DA1 1JQ Established over 25 years ago, Kentec Electronics Ltd. Has evolved into one of the world's leading independent fre control panel manufacturers. Kentec ofers the most comprehensive range of conventional, analogue addressable fre detection and extinguishant control panels available. Marine products are now an important part of our product portfolio and we have now introduced the all new "taktis" product range.
DA1 1JQ Established over 25 years ago, Kentec Electronics Ltd. Has evolved into one of the world's leading independent fre control panel manufacturers. Kentec ofers the most comprehensive range of conventional, analogue addressable fre detection and extinguishant control panels available. Marine products are now an important part of our product portfolio and we have now introduced the all new "taktis" product range.
DA1 1JQ Established over 25 years ago, Kentec Electronics Ltd. Has evolved into one of the world's leading independent fre control panel manufacturers. Kentec ofers the most comprehensive range of conventional, analogue addressable fre detection and extinguishant control panels available. Marine products are now an important part of our product portfolio and we have now introduced the all new "taktis" product range.
DA1 1JQ Established over 25 years ago, Kentec Electronics Ltd. Has evolved into one of the world's leading independent fre control panel manufacturers. Kentec ofers the most comprehensive range of conventional, analogue addressable fre detection and extinguishant control panels available. Marine products are now an important part of our product portfolio and we have now introduced the all new "taktis" product range.
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online from Scribd
Download as pdf or txt
You are on page 1of 112
By Appointment to Her Majesty The Queen
Supplier of Fire Detection Equipment
Kentec Electronics Ltd. Dartford, Kent. DA1 1JQ Leading in Fire Detection Control Systems For Over 25 Years Product Catalogue 2011 - 2012
Leading in Fire Detection Control Systems For Over 25 Years By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford, Kent. DA1 1JQ Miscellaneous Custom Power Supplies Extinguishant Conventional Analogue Addressable Leading in Fire Detection Control Systems For Over 25 Years By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford, Kent. DA1 1JQ Established over 25 years ago, Kentec Electronics Ltd. has evolved into one of the worlds leading independent fre control panel manufacturers. Over the years the Kentec name has become synonymous with World class product, great service and excellent support. Based in the UK, Kentec is a truly global supplier, exporting control equipment to over 80 countries Worldwide, and in many diferent languages. In keeping with our philosophy of in-house production we continue to invest heavily in state of the art manufacturing equipment for all areas of the business. This has allowed us to react quickly to customer requirements and market trends whilst maintaining our position at the forefront of Control panel design & manufacture. As an example of this, in early 2011, we opened our new World Class electronics manufacturing facility in Dartford. With this new facility we have been able to increase our capacity by over 30% resulting in even better customer support. Kentec ofers the most comprehensive range of conventional, analogue addressable fre detection and extinguishant control panels available. Our custom build service is also highly regarded in the industry and utilises our expertise in control panel technology to design and build high quality product to exacting customer specifcations. Marine products are now an important part of our product portfolio and we have now introduced the all new Taktis product range. Taktis will become one of the most comprehensive and dynamic products within the industry with its focus on added value and advanced technology. At Kentec we believe that the quality of our products should be paramount; rigorous testing procedures are employed at every stage of the manufacturing process to ensure that all equipment is supplied to the highest standards. For this reason we are confdent in ofering an industry leading 3 years warranty on all product that we supply. We also understand that service is a key part of how a manufacturers quality is judged. To this end we have invested extensively not only in our manufacturing facilities but in our support team including technical support and training. As part of our customer care Kentec ofers frst rate technical support facilities and a dedicated team of highly trained personnel provide direct telephone assistance; this is backed up by regular technical e-mail bulletins and on-site and of- site customer specifc training. Kentecs products are tested and approved to international standards such as EN54, EN12094, UL and FM. Kentec achieved Investors in people accreditation in 2004. Our management systems are ISO 9001:2008 approved and our policy for environmental awareness was ofcially recognized in 2007 when we gained our ISO 14001 certifcation from BSI. In 2008 Kentec was proud to be awarded the Royal Warrant of Appointment by Her Majesty the Queen. P a g e s
8 - 4 5 P a g e s
4 8 - 6 1 P a g e s
