A Novel Method For Noninvasive Estimation of Utility Harmonic Impedance Based On Complex Independent Component Analysis
A Novel Method For Noninvasive Estimation of Utility Harmonic Impedance Based On Complex Independent Component Analysis
Abstract—This paper presents a new noninvasive method for A wide variety of methods has been developed to measure
calculating utility harmonic impedance at the point of common the utility harmonic impedance at the PCC. These methods can
coupling (PCC). The proposed method is based on a statistical be categorized into two types: 1) the invasive methods and 2)
signal-processing technique, known as independent component
analysis (ICA). The complex ICA technique is applied to the equa- noninvasive methods. In invasive methods, the utility harmonic
tions derived from Northon equivalent circuit model at the PCC impedance is extracted from the variations of voltage and cur-
in order to estimate the utility harmonic current values. Then, the rent which are caused by the injected disturbances or (inter)har-
estimated values of the utility harmonic current are used in an monic currents to the connected network [1]–[4]. Due to the sig-
optimization problem to calculate the utility harmonic impedance. nificant level of excitation, a wideband frequency result is ob-
Due to considering the utility harmonic current variations in
utility harmonic impedance calculation, the proposed method is tained from invasive methods. Despite sufficient accuracy, the
relatively robust against the background harmonic fluctuations. need for an expensive high-speed data-acquisition system and
The results obtained from computer simulation and a real case disturbance injection devices has restricted the application of
study verify the effectiveness of the proposed method. invasive methods. Moreover, the invasive methods cannot be
Index Terms—Background harmonic, harmonic impedance, performed repeatedly, because the injected disturbances may be
noninvasive method, power quality (PQ). harmful to the network especially in medium-voltage (MV) and
high-voltage (HV) systems.
On the other hand, in noninvasive methods, the natural varia-
I. INTRODUCTION
tions of voltage and current caused by harmonic load variability
are used to estimate the utility harmonic impedance at the PCC.
0885-8977 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
1844 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 4, AUGUST 2015
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
KARIMZADEH et al.: NOVEL METHOD FOR NONINVASIVE ESTIMATION OF UTILITY HARMONIC IMPEDANCE 1845
(9)
Before applying the FastICA algorithm to the data, the
observed signals are preprocessed by centering and whitening where
in order to simplify the ICA algorithm. Centering transforms
the observed signals to zero-mean variables and whitening (10)
linearly transforms the observed and centered signals, such that
the transformed signals are uncorrelated, have zero mean, and (11)
their variances equal unity [10].
(12)
III. PROPOSED METHOD
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
1846 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 4, AUGUST 2015
It is shown in [11] that the fast-varying components of har- where and represent the real and imaginary parts of
monic loads currents are statistically independent and have non- vector , respectively; gives the mean value of vector
Gaussian distribution. Since the variations are related to the ; and scales the range of vector values in [0,1]. The
distributed harmonic loads in the utility side, and variations relationship of can be defined as follows:
are related to the harmonic loads in the consumer side, one can
deduce that the fast-varying components of and have the
same properties as harmonic loads currents, that is, they are (22)
statistically independent and have non-Gaussian distribution.
Therefore, the ICA technique can be applied to the fast-varying
components of the measured voltage and current at the PCC and, where and are the minimum and maximum
consequently, the separating matrix can be estimated. The values of vector , respectively.
separating matrix is then used to recover the slow-varying In this paper, the exhaustive search method is utilized to solve
components of the matrix as follows: the optimization problem. According to this method, first, a list
of all potential solutions to the problem is generated. Then,
(17) the potential solutions are evaluated one by one and the one
that gives the minimum is chosen. The upper limit, lower
where the matrix consists of the estimated slow-varying com- limit, and the resolution of real and imaginary parts of are
ponents of source signals and . There are two indetermi- critical parameters in solving the aforementioned optimization
nacies in the estimation of the ICA model which exist due to problem with an exhaustive search method. These parameters
the fact that the source signals and the way they are mixed are can be determined as a function of the fundamental short-circuit
unknown. The first indeterminacy is related to the ordering of impedance of the utility at the PCC. Empirically, it is recom-
source signals, that is, the vector could be the first or the mended that the limitations of the real and imaginary parts of
second row of , and the second indeterminacy is related to the are set to , and , respec-
scaling of source signals. The prior information about the source tively, and the resolution of changes is also set to .
