Eastron SDM630MCT-Lora Series User Manual V1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SDM630 MCT - LoRa

Wireless Remote Communication Select the Power display screens. In Set- Press to enter the
up Mode, this is the “Down” button. selection routine. The
Total active energy in kWh.
current time interval will
flash.
Select the Energy display screens. In Set-
up mode, this is the “Enter” or “Right”
button.
MD
Total reactive energy in Use and
kVArh. buttons to select the time
required.
3.1 Voltage and Current
Each successive press of the button selects a new parameter:

LoRa Meter ID Press to confirm the


8 digits selection. SET indicator
Phase to neutral voltages. will appear.

LoRa ENERGY METER


FOR SINGLE AND THREE PHASE
ELECTRICAL SYSTEMS Press to exit the DIT selection routine and return to the menu.
4.Set Up
User Manual V1.0 To enter set-up mode, press the button for 3 seconds,
Current on each phase. until the password screen appears. Warnings
1.Introduction Important Safety Information is contained in the
This document provides operating, maintenance and Setting up is password- Maintenance section. Familiarize yourself with this
installation instructions. This unit measures and displays protected so you must information before attempting installation or other
the characteristics of single phase two wires(1p2w),three enter the correct password procedures. Symbols used in this document:
phase three wires(3p3w) and three phase four wires(3p4w) (default ‘1000’) before
Phase to neutral voltage processing.
networks.The measuring parameters include voltage(V), Risk of Danger: These instructions contain
THD%.
frequency(Hz),current(A),power(kW/Kva/Kvar),import,
export and total Energy(kWh/kvArh).The unit can also
! important safety information. Read them before
starting installation or servicing of the equipment.
measures Maximum demand current and power, this is If an incorrect password
measured over preset periods of up to 60 minutes. is entered, the display will Caution: Risk of Electric Shock
show:
This unit is a 1A or 5A or 333mV CT operated and can
be configured to work with a wide range of CTs. Built-in pulse Current THD% for each PASS Err
outputs and LoRa module enables wireless communication. phase. 4.4 Supply System
The users are free from Bus line wiring and layout. The unit has a default setting of 3Phase 4wire (3P4).
Configuration is password protected. To exit setting-up mode, press repeatedly until the
Use this section to set the type of electrical system.
measurement screen is restored.
This unit can be powered from a separate auxiliary (AC or DC) From the set-up menu, use
supply. Alternatively it can be powered from the monitored 3.2 Frequency and Power Factor and Demand 4.1 Set-up Entry Methods MD
and buttons to
supply by linking the voltage reference and neutral reference in select the system option.
Some menu items, such as password and CT, require a
to terminals 5 and 6 (Please refer to wiring diagram). Each successive press of the MD
button selects a new range: The screen will show the
four-digit number entry while others, such as supply system,
currently selected power
SDM630MCT-LoRa has two versions: require selection from a number of menu options.
supply.
V1: LoRa Mesh (Eastron defined protocol)
Frequency and Power 4.1.1 Menu Option Selection
V2: LoRaWan
Factor (total).
1. Use the MD and buttons to scroll through the Press to enter the
different options of the set up menu. selection routine. The
current selection will flash.
1.1 Unit Characteristics 2. Press to confirm your selection

The Unit can measure and display: 3. If an item flashes, then it can be adjusted by the MD
and
Power Factor of each buttons.
• Voltage (L-N and L-L) of all phases
phase. Use MD and
• THDu % of each phase (total harmonic distortion) 4. Having selected an option from the current layer, press
• Currents of each phase and Neutral buttons to select the
to confirm your selection. The SET indicator will appear. required system option:
• THDi % of each phase (total harmonic distortion)
5. Having completed a parameter setting, press to return 1P2(W),3P3(W) ,3P4(W).
• Line frequency
• Power, maximum power demand and power factor to a higher menu level. The SET indicator will be removed
• Active energy imported and exported and you will be able to use the MD and buttons for
Maximum Power Demand. further menu selection.
• Reactive energy imported and exported
Press to confirm the
6. On completion of all setting-up, press repeatedly until
selection. SET indicator
the measurement screen is restored.
will appear.
1.2 Current Transformer Primary Current

