Site: Licence Reg. No.

Bund Ref. No.:1 Bund Type (Local/Remote/Combined/Portable):


Diesel Bund Local
Bund Dimensions: Primary Vessel(s) – Materials of Construction:
3.60m x 2.60m x 0.50m Plastic
Bund Construction Material: Primary Vessel(s) – Total Storage Volume:
Concrete 2m3
Bund Lining Material: Primary Vessel(s) – 110% Volume of Largest Vessel:
Concrete 2.2m3
Bund Retention Volume: Primary Vessel(s) – 25% of Total Storage Volume:
4.68m3 0.50m3
Deemed Practicable / Safe to Conduct Hydrostatic Test? Yes/No Yes
If no give reasons:

HYDROSTATIC TEST DETAILS:

Code & Standard BS8007


Fill Rate Pre-filled
Stabilisation Period 24 hours
Duration of the Test 24 hours
Acceptance Criteria (Total 0mm
permissible drop in water No visible leaks
level)
Water Level Change in N/A
Reference Vessel

Date and Time Water Level in Bund Water Level in Reference Vessel
30.06.20 08.30am 330mm N/A
01.07.20 09.00am 330mm N/A

Description / Comments of Hydrostatic Test:


The test was carried out broadly in accordance with the procedure recommended in BS8007:1987 and consisted
of the following:

The tank was filled to a level of 0.330m with water for a liquid stabilization period of 24hours. After stabilization
the level of the liquid surface was recorded over a 24-hour period.

At the end of this period the total drop in water level was Integrity 0mm and based on this we certify that the
bund satisfies the test for liquid tightness described in Section 9 of BS8007:1987.

VISUAL TEST DETAILS: INSPECTION DESCRIPTION & RESULTS:


On visual inspection the structural integrity of the bund appears sound.

Result (Pass/Fail) Pass


Recommendation(s):
Inspection regime to be maintained

Signed: Qualification: Date: