Leary Glue Valve Controller Q4
Leary Glue Valve Controller Q4
Leary Glue Valve Controller Q4
MIQRO Controller
Controller Package CP001 - Setup and Operation Guide
MIQRO Four Channel Output MIQRO™ Controller
Table of Contents
MIQRO™ Controller 1
1. Safety Precautions 1
1.1 Declaration of Conformity 3
1.1.1 FCC Regulatory Compliance 3
2. Introduction 4
2.1 Features 5
2.2 Specifications 5
2.3 Powering the MIQRO On and Off 8
2.3.1 Switching the controller off 8
2.4 External Connections 9
3. Setup Overview 10
3.1 Example for MIQRO Controller Setup 10
3.2 1. Controller Setup Mode 12
3.3 2. Language and Units Adjustment Screen 12
3.4 3. Output Mode 14
3.5 4. Set Glue Line Position and Lengths 15
3.6 5. Position the Glue Valves on the Machine 17
3.7 6. Position the Trigger Sensor 17
3.8 7. Enter Glue Pattern Line 1 Start and End Positions 18
3.9 8. Enter Glue Pattern Line 2 Start and End Positions 20
3.10 9. Set trigger parameters 22
3.11 10. Set Glue Pattern Spot Parameters 23
3.12 11. Set Glue Valve Compensation Settings 24
3.13 12. Select Set or Run Mode Option 25
3.14 13. Set Pressure Regulation (GRU) Control 26
3.15 14. Production data information 29
4. System Settings 30
4.1 Freeform Mode 31
4.2 Run Hold Mode 32
4.3 Encoder Configuration 33
2
MIQRO Four Channel Output MIQRO™ Controller
© (2015-16, W. H. Leary Co., Inc.) All rights reserved. No part of this manual may be reproduced or transmitted in any
form or by any means without the prior written permission of W. H. Leary Co, Inc., unless such copying is expressly
permitted by federal copyright law. Address inquiries to W. H. Leary Co., Inc., 8440 B West 183rd Place, Tinley Park, IL
60487 USA
Document Purpose
This document was created for use in Operator Training for customers and service personnel who interact with Leary
Systems, Array controllers and individual controller stations. General knowledge of the industry and the intended
purpose of the equipment is required.
3
MIQRO Four Channel Output 1. Safety Precautions
1. Safety Precautions
As with all electronic equipment, read and follow all safety precautions as well as operation instructions. Contact
your distributor for any service, installation or repairs.
1. Before attempting to install or operate the controller, please read and thoroughly understand the contents of this
instruction manual. Special attention should be paid to all warnings and recommendations.
2. This equipment is designed to operate safely and reliably in its intended application and in a normal industrial
environment. However, disregard of safety precautions and operating instructions, attempted adjustment or ser-
vicing by unqualified personnel, substitution of unauthorized parts, exposure to mechanical damage or electrical
abuse, subjection to abnormal environmental conditions, or other misapplications may impair the reliability of
operation and create hazards to both equipment and personnel and may void any and all warranties or guar-
antees.
3. Operate this equipment only from an AC power line of the voltage specified. If rewiring to accommodate a dif-
ferent supply voltage is necessary, this should be undertaken only by a qualified service technician and verified by
a qualified technician or engineer.
4. The power cable of this equipment should be connected only to a properly grounded 3-wire receptacle. Do not use
grounding adapters.
5. If the power or any other cable of this equipment should become damaged or worn, turn off the power supply at
source and disconnect, and no attempt should be made to operate the equipment until the defective cable has
been replaced.
6. Do not install equipment in wet locations or where it may be subjected to water or other liquids in the form of
drips, splashes, sprays, etc.
7. When installing or relocating this equipment, proper care should be taken to ensure that the controller is moun-
ted out of the traffic aisle, so it is not exposed to damage from passing traffic (carts, lift trucks, etc.) and will not be
a hazard to passing personnel.
8. All cables, hoses, etc. should be secured in such a manner as to eliminate every risk of accidental snagging by
passing equipment or personnel. All cables, hoses, and sensors should also be safely secured and protected from
accidental contact with moving parts and products.
9. Do not open the controller enclosure. There are no user or serviceable items inside the enclosure. Opening the
enclosure may expose personnel to hazardous voltages.
10. Adjustment or repair of this equipment should be undertaken only by qualified service personnel. Tampering with
this equipment by unqualified personnel could lead to injury, as well as damage to or malfunction of the equip-
ment.
1
MIQRO Four Channel Output 1. Safety Precautions
11. Do not introduce screwdrivers or other metallic objects into the interior circuitry or exterior connections. These
objects have current-conducting capabilities and may create an electrical hazard as well as cause extensive damage
to the equipment.
