Gama Power m50 Internal Battery Brochure

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

 

 
THE NEXT GENERATION IN MODULAR UPS 

GAMATRONIC POWER + 
 
The Gamatronic Power + three-phase UPS system employs a single-
unit form factor that conserves data-center floor space, and its light-
weight, user friendly, 10kVA modules provide simple, reliable low-cost
expansion to meet your growing power needs. Because the Power +
is modular and scalable, you conserve capital – only investing in
capacity when you need it. The Power + operates at super-high 94%
efficiency, which means less heat and lower cooling costs, too.

POWER+ M50 SERIES


INTERNAL BATTERY MODELS
THREE-PHASE 10 - 30kVA UPS
SINGLE-PHASE 7.5 – 22.5kVA UPS
Modular ● Scalable ● Hot-Plug ● Hot-Swap ● N+1 Redundancy ● Affordable

• Double-conversion power provides completely clean, consistent AC


output to the data center power bus.
• True online battery is galvanically connected to the rectifier and
inverter on a common DC link for increased reliability.
• Hot-plug, hot-swap system enables power modules and controller to
be added or swapped without interruption of output power and without
transferring to bypass.
• Scalability enables UPS to grow in 10kVA steps with your expanding
power protection needs.
• Field configurable for 120/208 VAC or 120/240 VAC single-phase, or
120/208 VAC three-phase operation.
• Allows cost-effective N+1 or N+2 redundancy, ensuring that the load
will continue to be supported even if a module fails.
• Hybrid static switch ensures fastest, safest transfer to backup with
long term reliability.
• Lightweight power modules are only 2U and 22 lbs. each.
• Highest AC – AC efficiency rating of 94% results in lower energy
costs and reduced heat.
• System controller provides advanced management and control
functions including Internet, TCP/IP, and SNMP communications
standard. System can operate with controller damaged or removed.
• Internal battery saves valuable data center floor space.
• Rotary and three-breaker maintenance bypass switches available.
POWER +M50 THREE-PHASE TECHNICAL SPECIFICATIONS
Model M50 10kVA 20kVA 30kVA
Capacity (kVA / kW) 10 / 8 20 / 16 30 / 24
On-Line Double-Conversion Modular Redundant with Hybrid Central Static
Topology
Switch
Input
Voltage 208V Three-Phase, L1, L2, L3, N
Voltage Range -25% TO +15%
Current 29.6 Amps per 10kVA Module – No inrush current at Startup
Frequency (Hz) 47 – 63
Power Walk In > 60 Seconds
Current Distortion (THDI) 5% at full load
Input Power Factor 0.99
Output
Voltage 120 / 208 Three-Phase, L1, L2, L3, N
Current 27.8 Amps Per 10kVA Module
Frequency Tracking Range 60Hz +/- 2 Hz
Static Regulation +/- 1%
Regulation for Unbalanced Load +/- 1% for 100% Unbalanced Load
Dynamic Response to 100% Step Load +/- 2%
Overload 110% for 10 min; 125% for 60 sec; 1000% for 1 cycle
THD Less than 2% for linear load
Load Crest Factor (Max) 4:1
Efficiency (Nominal) AC/AC 94% on-line, DC/AC 97%
Static Switch
Type Hybrid 50kVA Static Switch with Auto Wrap-around Contactor
Control Connections EPO Connection (powered NC) and Load on Bypass (dry contacts NC)
General
Ambient Temperature 14°F to 104°F (operating), -4°F to 140°F (storage)
10kVA/8kW Module Weight (lbs) 22
51.8” x 23.6” x 29.2” (2 slot model)
UPS Dimensions (H x W x D) 66.1” x 23.6” x 29.2” (3 slot model)

UPS System Weight (lbs.)


2 slot model 774 796 --
3 slot model 1048 1070 1092
UPS Shipping Weight (lbs.) Add 150 lbs to System Weight
Acoustic Noise (Full Load) @ 1.5M (dB) 51 54 55
Maximum Heat Dissipation (btu/h) 1740 3480 5220
Power+ Controller
Display 4x40 Character LCD with Backlight
Input Channels 4 Digital, 8 Analog
Output Contacts 4 Dry Contacts
System Operation without Controller Continuous without disruption
Load Bar Graph, UPS Module Status, Static Switch Status,
On Screen Parameters
Battery Temperature Sensor
Power Meter Input and Output kW, kVA, and PF
Module Failure, AC Alarm, DC Alarm, On Bypass, Battery Test Fail,
Alarms
Overload, Over/Under Temp
Log (events memory) 255 Events
Communications SNMP / Web Interface, TCP/IP Standard
Standards
EMC Emission IEC62040-2; FCC part 15 / 8
Safety UL 1778; IEC62040-1-1
Battery/Charger
DC Link Voltage Nominal 384V (+192, -192)
Battery Pack Internal Battery
Max Charging Current at full load (amps) 4.5 9 13.5
Runtime (Minutes) 10kVA 20kVA 30kVA
2 slot model 29 10 --
3 slot model 48 19 10