signals is needed to eliminate two aforementioned indetermina- It should be noted that the aforementioned limitations can be
cies. Here, we have no prior information about the vector. sufficient for calculating utility harmonic impedance up to the
Hence, it is necessary to find a way to clear these two indeter- 25th harmonic even if there is a resonance condition in the fre-
minacies. In order to distinguish the order of the vector in the quency response of utility impedance.
matrix, the assumption of is utilized. According The aforementioned optimization problem can also be solved
to this assumption, the current at the PCC is approximately by other optimization methods.
equal to . Therefore, there should be a linear correlation be-
tween the and vector. This point is the key idea to find
B. Method Guideline
the order in the matrix. It means that the row of , which
has less correlation with , is , and the row of , which The procedures of the proposed method are summarized as
has a greater correlation with is . follows.
Although the ordering indeterminacy is solved by using the 1) Measure the and samples during the appropriate
correlation concept, the scaling indeterminacy still exists. In the time interval (for example, 1-h time interval with a data
following text, we represent that it is not necessary to eliminate resolution of 1 sample/s).
the scaling indeterminacy of . Instead of that, the normalized 2) Decompose and into the fast- and slow-varying
values of suffice to estimate the utility harmonic impedance. components by utilizing the linear filter.
The utility harmonic impedance estimation can be simply con- 3) Apply the ICA technique to the fast-varying components
verted to an optimization problem as follows. According to (8), of and and estimate the separating matrix .
the slow-varying component of can be defined as a function 4) Employ separating matrix to estimate the
of slow-varying components of and .
(18) 5) Use the correlation concept to find the order of in the
matrix.
The value of that minimizes the following objective function 6) Find by solving the optimization problem.
is the answer of the optimization problem:
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
KARIMZADEH et al.: NOVEL METHOD FOR NONINVASIVE ESTIMATION OF UTILITY HARMONIC IMPEDANCE 1847
(23)
(24)
where is the mean value of the -sequence harmonic cur- Fig. 3. Profiles of simulated harmonic current sources for case 2. (a) Real part
rent samples and is the mean value of the fundamental of the utility harmonic current source. (b) Imaginary part of the utility harmonic
component of positive-sequence current samples at the PCC. current source. (c) Real part of the consumer harmonic current source. (d) Imag-
inary part of the consumer harmonic current source.
In (24), the subscript represents the positive-, negative-, or
zero-sequence component.
TABLE I
IV. SIMULATION AND FIELD TEST VERIFICATION CHARACTERISTICS OF THE SIMULATED MODEL
A. Computer Simulation
In this section, the model represented in Fig. 2 is simulated
to examine the performance of the proposed method. Here,
the utility harmonic impedance is assumed to be constant and
has a smaller value in comparison with consumer harmonic
impedance. The consumer harmonic impedance is defined by
normal distribution with the expectation of and PCC are caused more by the utility side. The characteristics of
variance of . As mentioned before, the harmonic current the simulated network for two cases are represented in Table I.
sources of the utility and consumer are composed of slow- The symbol stands for the Laplace distribution
and fast-varying components. In [11], a typical harmonic load with the expectation of and variance of .
profile is used to simulate the slow-varying component of the The proposed method is applied to the voltage and current of
harmonic current source. Moreover, the Laplace distributed PCC, and the utility harmonic impedance is calculated. The fast-
random variables are added to the slow-varying component and slow-varying components of and are separated by
to simulate the fast-varying component. It should be noted an 8-point moving average filter. Fig. 4 demonstrates the fast-
that the Laplace distributed random variables are statistically and slow-varying components of the real and imaginary parts of
independent; therefore, they are suitable to be considered as and related to case 2. The correlation analysis for de-
a fast-varying component. Similar to [11], here, two typical tecting the order of the vector in the matrix is represented
harmonic load profiles in accordance with the actual measure- in Fig. 5 for cases 1 and 2. In this figure, and represent
ments are allotted to and to simulate the slow-varying the samples of the first and second rows of the matrix, respec-
components of harmonic current sources. In addition, zero tively. As can be seen, in both cases, the samples magnitudes of
mean Laplace distributed random variables with specified the first row of the matrix have greater correlation with the
variances values are added to the normalized harmonic load magnitudes of the samples. Therefore, it can be simply in-
profiles to consider the fast-varying components. Fig. 3 illus- ferred that the samples of the second row of the matrix belong
trates the real and imaginary parts of and generated from to the utility-side harmonic source.