6 4 - 8 1 P a g e s
9 2 - 1 0 1 P a g e s 1 0 4 - 1 0 9 P a g e s
8 4 - 8 8 Page 4 We also have a full range of bending, cropping, studding and welding plant equipment allowing us the capability and exibility to produce single items or volume product. Integral to our sheet metal fabrication department is a state of the art computer controlled Amada break press. A comprehensive range of tooling is available in this key area of our manufacturing process. Our versatile painting department features a semi automatic powder coating plant. Introduced in 2009 it continues to provide all our metal component nishing needs. At the heart of our business lies the many in-house facilities that are at our disposal. From the initial design process, to sheet metal fabrication, to powder coating and printing through to panel construction, we have full control at every stage of our manufacturing process allowing us to oer industry leading delivery times and with quality that you can have condence in. In March 2009 we opened a new facility in Dartford which now houses the metal fabrication, paint and print shops, and has more than tripled our overall size. This was further enhanced with the commissioning of our new World Class electronics manufacturing facility in early 2011. Our In-house facilities... Overview Page 5 We also have a full range of bending, cropping, studding and welding plant equipment allowing us the capability and exibility to produce single items or volume product. Integral to our sheet metal fabrication department is a state of the art computer controlled Amada break press. A comprehensive range of tooling is available in this key area of our manufacturing process. Our versatile painting department features a semi automatic powder coating plant. Introduced in 2009 it continues to provide all our metal component nishing needs. At the heart of our business lies the many in-house facilities that are at our disposal. From the initial design process, to sheet metal fabrication, to powder coating and printing through to panel construction, we have full control at every stage of our manufacturing process allowing us to oer industry leading delivery times and with quality that you can have condence in. In March 2009 we opened a new facility in Dartford which now houses the metal fabrication, paint and print shops, and has more than tripled our overall size. This was further enhanced with the commissioning of our new World Class electronics manufacturing facility in early 2011. Our In-house facilities... Overview Our printing department has recently been subject to a complete transformation moving from a traditional silk screen printing process to state of the art digital printing. In late 2010 we acquired an OCE Arizona digital UV large format printer. The introduction of the Arizona printer has revolutionised the department oering increased capacity, consistency and quality. We are now seeing over 95% of products printed using this new process and we will be moving forward to oer more attractive and visually pleasing products as we employ more of the features oered by the Arizona printer. All panels supplied by Kentec are manufactured and assembled in-house in the U.K. Before despatch all panels undergo a rigorous testing procedure, they are then given a nal visual inspection. Electronic Sub assemblies are produced using our fully automated state of the art surface mount production line. We systematically utilise both Optical and electrical automatic test equipment to ensure each and every assembly is built to the same high standard and is fault free. To underpin our industry leading in-house manufacturing activities we employ teams of qualied and experienced mechanical, software and electronic hardware developers and technicians dedicated to both new product developments and existing ongoing product support. Analogue Fire Detection Control Equipment Pages 8-45 Analogue Fire Detection Control Equipment Pages 8-45 Syncro AS Single or Two Loop Analogue Addressable Fire Control Panels Page 8-9 Syncro Guide PC Graphics Software Page 28-29 Syncro Multi Loop Analogue Addressable Fire C/Ps Page 10-13 Syncro Guide Repeater Providing Repeater Facility for any GUIDE System Page 30-31 Syncro Response Analogue Addressable Fire Control Panel Repeaters Page 14-15 MIOU/LIOU Multi Input/ Output Unit (Standard and Light versions) Page 32-33 Syncro Focus Network LCD Repeater for Syncro System Page 16-17 Syncro I/O A range of I/O boards and enclosures Page 34-43 Syncro View Serial LCD Repeater for Syncro System Page 18-19 Syncro Ident Programmable LED Indication Panels Page 20-21 Syncro Matrix Intelligent Fire Alarm Mimic Display System Page 22-23 Syncro Net Syncro Network Interface Page 24-25 Syncro Comms Syncro Communications Module Page 26-27 OpenConnect BMS Communications Interface Page 44-45 I M PROVED! I M PROVED! I M PROVED! N EW ! Page 8 Single or Two Loop Analogue Addressable Control Panel Features Product Overview Syncro AS is a versatile range of open protocol fre alarm control panels compatible with existing Syncro fre alarm panel technology. Available with one or two detection loops capable of hosting up to 126 devices (Apollo), 240 devices (Argus Vega) or 127 devices (Hochiki). Syncro AS