Eio0000001438 04

Download as pdf or txt
Download as pdf or txt
You are on page 1of 124

Modicon M241 Logic Controller

EIO0000001438 03/2018

Modicon M241 Logic


Controller
System Functions and Variables
PLCSystem Library Guide
03/2018
EIO0000001438.04

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2018 Schneider Electric. All Rights Reserved.

2 EIO0000001438 03/2018
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 M241 System Variables . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1 System Variables: Definition and Use . . . . . . . . . . . . . . . . . . . . . . . . . 12
Understanding System Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Using System Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.2 PLC_R and PLC_W Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PLC_R: Controller Read-Only System Variables . . . . . . . . . . . . . . . . . 18
PLC_W: Controller Read/Write System Variables . . . . . . . . . . . . . . . . 23
1.3 SERIAL_R and SERIAL_W Structures . . . . . . . . . . . . . . . . . . . . . . . . 24
SERIAL_R[0...1]: Serial Line Read-Only System Variables . . . . . 25
SERIAL_W[0...1]: Serial Line Read/Write System Variables . . . . . 26
1.4 ETH_R and ETH_W Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ETH_R: Ethernet Port Read-Only System Variables . . . . . . . . . . . . . 28
ETH_W: Ethernet Port Read/Write System Variables. . . . . . . . . . . . . . 33
1.5 TM3_MODULE_R Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TM3_MODULE_R[0...13]: TM3 Modules Read-Only System
Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1.6 TM3_BUS_W Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TM3_BUS_W: TM3 Bus System Variables . . . . . . . . . . . . . . . . . . . . . . 35
1.7 PROFIBUS_R Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
PROFIBUS_R: PROFIBUS Read-Only System Variables . . . . . . . . . 36
1.8 CART_R Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
CART_R_STRUCT: Cartridge Read-Only System Variables . . . . . . . 37
Chapter 2 M241 System Functions . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.1 M241 Read Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
GetImmediateFastInput: Read Input of an Embedded Expert I/O 41
GetRtc: Get Real Time Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
IsFirstMastColdCycle: Indicate if this Cycle is the First MAST
Cold Start Cycle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
IsFirstMastCycle: Indicate if this Cycle is the First MAST Cycle . 44
IsFirstMastWarmCycle: Indicate if this Cycle is the First MAST
Warm Start Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

EIO0000001438 03/2018 3
2.2 M241 Write Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
PhysicalWriteFastOutputs: Write Fast Output of an Embedded
Expert I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SetRTCDrift: Set Compensation Value to the RTC . . . . . . . . . . . . . 49
2.3 M241 User Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
DataFileCopy: Copy File Commands. . . . . . . . . . . . . . . . . . . . . . . . 52
ExecuteScript: Run Script Commands . . . . . . . . . . . . . . . . . . . . . . 55
2.4 TM3 Read Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
TM3_GetModuleBusStatus: Get TM3 Module Bus Status. . . . . . . . 58
TM3_GetModuleFWVersion: Get TM3 Module Firmware Version . . 59
TM3_GetModuleInternalStatus: Get TM3 Module Internal Status 60
Chapter 3 M241 PLCSystem Library Data Types . . . . . . . . . . . . . . . 63
3.1 PLC_RW System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . . 64
PLC_R_APPLICATION_ERROR: Detected Application Error Status
Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes . . . . 67
PLC_R_IO_STATUS: I/O Status Codes. . . . . . . . . . . . . . . . . . . . . . . . 68
PLC_R_SDCARD_STATUS: SD Card Slot Status Codes . . . . . . . . . . 69
PLC_R_STATUS: Controller Status Codes . . . . . . . . . . . . . . . . . . . . . 70
PLC_R_STOP_CAUSE: From RUN State to Other State Transition
Cause Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection
Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes . . . . . . . . . . . . . . 74
PLC_W_COMMAND: Control Command Codes . . . . . . . . . . . . . . . . . 75
3.2 DataFileCopy System Variables Data Types . . . . . . . . . . . . . . . . . . . . 76
DataFileCopyError: Detected Error Codes. . . . . . . . . . . . . . . . . . . . . . 77
DataFileCopyLocation: Location Codes. . . . . . . . . . . . . . . . . . . . . . . . 78
3.3 ExecScript System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . 79
ExecuteScriptError: Detected Error Codes . . . . . . . . . . . . . . . . . . . . . 79
3.4 ETH_RW System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . . 80
ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes . 81
ETH_R_IP_MODE: IP Address Source Codes . . . . . . . . . . . . . . . . . . 82
ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes . . . . . 83
ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes . . . 84
ETH_R_PORT_LINK_STATUS: Communication Link Status Codes. . 85
ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port
Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes . . . . . . . 87

4 EIO0000001438 03/2018
3.5 TM3_MODULE_RW System Variables Data Types . . . . . . . . . . . . . . 88
TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes . . 89
TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read
Array Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
TM3_MODULE_STATE: TM3 Expansion Module State Codes . . . . . 91
TM3_BUS_W_IOBUSERRMOD: TM3 bus error mode . . . . . . . . . . . . 92
3.6 Cartridge System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . . 93
CART_R_ARRAY_TYPE: Cartridge Read Array Type . . . . . . . . . . . . 94
CART_R_MODULE_ID: Cartridge Read Module Identifier . . . . . . . . . 95
CART_R_STATE: Cartridge Read State . . . . . . . . . . . . . . . . . . . . . . . 96
3.7 System Function Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
IMMEDIATE_ERR_TYPE: GetImmediateFastInput Read Input of
Embedded Expert I/O Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Appendices ......................................... 101
Appendix A Function and Function Block Representation . . . . . . . . 103
Differences Between a Function and a Function Block . . . . . . . . . . . . 104
How to Use a Function or a Function Block in IL Language . . . . . . . . 105
How to Use a Function or a Function Block in ST Language . . . . . . . 109
Glossary ......................................... 113
Index ......................................... 121

EIO0000001438 03/2018 5
6 EIO0000001438 03/2018
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.

EIO0000001438 03/2018 7
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.

8 EIO0000001438 03/2018
About the Book

At a Glance

Document Scope
This document will acquaint you with the system functions and variables offered within the Modicon
M241 Logic Controller. The M241 PLCSystem library contains functions and variables to get
information from and send commands to the controller system.
This document describes the data type functions and variables of the M241 PLCSystem library.
The following knowledge is required:
 Basic information on the functionality, structure, and configuration of the M241 Logic Controller.
 Programming in the FBD, LD, ST, IL, or CFC language.
 system variables (global variables).

Validity Note
This document has been updated for the release of TM3TI4D Add-on for SoMachine V4.3.

Related Documents

Title of Documentation Reference Number


SoMachine Programming Guide EIO0000000067 (ENG);
EIO0000000069 (FRE);
EIO0000000068 (GER);
EIO0000000071 (SPA);
EIO0000000070 (ITA);
EIO0000000072 (CHS)
Modicon M241 Logic Controller Hardware Guide EIO0000001456 (ENG);
EIO0000001457 (FRE);
EIO0000001458 (GER);
EIO0000001459 (SPA);
EIO0000001460 (ITA);
EIO0000001461 (CHS)

EIO0000001438 03/2018 9
Title of Documentation Reference Number
Modicon M241 Logic Controller Programming Guide EIO0000001432 (ENG);
EIO0000001433 (FRE);
EIO0000001434 (GER);
EIO0000001435 (SPA);
EIO0000001436 (ITA);
EIO0000001437 (CHS)

You can download these technical publications and other technical information from our website
at https://www.schneider-electric.com/en/download

Product Related Information

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths
and, for certain critical control functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are emergency stop and overtravel
stop, power outage and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.1
 Each implementation of this equipment must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1
For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest
edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

10 EIO0000001438 03/2018
Modicon M241 Logic Controller
M241 System Variables
EIO0000001438 03/2018

Chapter 1
M241 System Variables

M241 System Variables

Overview
This chapter:
 gives an introduction to the system variables (see page 12)
 describes the system variables (see page 18) included with the M241 PLCSystem library

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
1.1 System Variables: Definition and Use 12
1.2 PLC_R and PLC_W Structures 17
1.3 SERIAL_R and SERIAL_W Structures 24
1.4 ETH_R and ETH_W Structures 27
1.5 TM3_MODULE_R Structure 34
1.6 TM3_BUS_W Structure 35
1.7 PROFIBUS_R Structure 36
1.8 CART_R Structure 37

EIO0000001438 03/2018 11
M241 System Variables

Section 1.1
System Variables: Definition and Use

System Variables: Definition and Use

Overview
This section defines system variables and how to implement them in the Modicon M241 Logic
Controller.

What Is in This Section?


This section contains the following topics:
Topic Page
Understanding System Variables 13
Using System Variables 15

12 EIO0000001438 03/2018
M241 System Variables

Understanding System Variables

Introduction
This section describes how system variables are implemented. System variables:
 allow you to access general system information, perform system diagnostics, and command
simple actions.
 are structured variables conforming to IEC 61131-3 definitions and naming conventions. You
can access the system variables using the IEC symbolic name PLC_GVL. Some of the PLC_GVL
variables are read-only (for example, PLC_R) and some are read/write (for example, PLC_W).
 are automatically declared as global variables. They have system-wide scope and can be
accessed by any Program Organization Unit (POU) in any task.

Naming Convention
The system variables are identified by:
 a structure name that represents the category of system variable. For example, PLC_R
represents a structure name of read-only variables used for the controller diagnostic.
 a set of component names that identifies the purpose of the variable. For example,
i_wVendorID represents the controller vendor ID.
You can access the system variables by typing the structure name of the variables followed by the
name of the component.
Here is an example of system variable implementation:
VAR
myCtr_Serial : DWORD;
myCtr_ID : DWORD;
myCtr_FramesRx : UDINT;
END_VAR
myCtr_Serial := PLC_R.i_dwSerialNumber;
myCtr_ID := PLC_R.i_wVendorID;
myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK;
NOTE: The fully qualified name of the system variable in the example above is
PLC_GVL.PLC_R.i_wVendorID. The PLC_GVL is implicit when declaring a variable using the
Input Assistant, but it may also be entered in full. Good programming practice often dictates the
use of the fully qualified variable name in declarations.

EIO0000001438 03/2018 13
M241 System Variables

System Variables Location


2 kinds of system variables are defined for use when programming the controller:
 located variables
 unlocated variables

The located variables:


 have a fixed location in a static %MW area: %MW60000 to %MW60199 for read-only system
variables.
 are accessible through Modbus TCP, Modbus serial, and EtherNet/IP requests both in
RUNNING and STOPPED states.
 are used in SoMachine programs according to the structure_name.component_name
convention explained previously. %MW addresses from 0 to 59999 can be accessed directly.
Addresses greater than this are considered out of range by SoMachine and can only be
accessed through the structure_name.component_name convention.
The unlocated variables:
 are not physically located in the %MW area.
 are not accessible through any fieldbus or network requests unless you locate them in the
relocation table, and only then these variables can be accessed in RUNNING and STOPPED
states. The relocation table uses the following dynamic %MW areas:
 %MW60200 to %MW61999 for read-only variables
 %MW62200 to %MW63999 for read/write variables

 are used in SoMachine programs according to the structure_name.component_name


convention explained previously. %MW addresses from 0 to 59999 can be accessed directly.
Addresses greater than this are considered out of range by SoMachine and can only be
accessed through the structure_name.component_name convention.

14 EIO0000001438 03/2018
M241 System Variables

Using System Variables

Introduction
This section describes the steps required to program and to use system variables in SoMachine.
System variables are global in scope, and you can use them in all the Program Organization Units
(POUs) of the application.
System variables do not need to be declared in the Global Variable List (GVL). They are
automatically declared from the controller system library.