aforementioned instruction. There are 1440 samples for the The simulation results obtained for two cases are listed in Ta-
entire day, that is, one sample per minute. Two cases are defined bles II and III, respectively. The results obtained from the pro-
to evaluate the effectiveness of the proposed method. In the first posed method are compared with the results obtained from dif-
case, the fluctuations are larger than the ones, implying ferent well-known noninvasive methods. In Tables II and III,
that the variations of voltage at the PCC are caused more by the methods 1, 2, and 3 are the methods proposed in [5]–[7], respec-
consumer side. In the second case, the fluctuations are larger tively. Two data-selection approaches are proposed in [6] to esti-
than the ones, implying that the variations of voltage at the mate the utility harmonic impedance. In this paper, the threshold
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
1848 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 4, AUGUST 2015
TABLE II
SIMULATION RESULTS FOR CASE 1
TABLE III
SIMULATION RESULTS FOR CASE 2
Error (25)
The error between the real part of the estimated utility harmonic
impedance and the actual value , and the error between
the imaginary part of the estimated utility harmonic impedance
and the actual value can be calculated through (25).
According to the simulation results for case 1, all of the
methods have acceptable accuracy in the estimation of the
utility harmonic impedance. These results are reasonable be-
cause the influence of the utility harmonic current fluctuations
(background harmonic) on the harmonic voltage of PCC is
trifle. In case 1, the VR is 60% (which is more than 20%),
and NS is 28. It means that in method 2, the utility har-
monic impedance is estimated from the second data-selection
approach.
In contrast to case 1, the effect of the utility harmonic current
fluctuations is dramatically increased in case 2. The simulation
results indicate that the proposed method gives the best result for
case 2. This fact proves the robustness of the proposed method
against the background harmonic fluctuations. In case 2, the VR
is 11.8% (which is less than 20%), and NS is zero. It means that
in method 2, the utility harmonic impedance is estimated from
Fig. 5. Correlation analysis for detecting the vector in the matrix. Plots
of (a) samples versus samples for case 1. (b) samples versus
the first data-selection approach.
samples for case 1. (c) samples versus samples for case 2.
(d) samples versus samples for case 2. B. Field Test Verification
In this section, the practical feasibility of the proposed
method is evaluated by utilizing actual data. The measurement
of variance ratio (VR) is set to 20% for the first data-selection has been carried out at the secondary of a 1-MVA 20/0.4-kV
approach, and the threshold of is set to 0.9 for the second distribution transformer. This transformer is one of the quadru-
data-selection approach. The number of samples selected by the plet transformers of an ore-processing factory. This factory
second data selection is represented by NS. The best answer be- is a part of the Golgohar iron ore mine, which is located in
tween two data-selection approaches is reported as the result of Kerman. The one-line diagram of the electrical network of
method 2 in Tables II and III. For methods 1 and 2, the length this factory is demonstrated in Fig. 6. According to Fig. 6,
of each subinterval is set to 10 samples. the TR2 transformer supplies the combination of linear and
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
KARIMZADEH et al.: NOVEL METHOD FOR NONINVASIVE ESTIMATION OF UTILITY HARMONIC IMPEDANCE 1849
nonlinear loads. The linear loads are the induction motors, and
the nonlinear loads are the adjustable speed drives (ASDs).
The aggregation of the upstream network harmonic current and
the injected harmonic currents of TR3 and TR4 transformers
nonlinear loads make the background harmonic at the PCC.
The voltage and current at the PCC are measured by using a
MAVOWATT70 PQ analyzer. Since the phase data of voltage
and current are required by the proposed method, the proposed
method is sensitive to the synchronization of sampling. Here,
the voltages and currents are sampled synchronously by the
measurement instrument. The discrete Fourier transform (DFT)
tool is used to obtain harmonic voltage and current parame-
ters. According to the IEC 61000-4-7 standard [13], the DFT
window width is 10 cycles (for a 50-Hz system) with rectangular
weighting. The calculated harmonic parameters are averaged in
one second. All of the harmonic phases refer to the fundamental Fig. 7. Harmonic spectra of the (a) measured voltage and (b) measured current
at the PCC.
