use it or use the actual value.
Note: Some designers neglect the effect of the self weight of the footing in calculating the bearing
pressure.
102
Design of Reinforced Concrete Elements
F = 1600kN
W= 256kN/
(a) Bearing pressure
1.1m
Fig 7.2
0.3m
1.1m
2.5m
W= 256kN/ x 1m = 256kN/m
(c)
The loading is treated as a cantilever with the maximum moment occurring at the column face.
Moreover, since both the column and the pad are square, the cantilever on both sides of the
footing will be the same
From the cantilever in Fig 7.2c, the maximum moment at the column face is given by
M= = = 154.88kNm
Area of steel
103
Design of Reinforced Concrete Elements
Experiments have shown that in pad foundations, the weight of the column has a tendency of punching a
hole through the footing. The weight of the column develops some stresses referred to as punching shear
around a certain perimeter of the footing. This perimeter is referred to as punching shear or critical
perimeter and it is measured on an imaginary line 1.5d away from the column faces (Fig 7.4).
1.5d
1.5d
Critical perimeter
104
1.5d 1.5d
1.5d
0.3m
Design of Reinforced Concrete Elements
= 12(434) + 1200
= 6400mm
= 0.79 x x x
Now, since the resistance of concrete to shear ( = 0.47N/ ) is greater than the punching shear stress
(0.34N/ ) there will be no punching shear in the footing and the thickness of the footing is ok. NB: If
the punching shear exceeds the concrete shear stress, you have to increase the depth of the pad and also
revise the calculation for the area of steel.
The critical section for shear is taken to be 1.0d from the column face. At this point
105
Design of Reinforced Concrete Elements
V = 426.24kN
2.5m
Shear stress, v =
0.666 0.434
=
Since the shear (v) is also less than the concrete ( ) the section is adequate in terms of shear.
Step 6: Detailing
BENDING SCHEDULE
1 16 21 2700 150
2400
2 16 21 2700 150
2400
106
Design of Reinforced Concrete Elements
Fig 7.7
107
between the two columns so that the base is designed as an inverted T– beam. The footing should be
neither too long nor too short.
Example 2: With reference to Fig 7.9 Design and Detail a suitable combine pad foundation to distribute
the loads from columns D3 and D4. The characteristic loads from each column are as follows: Column
108
Design of Reinforced Concrete Elements
The safe bearing capacity of the soil is 200kN/ . Use steel grade 460 and concrete grade C30.
B C D E
6000 4200 4200
1 1
2500
2 5100
3
2100
4
4500
5
5200
4500
7
8400 8400
A B C D E
Solution
109
Design of Reinforced Concrete Elements
Total dead load = 160 + 350 + 400 = 910kN and = 180 + 190 = 370kN
600
Fig 7.10
2200
1100
D3 = 530kN R D4 = 590kN
x 110
Fig 7.11a
Design of Reinforced Concrete Elements
R x = 590(2.1) + (530) (0), where R is the resultant column load = 530 + 590 = 1120kN
3.10m
NB: The extent of the base from the centroid must be equal to avoid loading eccentricity.
NB: This time the self weight of the footing is ignored in calculating the bearing pressure
Elastic curve
Design of Reinforced Concrete Elements
NB: Always multiply the bearing pressure by the width of the footing to convert it to kN/m.
The loading is treated as a cantilever with the maximum bending moment occurring at the column face.
Taking one meter of the width (Fig 7.12b), the load w = 240.76 kN/ x 1m = 240.76kN/m
W = 240.76kN/m
Fig 7.12a
0.95m
1m
Loading 0.95m
1.10m
112
From the cantilever in Fig 7.12a, the maximum moment at the column face is given by
M = 51kNm (sagging). Note: the 51kNm is the moment at the centre of the column (Fig 7.11c). The
actual moment will be slightly smaller than this value, hence for safety reasons, the 51kNm is used for the
design.
The minimum area of steel in slab for steel grade 460 is given by
113
Design of Reinforced Concrete Elements
Hence from the steel chart, provide Y16 bars at 250mm ( =804 /m) at the bottom of the
footing.
M = 83kNm (sagging). By inspection the lever arm will be more than 0.95d, hence per the code’s
specification
Z = 0.95d = 507.3mm
= = = 374.40 /m
Provide Y16 bars at 250mm ( = 804 /m) at the bottom of the footing.
= = = 1032.97 /m
Provide Y16 bars at 175mm ( = 1149 /m) at the top of the footing
M = 108.64kNm Z = 507.3mm
= = = 490.05 /m
Provide Y12 bars at 125mm ( = 905 /m) as distribution bars top and bottom
Step 6: Detailing
114
Design of Reinforced Concrete Elements
Fig 7.13
115
Design of Reinforced Concrete Elements
Exercise
1. Design a rectangular base to support two columns carrying the following loads:
Column 1: Dead load 350 kN, imposed load 160 kN
Column 2: Dead load 480 kN, imposed load 220 kN
The columns are each 350 mm square and are spaced at 2.5 m centres. The width of the base is
not to exceed 2.0 m. The safe bearing pressure on the ground is 180 kN/ . Use concrete grade
C30 and steel grade 460
2. Design a suitable pad foundation to support a 225mm square column with = 450kN and
= 185kN. The surrounding soil is loose sand and gravel with safe bearing capacity of 150 kN/ .
