A6V10239487 - Extension Modules PXX-L1.. - en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

s 9 282

9282P01

Desigo™ PX

Extension modules PXX-L11


PXX-L12
Use together with PXC....D or PXC...-E.D

• For the integration of room controllers in the Desigo RXC range into the
Desigo building automation and control system
• For the grouping of rooms
• For the implementation of higher-level system functions
• Integration of LONWORKS ®-compatible third-party equipment

Type summary

Type Number of connectable RXC / LONWORKS devices


PXX-L11 60
PXX-L12 120

CM1N9282en_06
2015-12-23 Building Technologies
Equipment combinations

System controller / automation station


With system Desigo... ≥V4 ≥ V5 ≥ V5 ≥ V5
Type (data sheet CM1N9222) PXC00.D, PXC50.D, PXC100.D, PXC200.D,
PXC00-E.D PXC50-E.D PXC100-E.D PXC200-E.D
Number of RXC with PXX-L11 60 10 60 *) 60 *)
Number of RXC with PXX-L12 120 10 120 *) 120 *)

*) A great number of RXC will reduce the performance of the PXC... for the
connected TX-I/O data points.

Funktionen

The system controller LONW ORKS, PXC00.D or PXC00-E.D with PXX-Lxx, fulfills
the following primary tasks:
• Compresses data from the room controllers at the automation level
• Maps Desigo RXC applications to BACnet for operation and monitoring (grouped
as HVAC, lighting and blind control functions)
• Execution of higher functions for room automation:
Room and zone-based groups, and system functions such as changeover and
summer/winter compensation etc.
• System functions such as trend, alarming and schedulers

On the system controller LONW ORKS, RXC applications are mapped in a way that
creates a room view. This enables the rooms to be grouped together, e.g. for
shared occupancy programs, or for shared commands for the control of lighting or
blinds.

Hardware Hardware consists of


− a PXC....D / PXC...-E.D system controller.
− and a PXX-L11 or -L12 extension module.

Topology
Desigo Insight

PXM20

BACnet/LonTalk oder BACnet/IP

PXC50...D,
PXC100...D, PXC...D
PXC200...D TXM1.... PXC... PXX-L.. PXC...D

QAX...

QAX...

Rooms

RXC... RXC... RXC...


QAX5... 3rd party device

Note: For an overview on the Desigo RXC product range see document CA110333.

2/6
Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06
Building Technologies 2015-12-23
Extended Command The PXX-Lxx extension modules support Extended Command Set (ECS) to EIA-
Set (ECS) 709.1-B protocol. If a LONW ORKS node is written with an ECS command (e.g.
installation by NL220), several legacy commands will be refused by the module
from this moment on. A module configured in this manner will only allow restricted
communication with older tools that do not support ECS (e.g. the diagnostic tool
NLUtil).

Mechanical design

The compact construction enables the extension module to be used in highly


confined spaces.

Housing

1 Plastic housing
2 LED display for device and system status
3 Interface to automation station
4 Service button
5 Tool interface
6 FW download button
7 Plug-in terminal block with screw
terminals (LONW ORKS bus)
8 Slider for mounting on DIN rail

LED display, LED Color Activity Meaning /  Corrective action


service button RUN Green Continuously off No power supply.
 Check power supply.
Continuously on Power supply ok; firmware functions ok.
FLT Red Continuously off Everything ok.
Continuously on Hardware fault detected during self-test.
 PXX-Lxx must be replaced.
Fast flashing No valid firmware present.
 Reload firmware.

TX Yellow Flashing Sending LonWorks® data packets


RX Yellow Flashing Receiving LonWorks® data packets
SVC Red Continuously off Everything OK.
LonWorks® node configured
Continuously on Faulty LonWorks® chip or service pin is being
pressed.
Flashing LonWorks® node not configured  Configure
with LNS
Service button Press with pointed object

FW download button Press with pointed object

3/6

Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06


Building Technologies 2015-12-23
Mounting

The extension modules PXX-Lxx can be snapped on to standard mounting rails.


To connect, push the extension module from left to the PXC....D / PXC...-E.D
system controller until the interfaces establish a connection.

Disposal

The devices are classified as waste electronic equipment in terms of the


European Directive 2012/19/EU (WEEE) and should not be disposed of as
unsorted municipal waste.
The relevant national legal rules are to be adhered to.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.

4/6
Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06
Building Technologies 2015-12-23
Technical data

General device data Power supply DC 24 V ± 20% (SELV)


or DC 24 V class 2 (US)
50 mA, 1.2 W
from system controller
PXC....D / PXC...-E.D

Connection LONW ORKS® BUS Interface type TP/FT-10


Transceiver FTT-10A
Bit rate 78 kbps
Protocol LonTalk
RJ45 connector wiring
Connecting cable for LNS tool Max. 3m
Wiring
Plug-in screw terminal Stranded or solid conductors
2 2
0.25 to 2.5 mm or 2 x 1.5 mm
Cable type See specifications in the RXC
installation manual, CA110334
Cable length Max. 450m in free topology
Max. 900m in serial topology
See Installation Guide RXC, CA110334 for more details

Protection data Housing protection standard IP30 (IP30) to EN 60529


Protection class III to EN 60730-1
Ambient conditions Normal operation Class 3K5 to IEC 721
Temperature 0 ... 50 °C
Humidity < 85 % r.h.
Transport Class 2K3 to IEC 721
Temperature – 25 ... 65 °C
Humidity < 95 % r.h.

Standards, directives and Product standard EN 60730-1 Automatic electrical controls for
approvals household and similar use
Electromagnetic compatibility (Applications) For use in residential, commerce,
light-industrial and industrial
environments
EU conformity (CE) CM1T9282xx *)
UL certification (US) UL 916, http://ul.com/database
RCM-conformity (EMC) CM1T9222en_C1 *)
EAC conformity Eurasia conformity
FCC 47 CFR Part 15 Class B
Environmental compatibility Product environmental declaration CM1E9282 *)
(contains data on RoHS compliance,
materials composition, packaging,
environmental benefit, disposal)

Dimensions See “Dimensions”


Weight Without / with packaging 0.129 kg / 0.140 kg

*) The documents can be downloaded from http://siemens.com/bt/download.

5/6

Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06


Building Technologies 2015-12-23
Dimensions

Dimensions in mm
90

45

77.5
70
44
98
108

5 64 3

9282M01

64 192

PXX-Lx with a PXC....D / PXC...-E.D system controller

Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd 2009
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change

6/6
Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06
Building Technologies 2015-12-23