voltage in order to eliminate the phase errors caused by the fun-
damental frequency variation. The total measurement duration
is one hour and the data resolution is 1 sample/s. This way, 3600
samples are gathered for calculating utility impedance in dif-
ferent harmonics. Fig. 7 illustrates the typical spectra of voltage
and current which are calculated by performing DFT on 10-cy-
cles voltage and current snapshots. The THD of voltage for three
phases is about 1.75% and the THD of current is about 25% for
phases A and C, and about 20% for phase B. It can be seen from
Fig. 7 that significant imbalances exist in some harmonics of
voltage and current. In order to evaluate the background har-
monic level, a measurement has been performed at the PCC
when the TR2 transformer loads are out of service. Fig. 8 shows
the measured voltage spectrum in this situation. The voltage
spectrum obviously represents the considerable role of back- Fig. 8. Harmonic spectrum of the measured voltage at the PCC before con-
ground harmonic voltage in the harmonic voltage level at the necting the TR2 transformer loads.
PCC. This fact implies that this case study is well chosen to ex-
amine the robustness of the proposed method against negative
effects of the background harmonic. and the negative sequence of the utility harmonic impedance can
The three-phase measured voltages and currents of the 3rd, be calculated for 3rd, 5th, and 11th orders.
5th, 7th, 11th, and 13th harmonic orders are converted to the In order to estimate the utility harmonic impedance, the pro-
positive, negative, and zero sequences by employing (23). As posed algorithm is implemented in a PC using Intel Core i5
an example, Fig. 9 shows the magnitudes of positive, negative, CPU (3.30 GHz) and 4 GB of RAM by MATLAB software.
and zero sequences of the third harmonic voltage and current. The computation time required to estimate each of the harmonic
Applying the criterion of (25) for different sequences of har- impedances is almost 11213 s. Most of the computation time
monics indicates that the positive sequence of the utility har- is allocated to the exhaustive search method. Since the funda-
monic impedance can be calculated for 3rd, 7th, and 13th orders, mental short-circuit impedance of the utility at the PCC is ap-
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
1850 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 4, AUGUST 2015
Fig. 12. Correlation analysis for detecting the vector in the matrix in
Fig. 9. Magnitudes of positive, negative, and zero sequences of the third har- the third harmonic positive-sequence impedance calculation. (a) Magnitude of
monic (a) voltage and (b) current at the PCC. the first row samples of the matrix versus and (b) magnitude of the
second row samples of the matrix versus .
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
KARIMZADEH et al.: NOVEL METHOD FOR NONINVASIVE ESTIMATION OF UTILITY HARMONIC IMPEDANCE 1851
VI. CONCLUSION
In this paper, a new noninvasive method is proposed to es-
timate the utility harmonic impedance at the PCC. The pro-
posed method is developed based on the Norton equivalent cir-
cuit model at the PCC and ICA technique. The utility back-
ground harmonic current is estimated by the complex FastICA
approach. The estimated utility harmonic current is then used
in an optimization problem to calculate the utility harmonic
impedance. The results obtained from computer simulation and
field test prove the capability of the proposed method in the es-
timation of the utility harmonic impedance especially in cases
in this situation. First, since the measurement duration for cal- that the background harmonic fluctuations are dominated at the
culating utility harmonic impedance using the proposed method PCC. The proposed method does not require an expensive data
is relatively short (for example, one hour), the filter or capac- gathering instrument or other extra elements. It only needs the
itor can be disconnected temporarily in order to eliminate the voltage and current samples which can be simply achieved by a
negative effects of them on utility harmonic impedance calcu- low-cost PQ analyzer at the PCC.
lation. If disconnection of the filter or capacitor is not possible,
the integration approach, which is discussed in [5], is recom- REFERENCES
mended. In this approach, the metering point is replaced to the [1] A. Robert and T. Deflandre, “Guide for assessing the network harmonic
impedance,” presented at the Int. Conf. Elect. Distrib., Birmingham,
point between the filter (or capacitor) and consumer. So the cal- U.K., Jun. 1997, Joint CIGRE/CIGRE Working Group CC02.
culated impedance at the new metering point is or [2] M. Nagpal, W. Xu, and J. Sawada, “Harmonic impedance measurement
. Since the parameters of the harmonic filter and using three-phase transients,” IEEE Trans. Power Del., vol. 13, no. 1,
pp. 272–277, Jan. 1998.
power factor correction capacitor are commonly available; the [3] P. Bettini and A. D. Lorenzi, “400-kV-network harmonic impedance
utility harmonic impedance can be easily calculated. evaluation from harmonic distortion measurements at RFX site,” Eur.