12. If a fuse blows, turn the power off and contact your distributor for technical support. Any attempt to replace the
fuse and continue operations without locating the cause of the blown fuse may result in damage to the system or
an electrical hazard to personnel.
13. In the event of any unusual occurrence, which might indicate serious malfunction or damage, such as smoke,
sparks, burning odor, etc., as with any electrical equipment, switch off and disconnect the power supply at the
source, then contact your distributor for technical support.
14. If physical damage to the controller, sensors, encoder wheel, etc. is visible, it should be examined by qualified per-
sonnel before the system is allowed to continue operations.
15. If any adjustments need to be made to any part of the system while the machine is operational, as with any high-
speed machinery, special care should be taken to ensure the safety of personnel.
2
MIQRO Four Channel Output 1.1 Declaration of Conformity
Declares the following equipment complies with the requirements listed below:
This equipment has been designed, manufactured and tested by application of the following standards:
Product Serial number and CE marking is viewable on product label. See example image.
3
MIQRO Four Channel Output 2. Introduction
2. Introduction
4
MIQRO Four Channel Output 2.1 Features
2.1 Features
l Back-lit LCD programming/display screen
l Four output channels with up to four glue valve total capacity
l Programmable with 1-4 glue lines/rows of spots (events) per product
l Automatically convert a glue line to a row of spots below a selected machine speed
l Digital display of production data including machine speed, work rate, and work total
l Precise adhesive volume control over the machine speed range by using a 4-point pressure curve to vary control
pressure with respect to machine speed
l Low-speed cut-out inhibits valve outputs when the machine is running below a specified speed
l Compensation making fine pattern adjustments in either direction to compensate for various factors such as glue
valve construction, adhesive, orifice size, temperature, pressure, and height
l Programmable start position and glue line lengths
l Internal timer function for fixed speed machines
l Selectable glue valve purge pressure
l Adjustable PWM valve outputs to suit all Leary glue valves and many other actuators including most hot melt glue
valves*
l Ability to use a proprietary encoder
l Meets European CE standards
* A special version of the MIQRO controller specifically designed for the Robatech SpeedStar electric hot melt valve.
2.2 Specifications
Electrical Input AC Input Range: 110-240VAC, 50/60Hz
Power
320 W max.
Consumption
5
MIQRO Four Channel Output 2.2 Specifications
Output cycle Trigger: indicates trigger signal has been received from the trigger sensor
information
LEDs
Lockout An output cycle will not be re-triggered until the distance set in the lockout has passed.
Outputs are inhibited until the machine reaches the required speed. As the machine slows down the
Low speed cut-
outputs are again inhibited when the speed falls below the required setting. Range 2m/min to
out
600m/min.
Low speed
Below the set speed a glue line will automatically convert its output from line to spots. Range 2m/min
spotting/auto-
to 300m/min.
spotting
When the button is pressed the relevant valve output is actuated. If the controller is connected to a
glue regulator the adhesive pressure will be regulated to the test pressure that has been preset in the
system setup menu.
Purge
6
MIQRO Four Channel Output 2.2 Specifications
Custom encoders with pulses in the range of 1 pulse per 0.01 to 1.99mm of product travel may be
Encoder
selected.
Settings: dark to light (Q) for leading product edge detection or light to dark (NQ) for trailing product
Trigger
edge detection.
4 programmable pressure set points
Adhesive Test pressure setting for when outputs are in purge mode
Pressure
control Output signals: 0 -10 volts or 4-20mA
Use with suitable Leary GRU and pressure tank or pump
Production
Shows machine speed in m/min, work rate per hour and total count.
Data
7
MIQRO Four Channel Output 2.3 Powering the MIQRO On and Off
8
MIQRO Four Channel Output 2.4 External Connections
9
MIQRO Four Channel Output 3. Setup Overview
3. Setup Overview
Step 1 must be performed prior to setting up (configuring) the controller.
Detailed instructions about each step below are contained in the numbered sections that follow.
1. Turn the controller on in setup mode.
2. Adjust Language and measurement setting if desired.
3. Output mode settings.
4. Set the glue pattern start and end positions.
5. Position the glue valves on the machine.
6. Position the triggers on the machine.
7. Enter glue pattern line 1 start and end positions.
8. Enter glue pattern line 2 start and end positions.
9. Set the trigger parameters for each trigger being used.
10. Set glue pattern spot parameters (if required).
11. Set glue valve compensation parameters.
12. Select set or run mode option.
13. Set pressure regulation (GRU) control.
14. Reset production data (if required).
10
MIQRO Four Channel Output 3.1 Example for MIQRO Controller Setup
IMAGE DESCRIPTION
A 50 mm lead distance
B 228 mm lockout - Lockout is the distance that the trigger passes from the trigger edge (in this case the leading
edge of the product) to the other edge of the product (the trailing edge).
C Start for line 1 of pattern (S1) = 13 mm
D End for line 1 of pattern: (E1) = 38 mm
E Start for line 2 of pattern (S2) = 189 mm
F End for line 2 of pattern (E2) = 214 mm
G Direction of carton travel
H Line 2 (L2) spot pitch = 5 mm (Spot pitch is measured from the start of one glue spot to the start of the next
glue spot)
Note: The measurements and settings given throughout this guide are specific to the gluing application
example above.
11
MIQRO Four Channel Output 3.2 1. Controller Setup Mode
Note: Do not power off controller until program settings are completed. Setup mode is exited by powering the
controller off.
l Press the increase or decrease button to select one of several languages available. (English is the default setting.)
l Press the right arrow button until the cursors highlight the unit format selection.
l Press the increase or decrease button to select Inches or metric. (Metric is the default setting.)
12
MIQRO Four Channel Output 3.3 2. Language and Units Adjustment Screen
l PWM DC Limit - Do not adjust this setting. Contact distributor for more information.
l Spot Compensation - this setting adds compensation affecting all active valve outputs for the first spot only when
valves are in spotting mode. Adjustments are made in .01 increments with a range of 0-5 ms.
13
MIQRO Four Channel Output 3.4 3. Output Mode
Press the increase and decrease buttons to set the value for output 1 mode.
14
MIQRO Four Channel Output 3.5 4. Set Glue Line Position and Lengths
The start positions are referred to in the Example as ‘S’. The end distance for any line number is always
measured from the leading trigger edge.
Example 1:
Start for line 1 of pattern (S1) = 13mm
Start for line 2 of pattern (S2) = 189mm
Example 1:
End for line 1 of pattern (E1) = 38mm
End for line 2 of pattern (E2) = 214mm
Any of the lines can be converted to a series of spots (See also steps 7 and 8).
Example 1: Line 2 (L2) spot pitch 5mm
Spot pitch is measured from the start of one glue spot to the start of the next glue spot.
l Press the right arrow button until the cursors indicate variable spot pitch.
15
MIQRO Four Channel Output 3.5 4. Set Glue Line Position and Lengths
l Press the increase or decrease button to turn variable spot pitch on or off.
Note: If two or more lines are used, the spot pitch and spot time must be the same for all pattern lines.
16
MIQRO Four Channel Output 3.6 5. Position the Glue Valves on the Machine
17
MIQRO Four Channel Output 3.8 7. Enter Glue Pattern Line 1 Start and End Positions
2. Press the left or right arrowbutton until the cursors flash each side of the start value.:
3. Press the increase or decrease button to change to value of the start until it reads 13 mm.
4. Press the left or right arrow button until the cursors flash each side of the end value.
5. Press the increase or decrease button to change to value of the end reads 38 mm.
6. Press theleft or right arrow button until the cursors flash each side of the spot value.
7. Press theleft or right arrow button until the cursors flash each side of the spot value.
8. The first line in the example is a solid line and therefore the spot function is not required.
9. Press the increase or decrease button until the spot parameter displays “Off.”
18
MIQRO Four Channel Output 3.8 7. Enter Glue Pattern Line 1 Start and End Positions
10. This completes the settings required for line 1 of pattern and the display screen should read as follows:
19
MIQRO Four Channel Output 3.9 8. Enter Glue Pattern Line 2 Start and End Positions
2. Press theleft or right arrow button until the cursors flash on each side of the start field.
3. You will notice that there is a minimum value provided automatically. This value is calculated from the end of the
last line by adding 1 mm. This provides a safety margin so that the lines do not overlap.
4. Press the increase button to change the value until it reads 189 mm.
5. Press the left or right arrowbutton until the cursors flash the end parameter.
6. Press the increase button to change the value until it reads 214 mm.
7. Press the left or right arrowbutton until the cursors flash the spot parameter.
8. The second line of Example 1 is a spotted line, and therefore the spot function is required.
9. Press the increase button until the spot parameter displays “On.”
20
MIQRO Four Channel Output 3.9 8. Enter Glue Pattern Line 2 Start and End Positions
10. This completes the settings for line 2 of pattern 1 and the display screen should read as follows:
21
MIQRO Four Channel Output 3.10 9. Set trigger parameters
Lead
l Press the left or right arrowbutton until the cursor flashes the lead field (minimum 2 mm).
l The lead value is the distance in millimeters from the trigger to the glue valve, and is normally set at 50 mm. When
entered, this enables subsequent line delay and line length adjustments to be measured from the product’s lead-
ing edge. If the lead distance subsequently changes,( i.e. if the trigger or glue valve is repositioned, then the lead
value must be altered accordingly).
l Press the increase or decreasebutton until a lead value of 50 mm is displayed.