SDM630MCT Series is CT operated.you will need to set Maximum Current 4.1.2 Number Entry Procedure Press to exit the system selection routine and return to
the correct ratio. Demand. the menu. SET will disappear and you will be returned to the
When Setting up the unit, some screens require the entering main set-up Menu.
As an example: If using 100/5A CT, you will need to insure of a number. In particular, on entry to the setting up section, a
CT2 (Secondary) is set to 5 and CT rate is 0020. You divide password must be entered. Digits are set individually, from left
the primary by the secondary to get the CT rate to be entered
4.5 CT
to right. The procedure is as follows:
(100/5=20). The CT option sets the secondary current (CT2 1A or 5A)
3.3 Power 1. The current digit to be set flashes and is set using the MD
of the current transformer (CT) that wires to the meter.
and buttons
1.3 Lora Communication Each successive press of the button select a new range:
2. Press to confirm each digit setting. The SET indicator
appears after the last digit has been set. From the set-up menu,
SDM630MCT-LoRa has Lora wireless communication module
use MD and buttons
combined inside the meter. With Eastron Lora gateway ESP-6,
the user can remote monitor and program the meters. It saves 3. After setting the last digit, press to exit the number to select the CT option.
lot of labor work for meter reading, Bus line wiring and Instantaneous Active setting routine. The SET indicator will be removed.
maintenance. Power in kW.

by LoRaWAN, the communication distance between submeter 4.2 Change Password Secondary CT setting
to gateway can reach several kilometers. by LoRaMesh, data
supports 4 relay hoppings. Press to enter the
CT secondary current
The frequency band is 470Mhz. if other band is request, selection routine.:5A/1A
Instantaneous Reactive
please specify when you order. 433,869,915Mhz is available. Power in kVAr. Use the MD and
to choose the change
password option. Set CT Ratio value
1.4 Pulse output
Press to enter the
Two pulse outputs that pulse measured active and reactive CT Ratio setting screen.
energy.The Pulse 2 constant for active energy is 3200imp/kWh. The range is from 0001
(Terminals 11 & 12) The pulse width for Pulse 1 can be set Instantaneous Volt-Amps Press the to enter the to 9999.
from the set-up menu (Terminals 9 & 10). in KVA. change password routine.
The new password screen
will appear with the first For example, if using a 100/5A current transformer you
2.Start Up Screens digit flashing. will enter 0020, as you need to divide the primary by the
secondary to get the ratio (CT rate).

Use MD and to set * Please note for the MID approved version device,you will
The first screen lights up Total kW, kVArh, kVA. the first digit and press only have one opportunity to set the ratio.
all display segments and to confirm your
can be used as a display
check.
selection. The next digit 4.6 PT
C1C2
will flash.
The PT option sets the secondary voltage (PT2 100 to 500V) of
the voltage transformer (PT) that may be connected to the meter.
3.4 Energy Measurements
Each successive press of the button selects a new range: Repeat the procedure for Use MD and buttons
Software version information the remaining three digits. to select the PT option.
The screen will show the
voltage PT secondary
Import active energy voltage value. The default
in kWh. value is 400V.

The interface performs a After setting the last digit,


self-test and indicates the SET will show. Secondary PT setting
result if the test passes. Press to enter the
PT secondary voltage
Export active energy selection routine. The
in kWh. range is from 100 to 500V.
*After a short delay, the screen will display active energy
measurements. Press to exit the number setting routine and return to the
Set-up menu. SET will be removed
Set PT ratios value
Press to enter the PT
3.Measurements 4.3 DIT Demand Integration Time ratio screen.
Import reactive energy The range is from 0001
The buttons operate as follows: This sets the period in minutes over which the current
in kVArh. to 9999.
and power readings are integrated for maximum demand
measurement. The options are: off, 5, 10,15 30,60 minutes.
Selects the Voltage and Current display For example, if set the ratio to be 100,it means the primary
screens. In Set-up Mode, this is the “Left” voltage equals secondary voltage x100.
or “Back” button. From the set-up menu, use
MD
and buttons 4.7 Pulse Output
Export reactive energy to select the DIT option.
Select the Frequency and Power factor This option allows you to configure the pulse output. The
in kVArh. The screen will show
display screens. In Set-up Mode, this is output can be set to provide a pulse for a defined amount of
the currently selected
the “Up” button. energy active or reactive. Use this section to set up the relay
integration time.
pulse output—Units: kWh, kVArh
4.9 Backlit set-up The Pulse output 1 is configurable. it can be set to generate
pulses to present kWh or kVarh
From the set-up menu, use The meter provides a function to set the blue backlit
MD and buttons Rate can be set to generate 1 pulse per:
lasting time( 0/5/10/30/60/120 minutes).
to select the Pulse output 0.01 = 10 Wh/VArh
option. Option 0 means the backlit always on here. 0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
Default:60 100 = 100 kWh/kVArh
1000 = 1000 kWh/kVArh
Press to enter the If it’s setted as 5,the backlit
will be off in 5minutes. Pulse width 200/100/60 ms.
selection routine. The unit
Relay Rating 240V ac 50mA
symbol will flash.