Use concrete grade C30 and steel grade 250
116
Design of Reinforced Concrete Elements
CHAPTER EIGHT
RETAINING WALLS
8.1. Introduction
Retaining walls are structures used to retain earth which would not be able to stand vertically
unsupported. The weight of the soil exerts pressure on the wall and hence tries to destabilize it.
Retaining walls are usually used at bridge sites, riverbank areas, sloppy terrains and basement
areas within the house. They are constructed of masonry, mass or reinforced concrete.
Concrete retaining walls can be categories into three groups: (1) Gravity (2) Cantilever and (3)
counterfort retaining walls. Within each group they may be variant forms. Moreover, though the structural
action of each type is fundamentally different, the techniques used in their analysis, design and detailing
are those used for concrete structures
(a) Gravity retaining walls: These types of retaining walls depend on their weight to achieve stability. It
uses its dead weight alone to resist sliding and overturning. They are usually constructed of mass
concrete, with reinforcement included in the faces to restrict thermal and shrinkage cracking.
Moreover, because of their size, they are economical up to a height of 3.0m.
(b) Cantilever retaining walls: the walls are designed as vertical cantilevers spanning from a large rigid
base. Stability is provided by the weight of structure and the weight of backfill on an inner base or the
weight of the structure only when the base is constructed externally. Cantilever retaining walls are
economical in the use of materials and can be up to 7.5m high.
(c) Counterfort retaining walls: In this type, the slab is supported on three sides by the base and
counterfort or buttress walls. They are used where the overall height of the wall is too large to be
constructed economically either in mass concrete or as a cantilever. The basis of design of counterfort
walls is that the earth pressures act on a thin wall which spans horizontally between the counterforts.
The wall must be large enough to provide the necessary dead load to meet the requirements for
stability. The weight of the backfill on the base can also be relied on for stability. The counterforts
are designed as cantilevers to resists any moment at those points. The counterforts are spaced in such
a way that there will be satisfactory span−depth ratio for the wall which is designed as a continuous
slab.
117
Design of Reinforced Concrete Elements
Fig. 8.1 (a) Gravity wall; (b) cantilever walls; (c) buttress wall; (d) counterfort wall.
(a) Active soil pressure ( ) = this is the pressure of the earth acting at the back of the retaining wall.
This pressure is zero at the top of the wall and increases (in the shape of a triangle) to its maximum
at the depth of the wall. It is calculated using the formula
= angle of internal shearing resistance of the soil (or the angle of repose)
118
Design of Reinforced Concrete Elements
(b) Passive soil pressure ( ) = this is the pressure which offers passive resistance to the retaining wall.
h = the depth of soil of the soil on the wall offering the passive resistance
(c) Hydraulic pressure = this is the pressure created as a result of the water retained at back of the wall.
To reduce this pressure, weep holes are provided in the walls to drain the water.
(d) Surcharge pressure = this is the pressure due to weight of permanent load behind the wall. This
pressure is uniform (i.e. rectangular) at the back of the wall.
Fig 8.2
119
Design of Reinforced Concrete Elements
The forces acting can be grouped into two: (a) Horizontal forces resulting from the active soil pressure,
hydraulic pressure and surcharge. Their effect is to destabilize the retaining wall (b) Vertical forces: these
forces resist the action of the horizontal forces and hence ensure or restore stability. The weight of the
wall and any soil on it constitutes the vertical forces. The design should ensure that the following
conditions do not occur.
1. Overturning of wall: This usually occurs at the heel (i.e. point B) of the wall (Fig 8.3a). To ensure
stability, the total stabilizing moment ( ) should be at least 2 times the overturning moment
∑ = 2∑ ……………………. (2)
A B B
A
Fig 8.3a: Overturning Fig 8.3b: Sliding
Wμ = 1.6P …………… (3) Where W= total vertical force; μ = tan ϕ = the coefficient of
friction between the base of the wall and the soil; P = total horizontal force (excluding that due to passive
soil pressure). The 1.6 is a factor of safety. A nib can be added, as shown in Fig 8.4 to increase the
resistance to sliding through passive earth pressure.
3. Settlement. The maximum earth pressure occurring at the base of the wall must not exceed the
permissible bearing capacity of the soil.
Maximum pressure, = +
Where, M = the net moment about the centre−line of the base and D = the breadth of the base
120
Design of Reinforced Concrete Elements
4. Tension occurring in the masonry. This requirement applies to gravity retaining walls where there is
no reinforcement.
8.5. Design Procedure
1. Assume a breadth for the base and a thickness for the wall. About 75% of the wall height can
be used as the breadth of the base. To increase resistance to sliding a nib is introduced
2. Calculate the horizontal pressure of earth and check the stability of the wall against Sliding,
Overturning and Settlement
3. Design the reinforced concrete. At this point a partial factor of safety of 1.4 is applied to the wall and
the earth pressures including surcharge if present. The design consists of the following
(a) The wall, calculate shear forces and moments caused by the horizontal earth pressure. Design the
vertical moment steel for the inner face and check the shear stresses. Provide minimum secondary
steel in the horizontal direction for the inner face (where the soil is) and both vertically and
horizontally for the outer face.