Lockout
l Press the left or right arrowbutton until the cursor flashes the lockout value (minimum 2 mm).
l Lockout is the distance that the trigger passes from the trigger edge (in this case the leading edge of the product)
to the other edge of the product (the trailing edge). The trigger will be disabled for the distance entered for the
lockout value, thereby preventing unwanted triggering caused by any holes or contrasting colors on the product.
l Press the increase or decreasebutton until a lockout value of 228 mm is displayed.
22
MIQRO Four Channel Output 3.11 10. Set Glue Pattern Spot Parameters
Spot Size
l Press the left or right arrowbutton until the cursors indicate the spot size parameter.
l The spot size controls the glue valve opening time, which governs the size of the glue spot. The value is displayed
in milliseconds (ms) and is adjustable from 0.10 ms to 4.5 ms in steps of 0.01 ms.
l The spot size is dependent on several factors including the type of glue valve, the speed of the machine, the size of
spot required, the viscosity of the glue, and the distance from the glue valve nozzle to the product surface.
l Therefore, the spot size can only be accurately set while the machine is running at production speed. However,
the suggested starting figure is as follows:
l Press the increase or decreasebutton to set the pitch to 5 mm.
23
MIQRO Four Channel Output 3.12 11. Set Glue Valve Compensation Settings
On compensation time represents the on response time of the glue valve, and is needed to keep the line
start position consistent. This value is dependent on several variables including glue viscosity, nozzle size
and height of the glue valve above the product surface. The value is displayed in milliseconds and is
adjustable from 0.00 ms to 50 ms in steps of 0.01 ms.
Off compensation time represents the off response time of the glue valve, and is needed to keep the line
end position consistent. Like on comp., this value is dependent on a number of variables. The value is
displayed in milliseconds and is adjustable from 0.00 ms to 50.00 ms in steps of 0.01 ms.
24
MIQRO Four Channel Output 3.13 12. Select Set or Run Mode Option
l Press the increase or decrease button to toggle between the two options available: Set or Run.
25
MIQRO Four Channel Output 3.14 13. Set Pressure Regulation (GRU) Control
2. Press the left or right arrow button until the cursors indicate the % value for P1.
3. Press the increase or decrease button to set the value for P1 at 20%.
4. Press the right arrow button and the cursor will move to speed 2.
26
MIQRO Four Channel Output 3.14 13. Set Pressure Regulation (GRU) Control
5. Press the increase or decrease button to set the value for speed 2 at 100 m/min.
6. Press the right arrow button and the cursor will move to P2.
7. Press the increase or decrease button to set the value for P2 at 40%.
8. Press the right arrow button and the cursor will move to speed 3.
9. Press the increase or decrease button to set the value for speed 3 at 300 m/min.
10. Press the right arrow button and the cursor will move to P3.
11. Press the increase or decrease button to set the value for P3 at 50%.
12. Press the right arrow button and the cursor will move to speed 4.
13. Press the increase or decrease button to set the value for speed 4 at 450 m/min.
14. Press the right arrow button and the cursor will move to P4.
15. Press the increase or decrease button to set the value for P4 at 90%.
27
MIQRO Four Channel Output 3.14 13. Set Pressure Regulation (GRU) Control
Adjustment of the pressure and speed values can be carried out while the machine is running. Not all of the coordinates
must be used. Unused speed coordinates are set to zero, and their corresponding pressure values will automatically be
set to the P1 value.
28
MIQRO Four Channel Output 3.15 14. Production data information
This screen is for general information only; it does not affect the operation of the controller in any way.
l Speed shows the actual machine running speed in meters per minute.
l Work Rate shows an average figure of how many items of product per hour are being processed.
l Total indicates the number of product items that have been processed by the system since the count was last
cleared to zero. This value increments every time the trigger detects a product.
l The total count can be cleared to zero by pressing the decrease button.
l Press the forward menubutton to complete the menu loop and return to the output 1 of pattern screen.
29
MIQRO Four Channel Output 4. System Settings
4. System Settings
The following System Settings may be accessed only while in Controller Setup Mode.