uses leading edge microprocessor based electronics to provide a fexible control system with high reliability and integrity. Suitable for all small to medium sized fre detection systems, Syncro AS control panels can be expanded and networked to become part of much larger systems if the need arises, therefore providing a future proof solution for any installation. With its large graphical display and ergonomic button and indicator layout, the Syncro AS control panel is simple and straightforward to understand for installers, commissioning engineers and end users alike. Comprehensive day/night mode facility Programmable one touch test mode Powerful and versatile cause & efect programming Cause & efect wizard including: Cause & efect action Disablement confguration Test mode confguration 16 zonal LED indicators
2 programmable sounder circuits
5 programmable inputs
3 programmable relays
3A power supply
Large graphic display
Real time clock Expandable from 1 to 2 loops* Certifed to EN54-2/ EN54-4
Up to 512 additional programmable I/O via Syncro I/O modules *
Powerful, network wide cause and efects *
Sensitivity adjustment and Drift Compensation
Can be networked with Syncro control panels *
Compatible with Focus and View repeaters *
Supports Apollo, Argus Vega and Hochiki protocols
Same look and feel as Syncro range
Stores 500 last events in event log
Dial up modem connection available
Compact, stylish enclosure
Installer friendly, removable equipment chassis
Diferent language and character set variants available
Fully EN54-2 and EN54-4 compliant improved front loading Printer option * ** Confg. Features Model No. #80161M2 * These items not available on Syncro AS Lite panel ** Can be ftted to M3 size enclosure only (Also backward-compat ible wit h Series 90 det ect ors) R AS Syncro BS- EN54- 2 BS- EN54- 4 KM 73505 I M P R O V E D ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 9 Construction Finish Colour - lid & box Colour - controls plate & labels Display Mains voltage supply
Mains supply fuse Power supply DC rating Aux 24V supply Battery (24 hour standby) Fault contact rating Fire contact rating Alarm contact rating Sounder output rating Detection loop Detector protocols
Printer port Serial expansion port
PC port Network connection
Remote Silence input (SIL) Remote fault input (FLT) Remote reset input (RES) Remote alert input (INT) Remote evacuate input (CNT) Download lead Confguration PC graphics Modem - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels Product Code A80161M2 A80162M2 A80161M3 A80162M3 A80161M3P A80162M3P V80161M2 V80162M2 V80161M3 V80162M3 V80161M3P V80162M3P H80161M2 H80162M2 H80161M3 H80162M3 H80161M3P H80162M3P Protocol Apollo Apollo Apollo Apollo Apollo Apollo Argus Vega Argus Vega Argus Vega Argus Vega Argus Vega Argus Vega Hochiki Hochiki Hochiki Hochiki Hochiki Hochiki Zones 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Size (mm) 385 x 310 x 90 * 385 x 310 x 90 * 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 310 x 90 * 385 x 310 x 90 * 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 310 x 90 * 385 x 310 x 90 * 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 * Flush versions are available to order (See price guide). Loops 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Printer No No No No Yes Yes No No No No Yes Yes No No No No Yes Yes Lite Panels Product Code LA80161M2 LV80161M2 LH80161M2 Protocol Apollo Argus Vega Hochiki Zones 16 16 16 Size (mm) 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90 Loops 1 1 1 Printer No No No DS47.06.2011 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 8 lines of 40 characters graphic LCD 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) 1.6A 250V 24V 3 Amps Fused at 500 milliamps 9Ah 12V (2 per panel) (non-networked) 30V DC 1 Amp 30V DC 1 Amp 30V DC 1 Amp Fused at 1 Amp each 400 milliamp output Apollo (S90, XP95, Discovery), Argus Vega or Hochiki ESP Serial RS232 Serial RS485 (Compatible with all Syncro I/O modules) Serial RS232 RS485 - Up to 64 panels via fully fault tolerant optional network card Switched -ve Switched -ve Switched -ve Switched -ve Switched -ve Standard S187, X187LS economy Via Loop Explorer PC utility Via Guide systems Optional dial up modem for remote diagnostics (Can be ftted to M3 size enclosure only) Product Code K555 K560 K547 K546 K545
K556P
K768AS K18002 B3472 Description Fault tolerant Network interface card 16 channel input/output board 8 way relay extender board 6 way sounder extender board 4 way conventional detection zone board Modem module (PSTN) (M3 size enclosure only) Printer Module - New front loading feature (M3 size enclosure only) Retroft Vision Window Door (M2 size enclosure only) Thermal Printer Paper Roll Options Page 10 Analogue Addressable Fire Control Panels Features Product Overview Available with 2 or 4 detection circuits, each capable of hosting up to 126 devices (Apollo), 240 devices (Argus Vega) or 127 devices (Hochiki). Syncro uses the most advanced microprocessor technology to provide a control system of extremely high integrity. Syncro can be confgured to suit all types of system, from the most simple, to the highly complex. Its fully integrated and secure network provides an intelligent interface for building