The normal response is an echo of the request, returned after the date-time has
been updated in the remote device. If the date-time structure content is not
consistent with a true date-time (that is, an invalid date-time), the value returned in
the Date-Time field is set to 0 by the device.
In case of 24 Vdc power loss, the date and time of the Modbus slaves without
battery is not refreshed anymore. It is therefore mandatory to set date and time for
all Modbus slaves after recovering the 24 Vdc power supply.
Furthermore, due to the clock drift of each Modbus slave, it is mandatory to set
date and time for all Modbus slaves periodically. Recommended period is at least
every 15 minutes.
100 (0x64) 4 (0x04) Read scattered holding register Read n non-contiguous registers
The maximum value for n is 100 but when using a MasterPact MicroLogic A or E
trip unit, it is recommended to have n lower or equal to 21.