Using System Variables in a POU


SoMachine has an auto-completion feature. In a POU, start by entering the system variable
structure name (PLC_R, PLC_W...) followed by a dot. The system variables appear in the Input
Assistant. You can select the desired variable or enter the full name manually.

NOTE: In the example above, after you type the structure name PLC_R., SoMachine offers a pop-
up menu of possible component names/variables.

EIO0000001438 03/2018 15
M241 System Variables

Example
The following example shows the use of some system variables:
VAR
myCtr_Serial : DWORD;
myCtr_ID : WORD;
myCtr_FramesRx : UDINT;
END_VAR
myCtr_Serial := PLC_R.i_dwSerialNumber;
myCtr_ID := PLC_R.i_wVendorID;
myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK;

16 EIO0000001438 03/2018
M241 System Variables

Section 1.2
PLC_R and PLC_W Structures

PLC_R and PLC_W Structures

Overview
This section lists and describes the different system variables included in the PLC_R and PLC_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
PLC_R: Controller Read-Only System Variables 18
PLC_W: Controller Read/Write System Variables 23

EIO0000001438 03/2018 17
M241 System Variables

PLC_R: Controller Read-Only System Variables

Variable Structure
This table describes the parameters of the PLC_R system variable (PLC_R_STRUCT type):

Modbus Var Name Type Comment


Address (1)
60000 i_wVendorID WORD Controller Vendor ID.
101A hex = Schneider Electric
60001 i_wProductID WORD Controller Reference ID.
NOTE: Vendor ID and Reference ID are the
components of the Target ID of the controller
displayed in the communication settings
view (Target ID = 101A XXXX hex).
60002 i_dwSerialNumber DWORD Controller Serial Number
60004 i_byFirmVersion ARRAY[0..3] Controller Firmware Version
OF BYTE [aa.bb.cc.dd]:
 i_byFirmVersion[0] = aa
 ...
 i_byFirmVersion[3] = dd

60006 i_byBootVersion ARRAY[0..3] Controller Boot Version [aa.bb.cc.dd]:


OF BYTE  i_byBootVersion[0] = aa
 ...
 i_byBootVersion[3] = dd

60008 i_dwHardVersion DWORD Controller Hardware Version.


60010 i_dwChipVersion DWORD Controller Coprocessor Version.
60012 i_wStatus PLC_R_STATUS State of the controller.
(see page 70)
60013 i_wBootProjectStatus PLC_R_BOOT_ Returns information about the boot
PROJECT_STATUS application stored in FLASH memory.
(see page 67)
60014 i_wLastStopCause PLC_R_STOP_ Cause of the last transition from RUN to
CAUSE (see page 71) another state.
60015 i_wLastApplicationError PLC_R_APPLICATION Cause of the last controller exception.
_ERROR
(see page 65)

18 EIO0000001438 03/2018
M241 System Variables

Modbus Var Name Type Comment


Address (1)
60016 i_lwSystemFault_1 LWORD Bit field FFFF FFFF FFFF FFFF hex
indicates no error detected.
A bit at low level means that an error has
been detected:
 bit 0 = Expert I/O error detected
 bit 1 = TM3 error detected
 bit 2 = Ethernet IF1 error detected
 bit 3 = Ethernet IF2 error detected
 bit 4 = Serial 1 in overcurrent error
detected
 bit 5 = Serial 2 error detected
 bit 6 = CAN 1 error detected
 bit 7 = Cartridge 1 error detected
 bit 8 = Cartridge 2 error detected
 bit 9 = TM4 error detected
 bit 10 = SD Card error detected
 bit 11 = Firewall error detected
 bit 12 = DHCP server error detected
 bit 13 = OPC UA server error detected

60020 i_lwSystemFault_2 LWORD Bit field FFFF hex indicates no error


detected.
If i_wIOStatus1 =
PLC_R_IO_SHORTCUT_FAULT, the
meaning of i_lwSystemFault_2 is:
 bit 0 = 0: short-circuit detected in output
group 0 (Q0...Q1)
 bit 1 = 0: short-circuit detected in output
group 1 (Q2...Q3)
 bit 2 = 0: short-circuit detected in output
group 2 (Q4...Q7)
 bit 3 = 0: short-circuit detected in output
group 3 (Q8...Q11)
 bit 4 = 0: short-circuit detected in output
group 4 (Q12...Q15)
60024 i_wIOStatus1 PLC_R_IO_ Embedded Expert I/O status.
STATUS (see page 68)
60025 i_wIOStatus2 PLC_R_IO_ TM3 I/O status.
STATUS (see page 68)

EIO0000001438 03/2018 19
M241 System Variables

Modbus Var Name Type Comment


Address (1)
60026 i_wClockBatterystatus WORD Status of the battery of the RTC:
 0 = Battery change needed
 100 = Battery fully charged

Other values (1...99) represents the


percentage of charge. For example, if the
value is 75, it represents that the battery
charge is 75%.
60028 i_dwAppliSignature1 DWORD First DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by
the software during build.
60030 i_dwAppliSignature2 DWORD Second DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by
the software during build.
60032 i_dwAppliSignature3 DWORD Third DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by
the software during build.
60034 i_dwAppliSignature4 DWORD Fourth DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by
the software during build.
(1) Not accessible through the application.

20 EIO0000001438 03/2018
M241 System Variables

n/a i_sVendorName STRING(31) Name of the vendor: “Schneider Electric”.


n/a i_sProductRef STRING(31) Reference of the controller.
n/a i_sNodeName STRING(99) Node name on SoMachine Network.
n/a i_dwLastStopTime DWORD The time of the last detected STOP in seconds
beginning with January 1, 1970 at 00:00 UTC.
n/a i_dwLastPowerOffDate DWORD The date and time of the last detected power off
in seconds beginning with January 1, 1970 at
00:00 UTC.
NOTE: Convert this value into date and time by
using the function
SysTimeRtcConvertUtcToDate. For more
information about Time and Date conversion,
refer to the Systime Library Guide
(see SoMachine, Getting & Setting Real Time
Clock, SysTimeRtc and SysTimeCore Library
Guide).
n/a i_uiEventsCounter UINT Number of external events detected on inputs
configured for external event detection since the
last cold start.
Reset by a Cold Start or by the
PLC_W.q_wResetCounterEvent command.
n/a i_wTerminalPortStatus PLC_R_TERMINAL_ Status of the USB Programming Port
PORT_STATUS (USB Mini-B).
(see page 73)
n/a i_wSdCardStatus PLC_R_SDCARD_ Status of the SD card.
STATUS
(see page 69)
n/a i_wUsrFreeFileHdl WORD Number of available File Handles.
A File Handle is the resource allocated by the
system when you open a file.
n/a i_udiUsrFsTotalBytes UDINT User FileSystem total memory size (in bytes).
It is the size of the flash memory for the directory
"/usr/".
n/a i_udiUsrFsFreeBytes UDINT User FileSystem free memory size (in bytes).

EIO0000001438 03/2018 21
M241 System Variables

n/a i_uiTM3BusState PLC_R_TM3_BUS_ TM3 bus state.


STATE i_uiTM3BusState can have the following
(see page 74) values:
 1: TM3_CONF_ERROR
Configuration mismatch between physical
configuration and SoMachine configuration.
 3: TM3_OK
Physical configuration matches SoMachine
configuration.
 4: TM3_POWER_SUPPLY_ERROR
TM3 bus is not powered (for example when
the Logic Controller is powered by USB).
n/a i_ExpertIO_RunStop_Input BYTE Run/Stop input location is:
 16...FF hex if the expert I/O is not configured
 0 for %IX0.0
 1 for %IX0.1
 2 for %IX0.2
 ...and so on.

n/a i_x10msClk BOOL TimeBase bit of 10 ms.


This variable is toggling On/Off with
period = 10 ms. The value toggles when the logic
controller is in Stop and in Run state.
n/a i_x100msClk BOOL TimeBase bit of 100 ms.
This variable is toggling On/Off with period =
100 ms. The value toggles when the logic
controller is in Stop and in Run state.
n/a i_x1sClk BOOL TimeBase bit of 1 s.
This variable is toggling On/Off with period = 1 s.
The value toggles when the logic controller is in
Stop and in Run state.

NOTE: n/a means that there is no pre-defined Modbus address mapping for this system variable.

22 EIO0000001438 03/2018
M241 System Variables

PLC_W: Controller Read/Write System Variables

Variable Structure
This table describes the parameters of the PLC_W system variable (PLC_W_STRUCT type):

%MW Var Name Type Comment


n/a q_wResetCounterEvent WORD Transition from 0 to 1 resets the events
counter (PLC_R.i_uiEventsCounter).
To reset the counter again, it is necessary to
write 0 to this variable before another
transition from 0 to 1 can take place.
n/a q_uiOpenPLCControl UINT When Value passes from 0 to 6699, the
command previously written in the following
PLC_W.q_wPLCControl is executed.
n/a q_wPLCControl PLC_W_COMMAND Controller RUN / STOP command executed
(see page 75) when the system variable
PLC_R.q_uiOpenPLCControl value
passes from 0 to 6699.

NOTE: n/a means that there is no pre-defined %MW mapping for this system variable.

EIO0000001438 03/2018 23
M241 System Variables

Section 1.3
SERIAL_R and SERIAL_W Structures

SERIAL_R and SERIAL_W Structures

Overview
This section lists and describes the different system variables included in the SERIAL_R and
SERIAL_W structures.

What Is in This Section?


This section contains the following topics:
Topic Page
SERIAL_R[0...1]: Serial Line Read-Only System Variables 25
SERIAL_W[0...1]: Serial Line Read/Write System Variables 26

24 EIO0000001438 03/2018
M241 System Variables

SERIAL_R[0...1]: Serial Line Read-Only System Variables

Introduction
SERIAL_R is an array of 2 SERIAL_R_STRUCT type. Each element of the array returns diagnostic
system variables for the corresponding serial line.
For the M241 Logic Controller:
 Serial_R[0] refers to the serial line 1
 Serial_R[1] refers to the serial line 2

Variable Structure
This table describes the parameters of the SERIAL_R[0...1] system variables:

%MW Var Name Type Comment


Serial Line
n/a i_udiFramesTransmittedOK UDINT Number of frames successfully transmitted.
n/a i_udiFramesReceivedOK UDINT Number of frames received without any errors
detected.
n/a i_udiRX_MessagesError UDINT Number of frames received with errors
detected (checksum, parity).
Modbus Specific
n/a i_uiSlaveExceptionCount UINT Number of Modbus exception responses
returned by the logic controller.
n/a i_udiSlaveMsgCount UINT Number of messages received from the Master
and addressed to the logic controller.
n/a i_uiSlaveNoRespCount UINT Number of Modbus broadcast requests
received by the logic controller.
n/a i_uiSlaveNakCount UINT Not used
n/a i_uiSlaveBusyCount UINT Not used
n/a i_uiCharOverrunCount UINT Number of character overruns.
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-
zero, it should be considered extraneous.

The SERIAL_R counters are reset on:


 Download.
 Controller reset.
 SERIAL_W[x].q_wResetCounter command.
 Reset command by Modbus request function code number 8.