control. A large area graphic display ensures that information is presented in plain language with detailed extra help available by pressing a help button. Syncro supports three of the most widely used communication protocols produced by leading fre detector manufacturers and employs daily calibration routines to ensure that the system is always at optimum performance. Comprehensive day/night mode facility Programmable one touch test mode Powerful and versatile cause & efect programming Cause & efect wizard including: Cause & efect action Disablement confguration Test mode confguration Confg. Features 2 or 4 loop versions as standard (for 6 - 8 loop versions see DS57 page 12-13) Larger enclosure available (fts 24A/H SLAs) Loopless panel option (repeater) 0, 16, 48, or 96 zone indicators Option for Enable Control keyswitch Fully supports Apollo, Argus Vega & Hochiki protocols Network up to 64 panels/repeaters 4 programmable sounder circuits as standard 5.25 amp power supply to EN54 part 4 Large graphic display In built help and alarm information screens Certifed to EN54-2/ EN54-4 Real time clock Supports Apollo, Argus Vega and Hochiki loop powered sounders and beacons Supports Apollo Ancillary Base Sounder Supports Apollo Intelligent Beam Stylish enclosure design Soft-touch tactile buttons 2 programmable function buttons 3 programmable front panel mounted LEDs Improved Front loading Printer (optional) Up to 512 programmable inputs/outputs per panel via 2 wire RS485 serial link (optional) Simple Windows graphical confguration utility Model No. EN#6396403P Syncro (Also backward-compat ible wit h Series 90 det ect ors) R BS- EN54- 2 BS- EN54- 4 KM 73505 I M P R O V E D ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 11 Construction Finish Colour - lid & box Colour - controls plate & labels Display Detection circuits (Loops) Zone LEDs 4 sounder circuits Fire contact Alarm contact Fault contact Programmable relay 1 Programmable relay 2 Fire routing output Fault routing output Extinguisher output Fault input Reset input Intermittent input Continuous input Silence input Programmable input 1 Programmable input 2 Programmable input 3 Auxiliary 24V DC output System fuse Mains fuse Operating Temperature Operating humidity Mains voltage supply Battery (24 hour standby) Day/night modes Input delays Output delays 2 programmable function buttons 3 programmable indicators Network (option) Printer (option) Download lead 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 8 lines of 40 characters graphic LCD 2 or 4 (400mA each) 0, 16, 48, or 96 (up to 500 software zones) Each fused at 1 Amp (total load 2 Amp) Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Monitored-voltage reversing, fused at 500mA Monitored-voltage reversing, fused at 500mA Monitored-voltage reversing, fused at 1A Volt free contact input signals fault Volt free contact input resets panel Volt free contact input pulses sounder outputs Volt free contact input for continuous sounders Volt free contact input silences sounders Volt free contact for any action required Volt free contact for any action required Volt free contact for any action required Fused at 500mA 5 Amp self-resetting polyfuse 20mm 3 Amp -5 to +50 deg. C To 95% (non-condensing) 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) 12Ah 12V (2 per panel) (non-networked) 2 with variable device sensitivity Individual for each device selectable up to 2 minutes Individual 2-stage to 10 minutes per stage Programmable to carry out any cause & efect, disablement or test action Red/yellow/green to indicate any action Up to 64 panels on 2 wires (K555 Network Card required) New front loading feature S187 (standard) or X187LS (economy) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels Product Code EN#6300203 EN#6316203 EN#6348203 EN#6396203 EN#6300403 EN#6316403 EN#6348403 EN#6396403 EN#6300415 EN#6316415 EN#6348415 EN#6396415 Zones 0 16 48 96 0 16 48 96 0 16 48 96 Size (mm) 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 460 x 190 500 x 460 x 190 500 x 460 x 190 500 x 460 x 190 # - replace with A for Apollo protocol, V for Argus Vega protocol or H for Hochiki protocol. Flush versions are available to order (See price guide). For ftted printer add P after stock code. Loops 2 2 2 2 4 4 4 4 4 4 4 4 Product Code K552# K555 K768SYN K560 K547 K546 K545 K556P B3472 Description Loop extension card (loops 3 & 4) Fault tolerant Network interface card Thermal printer kit (for retroftting to non-printer models) 16 channel input/output board 8 way relay extender board 6 way sounder extender board 4 way conventional detection zone board Modem module (PSTN) Thermal Printer Paper Roll Options # - replace with A for Apollo protocol, V for Argus Vega protocol or H for Hochiki protocol. 506mm 361mm 130mm Bezel extends 15mm in each direction Model No. EN#6396414 2
L o o p
P a n e l s 4
L o o p
P a n e l s DS16.14.2011 Flush Syncro Control Panel Flush mount cross section Control Panel Wall Note: There is one size for all standard fush Syncro control panels. For the hole size we recommend that you allow 5mm clearance all round. 4
L o o p
P a n e l s L a r g e r