5.6 Reference Conditions of Influence


Use MD and Quantities
buttons to choose the time
Use MD and Influence Quantities are variables that affect measurement
buttons to choose kWh or errors to a minor degree. Accuracy is verified under nominal
kVArh. value (within the specified tolerance) of these conditions.
• Ambient temperature 23°C ±1°C
Press to confirm the setting and press to return to
On completion of the entry procedure, press to confirm • Input frequency 50 or 60Hz ±2%
the main set up menu.
the setting and press to return to the main set up menu. • Input waveform Sinusoidal (distortion
4.10 CLR factor < 0·005)
• Auxiliary supply voltage Nominal ±1%
4.7.1 Pulse rate The meter provides a function to reset the maximum demand
value of current and power. • Auxiliary supply frequency Nominal ±1%
Use this to set the energy represented by each pulse.
• Auxiliary supply waveform (if AC) Sinusoidal (distortion
Rate can be set to 1 pulse per factor < 0·05)
0.01kWh/0.1kWh/1kWh/10kWh/100kWh.
From the set-up menu, use • Magnetic field of external origin Terrestrial flux
MD
and buttons to
select the reset option. 5.7 Environment
• Operating temperature -25°C to +55°C*
• Storage temperature -40°C to +70°C*
• Relative humidity 0 to 95%, non-
Press to enter the condensing
(It shows 1 impulse = 10kWh/kVArh) selection routine. The dIt • Altitude Up to 3000m
will flash.
• Warm up time 1 minute

From the set-up menu, • Vibration 10Hz to 50Hz, IEC


60068-2-6, 2g
use MD and buttons
to select the Pulse Rate Press to confirm the setting and press to return to • Shock 30g in 3 planes
option.
the main set up menu. * Maximum operating and storage temperatures are in the
context of typical daily and seasonal variation.

Press to enter the


5.Specifications 5.8 Mechanics
selection routine. The
current setting will flash. • DIN rail dimensions 72 x 94.5 mm (WxH)
0.01/0.1/1/10/100kWh/ 5.1 Measured Parameters per DIN 43880
kVArh per pulse. • Mounting DIN rail (DIN 43880)
The unit can monitor and display the following parameters of a
• Sealing Ip51 (indoor)
single phase two wire(1p2w), three phase three wire(3p3w) or
Use MD
and buttons to choose pulse rate. • Material Self-extinguishing
three phase four wire(3p4w) system.
Ul94 V-0
On completion of the entry procedure, press to confirm
the setting and press to return to the main set up menu.
5.1.1 Voltage and Current
• Phase to neutral voltages 100 to 289V a.c. (not for 3p3w 6.Dimensions
4.7.2 Pulse Duration supplies).
• Voltages between phases 173 to 500V a.c. (3p supplies
The energy monitored can be active or reactive and the pulse
only).
width can be selected as 200, 100 or 60ms.
• Percentage total voltage harmonic distortion (THD%) for
each phase to N ( not for 3p3w supplies).
• Percentage voltage THD% between phases (three phase
supplies only).
• Current THD% for each phase