EIO0000001438 03/2018 25
M241 System Variables

SERIAL_W[0...1]: Serial Line Read/Write System Variables

Introduction
SERIAL_W is an array of 2 SERIAL_W_STRUCT type. Each element of the array resets the
SERIAL_R system variables for the corresponding serial line to be reset.
For the M241 Logic Controller:
 Serial_W[0] refers to the serial line 1
 Serial_W[1] refers to the serial line 2

Variable Structure
This table describes the parameters of the SERIAL_W[0...1] system variable:

%MW Var Name Type Comment


n/a q_wResetCounter WORD Transition from 0 to 1 resets all
SERIAL_R[0...1] counters.
To reset the counters again, it is necessary to
write 0 to this variable before another transition
from 0 to 1 can take place.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

26 EIO0000001438 03/2018
M241 System Variables

Section 1.4
ETH_R and ETH_W Structures

ETH_R and ETH_W Structures

Overview
This section lists and describes the different system variables included in the ETH_R and ETH_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
ETH_R: Ethernet Port Read-Only System Variables 28
ETH_W: Ethernet Port Read/Write System Variables 33

EIO0000001438 03/2018 27
M241 System Variables

ETH_R: Ethernet Port Read-Only System Variables

Variable Structure
This table describes the parameters of the ETH_R system variable (ETH_R_STRUCT type):

%MW Var Name Type Comment


60050 i_byIPAddress ARRAY[0..3] OF IP address [aaa.bbb.ccc.ddd]:
BYTE  i_byIPAddress[0] = aaa
 ...
 i_byIPAddress[3] = ddd

60052 i_bySubNetMask ARRAY[0..3] OF Subnet Mask [aaa.bbb.ccc.ddd]:


BYTE  i_bySub-netMask[0] = aaa
 ...
 i_bySub-netMask[3] = ddd

60054 i_byGateway ARRAY[0..3] OF Gateway address


BYTE [aaa.bbb.ccc.ddd]:
 i_byGateway[0] = aaa
 ...
 i_byGateway[3] = ddd

60056 i_byMACAddress ARRAY[0..5] OF MAC address


BYTE [aa.bb.cc.dd.ee.ff]:
 i_byMACAddress[0] = aa
 ...
 i_byMACAddress[5] = ff

60059 i_sDeviceName STRING(15) Name used to get IP address from


server.
n/a i_wIpMode ETH_R_IP_MODE Method used to obtain an IP address.
(see page 82)
n/a i_byFDRServerIPAddress ARRAY[0..3] OF The IP address
BYTE [aaa.bbb.ccc.ddd] of the DHCP
or BootP server:
 i_byFDRServerIPAddress[0] = aaa
 ...
 i_byFDRServerIPAddress[3] = ddd

Equals 0.0.0.0 if Stored IP or Default


IP used.
n/a i_udiOpenTcpConnections UDINT Number of open TCP connections.
n/a i_udiFramesTransmittedOK UDINT Number of frames successfully
transmitted. Reset at Power ON or
with reset command
ETH_W.q_wResetCounter.
n/a means that there is no predefined %MW mapping for this system variable.

28 EIO0000001438 03/2018
M241 System Variables

%MW Var Name Type Comment


n/a i_udiFramedReceivedOK UDINT Number of frames successfully
received. Reset at Power ON or with
reset command
ETH_W.q_wResetCounter.
n/a i_udiTransmitBufferErrors UDINT Numbers of frames transmitted with
detected errors. Reset at Power ON or
with reset command
ETH_W.q_wResetCounter.
n/a i_udiReceiveBufferErrors UDINT Numbers of frames received with
detected errors. Reset at Power ON or
with reset command
ETH_W.q_wResetCounter.
n/a i_wFrameSendingProtocol ETH_R_FRAME_ Ethernet protocol configured for
PROTOCOL frames sending (IEEE 802.3 or
(see page 81) Ethernet II).
n/a i_wPortALinkStatus ETH_R_PORT_ Link of the Ethernet Port (0 = No Link,
LINK_STATUS 1 = Link connected to another Ethernet
(see page 85) device).
n/a i_wPortASpeed ETH_R_PORT_ Ethernet Port network speed (10Mb/s
SPEED or 100Mb/s).
(see page 86)
n/a i_wPortADuplexStatus ETH_R_PORT_ Ethernet Port duplex status (0 = Half or
DUPLEX_STATUS 1 = Full duplex).
(see page 83)
n/a i_udiPortACollisions UDINT Number of frames involved in one or
more collisions and subsequently
transmitted successfully. Reset at
Power ON or with reset command
ETH_W.q_wResetCounter.
n/a means that there is no predefined %MW mapping for this system variable.

EIO0000001438 03/2018 29
M241 System Variables

%MW Var Name Type Comment


Modbus TCP/IP Specific
n/a i_udiModbusMessageTransmitted UDINT Number of Modbus messages
transmitted.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiModbusMessageReceived UDINT Number of Modbus messages
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiModbusErrorMessage UDINT Modbus detected error messages
transmitted and received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a means that there is no predefined %MW mapping for this system variable.

%MW Var Name Type Comment


EtherNet/IP Specific
n/a i_udiETHIP_IOMessagingTransmitted UDINT EtherNet/IP Class 1 frames
transmitted.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiETHIP_IOMessagingReceived UDINT EtherNet/IP Class 1 frames received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiUCMM_Request UDINT EtherNet/IP Unconnected Messages
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiUCMM_Error UDINT EtherNet/IP invalid Unconnected
Messages received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it
should be considered extraneous.

30 EIO0000001438 03/2018
M241 System Variables

%MW Var Name Type Comment


n/a i_udiClass3_Request UDINT EtherNet/IP Class 3 requests
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiClass3_Error UDINT EtherNet/IP invalid class 3 requests
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_uiAssemblyInstanceInput UINT Input Assembly Instance number. See
the appropriate Programming Guide
of your controller for more information.
n/a i_uiAssemblyInstanceInputSize UINT Input Assembly Instance size. See the
appropriate Programming Guide of
your controller for more information.
n/a i_uiAssemblyInstanceOutput UINT Output Assembly Instance number.
See the appropriate Programming
Guide of your controller for more
information.
n/a i_uiAssemblyInstanceOutputSize UINT Output Assembly Instance size. See
the appropriate Programming Guide
of your controller for more information.
n/a i_uiETHIP_ConnectionTimeouts UINT Number of connection timeouts.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_ucEipRunIdle ETH_R_RUN_ Run (value = 1)/Idle(value = 0) flag for
IDLE EtherNet/IP class 1 connection.
(see page 87)
n/a i_byMasterIpTimeouts BYTE Ethernet Modbus TCP Master timeout
events counter.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_byMasterIpLost BYTE Ethernet Modbus TCP Master link
status: 0 = link OK, 1 = link lost.
n/a i_wPortAIpStatus ETH_R_PORT_ Ethernet TCP/IP port stack status.
IP_STATUS
(see page 84)
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it
should be considered extraneous.

EIO0000001438 03/2018 31
M241 System Variables

%MW Var Name Type Comment


n/a i_byIPAddress_If2 ARRAY[0..3] OF Not used.
BYTE
n/a i_bySubNetMask_If2 ARRAY[0..3] OF Not used.
BYTE
n/a i_byGateway_If2 ARRAY[0..3] OF Not used.
BYTE
n/a i_byMACAddress_If2 ARRAY[0..5] OF Not used.
BYTE
n/a i_sDeviceName_If2 STRING(15) Not used.
n/a i_wIpMode_If2 ETH_R_IP_MODE Not used.
(see page 82)
n/a i_wPortALinkStatus_If2 ETH_R_PORT_ Not used.
LINK_STATUS
(see page 85)
n/a i_wPortASpeed_If2 ETH_R_PORT_ Not used.
SPEED
(see page 86)
n/a i_wPortADuplexStatus_If2 ETH_R_PORT_ Not used.
DUPLEX_STATUS
(see page 83)
n/a i_wPortAIpStatus_If2 ETH_R_PORT_IP_ Not used.
STATUS
(see page 84)
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it
should be considered extraneous.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

32 EIO0000001438 03/2018
M241 System Variables

ETH_W: Ethernet Port Read/Write System Variables

Variable Structure
This table describes the parameters of the ETH_W system variable (ETH_W_STRUCT type):

%MW Var Name Type Comment


n/a q_wResetCounter WORD Transition from 0 to 1 resets all ETH_R counters.
To reset again, it is necessary to write 0 to this variable
before another transition from 0 to 1 can take place.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000001438 03/2018 33
M241 System Variables

Section 1.5
TM3_MODULE_R Structure

TM3_MODULE_R Structure

TM3_MODULE_R[0...13]: TM3 Modules Read-Only System Variables

Introduction
The TM3_MODULE_R is an array of 14 TM3_MODULE_R_STRUCT type. Each element of the array
returns diagnostic system variables for the corresponding TM3 expansion module.
For the Modicon M241 Logic Controller:
 TM3_MODULE_R[0] refers to the TM3 expansion module 0
 ...
 TM3_MODULE_R[13] refers to the TM3 expansion module 13

Variable Structure
The following table describes the parameters of the TM3_MODULE_R[0...13] system variable:

%MW Var Name Type Comment


n/a i_wProductID WORD TM3 expansion module ID.
n/a i_wModuleState TM3_MODULE_STATE Describes the state of the TM3 module.
(see page 91)

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

34 EIO0000001438 03/2018
M241 System Variables

Section 1.6
TM3_BUS_W Structure

TM3_BUS_W Structure

TM3_BUS_W: TM3 Bus System Variables

Variable Structure
This table describes the parameters of the TM3_BUS_W system variable (TM3_BUS_W_STRUCT
type):

Var Name Type Comment


q_wIOBusErrPassiv TM3_BUS_W_IOBUSERRMOD When set to ERR_ACTIVE (the default), bus errors
detected on TM3 expansion modules stop all I/O
exchanges.
When set to ERR_PASSIVE, passive I/O error
handing is used: the controller attempts to
continue data bus exchanges.
q_wIOBusRestart TM3_BUS_W_IOBUSINIT When set to 1, restarts the I/O expansion bus. This
is only necessary when q_wIOBusErrPassiv is
set to ERR_ACTIVE and at least one bit of
TM3_MODULE_R[i] .i_wModuleState is set to
TM3_BUS_ERROR.

For more information, refer to I/O Configuration General Description.

EIO0000001438 03/2018 35
M241 System Variables

Section 1.7
PROFIBUS_R Structure

PROFIBUS_R Structure

PROFIBUS_R: PROFIBUS Read-Only System Variables

Variable Structure
This table describes the parameters of the PROFIBUS_R system variable (PROFIBUS_R_STRUCT
type):

%MW Var Name Type Comment


n/a i_wPNOIdentifier WORD Slave identification code.
n/a i_wBusAdr UINT PROFIBUS slave address.
n/a i_CommState UDINT Value representing the state of the PROFIBUS module:
 0x00: Unknown
 0x01: Not configured
 0x02: Stop
 0x03: Idle
 0x04: Operate

n/a i_CommError UDINT Communication error code.


n/a i_ErrorCount UDINT Communication error counter.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

36 EIO0000001438 03/2018
M241 System Variables

Section 1.8
CART_R Structure

CART_R Structure

CART_R_STRUCT: Cartridge Read-Only System Variables

Variable Structure
The following table describes the parameters of the CART_R_STRUCT system variable:

%MW Var Name Type Comment


n/a i_uiModuleId CART_R_MODULE_ID Module ID
(see page 95)
n/a i_uifirmwareVersion UINT Firmware version
n/a i_udiCartState CART_R_STATE Cartridge state
(see page 96)

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000001438 03/2018 37
M241 System Variables

38 EIO0000001438 03/2018
Modicon M241 Logic Controller
M241, System Functions
EIO0000001438 03/2018

Chapter 2
M241 System Functions

M241 System Functions

Overview
This chapter describes the system functions included in the M241 PLCSystem library.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
2.1 M241 Read Functions 40
2.2 M241 Write Functions 47
2.3 M241 User Functions 51
2.4 TM3 Read Functions 57

EIO0000001438 03/2018 39
M241, System Functions

Section 2.1
M241 Read Functions

M241 Read Functions

Overview
This section describes the read functions included in the M241 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
GetImmediateFastInput: Read Input of an Embedded Expert I/O 41
GetRtc: Get Real Time Clock 42
IsFirstMastColdCycle: Indicate if this Cycle is the First MAST Cold Start Cycle 43
IsFirstMastCycle: Indicate if this Cycle is the First MAST Cycle 44
IsFirstMastWarmCycle: Indicate if this Cycle is the First MAST Warm Start Cycle 46

40 EIO0000001438 03/2018
M241, System Functions

GetImmediateFastInput: Read Input of an Embedded Expert I/O

Function Description
This function returns the current physical value of the input, which may be different from the current
logical value of that input. The value is read immedialely from the hardware at function call time.
Only I0 to I7 can be accessed through this function.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


The following table describes the input variables:

Input Type Comment


Block INT Not used.
Input INT Input Index to read from 0...7.