E n c l o s u r e Page 12 Analogue Addressable Fire Control Panels 6 or 8 Loops Features Product Overview Available with 6 or 8 detection circuits, each capable of hosting up to 126 devices (Apollo), 240 devices (Argus Vega) or 127 devices (Hochiki). Syncro uses the most advanced microprocessor technology to provide a control system of extremely high integrity. Syncro can be confgured to suit all types of system, from the most simple, to the highly complex. Its fully integrated and secure network provides comprehensive scalability. A large area graphic display ensures that information is presented in plain language with detailed extra help available by pressing a help button. Syncro supports three of the most widely used communication protocols produced by leading fre detector manufacturers and employs daily calibration routines to ensure that the system is always at optimum performance. Comprehensive day/night mode facility Programmable one touch test mode Powerful and versatile cause & efect programming Cause & efect wizard including: Cause & efect action Disablement confguration Test mode confguration Confg. Features 6 or 8 loop versions as standard 96 zone indicators Fully supports Apollo, Argus Vega & Hochiki protocols Network up to 32 6 or 8 loop panels 8 programmable sounder circuits as standard 2 x 5.25 amp PSUs to EN54 part 4 Large graphic display In built help and alarm information screens Certifed to EN54-2/ EN54-4 Real time clock Supports Apollo, Argus Vega and Hochiki loop powered sounders and beacons Stylish enclosure design Soft-touch tactile buttons 2 programmable function buttons 3 programmable front panel mounted LEDs Improved Front loading Printer (optional) Up to 1024 programmable inputs/outputs per panel via 2 wire RS485 serial link (optional) Simple Windows graphical confguration utility Wide choice of languages available Model No. EN#63966S4P Syncro (Also backward-compat ible wit h Series 90 det ect ors) R I M P R O V E D ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 13 Construction Finish Colour - lid & box Colour - controls plate & labels Display Detection circuits (Loops) Zone LEDs 8 sounder circuits 2 x Fire contact 2 x Alarm contact 2 x Fault contact 2 x Programmable relay 1 2 x Programmable relay 2 2 x Fire routing output 2 x Fault routing output 2 x Extinguisher output 2 x Fault input 2 x Reset input 2 x Intermittent input 2 x Continuous input 2 x Silence input 2 x Programmable input 1 2 x Programmable input 2 2 x Programmable input 3 2 x Auxiliary 24V DC output 2 x System fuse 2 x Mains fuse Operating Temperature Operating humidity Mains voltage supply Battery (24 hour standby) Day/night modes Input delays Output delays 2 programmable function buttons 3 programmable indicators Network Printer (option) Download lead 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 8 lines of 40 characters graphic LCD 6 or 8 (400mA each) 96 (up to 500 software zones) Each fused at 1 Amp (total load 2 Amp per bank of 4 circuits) Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Monitored-voltage reversing, fused at 500mA Monitored-voltage reversing, fused at 500mA Monitored-voltage reversing, fused at 1A Volt free contact input signals fault Volt free contact input resets panel Volt free contact input pulses sounder outputs Volt free contact input for continuous sounders Volt free contact input silences sounders Volt free contact for any action required Volt free contact for any action required Volt free contact for any action required Fused at 500mA 5 Amp self-resetting polyfuse 20mm 3 Amp -5 to +50 deg. C To 95% (non-condensing) 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) 12Ah 12V (4 per panel) 2 with variable device sensitivity Individual for each device selectable up to 2 minutes Individual 2-stage to 10 minutes per stage Programmable to carry out any cause & efect, disablement or test action Red/yellow/green to indicate any action Up to 32 6 or 8 loop panels on 2 wires New front loading feature S187 (standard) or X187LS (economy) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels Product Code EN#63966S4 ENS#63966S4 EN#63968S4 ENS#63968S4 Zones 96 96 96 96 Size (mm) 500W x 650H x 137D 500W x 650H x 137D 500W x 650H x 137D 500W x 650H x 137D # - replace with A for Apollo protocol, V for Argus Vega protocol or H for Hochiki protocol. For ftted printer add P after stock code. Loops 6 6 8 8 Product Code K552# K768SYN K560 K547 K546 K545 K556P B3472 Description Loop extension card (loops 7 & 8) Thermal printer kit (for retroftting to non-printer models) 16 channel input/output board 8 way relay extender board 6 way sounder extender board 4 way conventional detection zone board Modem module (PSTN) Thermal Paper Printer Roll Options # - replace with A for Apollo protocol, V for Argus Vega protocol or H for Hochiki protocol. DS57.03.2011 Enable Control No Yes No Yes Page 14 Analogue Addressable Fire Control Panel Repeaters Features Product Overview Syncro Response is a full function repeater panel used to compliment the Syncro control panel range. Syncro Response uses the most advanced microprocessor technology to provide a control system of extremely high integrity. Syncro Response can be confgured to suit all types of system, to provide selectable event reporting and controls from each panel on the network. A large area graphic display ensures that