5.1.2 Power factor and Frequency and


(It shows pulse width of 200ms) Max. Demand
• Frequency in Hz
From the set-up menu, • Instantaneous power:
use MD and buttons • Power 0 to 3600 MW
to select the Pulse width • Reactive power 0 to 3600 MVAr
option.
• Volt-amps 0 to 3600 MVA 7.Installation
• Maximum demanded power since last Demand reset The wiring diagram of SDM630MCT-Lora series has little
Power factor differencefrom different models. please make sure the wiring
is correct before turn on power of the meter.
Press to enter the • Maximum neutral demand current, since the last Demand
selection routine. The reset (for three phase supplies only)
current setting will flash.
7.1 current and Voltage inputs

5.1.3 Energy Measurements


3 PHASE 4 WIRE

P2 P1
L1
P2 P1 S2
Use MD
and buttons to choose pulse width. • Import/Export active energy 0 to 9999999.9 kWh
S1
L2
P2 P1 S2 S1
L3
On completion of the entry procedure press to confirm • Import/Export reactive energy 0 to 9999999.9 kVArh S2 S1
N
the setting and press to return to the main set up menu. • Total active energy 0 to 9999999.9 kWh
• Total reactive energy 0 to 9999999.9 kVArh
1 2 3 4 15 16 17 18 19 20
4.8 Lora Communication MEASURED VOLTAGE CURRENT INPUTS

The meter has an built-in Lora module for wireless 5.2 Measured Inputs
communication.The communication distance is affacted by the
installation conditionand the spreading factor setting. The bigg Voltage inputs through 4-way fixed connector with 2.5mm²
er value SF is set, the longerdistance data transmit at slower stranded wire capacity.single phase two wire(1p2w), three
3 PHASE 3 WIRE

speed, vice versa. phase three wire(3p3w) or three phase four wire(3p4w) P2 P1
L1
unbalanced. Line frequency measured from L1 voltage or S2 S1
L2
4.8.3 Spreading factor L3 voltage. P2 P1
L3
S2 S1
Three current inputs (six physical terminals) with 2.5mm²
From the set-up menu, stranded wire capacity for connection of external CTs. Nominal
use MD and buttons rated input current 5A or 1A a.c. Rms. 1 2 3 4 15 16 17 18 19 20
to select the Spreading MEASURED VOLTAGE CURRENT INPUTS
factor option.
5.3 Accuracy
1 PHASE 2 WIRE

P2 P1
• Voltage 0.5% of range maximum L1
S2 S1

• Current 0.5% of nominal


Press to enter the
selection routine. The • Frequency 0.2% of mid-frequency
N
current setting will flash. • Power factor 1% of unity (0.01)
• Active power (W) ±1% of range maximum 1 2 3 4 15 16 17 18 19 20
MEASURED VOLTAGE CURRENT INPUTS
• Reactive power (VAr) ±1% of range maximum
Use MD and • Apparent power (VA) ±1% of range maximum
7.2 Definitions of other terminals
buttons to choose spreading • Active energy (Wh) Class 1 IEC 62053-21
factor 7, 8, 9,10, 11, 12. AUXILIARY POWER
• Reactive energy (VArh) ±1% of range maximum SUPPLY OUTPUT
1 2
• Total harmonic distortion 1% up to 31st harmonic 5 6 7 8 9 10 11

• Response time to step input 1s, typical, to >99% of L N L N


On completion of the entry procedure, press to confirm
final reading, at 50 Hz.
the setting and press to return to the main set up menu.
Zhejiang Eastron Electronic Co.,Ltd.
5.4 Auxiliary Supply Building 2,No 1369. Chengnan Rd.
Two-way fixed connector with 2·5mm2 stranded wire capacity. Jiaxing,Zhejiang,CHINA
Spreading factor Transmission baud rate
85 to 275V a.c. 50/60Hz ±10% or 120V to 380V d.c. ±20%. Tel:86 573 83698881/83698882
7 5.17 kbps Tel:86 573 83698883
Consumption < 10W.
8 2.93 kbps Email:[email protected]
Web:www.eastron.com.cn
9 1.63 kbps
5.5 Pulse Outputs
MID
10 0.9 kbps
Two Pulse outputs are provided to indicate real-time
11 0.5 kbps
measured energy.Pulse out 2 is non-configurable with constant
12 0.27 kbps 3200imp/kWh

You might also like