The following table describes the output variable:

Output Type Comment


GetImmediateFastInput BOOL Value of the input <Input> – FALSE/TRUE.

The following table describes the input/output variables:

Input/Output Type Comment


Error BOOL FALSE= operation is okay.
TRUE= operation error, the function returns an invalid
value.
ErrID IMMEDIATE_ERR_TYPE Operation error code when Error is TRUE.
(see page 98)

EIO0000001438 03/2018 41
M241, System Functions

GetRtc: Get Real Time Clock

Function Description
This function returns RTC time in seconds in UNIX format (time expired in seconds since January
1, 1970 at 00:00 UTC).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


The following table describes the I/O variable:

Output Type Comment


GetRtc DINT RTC in seconds in UNIX format.

Example
The following example describes how to get the RTC value:
VAR
MyRTC : DINT := 0;
END_VAR
MyRTC := GetRtc();

42 EIO0000001438 03/2018
M241, System Functions

IsFirstMastColdCycle: Indicate if this Cycle is the First MAST Cold Start Cycle

Function Description
This function returns TRUE during the first MAST cycle after a cold start (first cycle after download
or reset cold).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


The table describes the output variable:

Output Type Comment


IsFirstMastColdCycle BOOL TRUE during the first MAST task cycle after a cold start.

Example
Refer to the function IsFirstMastCycle (see page 44).

EIO0000001438 03/2018 43
M241, System Functions

IsFirstMastCycle: Indicate if this Cycle is the First MAST Cycle

Function Description
This function returns TRUE during the first MAST cycle after a start.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description

Output Type Comment


IsFirstMastCycle BOOL TRUE during the first MAST task cycle after a start.

Example
This example describes the three functions IsFirstMastCycle, IsFirstMastColdCycle and
IsFirstMastWarmCycle used together.
Use this example in MAST task. Otherwise, it may run several times or possibly never (an
additional task might be called several times or not called during 1 MAST task cycle):
VAR
MyIsFirstMastCycle : BOOL;
MyIsFirstMastWarmCycle : BOOL;
MyIsFirstMastColdCycle : BOOL;
END_VAR
MyIsFirstMastWarmCycle := IsFirstMastWarmCycle();
MyIsFirstMastColdCycle := IsFirstMastColdCycle();
MyIsFirstMastCycle := IsFirstMastCycle();
IF (MyIsFirstMastWarmCycle) THEN
(*This is the first Mast Cycle after a Warm Start: all variables are set
to their initialization values except the Retain variables*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;

44 EIO0000001438 03/2018
M241, System Functions

IF (MyIsFirstMastColdCycle) THEN
(*This is the first Mast Cycle after a Cold Start: all variables are set
to their initialization values including the Retain Variables*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;
IF (MyIsFirstMastCycle) THEN
(*This is the first Mast Cycle after a Start, i.e. after a Warm or Cold
Start as well as STOP/RUN commands*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;

EIO0000001438 03/2018 45
M241, System Functions

IsFirstMastWarmCycle: Indicate if this Cycle is the First MAST Warm Start Cycle

Function Description
This function returns TRUE during the first MAST cycle after a warm start.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


This table describes the output variable:

Output Type Comment


IsFirstMastWarmCycle BOOL TRUE during the first MAST task cycle after a warm start.

Example
Refer to the function IsFirstMastCycle (see page 44).

46 EIO0000001438 03/2018
M241, System Functions

Section 2.2
M241 Write Functions

M241 Write Functions

Overview
This section describes the write functions included in the M241 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
PhysicalWriteFastOutputs: Write Fast Output of an Embedded Expert I/O 48
SetRTCDrift: Set Compensation Value to the RTC 49

EIO0000001438 03/2018 47
M241, System Functions

PhysicalWriteFastOutputs: Write Fast Output of an Embedded Expert I/O

Function Description
This function writes a physical state to the Q0 to Q3 outputs at function call time.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


The following table describes the input variables:

Input Type Comment


Q0Value BOOL Requested value for the output 0.
Q1Value BOOL Requested value for the output 1.
Q2Value BOOL Requested value for the output 2.
Q3Value BOOL Requested value for the output 3.

The following table describes the output variable:

Output Type Comment


PhysicalWriteFastOutputs WORD Output value of the function.

NOTE: Only the first 4 bits of the returned value are significant and used as a bit field to indicate if
the output is written.
If the bit corresponding to the output is 1, the output is written successfully.
If the bit corresponding to the output is 0, the output is not written because it is already used by an
expert function.
If the bit corresponding to the output is 0b1111, all of the 4 outputs are written correctly.
If the bit corresponding to the output is 0b1110, Q0 is not written because it is used by a frequency
generator.

48 EIO0000001438 03/2018
M241, System Functions

SetRTCDrift: Set Compensation Value to the RTC

Function Description
This function accelerates or slows down the frequency of the RTC to give control to the application
for RTC compensation, depending on the operating environment (temperature, …). The
compensation value is given in seconds per week. It can be positive (accelerate) or negative (slow
down).
NOTE: The SetRTCDrift function must be called only once. Each new call replaces the
compensation value by the new one. The value is kept in the logic controller hardware while the
RTC is powered by the main supply or by the battery. If both battery and power supply are
removed, the RTC compensation value is not available.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variables Description


This table describes the input parameters:

Inputs Type Comment


RtcDrift SINT(-36...+73) Correction in seconds per week (-36 ... +73).

NOTE: The parameters Day, Hour, and Minute are used only to ensure backwards compatibility.
NOTE: If the value entered for RtcDrift exceeds the limit value, the logic controller firmware sets
the value to its maximum value.
This table describes the output variable:

Output Type Comment


SetRTCDrift RTCSETDRIFT_ERROR Returns RTC_OK (00 hex) if command is correct
(see page 99) otherwise returns the ID code of the detected error.

EIO0000001438 03/2018 49
M241, System Functions

Example
In this example, the function is called only once during the first MAST task cycle. It accelerates the
RTC by 4 seconds a week (18 seconds a month).
VAR
MyRTCDrift : SINT (-36...+73) := 0;
MyDay : DAY_OF_WEEK;
MyHour : HOUR;
MyMinute : MINUTE;
END_VAR
IF IsFirstMastCycle() THEN
MyRTCDrift := 4;
MyDay := 0;
MyHour := 0;
MyMinute := 0;
SetRTCDrift(MyRTCDrift, MyDay, MyHour, MyMinute);
END_IF

50 EIO0000001438 03/2018
M241, System Functions

Section 2.3
M241 User Functions

M241 User Functions

Overview
This section describes the DataFileCopy and ExecuteScript functions included in the M241
PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
DataFileCopy: Copy File Commands 52
ExecuteScript: Run Script Commands 55

EIO0000001438 03/2018 51
M241, System Functions

DataFileCopy: Copy File Commands

Function Block Description


This function block copies memory data to a file and vice versa. The file is located either within the
internal file system or an external file system (SD card).
The DataFileCopy function block can:
 Read data from a formatted file or
 Copy data from memory buffer to a formatted file. For further information, refer to Flash Memory
Organization (see Modicon M241 Logic Controller, Programming Guide).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


This table describes the input variables:

Input Type Comment


xExecute BOOL On rising edge, starts the function block execution.
On falling edge, resets the outputs of the function block when its execution terminates.
sFileName STRING File name without extension (the extension .DTA is automatically added). Use only a...z,
A...Z, 0...9 alphanumeric characters.
xRead BOOL TRUE: copy data from the file identified by sFileName to the internal memory of the
controller.
FALSE: copy data from the internal memory of the controller to the file identified by
sFileName.
xSecure BOOL TRUE: The MAC address is always stored in the file. Only a controller with the same
MAC address can read from the file.
FALSE: Another controller with the same type of memory can read from the file.

52 EIO0000001438 03/2018
M241, System Functions

Input Type Comment


iLocation INT 0: the file location is /usr/DTA in internal file system.
1: the file location is /usr/DTA in external file system (SD card).
uiSize UINT Indicates the size in bytes. Maximum is 65534 bytes.
Only use addresses of variables conforming to IEC 6113-1 (variables, arrays,
structures), for example:
Variable : int;
uiSize := SIZEOF (Variable);
dwAdd DWORD Indicates the address in the memory.
Only use addresses of variables conforming to IEC 6113-1 (variables, arrays,
structures), for example:
Variable : int;
dwAdd := ADR (Variable);

WARNING
UNINTENDED EQUIPMENT OPERATION
Verify that the memory location is of the correct size and the file is of the correct type before
copying the file to memory.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

This table describes the output variables:

Output Type Comment


xDone BOOL TRUE = indicates that the action is successfully completed.
xBusy BOOL TRUE = indicates that the function block is running.
xError BOOL TRUE = indicates that an error is detected and the function block
aborted the action.
eError DataFileCopyError Indicates the type of the data file copy detected error.
(see page 77)

NOTE: If you write to memory variable within the area of the file write, you generate a CRC
detected error.

EIO0000001438 03/2018 53
M241, System Functions

Example
This example describes how to copy file commands:
VAR
LocalArray : ARRAY [0..29] OF BYTE;
myFileName: STRING := 'exportfile';
EXEC_FLAG: BOOL;
DataFileCopy: DataFileCopy;
END_VAR
DataFileCopy(
xExecute:= EXEC_FLAG,
sFileName:= myFileName,
xRead:= FALSE,
xSecure:= FALSE,
iLocation:= DFCL_INTERNAL,
uiSize:= SIZEOF(LocalArray),
dwAdd:= ADR(LocalArray),
xDone=> ,
xBusy=> ,
xError=> ,
eError=> );

54 EIO0000001438 03/2018
M241, System Functions

ExecuteScript: Run Script Commands

Function Block Description


This function block can run the following SD card script commands:
 Download
 Upload
 SetNodeName
 Delete
 Reboot
 ChangeModbusPort

For information on the required script file format, refer to Script Files for SD Cards.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

EIO0000001438 03/2018 55
M241, System Functions

I/O Variable Description


This table describes the input variables:

Input Type Comment


xExecute BOOL On detection of a rising edge, starts the function block execution.
On detection of a falling edge, resets the outputs of the function block
when its execution terminates.
sCmd STRING SD card script command syntax.
Simultaneous command executions are not allowed: if a command is
being executed from another function block or from an SD card script
then the function block queues the command and does not execute it
immediately.
NOTE: An SD card script executed from an SD card is considered as
being executed until the SD card has been removed.