To access the Controller Setup Setup Mode, follow these steps:
l Switch off the controller.
l Press and hold the left and right arrow buttons simultaneously while switching on the power.
Note: Do not power off controller until program settings are completed. Setup mode is exited by powering the
controller off.
30
MIQRO Four Channel Output 4.1 Freeform Mode
2. Press the left or right arrow button until the cursors flash each side of the start value.
3. Press the increase or decrease button to change the value of the offsets until it reads the desired value.
4. Press the left or right arrow button until the cursors flash each side of the end value.
5. Press the increase or decrease button to change the value of the offsets until it reads the desired value.
31
MIQRO Four Channel Output 4.2 Run Hold Mode
2. Press the left or right arrow button until the cursors flash each side of the Spot value.
32
MIQRO Four Channel Output 4.3 Encoder Configuration
2. Press the left or right arrow button until the cursors indicate the Encoder setting.
3. There are five options which can be used for the Encoder and these are as follows:
a. 1 mm: Used for encoders that give 1 pulse per 1 mm of product travel
b. 2 mm: Used for encoders that give 1 pulse per 2 mm of product travel
c. 0.01 in. A standard Leary encoder gives 1 pulse per 0.25 mm (0.01 in) of product travel (standard 1,200 ppr
and small 800 ppr encoders). The high resolution 3,000 ppr Leary encoder cannot be used. Standard Leary
encoder cables can be used.
d. Internal: Internally generated pulse which is a constant 1 ms simulating a 1 mm encoder at 60 m /min.
e. Custom: Custom option allows the user to input a resolution in the range of 0.01 mm to 1.0 mm in incre-
ments of 0.01 mm.
4. Press the increase or decrease button to select the option required.
2. Press the increase or decrease button to select the desired value if this option is required.
33
MIQRO Four Channel Output 4.4 Trigger Input
l The and symbols are used to indicate leading edge and trailing edge detection for triggers.
l PNP and NPN inputs can be accepted.
l All standard Leary triggers are PNP and standard Leary cables can be used.
34
MIQRO Four Channel Output 4.5 Glue Valve Output
2. Press the right arrow button and the cursors will move to the PWM Duty Cycle setting.
3. The PWM duty cycle is the voltage that keeps the glue valve open once initiated. The value is dependent on the
glue valve being used, but as a default it is set to 15% which is suitable for all standard Leary valves.
Note: Duty cycle values above 25% are not recommended as it may cause damage to the valve.
35
MIQRO Four Channel Output 4.6 High Time
l Press the right arrow button and the cursors will move to the high time setting.
36
MIQRO Four Channel Output 4.7 Low Speed Cut-Out and Low Speed Spotting
37
MIQRO Four Channel Output 4.8 Purge Pressure Setting
l Press the right arrow button until the cursors indicate test pressure setting.
38
MIQRO Four Channel Output 4.9 Variable Spot Pitch
l Press the right arrow button until the cursors indicate variable spot pitch.
l Press the increase or decrease button to turn variable spot pitch on or off.
Note: If two or more lines are used, the spot pitch and spot time must be the same for all pattern lines.
39
MIQRO Four Channel Output 4.10 Dump Output Duration
l Press the right arrow button until the cursors indicate dump output.
l Press the increase or decrease button to a time value for the dump output.
40
MIQRO Four Channel Output 4.11 GRU Control Output
l Press the forward menu button until the screen above is shown.
l Press the right arrow button until the cursors indicate GRU V/I output.
l Press the increase or decrease button to select voltage control output (V) or current control output (I).
41
MIQRO Four Channel Output 4.12 Factory Defaults
l Hold the buttons down until the unit completely powers up and displays the model screen. The unit is now set to
factory defaults.
All prior settings will be permanently deleted when returning the MIQRO to factory default settings.
42
MIQRO Four Channel Output 5. MIQRO Feature Licensing
2. Use the increase or decrease buttons to select the first character (0-9, A-F) in the license key code.
3. When the correct digit is shown, press the right arrow button to advance to the next character.
4. Do the same for all 12 characters. If required, you may use the left arrow button to go back and make corrections.
5. When the last digit is entered, press the right arrow button to validate the license key code. The display will
inform you whether the license key code passed or failed validation. If passed, simply power off the unit and then
power on again – the new feature(s) are enabled.
43
MIQRO Four Channel Output 5. MIQRO Feature Licensing
6. If the license key validation failed, press the back menu key to attempt re-entry. If problems are still encountered,
contact Distributor. If the license key validation fails, it does not disable any existing features – the unit will
continue to operate as before.
44