Trans. Elect. Power, vol. 8, no. 1, pp. 31–38, Feb. 1998.
B. Long Underground Cable Supplying the Load [4] W. Xu, E. E. Ahmed, X. Zhang, and X. Liu, “Measurement of network
harmonic impedances: Practical implementation issues and their solu-
There are not very uncommon cases when the long under- tions,” IEEE Trans. Power Del., vol. 17, no. 1, pp. 210–216, Jan. 2002.
[5] J. Hui, H. Yang, S. Lin, and M. Ye, “Assessing utility harmonic
ground cable supplying the load is overcompensated due to ad- impedance based on the covariance characteristic of random vectors,”
ditional reactive power compensation. Therefore, the equivalent IEEE Trans. Power Del., vol. 25, no. 3, pp. 1778–1786, Jul. 2010.
characteristic of load is capacitive so that the magnitude of the [6] J. Hui, W. Freitas, J. C. M. Vieira, H. Yang, and Y. Liu, “Utility har-
monic impedance measurement based on data selection,” IEEE Trans.
consumer impedance decreases with frequency up to some Power Del., vol. 27, no. 4, pp. 2193–2202, Oct. 2012.
limit frequency. In this situation, the magnitude of the consumer [7] D. Borkowski, A. Wetula, and A. Bien, “New method for noninvasive
impedance may be smaller than or equal to the magnitude measurement of utility harmonic impedance,” presented at the Power
Energy Soc. Gen. Meeting, San Diego, CA, USA, 2012.
of the utility impedance . In order to estimate the utility [8] A. Hyvarinen and E. Oja, “Independent component analysis: Algo-
harmonic impedance by using the proposed method in this sit- rithms and applications,” Neural Netw., vol. 13, pp. 411–430, May/Jun.
uation, replacing the metering point to the point between the 2000.
[9] H. W. Liao and D. Niebur, “Load profile estimation in electric transmis-
cable and consumer is recommended. Hence, the combination sion networks using independent component analysis,” IEEE Trans.
of cable and utility impedance is calculated by proposed method Power Syst., vol. 18, no. 2, pp. 707–715, May 2003.
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.
1852 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 4, AUGUST 2015
[10] E. Gursoy and D. Niebur, “Harmonic load identification using complex Saeid Esmaeili was born in Rafsanjan, Iran, in
independent component analysis,” IEEE Trans. Power Del., vol. 24, 1976. He received the B.Sc. degree in power elec-
no. 1, pp. 285–292, Jan. 2009. trical engineering from K. N. Toosi University
[11] E. Gursoy, “Independent component analysis for harmonic source of Technology, Tehran, Iran, in 1999, the M.Sc.
identification in electric power systems,” Ph.D. dissertation, Elect. degree in power electrical engineering from Iran
Comput. Eng. Dept., Drexel University, Philadelphia, PA, USA, 2007. University of Science and Technology, Tehran, in
[12] E. Bingham and A. Hyvarinen, “A fast fixed-point algorithm for inde- 2002, and the Ph.D. degree in electrical engineering
pendent component analysis of complex valued signals,” Int. J. Neural from Amirkabir University of Technology (Tehran
Syst., vol. 10, pp. 1–8, 2000. Polytechnic), Tehran, Iran, in 2007.
[13] Electromagnetic Compatibility (EMC)—Part 4: Section 7: Testing and Currently, he is an Assistant Professor in the De-
Measurement Techniques—General Guide on Harmonics and Inter- partment of Electrical Engineering at the Shahid Ba-
harmonics Measurements and Instrumentation, for Power Supply Sys- honar University of Kerman, Kerman, Iran. His research interests include anal-
tems and Equipment Connected Thereto, IEC 61000-4-7, 2002. ysis and optimization of electrical power systems, power quality, and dynamics
[14] T. Pfajfar, B. Blažič, and I. Papič, “Harmonic contributions evaluation of electrical power systems.
with the harmonic current vector method,” IEEE Trans. Power Del.,
vol. 23, no. 1, pp. 425–433, Jan. 2008.
Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on August 01,2022 at 15:35:31 UTC from IEEE Xplore. Restrictions apply.