This table describes the output variables:

Output Type Comment


xDone BOOL TRUE indicates that the action is successfully completed.
xBusy BOOL TRUE indicates that the function block is running.
xError BOOL TRUE indicates error detection; the function block aborts the
action.
eError ExecuteScriptError Indicates the type of the execute script detected error.
(see page 79)

Example
This example describes how to execute an Upload script command:
VAR
EXEC_FLAG: BOOL;
ExecuteScript: ExecuteScript;
END_VAR
ExecuteScript(
xExecute:= EXEC_FLAG,
sCmd:= 'Upload "/usr/Syslog/*"',
xDone=> ,
xBusy=> ,
xError=> ,
eError=> );

56 EIO0000001438 03/2018
M241, System Functions

Section 2.4
TM3 Read Functions

TM3 Read Functions

Overview
This section describes the TM3 read functions included in the M241 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
TM3_GetModuleBusStatus: Get TM3 Module Bus Status 58
TM3_GetModuleFWVersion: Get TM3 Module Firmware Version 59
TM3_GetModuleInternalStatus: Get TM3 Module Internal Status 60

EIO0000001438 03/2018 57
M241, System Functions

TM3_GetModuleBusStatus: Get TM3 Module Bus Status

Function Description
This function returns the bus status of the module. The index of the module is given as an input
parameter.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


The following table describes the input variable:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for the
second, and so on).

The following table describes the output variable:

Output Type Comment


TM3_GetModuleBusStatus TM3_ERR_CODE Returns TM3_OK (00 hex) if command is correct
(see page 89) otherwise returns the ID code of the detected error.

58 EIO0000001438 03/2018
M241, System Functions

TM3_GetModuleFWVersion: Get TM3 Module Firmware Version

Function Description
This function returns the firmware version of a specified TM3 module.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description


The following table describes the input variables:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for
the second, and so on).

The following table describes the output variable:

Output Type Comment


TM3_GetModuleFWVersion UINT Returns the firmware version of the module, or
FFFF hex if the information cannot be read.
For example, 001A hex indicates firmware version 26.

EIO0000001438 03/2018 59
M241, System Functions

TM3_GetModuleInternalStatus: Get TM3 Module Internal Status

Function Description
This function fills the pStatusBuffer with the status table of the module ModuleIndex.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 103).

I/O Variable Description

WARNING
UNINTENDED EQUIPMENT OPERATION
Ensure that the pStatusBuffer is allocated.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The following table describes the input variables:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for
the second, and so on).
StatusOffset BYTE Offset of the first status to be read in the status table.
StatusSize BYTE Number of bytes to be read in the status table.
pStatusBuffer POINTER TO BYTE Buffer containing the read status table.

The following table describes the output variable:

Output Type Comment


TM3_GetModuleInternalStatus TM3_ERR_CODE Returns TM3_OK (00 hex) if command is correct
(see page 89) otherwise returns the ID code of the error.

60 EIO0000001438 03/2018
M241, System Functions

Example
The following example describes how to get the module internal status:
VAR
AMM3HT_Channel1_Input_Status: BYTE;
END_VAR
TM3_GetModuleInternalStatus(0, 1, 1, ADR(AMM3HT_Channel1_Input_Status));

EIO0000001438 03/2018 61
M241, System Functions

62 EIO0000001438 03/2018
Modicon M241 Logic Controller
M241 PLC System Library Data Types
EIO0000001438 03/2018

Chapter 3
M241 PLCSystem Library Data Types

M241 PLCSystem Library Data Types

Overview
This chapter describes the data types of the M241 PLCSystem Library.
There are 2 kinds of data types available:
 System variable data types are used by the system variables (see page 11) of the M241
PLCSystem Library (PLC_R, PLC_W,...).
 System function data types are used by the read/write system functions (see page 39) of the
M241 PLCSystem Library.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
3.1 PLC_RW System Variables Data Types 64
3.2 DataFileCopy System Variables Data Types 76
3.3 ExecScript System Variables Data Types 79
3.4 ETH_RW System Variables Data Types 80
3.5 TM3_MODULE_RW System Variables Data Types 88
3.6 Cartridge System Variables Data Types 93
3.7 System Function Data Types 97

EIO0000001438 03/2018 63
M241 PLC System Library Data Types

Section 3.1
PLC_RW System Variables Data Types

PLC_RW System Variables Data Types

Overview
This section lists and describes the system variable data types included in the PLC_R and PLC_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
PLC_R_APPLICATION_ERROR: Detected Application Error Status Codes 65
PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes 67
PLC_R_IO_STATUS: I/O Status Codes 68
PLC_R_SDCARD_STATUS: SD Card Slot Status Codes 69
PLC_R_STATUS: Controller Status Codes 70
PLC_R_STOP_CAUSE: From RUN State to Other State Transition Cause Codes 71
PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection Status Codes 73
PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes 74
PLC_W_COMMAND: Control Command Codes 75

64 EIO0000001438 03/2018
M241 PLC System Library Data Types

PLC_R_APPLICATION_ERROR: Detected Application Error Status Codes

Enumerated Type Description


The PLC_R_APPLICATION_ERROR enumeration data type contains the following values:

Enumerator Value Comment What to do


PLC_R_APP_ERR_UNKNOWN FFFF hex Undefined error detected. Contact your local support.
PLC_R_APP_ERR_NOEXCEPTION 0000 hex No error detected. –
PLC_R_APP_ERR_WATCHDOG 0010 hex Task watchdog expired. Check your application. See
chapter (see Modicon M241
Logic Controller,
Programming Guide). A
reset is needed to enter Run
mode.
PLC_R_APP_ERR_ 0011 hex System watchdog expired. If the problem is
HARDWAREWATCHDOG reproducible, check for
disconnected
communication ports. If the
problem persists, update the
firmware. If the problem still
persists, contact your local
support.
PLC_R_APP_ERR_IO_CONFIG_ 0012 hex Incorrect I/O configuration Your application might be
ERROR parameters detected. corrupted. To resolve this
issue, use one of the
methods:
1. Build → Clean All
2. Export/Import your
application.
3. Upgrade SoMachine to
the latest version.
PLC_R_APP_ERR_UNRESOLVED_ 0018 hex Undefined functions detected. Delete the unresolved
EXTREFS functions from the
application.
PLC_R_APP_ERR_IEC_TASK_ 0025 hex Incorrect Task configuration Your application might be
CONFIG_ERROR parameters detected. corrupted. To resolve this
issue, use one of the
methods:
1. Build → Clean All
2. Export/Import your
application.
3. Upgrade SoMachine to
the latest version.
PLC_R_APP_ERR_ILLEGAL_ 0050 hex Undefined instruction detected. Debug your application to
INSTRUCTION resolve the problem.

EIO0000001438 03/2018 65
M241 PLC System Library Data Types

Enumerator Value Comment What to do


PLC_R_APP_ERR_ACCESS_ 0051 hex Attempted access to reserved Debug your application to
VIOLATION memory area. resolve the problem.
PLC_R_APP_ERR_DIVIDE_BY_ ZERO 0102 hex Integer division by zero Debug your application to
detected. resolve the problem.
PLC_R_APP_ERR_PROCESSORLOAD_ 0105 hex Processor overloaded by Reduce the application
WATCHDOG Application Tasks. workload by improving the
application architecture.
Increase the task cycle
duration. Reduce event
frequency.
PLC_R_APP_ERR_DIVIDE_REAL_ 0152 hex Real division by zero detected. Debug your application to
BY_ZERO resolve the problem.
PLC_R_APP_ERR_EXPIO_EVENTS_ 4E20 hex Too many events on expert I/Os Reduce the number of event
COUNT_EXCEEDED are detected. tasks.
PLC_R_APP_ERR_APPLICATION_ 4E21 hex Mismatch in the application The application version in
VERSION_MISMATCH version detected. the logic controller does not
match the version in
SoMachine. Refer to
Applications
(see SoMachine,
Programming Guide).

66 EIO0000001438 03/2018
M241 PLC System Library Data Types

PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes

Enumerated Type Description


The PLC_R_BOOT_PROJECT_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_NO_BOOT_PROJECT 0000 hex Boot project does not exist in Flash
memory.
PLC_R_BOOT_PROJECT_CREATION_IN_PROGRESS 0001 hex Boot project is being created.
PLC_R_DIFFERENT_BOOT_PROJECT 0002 hex Boot project in Flash is different from
the project loaded in RAM.
PLC_R_VALID_BOOT_PROJECT FFFF hex Boot project in Flash is the same as
the project loaded in RAM.

EIO0000001438 03/2018 67
M241 PLC System Library Data Types

PLC_R_IO_STATUS: I/O Status Codes

Enumerated Type Description


The PLC_R_IO_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_IO_OK FFFF hex Inputs/Outputs are operational.
PLC_R_IO_NO_INIT 0001 hex Inputs/Outputs are not initialized.
PLC_R_IO_CONF_FAULT 0002 hex Incorrect I/O configuration parameters
detected.
PLC_R_IO_SHORTCUT_FAULT 0003 hex Inputs/Outputs short-circuit detected.
PLC_R_IO_POWER_SUPPLY_FAULT 0004 hex Inputs/Outputs power supply error
detected.

68 EIO0000001438 03/2018
M241 PLC System Library Data Types

PLC_R_SDCARD_STATUS: SD Card Slot Status Codes

Enumerated Type Description


The PLC_R_SDCARD_STATUS enumeration data type contains the following values:

Enumerator Value Comment


NO_SDCARD 0000 hex No SD card detected in the slot or the slot is not connected.
SDCARD_READONLY 0001 hex SD card is in read-only mode.
SDCARD_READWRITE 0002 hex SD card is in read/write mode.
SDCARD_ERROR 0003 hex Error detected in the SD card. More detail on the error that
occurred is written to the file FwLog.txt.

EIO0000001438 03/2018 69
M241 PLC System Library Data Types

PLC_R_STATUS: Controller Status Codes

Enumerated Type Description


The PLC_R_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_EMPTY 0000 hex Controller does not contain an application.
PLC_R_STOPPED 0001 hex Controller is stopped.
PLC_R_RUNNING 0002 hex Controller is running.
PLC_R_HALT 0004 hex Controller is in a HALT state. (see the controller
state diagram in your controller programming
guide).
PLC_R_BREAKPOINT 0008 hex Controller has paused at a breakpoint.

70 EIO0000001438 03/2018
M241 PLC System Library Data Types

PLC_R_STOP_CAUSE: From RUN State to Other State Transition Cause Codes

Enumerated Type Description


The PLC_R_STOP_CAUSE enumeration data type contains the following values:

Enumerator Value Comment What to do


PLC_R_STOP_REASON_ 00 hex Initial value or stop cause is undefined. Contact your local support
UNKNOWN in case of undefined stop
cause.
PLC_R_STOP_REASON_HW_ 01 hex Stopped after hardware watchdog timeout. Contact your local support.
WATCHDOG
PLC_R_STOP_REASON_ 02 hex Stopped after reset. See reset possibilities in
RESET chapter .
PLC_R_STOP_REASON_ 03 hex Stopped after exception. Check your application.
EXCEPTION See chapter (see Modicon
M241 Logic Controller,
Programming Guide). A
reset is needed to enter
Run mode.
PLC_R_STOP_REASON_ 04 hex Stopped after a user request. See chapter (see Modicon
USER M241 Logic Controller,
Programming Guide).
PLC_R_STOP_REASON_ 05 hex Stopped after a program command –
IECPROGRAM request (for example: control command
with parameter
PLC_W.q_wPLCControl:
=PLC_W_COMMAND.PLC_W_STOP;).
PLC_R_STOP_REASON_ 06 hex Stopped after a remove application See chapter .
DELETE command.
PLC_R_STOP_REASON_ 07 hex Stopped after entering debug mode. –
DEBUGGING
PLC_R_STOP_FROM_ 0A hex Stopped after a request from the network, –
NETWORK_REQUEST the controller Web server, or PLC_W
command.
PLC_R_STOP_FROM_ INPUT 0B hex Stop required by a controller input. –
PLC_R_STOP_FROM_RUN_ 0C hex Stop required by the controller switch.
STOP_SWITCH

EIO0000001438 03/2018 71
M241 PLC System Library Data Types

Enumerator Value Comment What to do


PLC_R_STOP_REASON_ 0D hex Stopped after an unsuccessful check Retain variables were
RETAIN_MISMATCH context test during rebooting. deleted because they were
not referenced in the
application. If the
application sets retain
variables to their
intialization values, the
(see Modicon M241 Logic
Controller, Programming
Guide) is available.
PLC_R_STOP_REASON_ 0E hex Stopped after an unsuccessful compare Create a valid boot
BOOT_APPLI_MISMATCH between the boot application and the application.
application that was in the memory before
rebooting.
PLC_R_STOP_REASON_ 0F hex Stopped after a power interruption. –
POWERFAIL

For more information for reasons the controller has stopped, refer to the Controller State
Description.