information is presented in plain language with detailed extra help available by pressing a help button. Syncro networks support three of the most widely used communication protocols used by leading fre detection manufacturers. Programmable one touch test mode Powerful and versatile cause & efect programming Cause & efect wizard including: Cause & efect action Disablement confguration Test mode confguration Confg. Features 0, 16, 48, or 96 zone indicators Network up to 64 panels/repeaters 5.25 amp power supply to EN54 part 4 Large graphic display In built help and alarm information screens Complies with EN54-2 Real time clock Stylish enclosure design Soft-touch tactile buttons 2 programmable function buttons 3 programmable front panel mounted LEDs Improved Front loading Printer (optional) Up to 512 programmable inputs/outputs per panel via 2 wire RS485 serial link (optional) Simple Windows graphical confguration utility Model No. #6196003 Response Syncro I M P R O V E D ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 15 Construction Finish Colour - lid & box Colour - controls plate & labels Display Zones Alarm contact Fault contact Programmable relay 1 Programmable relay 2 Auxiliary 24V DC output System fuse Mains fuse Operating Temperature Operating humidity Mains voltage supply Battery (24 hour standby) Day/night modes Input delays Output delays 2 programmable function buttons 3 programmable indicators Printer (option) Download lead 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 8 lines of 40 characters graphic LCD 0, 16, 48, or 96 Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Volt free 1 Amp 30V DC Fused at 500mA 5 Amp self-resetting polyfuse 20mm 3 Amp -5 to +50 deg. C To 95% (non-condensing) 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) 12V 12Ah (2 per panel) 2 with variable device sensitivity Individual for each input selectable up to 2 minutes Individual 2-stage to 10 minutes per stage Programmable to carry out any cause & efect, disablement or test action Red/yellow/green to indicate any action New front loading feature S187 (standard) or X187LS (economy) - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels Product Code K6100003 K6116003 K6148003 K6196003 Zones 0 16 48 96 Size (mm) 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 Flush versions are available to order. For ftted printer add P after stock code Loops 0 0 0 0 Product Code K768SYN
K560 K547 K546 K545 K556P B3472 Description Thermal printer kit (for retroftting to non printer models) 16 channel input/output board 8 way relay extender board 6 way sounder extender board 4 way conventional detection zone board Modem module (PSTN) Thermal Printer Paper Roll Options Note: Syncro Response is supplied complete with K555 network interface card ftted. Note: If this panel is to be ftted to an existing system the main panel must be also be ftted with and K555 network interface card to enable communications. 6 & 8 loop panels have a network card ftted as standard. DS17.09.2011 Page 16 Network LCD Repeaters Features Product Overview This simple and attractive repeater panel can be connected to any point on a Syncro network to provide additional display points as needed. Using the same large format graphics display as the main control panel ensures that a clear and concise indication is given at all times. Ideal for additional building entrances, security desks or nurses stations this unit provides an economical alternative to a full function repeater panel. (Syncro Response) The repeater also acts as a network booster and can be used to extend cable runs beyond the specifed lengths as required. Large graphic display Simple connection to Syncro network 24V DC powered (230V AC available) Small attractive enclosure Confgurable to display all or any events Simple to install Volt free Alarm, Fire and Fault contacts Up to 63 repeaters can be connected to a panel Focus+ with full controls has the following extra buttons: Silence Alarm Resound Alarm Reset Focus+ Model No. K691000M1 Focus Model No. K69000M1 Foc us Syncro FOCUS+ PANEL 6 NETWORK NETWORK & CONTROL MONITORING REMOTE PC SYSTEM GRAPHICS FOCUS PANEL 5 REPEATER REPEATER PANEL 8 PANEL 9 NETWORK REPEATER BOOSTER PANEL 7 SIGNAL 2 LOOP PANEL 2 NETWORK 4 LOOP PANEL 3 NETWORK 4 LOOP PANEL 4 NETWORK 0 LOOP PANEL 1 NETWORK ALLOWS DISTANCES GREATER THAN 1.2 KILOMETRES 1.2 KILOMETRES MAX. B A Example of a Syncro high integrity network Note: Signal booster is a Focus or Focus+ repeater used as a booster. Foc us+ Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 17 Construction Finish Colour - lid & box Colour - controls plate & labels Display Input voltage (24V DC model) Input voltage (230V AC model) Current consumption Alarm current Alarm contact rating Fire contact rating Fault contact rating Display Cable entry Indicators Battery Size (24 hr. standby on 230V AC model) Communications Cable length
Network cable type Operating temperature 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture Ral 7047 light grey - satin 8 lines of 40 characters graphic LCD 21V DC - 30V DC 230V AC +10%/-15% 80mA at 24V DC (in fault condition) 100mA at 24V DC 30V DC 1 Amp max. 30V DC 1 Amp max. 30V DC 1 Amp max. 240 x 64 pixel graphic LCD 20mm knockouts 5mm high brightness LED 2.3Ah 12V (2 per panel)
