9282P01
Desigo™ PX
• For the integration of room controllers in the Desigo RXC range into the
Desigo building automation and control system
• For the grouping of rooms
• For the implementation of higher-level system functions
• Integration of LONWORKS ®-compatible third-party equipment
Type summary
CM1N9282en_06
2015-12-23 Building Technologies
Equipment combinations
*) A great number of RXC will reduce the performance of the PXC... for the
connected TX-I/O data points.
Funktionen
The system controller LONW ORKS, PXC00.D or PXC00-E.D with PXX-Lxx, fulfills
the following primary tasks:
• Compresses data from the room controllers at the automation level
• Maps Desigo RXC applications to BACnet for operation and monitoring (grouped
as HVAC, lighting and blind control functions)
• Execution of higher functions for room automation:
Room and zone-based groups, and system functions such as changeover and
summer/winter compensation etc.
• System functions such as trend, alarming and schedulers
On the system controller LONW ORKS, RXC applications are mapped in a way that
creates a room view. This enables the rooms to be grouped together, e.g. for
shared occupancy programs, or for shared commands for the control of lighting or
blinds.
Topology
Desigo Insight
PXM20
PXC50...D,
PXC100...D, PXC...D
PXC200...D TXM1.... PXC... PXX-L.. PXC...D
QAX...
QAX...
Rooms
Note: For an overview on the Desigo RXC product range see document CA110333.
2/6
Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06
Building Technologies 2015-12-23
Extended Command The PXX-Lxx extension modules support Extended Command Set (ECS) to EIA-
Set (ECS) 709.1-B protocol. If a LONW ORKS node is written with an ECS command (e.g.
installation by NL220), several legacy commands will be refused by the module
from this moment on. A module configured in this manner will only allow restricted
communication with older tools that do not support ECS (e.g. the diagnostic tool
NLUtil).
Mechanical design
Housing
1 Plastic housing
2 LED display for device and system status
3 Interface to automation station
4 Service button
5 Tool interface
6 FW download button
7 Plug-in terminal block with screw
terminals (LONW ORKS bus)
8 Slider for mounting on DIN rail
3/6
Disposal
4/6
Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06
Building Technologies 2015-12-23
Technical data
Standards, directives and Product standard EN 60730-1 Automatic electrical controls for
approvals household and similar use
Electromagnetic compatibility (Applications) For use in residential, commerce,
light-industrial and industrial
environments
EU conformity (CE) CM1T9282xx *)
UL certification (US) UL 916, http://ul.com/database
RCM-conformity (EMC) CM1T9222en_C1 *)
EAC conformity Eurasia conformity
FCC 47 CFR Part 15 Class B
Environmental compatibility Product environmental declaration CM1E9282 *)
(contains data on RoHS compliance,
materials composition, packaging,
environmental benefit, disposal)
5/6
Dimensions in mm
90
45
77.5
70
44
98
108
5 64 3
9282M01
64 192
Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd 2009
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change
6/6
Siemens PXX-L11, PXX-L12 – Extension modules CM1N9282en_06
Building Technologies 2015-12-23