72 EIO0000001438 03/2018
M241 PLC System Library Data Types

PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection Status Codes

Enumerated Type Description


The PLC_R_TERMINAL_PORT_STATUS enumeration data type contains the following values:

Enumerator Value Comment


TERMINAL_NOT_CONNECTED 00 hex No PC is connected to the programming port.
TERMINAL_CONNECTION_IN_PROGRESS 01 hex Connection is in progress.
TERMINAL_CONNECTED 02 hex PC is connected to the programming port.
TERMINAL_ERROR 0F hex Error detected during connection.

EIO0000001438 03/2018 73
M241 PLC System Library Data Types

PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes

Enumerated Type Description


The PLC_R_TM3_BUS_STATE enumeration data type contains the following values:

Enumerator Value Comment


TM3_CONF_ERROR 01 hex Error detected due to mismatch in the physical
configuration and the configuration in SoMachine.
TM3_OK 03 hex The physical configuration and the configuration in
SoMachine match.
TM3_POWER_SUPPLY_ERROR 04 hex Error detected in power supply.

74 EIO0000001438 03/2018
M241 PLC System Library Data Types

PLC_W_COMMAND: Control Command Codes

Enumerated Type Description


The PLC_W_COMMAND enumeration data type contains the following values:

Enumerator Value Comment


PLC_W_STOP 0001 hex Command to stop the controller.
PLC_W_RUN 0002 hex Command to run the controller.
PLC_W_RESET_COLD 0004 hex Command to initiate a Controller cold reset.
PLC_W_RESET_WARM 0008 hex Command to initiate a Controller warm reset.

EIO0000001438 03/2018 75
M241 PLC System Library Data Types

Section 3.2
DataFileCopy System Variables Data Types

DataFileCopy System Variables Data Types

Overview
This section lists and describes the system variable data types included in the DataFileCopy
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
DataFileCopyError: Detected Error Codes 77
DataFileCopyLocation: Location Codes 78

76 EIO0000001438 03/2018
M241 PLC System Library Data Types

DataFileCopyError: Detected Error Codes

Enumerated Type Description


The DataFileCopyError enumeration data type contains the following values:

Enumerator Value Description


ERR_NO_ERR 00 hex No error detected.
ERR_FILE_NOT_FOUND 01 hex The file does not exist.
ERR_FILE_ACCESS_REFUSED 02 hex The file cannot be opened.
ERR_INCORRECT_SIZE 03 hex The request size is not the same as size
read from file.
ERR_CRC_ERR 04 hex The CRC is not correct and the file is
assumed to be corrupted.
ERR_INCORRECT_MAC 05 hex The controller attempting to read from the
file does not have the same MAC address
as that contained in the file.

EIO0000001438 03/2018 77
M241 PLC System Library Data Types

DataFileCopyLocation: Location Codes

Enumerated Type Description


The DataFileCopyLocation enumeration data type contains the following values:

Enumerator Value Description


DFCL_INTERNAL 00 hex Data file with DTA extension is located in /usr/Dta directory.
DFCL_EXTERNAL 01 hex Data file with DTA extension is located in /sd0/usr/Dta directory.
DFCL_TBD 02 hex Not used.

78 EIO0000001438 03/2018
M241 PLC System Library Data Types

Section 3.3
ExecScript System Variables Data Types

ExecScript System Variables Data Types

ExecuteScriptError: Detected Error Codes

Enumerated Type Description


The ExecuteScriptError enumeration data type contains the following values:

Enumerator Value Description


CMD_OK 00 hex No error detected.
ERR_CMD_UNKNOWN 01 hex The command is not recognized.
ERR_SD_CARD_MISSING 02 hex SD card is not present.
ERR_SEE_FWLOG 03 hex There was an error detected during command
execution, see FwLog.txt. For more
information, refer to File Type (see Modicon
M241 Logic Controller, Programming Guide).
ERR_ONLY_ONE_COMMAND_ALLOWED 04 hex An attempt was made to execute several scripts
simultaneously.
CMD_BEING_EXECUTED 05 hex A script is already in progress.

EIO0000001438 03/2018 79
M241 PLC System Library Data Types

Section 3.4
ETH_RW System Variables Data Types

ETH_RW System Variables Data Types

Overview
This section lists and describes the system variable data types included in the ETH_R and ETH_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes 81
ETH_R_IP_MODE: IP Address Source Codes 82
ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes 83
ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes 84
ETH_R_PORT_LINK_STATUS: Communication Link Status Codes 85
ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port Codes 86
ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes 87

80 EIO0000001438 03/2018
M241 PLC System Library Data Types

ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes

Enumerated Type Description


The ETH_R_FRAME_PROTOCOL enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_802_3 00 hex The protocol used for frame transmission is IEEE 802.3.
ETH_R_ETHERNET_II 01 hex The protocol used for frame transmission is Ethernet II.

EIO0000001438 03/2018 81
M241 PLC System Library Data Types

ETH_R_IP_MODE: IP Address Source Codes

Enumerated Type Description


The ETH_R_IP_MODE enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_STORED 00 hex Stored IP address is used.
ETH_R_BOOTP 01 hex Bootstrap protocol is used to get an IP address.
ETH_R_DHCP 02 hex DHCP protocol is used to get an IP address.
ETH_DEFAULT_IP FF hex Default IP address is used.

82 EIO0000001438 03/2018
M241 PLC System Library Data Types

ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes

Enumerated Type Description


The ETH_R_PORT_DUPLEX_STATUS enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_PORT_HALF_DUPLEX 00 hex Half duplex transmission mode is used.
ETH_R_FULL_DUPLEX 01 hex Full duplex transmission mode is used.
ETH_R_PORT_NA_DUPLEX 03 hex No duplex transmission mode is used.

EIO0000001438 03/2018 83
M241 PLC System Library Data Types

ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes

Enumerated Type Description


The ETH_R_PORT_IP_STATUS enumeration data type contains the following values:

Enumerator Value Comment


WAIT_FOR_PARAMS 00 hex Waiting for parameters.
WAIT_FOR_CONF 01 hex Waiting for configuration.
DATA_EXCHANGE 02 hex Ready for data exchange.
ETH_ERROR 03 hex Ethernet TCP/IP port error detected (cable
disconnected, invalid configuration, and so on).
DUPLICATE_IP 04 hex IP address already used by another equipment.

84 EIO0000001438 03/2018
M241 PLC System Library Data Types

ETH_R_PORT_LINK_STATUS: Communication Link Status Codes

Enumerated Type Description


The ETH_R_PORT_LINK_STATUS enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_LINK_DOWN 00 hex Communication link not available to another device.
ETH_R_LINK_UP 01 hex Communication link available to another device.

EIO0000001438 03/2018 85
M241 PLC System Library Data Types

ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port Codes

Enumerated Type Description


The ETH_R_PORT_SPEED enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_SPEED_NA 0 dec Network speed is 0 megabits per second.
ETH_R_SPEED_10_MB 10 dec Network speed is 10 megabits per second.
ETH_R_100_MB 100 dec Network speed is 100 megabits per second.

86 EIO0000001438 03/2018
M241 PLC System Library Data Types

ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes

Enumerated Type Description


The ETH_R_RUN_IDLE enumeration data type contains the following values:

Enumerator Value Comment


IDLE 00 hex EtherNet/IP connection is idle.
RUN 01 hex EtherNet/IP connection is running.

EIO0000001438 03/2018 87
M241 PLC System Library Data Types

Section 3.5
TM3_MODULE_RW System Variables Data Types

TM3_MODULE_RW System Variables Data Types

Overview
This section lists and describes the system variable data types included in the TM3_MODULE_R and
TM3_MODULE_W structures.

What Is in This Section?


This section contains the following topics:
Topic Page
TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes 89
TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read Array Type 90
TM3_MODULE_STATE: TM3 Expansion Module State Codes 91
TM3_BUS_W_IOBUSERRMOD: TM3 bus error mode 92

88 EIO0000001438 03/2018
M241 PLC System Library Data Types

TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes

Enumerated Type Description


The TM3_ERR_CODE enumeration data type contains the following values:

Enumerator Value Comment


TM3_NO_ERR 00 hex Last bus exchange with the expansion module was successful.
TM3_ERR_FAILED 01 hex Error detected due to the last bus exchange with the expansion
module was unsuccessful.
TM3_ERR_PARAMETER 02 hex Parameter error detected in the last bus exchange with the
module.
TM3_ERR_COK 03 hex Temporary or permanent hardware error detected on one of the
TM3 expansion modules.
TM3_ERR_BUS 04 hex Bus error detected in the last bus exchange with the expansion
module.

EIO0000001438 03/2018 89
M241 PLC System Library Data Types

TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read Array Type

Description
The TM3_MODULE_R_ARRAY_TYPE is an array of 0...13 TM3_MODULE_R_STRUCT.

90 EIO0000001438 03/2018
M241 PLC System Library Data Types

TM3_MODULE_STATE: TM3 Expansion Module State Codes

Enumerated Type Description


The TM3_MODULE_STATE enumeration data type contains the following values:

Enumerator Value Comment


TM3_EMPTY 00 hex No module.
TM3_CONF_ERROR 01 hex Physical expansion module does not match with the one
configured in SoMachine.
TM3_BUS_ERROR 02 hex Bus error detected in the last exchange with the module.
TM3_OK 03 hex Last bus exchange with this module was successful.
TM3_MISSING_OPT_MOD 05 hex Optional module is not physically present.

EIO0000001438 03/2018 91
M241 PLC System Library Data Types

TM3_BUS_W_IOBUSERRMOD: TM3 bus error mode

Enumerated Type Description


The TM3_BUS_W_IOBUSERRMOD enumeration data type contains the following values:

Enumerator Value Comment


IOBUS_ERR_ACTIVE 00 hex Active mode. The logic controller stops all I/O exchanges
on the TM3 bus on detection of a permanent error. Refer to
I/O Configuration General Description (see Modicon M241
Logic Controller, Programming Guide).
IOBUS_ERR_PASSIVE 01 hex Passive mode. I/O exchanges continue on the TM3 bus
even if an error is detected.

92 EIO0000001438 03/2018
M241 PLC System Library Data Types

Section 3.6
Cartridge System Variables Data Types

Cartridge System Variables Data Types

Overview
This section lists and describes the system variable data types included in the Cartridge
structure.

What Is in This Section?


This section contains the following topics:
Topic Page
CART_R_ARRAY_TYPE: Cartridge Read Array Type 94
CART_R_MODULE_ID: Cartridge Read Module Identifier 95
CART_R_STATE: Cartridge Read State 96

EIO0000001438 03/2018 93
M241 PLC System Library Data Types

CART_R_ARRAY_TYPE: Cartridge Read Array Type

Description
The CART_R_ARRAY_TYPE is an array of 0..1 CART_R_STRUCT.