Syncro system network protocol only 1200 metres to adjacent nodes (subject to cable type) (see technical manual) Belden 9271, Belden 9860, FP200 Gold -5C to +40C - - - - - - - - - - - - - - - - - - - - Technical Focus Units Product Code K68000M1 K69000M1 K68000F1 K69000F1 PSU - 750mA - 750mA Weight 2.5kg 4.0kg 2.5kg 4.0kg Size (mm) 330 x 255 x 90 330 x 255 x 90 330 x 255 x 90 330 x 255 x 90 Build Surface Surface Semi Flush Semi Flush Focus+ Units NOTE: An K555 network card is required in the Syncro/Syncro AS panel in order to communicate with these products. 6 - 8 loop panels have a network card ftted as standard. Product Code K681000M1 K691000M1 K681000F1 K691000F1 PSU - 750mA - 750mA Weight 3.5kg 4.0kg 3.5kg 4.0kg Size (mm) 330 x 255 x 90 330 x 255 x 90 330 x 255 x 90 330 x 255 x 90 Build Surface Surface Semi Flush Semi Flush PSU FLT. NC C NO C NC NC C NO NO NC C NET. NET. IN FAULT FIRE ALARM OUT 24V 24V battery backed power Syncro Focus/Focus+ PCB From previous panel on network To normally closed contact on local PSU To next panel on network (2.3Ah for 24H standby) DS24.10.2011 Page 18 Local LCD Control Panel Repeater Features Product Overview Designed and manufactured to the highest standards in a quality controlled environment the Syncro VIEW fre alarm annunciator provides a simple and convenient method of extending the controls and indications of the Syncro fre alarm control panel to other locations. The large, graphic liquid crystal display and high brightness LED indicators duplicate the indications on the Syncro fre alarm control panel at up to 15 additional locations via a simple, two-wire serial data connection. The Syncro VIEW is available in either a 24V DC powered option (which can be powered via an additional 2 cores from the Syncro control panel/local 24V DC supply) or a 230V powered option with local battery back up. Syncro VIEW is housed in a small enclosure which is styled similarly to the Syncro control panel and is ideal for installations where a large control panel would be detrimental to dcor such as entrance halls. Up to 15 Syncro VIEW annunciators can be connected to each control panel on the Syncro network making VIEW ideal where multiple points of indication and/or control are required such as nurses stations or shop units. Up to 15 annunciators can be connected to each Syncro, Syncro Response or Syncro AS fre control panel. Large liquid crystal display (240 x 64 pixels) High brightness LED indications Internal sounder Replicates all Syncro panel controls Simple, two-wire serial connection Small, Syncro style enclosure Removable electronics for easy installation 24V DC or 230V AC power options Low power consumption Multi language options Connection monitored by Syncro fre control panel Model No. K67750M1 Vi ew Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 19 Construction Finish Colour - lid & box Colour - controls plate & labels Display Cable entry Mains supply (Mains models only) 24V supply (24V DC models only) Mains supply fuse Power supply rating Maximum ripple current Battery type (Yuasa NP) Battery charge voltage Battery charge current Battery fuse Maximum current draw from batteries Quiescent current of panel in mains fail Serial data connection Maximum terminal capacity 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture Ral 7047 light grey - satin 8 lines of 40 characters graphic LCD 5 x 20mm knockouts in top of box and 5 in rear 230V AC +10% - 15% (20 Watts maximum) 21 to 30V DC 2 Amp, 20mm 28V 750mA total (including battery charging) 200 millivolts Two 12 Volt 1.9Ah sealed lead acid in series 27.6VDC nominal 200mA maximum 200mA, 20mm, glass 95mA 0.03 Amps 2 core RS485 (Up to 1200 metres total cable length) 2.5mm - - - - - - - - - - - - - - - - - - - Technical Equipment Product Code K67000M1 K67750M1 K67001M1 K67751M1 PSU - 750mA - 750mA Size (mm) 330 x 255 x 90 330 x 255 x 90 330 x 255 x 90 330 x 255 x 90 Description Syncro View repeater panel Syncro View repeater panel Syncro View repeater panel c/w enable keyswitch Syncro View repeater panel c/w enable keyswitch Syncro Control Panel Syncro View #1 Comms In Comms Out 24V In 24V Out Syncro View #15 Comms In Comms Out 24V In 24V Out Comms Aux 24V DS43.04.2011 Semi-fush versions are available to order Page 20 Programmable, LED Indication Panels Features Product Overview Syncro Ident panels provide a compact and attractive display for up to 24 indications from a Syncro or Syncro AS fre control panel. As with all inputs and outputs on the Syncro system, each indicator is fully programmable to indicate a variety of events as well as being fully programmable via cause and efects to operate in response to logically connected inputs. Each indication defaults to a zonal fre indicator but may be confgured via the Loop Explorer confguration utility to operate upon any event type or combination of inputs. Requiring only a low current 24V power supply and a 2 core data connection to the fre panel, Syncro Ident panels can be installed quickly and easily to provide supplementary information on the status of the fre alarm system with the minimum of cost and efort. The compact, slimline enclosure is unobtrusive and is ideal for mounting in locations where a larger control and indication unit would be unsuitable. Each indication has a dedicated feld for customized text to provide a concise description of the indication. Multiple Syncro Ident panels can be connected to the Syncro serial bus to provide a diverse range of indications at multiple locations. 