(b) Inner footing (Heel): The net moment due to earth pressure on the top and bottom faces of the
inner footing causes tension in the top and reinforcement is designed for this position.
(c) Outer footing (Toe): The moment due to earth pressure causes tension in the bottom face of the
outer footing.
Fig 8.4
121
Design of Reinforced Concrete Elements
Example: The cantilever retaining wall shown in figure 8.5 is 15m long and supports a granular material
of saturated density, γ = 19kN/ and the allowable bearing pressure is 110 kN/ .There is also a
surcharge of 12kN/ . Check the stability of the wall and design the bending reinforcement using high
yield steel, = 460N/ and concrete grade C30. Take ϕ =
Fig 8.5
122
Design of Reinforced Concrete Elements
Solution
Earth pressure:
Vertical forces:
Total, W = 194.44 kN ―
123
Design of Reinforced Concrete Elements
= 13.12kN
= 42.08kN
2.03m
1.35m
Fig 8.6
Checks:
(a) Resistance to Sliding: The forces resisting sliding are the friction under the base (Wμ ) and the
passive resistance for a depth of earth of 550 mm to the top of the base ( ).
Passive resistance, = x 0.55m x 38.7kN/ = 10.64kN per meter. Now for stability against sliding,
124
Design of Reinforced Concrete Elements
Take moment of all the forces about the toe (i.e. point A, Fig 8.6)
Total = 83.40kNm
NB: the contribution of the passive soil pressure ( ) was not taken into account.
Since 324.07kNm > 166.8kNm, overturning of the wall will not occur.
Where, M = the net moment about the centre−line of the base and D = the breadth of the base
Taking moment about the centre−line of the base (i.e. point B, Fig 8.6)
Clockwise moment:
125
Design of Reinforced Concrete Elements
Anticlockwise moment
Total = 88.10kNm
Now, since the maximum pressure is less than the permissible bearing pressure (i.e. 110kN/ ) the
design is satisfactory.
3.24kN/
E
20.78kN/
Step 3: Design of Reinforced Concrete
(a) Wall
The wall is treated as a vertical cantilever with the maximum moment at the base. The load at the ultimate
limit state is used; hence a factor of 1.4 is applied to all dead loads. Therefore
126
Design of Reinforced Concrete Elements
Active pressure at base = 1.4 x 20.78 = 29.09kN/ Surcharge = 1.4 x 3.24kN/ = 4.54 kN/
Overall depth of wall, D = 300mm. Using 16mm bars and 50mm cover,
= = = 1204.09 /m
Provide Y16 bars at 150mm ( = 1340 /m) at the inner face of the wall as main bars
Distribution bars:
Provide Y10 bars at 150mm ( = 524 /m) horizontally as distribution bars for the inner
face. For the outer face, provide 10 mm diameter bars at 150 mm centres each way to control
cracking.
Take moment about the centre −line of the wall for the vertical loads on the heel and the bearing pressures
The vertical load in this case will comprise of the soil on the heel and the self weight of the heel (Fig.8.8).
These forces act clockwise (+ve) about the centre of the wall. The bearing pressure which for
convenience sake has been divided into a rectangle and triangle. The pressure acts anticlockwise about the
centre of the wall.
127
Design of Reinforced Concrete Elements
Fig 8.8
= = = 1026.42 /m
128
Design of Reinforced Concrete Elements
Provide Y16 bars at 175mm ( = 1149 /m) at the top of the heel and Y10 bars at 175mm
Take moment about the centre −line of the wall for the vertical loads and the bearing pressures
Bearing pressure at the outer face of wall,
= = = 320.06 /m
Provide Y12 bars at 200mm ( =565 /m) at the bottom of the toe and Y10 bars at 175mm
Provide minimum reinforcement: Y10 bars at 150mm ( = 524 /m) vertically and
Step 4: Detailing
129
Design of Reinforced Concrete Elements
Fig 8.9
130
Design of Reinforced Concrete Elements
References
BS8110–1 (1985): Structural use of concrete –Part 2 Code of practice for special circumstances
BS8110–1 (1997): Structural use of concrete –Part 1 Code of practice for design and construction
BS8110–3 (1985): Structural use of concrete –Part 3: Design charts for singly reinforced beams,
Manual (1990). British Library Cataloguing in Publication Data, UK. ISBN: 0 7506 0313 5
Reinforced and Prestressed Concrete, 3rd Edition (1987). Chapman & Hall Publications, 2−6
Reinforced Concrete Design Theory and Examples, 2nd Edition (1990). SPON Press, London & New
Reinforced concrete design, 3rd Edition (2005). AROS Ltd Publications, Nigeria. ISBN:
978−36217−3−4
Reinforced Concrete Designer’s Handbook, 10th Edition (1988). E & FN Spon (Taylor & Francis
131