94 EIO0000001438 03/2018
M241 PLC System Library Data Types

CART_R_MODULE_ID: Cartridge Read Module Identifier

Enumerated Type Description


The CART_R_MODULE_ID enumeration data type contains the following values:

Enumerator Value Description


CART_R_MODULE_ID 40 hex TMC4AI2
CART_R_MODULE_ID 41 hex TMC4AQ2
CART_R_MODULE_ID 42 hex TMC4TI2
CART_R_MODULE_ID 48 hex TMC4HOIS01
CART_R_MODULE_ID 49 hex TMC4PACK01
CART_R_MODULE_ID FF hex None

EIO0000001438 03/2018 95
M241 PLC System Library Data Types

CART_R_STATE: Cartridge Read State

Enumerated Type Description


The CART_R_STATE enumeration data type contains the following values:

Enumerator Value Comment


CONFIGURED 00 hex Cartridge is configured.
INITIALIZED_NOT_CONFIGURED 01 hex Cartridge is initialized but not configured.
NOT_INITIALIZED 02 hex Cartridge is not initialized.

96 EIO0000001438 03/2018
M241 PLC System Library Data Types

Section 3.7
System Function Data Types

System Function Data Types

Overview
This section describes the different system function data types of the M241 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
IMMEDIATE_ERR_TYPE: GetImmediateFastInput Read Input of Embedded Expert I/O 98
Codes
RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error Codes 99

EIO0000001438 03/2018 97
M241 PLC System Library Data Types

IMMEDIATE_ERR_TYPE: GetImmediateFastInput Read Input of Embedded


Expert I/O Codes

Enumerated Type Description


The enumeration data type contains the following values:

Enumerator Type Comment


IMMEDIATE_NO_ERROR Word No errors detected.
IMMEDIATE_UNKNOWN Word The reference of Immediate function
is incorrect or not configured.
IMMEDIATE_UNKNOWN_PARAMETER Word A parameter reference is incorrect.

98 EIO0000001438 03/2018
M241 PLC System Library Data Types

RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error Codes

Enumerated Type Description


The RTCSETDRIFT_ERROR enumeration data type contains the following values:

Enumerator Value Comment


RTC_OK 00 hex RTC drift correctly configured.
RTC_BAD_DAY 01 hex Not used.
RTC_BAD_HOUR 02 hex Not used.
RTC_BAD_MINUTE 03 hex Not used.
RTC_BAD_DRIFT 04 hex RTC Drift parameter out of range.
RTC_INTERNAL_ERROR 05 hex RTC Drift settings rejected on internal error detected.

EIO0000001438 03/2018 99
M241 PLC System Library Data Types

100 EIO0000001438 03/2018


Modicon M241 Logic Controller

EIO0000001438 03/2018

Appendices

EIO0000001438 03/2018 101


102 EIO0000001438 03/2018
Modicon M241 Logic Controller
Function and Function Block Representation
EIO0000001438 03/2018

Appendix A
Function and Function Block Representation

Function and Function Block Representation

Overview
Each function can be represented in the following languages:
 IL: Instruction List
 ST: Structured Text
 LD: Ladder Diagram
 FBD: Function Block Diagram
 CFC: Continuous Function Chart

This chapter provides functions and function blocks representation examples and explains how to
use them for IL and ST languages.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Differences Between a Function and a Function Block 104
How to Use a Function or a Function Block in IL Language 105
How to Use a Function or a Function Block in ST Language 109

EIO0000001438 03/2018 103


Function and Function Block Representation

Differences Between a Function and a Function Block

Function
A function:
 is a POU (Program Organization Unit) that returns one immediate result.
 is directly called with its name (not through an instance).
 has no persistent state from one call to the other.
 can be used as an operand in other expressions.

Examples: boolean operators (AND), calculations, conversion (BYTE_TO_INT)

Function Block
A function block:
 is a POU (Program Organization Unit) that returns one or more outputs.
 needs to be called by an instance (function block copy with dedicated name and variables).
 each instance has a persistent state (outputs and internal variables) from one call to the other
from a function block or a program.
Examples: timers, counters
In the example, Timer_ON is an instance of the function block TON:

104 EIO0000001438 03/2018


Function and Function Block Representation

How to Use a Function or a Function Block in IL Language

General Information
This part explains how to implement a function and a function block in IL language.
Functions IsFirstMastCycle and SetRTCDrift and Function Block TON are used as
examples to show implementations.

Using a Function in IL Language


This procedure describes how to insert a function in IL language:

Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see SoMachine, Programming Guide).
2 Create the variables that the function requires.
3 If the function has 1 or more inputs, start loading the first input using LD instruction.
4 Insert a new line below and:
 type the name of the function in the operator column (left field), or
 use the Input Assistant to select the function (select Insert Box in the context menu).

5 If the function has more than 1 input and when Input Assistant is used, the necessary number of lines
is automatically created with ??? in the fields on the right. Replace the ??? with the appropriate
value or variable that corresponds to the order of inputs.
6 Insert a new line to store the result of the function into the appropriate variable: type ST instruction
in the operator column (left field) and the variable name in the field on the right.

To illustrate the procedure, consider the Functions IsFirstMastCycle (without input parameter)
and SetRTCDrift (with input parameters) graphically presented below:

Function Graphical Representation


without input parameter:
IsFirstMastCycle

with input parameters:


SetRTCDrift

EIO0000001438 03/2018 105


Function and Function Block Representation

In IL language, the function name is used directly in the operator column:

Function Representation in POU IL Editor


IL example of a function
without input parameter:
IsFirstMastCycle

IL example of a function
with input parameters:
SetRTCDrift

106 EIO0000001438 03/2018


Function and Function Block Representation

Using a Function Block in IL Language


This procedure describes how to insert a function block in IL language:

Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see SoMachine, Programming Guide).
2 Create the variables that the function block requires, including the instance name.
3 Function Blocks are called using a CAL instruction:
 Use the Input Assistant to select the FB (right-click and select Insert Box in the context menu).
 Automatically, the CAL instruction and the necessary I/O are created.

Each parameter (I/O) is an instruction:


 Values to inputs are set by ":=".
 Values to outputs are set by "=>".

4 In the CAL right-side field, replace ??? with the instance name.
5 Replace other ??? with an appropriate variable or immediate value.

To illustrate the procedure, consider this example with the TON Function Block graphically
presented below:

Function Block Graphical Representation


TON

EIO0000001438 03/2018 107


Function and Function Block Representation

In IL language, the function block name is used directly in the operator column:

Function Block Representation in POU IL Editor


TON

108 EIO0000001438 03/2018


Function and Function Block Representation

How to Use a Function or a Function Block in ST Language

General Information
This part explains how to implement a Function and a Function Block in ST language.
Function SetRTCDrift and Function Block TON are used as examples to show implementations.

Using a Function in ST Language


This procedure describes how to insert a function in ST language:

Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding and
Calling POUs (see SoMachine, Programming Guide).
2 Create the variables that the function requires.
3 Use the general syntax in the POU ST Editor for the ST language of a function. The general syntax is:
FunctionResult:= FunctionName(VarInput1, VarInput2,.. VarInputx);

To illustrate the procedure, consider the function SetRTCDrift graphically presented below:

Function Graphical Representation


SetRTCDrift

The ST language of this function is the following:

Function Representation in POU ST Editor


SetRTCDrift PROGRAM MyProgram_ST
VAR myDrift: SINT(-29..29) := 5;
myDay: DAY_OF_WEEK := SUNDAY;
myHour: HOUR := 12;
myMinute: MINUTE;
myRTCAdjust: RTCDRIFT_ERROR;
END_VAR
myRTCAdjust:= SetRTCDrift(myDrift, myDay, myHour, myMinute);

EIO0000001438 03/2018 109


Function and Function Block Representation

Using a Function Block in ST Language


This procedure describes how to insert a function block in ST language:

Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information on adding,
declaring and calling POUs, refer to the related documentation (see SoMachine, Programming
Guide).
2 Create the input and output variables and the instance required for the function block:
 Input variables are the input parameters required by the function block
 Output variables receive the value returned by the function block

3 Use the general syntax in the POU ST Editor for the ST language of a Function Block. The general
syntax is:
FunctionBlock_InstanceName(Input1:=VarInput1, Input2:=VarInput2,...
Ouput1=>VarOutput1, Ouput2=>VarOutput2,...);

To illustrate the procedure, consider this example with the TON function block graphically
presented below:

Function Block Graphical Representation


TON

110 EIO0000001438 03/2018


Function and Function Block Representation

This table shows examples of a function block call in ST language:

Function Block Representation in POU ST Editor


TON

EIO0000001438 03/2018 111


Function and Function Block Representation

112 EIO0000001438 03/2018


Modicon M241 Logic Controller
Glossary
EIO0000001438 03/2018

Glossary

!
%MW
According to the IEC standard, %MW represents a memory word register (for example, a language
object of type memory word).

A
application
A program including configuration data, symbols, and documentation.
ARRAY
The systematic arrangement of data objects of a single type in the form of a table defined in logic
controller memory. The syntax is as follows: ARRAY [<dimension>] OF <Type>
Example 1: ARRAY [1..2] OF BOOL is a 1-dimensional table with 2 elements of type BOOL.
Example 2: ARRAY [1..10, 1..20] OF INT is a 2-dimensional table with 10 x 20 elements of
type INT.

B
BOOL
(boolean) A basic data type in computing. A BOOL variable can have one of these values: 0
(FALSE), 1 (TRUE). A bit that is extracted from a word is of type BOOL; for example, %MW10.4 is a
fifth bit of memory word number 10.
Boot application
(boot application) The binary file that contains the application. Usually, it is stored in the controller
and allows the controller to boot on the application that the user has generated.
BOOTP
(bootstrap protocol) A UDP network protocol that can be used by a network client to automatically
obtain an IP address (and possibly other data) from a server. The client identifies itself to the server
using the client MAC address. The server, which maintains a pre-configured table of client device
MAC addresses and associated IP addresses, sends the client its pre-configured IP address.
BOOTP was originally used as a method that enabled diskless hosts to be remotely booted over a
network. The BOOTP process assigns an infinite lease of an IP address. The BOOTP service
utilizes UDP ports 67 and 68.
byte
A type that is encoded in an 8-bit format, ranging from 00 hex to FF hex.

EIO0000001438 03/2018 113


Glossary

C
CFC
(continuous function chart) A graphical programming language (an extension of the IEC 61131-3
standard) based on the function block diagram language that works like a flowchart. However, no
networks are used and free positioning of graphic elements is possible, which allows feedback
loops. For each block, the inputs are on the left and the outputs on the right. You can link the block
outputs to the inputs of other blocks to create complex expressions.
configuration
The arrangement and interconnection of hardware components within a system and the hardware
and software parameters that determine the operating characteristics of the system.
control network
A network containing logic controllers, SCADA systems, PCs, HMI, switches, ...
Two kinds of topologies are supported:
 flat: all modules and devices in this network belong to same subnet.
 2 levels: the network is split into an operation network and an inter-controller network.

These two networks can be physically independent, but are generally linked by a routing device.
CRC
(cyclical redundancy check) A method used to determine the validity of a communication
transmission. The transmission contains a bit field that constitutes a checksum. The message is
used to calculate the checksum by the transmitter according to the content of the message.
Receiving nodes, then recalculate the field in the same manner. Any discrepancy in the value of
the 2 CRC calculations indicates that the transmitted message and the received message are
different.

D
DHCP
(dynamic host configuration protocol) An advanced extension of BOOTP. DHCP is more
advanced, but both DHCP and BOOTP are common. (DHCP can handle BOOTP client requests.)
DWORD
(double word) Encoded in 32-bit format.

E
element
The short name of the ARRAY element.
equipment
A part of a machine including sub-assemblies such as conveyors, turntables, and so on.

114 EIO0000001438 03/2018


Glossary

Ethernet
A physical and data link layer technology for LANs, also known as IEEE 802.3.
EtherNet/IP
(Ethernet industrial protocol) An open communications protocol for manufacturing automation
solutions in industrial systems. EtherNet/IP is in a family of networks that implement the common
industrial protocol at its upper layers. The supporting organization (ODVA) specifies EtherNet/IP
to accomplish global adaptability and media independence.

F
FB
(function block) A convenient programming mechanism that consolidates a group of programming
instructions to perform a specific and normalized action, such as speed control, interval control, or
counting. A function block may comprise configuration data, a set of internal or external operating
parameters and usually 1 or more data inputs and outputs.
firmware
Represents the BIOS, data parameters, and programming instructions that constitute the operating
system on a controller. The firmware is stored in non-volatile memory within the controller.
flash memory
A non-volatile memory that can be overwritten. It is stored on a special EEPROM that can be
erased and reprogrammed.
function
A programming unit that has 1 input and returns 1 immediate result. However, unlike FBs, it is
directly called with its name (as opposed to through an instance), has no persistent state from one
call to the next and can be used as an operand in other programming expressions.
Examples: boolean (AND) operators, calculations, conversions (BYTE_TO_INT)
function block
A programming unit that has 1 or more inputs and returns 1 or more outputs. FBs are called through
an instance (function block copy with dedicated name and variables) and each instance has a
persistent state (outputs and internal variables) from 1 call to the other.
Examples: timers, counters
function block diagram
One of the 5 languages for logic or control supported by the standard IEC 61131-3 for control
systems. Function block diagram is a graphically oriented programming language. It works with a
list of networks where each network contains a graphical structure of boxes and connection lines
representing either a logical or arithmetic expression, the call of a function block, a jump, or a return
instruction.

EIO0000001438 03/2018 115


Glossary

G
GVL
(global variable list) Manages global variables within a project.

H
hex
(hexadecimal)

I
I/O
(input/output)
ID
(identifier/identification)
IEC
(international electrotechnical commission) A non-profit and non-governmental international
standards organization that prepares and publishes international standards for electrical,
electronic, and related technologies.
IEC 61131-3
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with
controller programming languages and defines 2 graphical and 2 textual programming language
standards. The graphical programming languages are ladder diagram and function block diagram.
The textual programming languages include structured text and instruction list.
IEEE 802.3
A collection of IEEE standards defining the physical layer, and the media access control sublayer
of the data link layer, of wired Ethernet.
IL
(instruction list) A program written in the language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (refer to IEC 61131-3).
INT
(integer) A whole number encoded in 16 bits.
IP
(Internet protocol Part of the TCP/IP protocol family that tracks the Internet addresses of devices,
routes outgoing messages, and recognizes incoming messages.

116 EIO0000001438 03/2018


Glossary

L
LD
(ladder diagram) A graphical representation of the instructions of a controller program with symbols
for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to
IEC 61131-3).
LWORD
(long word) A data type encoded in a 64-bit format.

M
MAC address
(media access control address) A unique 48-bit number associated with a specific piece of
hardware. The MAC address is programmed into each network card or device when it is
manufactured.
MAST
A processor task that is run through its programming software. The MAST task has 2 sections:
 IN: Inputs are copied to the IN section before execution of the MAST task.
 OUT: Outputs are copied to the OUT section after execution of the MAST task.

N
network
A system of interconnected devices that share a common data path and protocol for
communications.

P
PLC
(programmable logic controller) An industrial computer used to automate manufacturing, industrial,
and other electromechanical processes. PLCs are different from common computers in that they
are designed to have multiple input and output arrays and adhere to more robust specifications for
shock, vibration, temperature, and electrical interference among other things.
POU
(program organization unit) A variable declaration in source code and a corresponding instruction
set. POUs facilitate the modular re-use of software programs, functions, and function blocks. Once
declared, POUs are available to one another.
program
The component of an application that consists of compiled source code capable of being installed
in the memory of a logic controller.

EIO0000001438 03/2018 117


Glossary

protocol
A convention or standard definition that controls or enables the connection, communication, and
data transfer between 2 computing system and devices.

R
run
A command that causes the controller to scan the application program, read the physical inputs,
and write to the physical outputs according to solution of the logic of the program.

S
ST
(structured text) A language that includes complex statements and nested instructions (such as
iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
STOP
A command that causes the controller to stop running an application program.
string
A variable that is a series of ASCII characters.
system variable
A variable that provides controller data and diagnostic information and allows sending commands
to the controller.

T
task
A group of sections and subroutines, executed cyclically or periodically for the MAST task or
periodically for the FAST task.
A task possesses a level of priority and is linked to inputs and outputs of the controller. These I/O
are refreshed in relation to the task.
A controller can have several tasks.
TCP
(transmission control protocol) A connection-based transport layer protocol that provides a
simultaneous bi-directional transmission of data. TCP is part of the TCP/IP protocol suite.

118 EIO0000001438 03/2018


Glossary

U
UDINT
(unsigned double integer) Encoded in 32 bits.
UINT
(unsigned integer) Encoded in 16 bits.
unlocated variable
A variable that does not have an address (refer to located variable).

V
variable
A memory unit that is addressed and modified by a program.

W
watchdog
A watchdog is a special timer used to ensure that programs do not overrun their allocated scan
time. The watchdog timer is usually set to a higher value than the scan time and reset to 0 at the
end of each scan cycle. If the watchdog timer reaches the preset value, for example, because the
program is caught in an endless loop, an error is declared and the program stopped.
WORD
A type encoded in a 16-bit format.

EIO0000001438 03/2018 119


Glossary

120 EIO0000001438 03/2018


Modicon M241 Logic Controller
Index
EIO0000001438 03/2018

Index

C D
CART_R_ARRAY_TYPE Data Types
Data Types, 94 CART_R_ARRAY_TYPE, 94
CART_R_MODULE_ID CART_R_MODULE_ID, 95
Data Types, 95 CART_R_STATE, 96
CART_R_STATE DataFileCopyError, 77
Data Types, 96 DataFileCopyLocation, 78
CART_R_STRUCT ETH_R_FRAME_PROTOCOL, 81
System Variable, 37 ETH_R_IP_MODE, 82
cycle ETH_R_PORT_DUPLEX_STATUS, 83
IsFirstMastColdCycle, 43 ETH_R_PORT_IP_STATUS, 84
IsFirstMastCycle, 44 ETH_R_PORT_LINK_STATUS, 85
IsFirstMastWarmCycle, 46 ETH_R_PORT_SPEED, 86
ETH_R_RUN_IDLE, 87
ExecuteScriptError, 79
IMMEDIATE_ERR_TYPE, 98
PLC_R_APPLICATION_ERROR, 65
PLC_R_BOOT_PROJECT_STATUS, 67
PLC_R_IO_STATUS, 68
PLC_R_SDCARD_STATUS, 69
PLC_R_STATUS, 70
PLC_R_STOP_CAUSE, 71
PLC_R_TERMINAL_PORT_STATUS, 73
PLC_R_TM3_BUS_STATE, 74
PLC_W_COMMAND, 75
RTCSETDRIFT_ERROR, 99
TM3_BUS_W_IOBUSERRMOD, 92
TM3_ERR_CODE, 89
TM3_MODULE_R_ARRAY_TYPE, 90
TM3_MODULE_STATE, 91
DataFileCopy
copying data to or from a file, 52
DataFileCopyError
Data Types, 77
DataFileCopyLocation
Data Types, 78

EIO0000001438 03/2018 121


Index

E I
embedded I/O IMMEDIATE_ERR_TYPE
GetImmediateFastInput, 41 Data Types, 98
PhysicalWriteFastOutputs, 48 IsFirstMastColdCycle
ETH_R first cold start cycle, 43
System Variable, 28 IsFirstMastCycle
ETH_R_FRAME_PROTOCOL first mast cycle, 44
Data Types, 81 IsFirstMastWarmCycle
ETH_R_IP_MODE first warm start cycle, 46
Data Types, 82
ETH_R_PORT_DUPLEX_STATUS
Data Types, 83 M
ETH_R_PORT_LINK_STATUS M241 PLCSystem
Data Types, 85 DataFileCopy, 52
ETH_R_PORT_SPEED ExecuteScript, 55
Data Types, 86 GetImmediateFastInput, 41
ETH_W GetRtc, 42
System Variable, 33 IsFirstMastColdCycle, 43
ExecuteScript IsFirstMastCycle, 44
running script commands, 55 IsFirstMastWarmCycle, 46
ExecuteScriptError PhysicalWriteFastOutputs, 48
Data Types, 79 SetRTCDrift, 49
TM3_GetModuleBusStatus, 58, 60
TM3_GetModuleFWVersion, 59
F
file copy commands
DataFileCopy, 52 P
functions PhysicalWriteFastOutputs
differences between a function and a writing output of an embedded expert I/O,
function block, 104 48
how to use a function or a function block PLC_R
in IL language, 105 System Variable, 18
how to use a function or a function block PLC_R_APPLICATION_ERROR
in ST language, 109 Data Types, 65
PLC_R_BOOT_PROJECT_STATUS
Data Types, 67
G PLC_R_IO_STATUS
GetImmediateFastInput Data Types, 68
getting the value of a fast input, 41 PLC_R_SDCARD_STATUS
GetRtc Data Types, 69
getting real time clock (RTC) value, 42 PLC_R_STATUS
Data Types, 70
PLC_R_STOP_CAUSE
Data Types, 71

122 EIO0000001438 03/2018


Index

PLC_R_TERMINAL_PORT_STATUS System Variable


Data Types, 73 SERIAL_R, 25
PLC_R_TM3_BUS_STATE SERIAL_W, 26
Data Types, 74 TM3_BUS_W, 35
PLC_W TM3_MODULE_R, 34
System Variable, 23 System Variables
PLC_W_COMMAND Definition, 13
Data Types, 75 Using, 15
PROFIBUS_R
System Variable, 36
T
TM3 module bus status
R TM3_GetModuleBusStatus, 58
real time clock TM3 module firmware version
GetRtc, 42 TM3_GetModuleFWVersion, 59
SetRTCDrift, 49 TM3 module internal status
RTC TM3_GetModuleInternalStatus, 60
GetRtc, 42 TM3_BUS_W
SetRTCDrift, 49 system variable, 35
RTCSETDRIFT_ERROR TM3_BUS_W_IOBUSERRMOD
Data Types, 99 Data Types, 92
TM3_ERR_CODE
Data Types, 89
S TM3_GetModuleBusStatus
script commands getting the bus status of a TM3 module,
ExecuteScript, 55 58
SERIAL_R TM3_GetModuleFWVersion
System Variable, 25 getting the firmware version of a TM3
SERIAL_W module, 59
System Variable, 26 TM3_GetModuleInternalStatus
SetRTCDrift getting the internal status of a TM3 mod-
accelerating or slowing the RTC frequen- ule, 60
cy, 49 TM3_MODULE_R
System Variable System Variable, 34
CART_R_STRUCT, 37 TM3_MODULE_R_ARRAY_TYPE
ETH_R, 28 Data Types, 90
ETH_W, 33 TM3_MODULE_STATE
PLC_R, 18 Data Types, 91
PLC_W, 23
System variable
PROFIBUS_R, 36

EIO0000001438 03/2018 123


Index

124 EIO0000001438 03/2018

You might also like