8 and 24 LED versions available as standard Large versions available to special order Up to 16 x 24 way Syncro Ident can be connected to each fre panel Programmable fashing or steady states Red, yellow or green indications/ options Common Fire, Fault and Disabled indication Customisable label identifcation tags Buzzer with silence control and re-sound Lamp test control Low power 24V DC supply Connects to 2 wire Syncro RS485 data bus Multiple language options Model No. K6524L2 I dent Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 21 Construction Finish Colour - lid & box Colour - controls plate & labels LED colours Supply Voltage Data Connection 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin
Red, yellow or green 18 to 30V DC RS485 Syncro comms bus (Max 1200 metres) - - - -
- - - Technical Panels Product Code K6508L2 K6524L2 No. of LEDs 8 24 Size (mm) 385 x 310 x 60 385 x 310 x 60 DS60.02.2011 15:05 Tuesday 10 October 2006 KENTEC ELECTRONICS LIMITED 4 3 2 1 ? More Events Fires More Exit Enter Enable Control Function Evacuate Reset Buzzer Silence (Acknowledge) Silence Alarm Re-Sound Sounder Fault/Disabled SystemFault Power Fault General Fault General Disablement More Events Delay Active Buzzer Silenced On Test Pre-Alarm Power On Test Lamp Alarm Fire in Zone 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Fire Model: Fire Detection Indicator Fire Power On Fault Disablement Buzzer Silence LampTest RS485 2 Core Data Cable 2 Core Power Cable Zonal Fire Indicators Plant Status Disabled Refuge Alarms Syncro View Syncro AS Fire Control Panel Model: Fire Protection Indicator Model: Fire Detection Indicator Fire Power On Fault Disablement Buzzer Silence LampTest Syncro Matrix Syncro I/O Model: Fire Detection Indicator Fire Power On Fault Disablement Buzzer Silence LampTest Examples of Syncro Ident panel used to provide supplementary indications from the re control panel COMMS OUT OUT I/O I/O CHANNEL 0V LT 0V 0V 24V 0V 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 COMMS IN IN 0V 24V 0V Fire Alarm Mimic Display Fire Power On Fault Disablement Buzzer Silence Lamp Test Alarm Silence Enable Control Reset Fire Alarm Repeater 4 3 2 1 ? 15:05 Tuesday 22 August 2006 KENTEC ELECTRONICS LIMITED Fire Silence Alarm Disablement General (Acknowledge) Re-Sound Fault/Disabled Fault/Disabled Fire Routing SystemFault Sounder Power Fault General Fault More Events Delay Active Buzzer Silenced On Test Fire Routing On Pre-Alarm Power On Buzzer Silence Test Lamp Reset Alarm Two Function One Function Events More More Fires Exit Enter Other RS485 compatible devices Versions with more LED indications available to special order Page 22 Intelligent Fire Alarm Mimic Display System Features Product Overview The Syncro Matrix system uses fexible, fbre optic light guides to illuminate areas on a foor plan, laid over a high resolution grid. This unique system dispenses completely with wiring and enables indicators to be moved, removed or added on site without the need for any wiring. All indicators can be confgured to operate upon any event type and at point, zone or group level via Kentecs powerful and intuitive Loop Explorer confguration programme. Syncro Matrix can be supplied with or without LEDs and controls. Optional LEDs indicate Power on, Fire, Fault and Disablement and optional controls are for Alarm silence, Buzzer silence, Lamp test and Reset. Housed in attractive, slimline enclosures to match Syncro and Syncro AS fre alarm panels and with high quality, full colour or monochrome foor plans, Syncro Matrix provides a clear, geographical indication of fre alarm activation enabling speedy identifcation of the source of an alarm. Up to 504 LEDs can be controlled from any Syncro or Syncro AS panel Full colour printing Available in a range of standard enclosures to suit any applications Bespoke sized units can be made upon request Choice of Red, Green or Yellow LEDs Available with or without controls Same look and feel as Syncro range Syncro Matrix can easily be upgraded on site with minimal cost and efort EN54-4 approved PSU (optional) Confgured via standard Loop Explorer Software M3 size Syncro Matrix Mat r i x Syncro View showing mimic mounted on inner door View showing LED grid View showing internal layout PSU opt ional Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 23 Construction Finish Colour - lid & box Colour - controls plate & labels Mimic Number of indicators (standard models) Mains supply (230V Versions only) Mains supply fuse (230 V Versions only) Power supply rating (230 V Versions only) Max. ripple current (230 V Versions only) Battery type (Yuasa NP) (230 V Versions only) Battery charge voltage (230 V Versions only) Battery charge current (230 V Versions only) Max. current draw from batteries (230 V Versions only) Quiescent current Supply voltage (24V versions) Supply current Terminal capacity Enable keyswitch (if ftted) Cabinet locks Communications interface Maximum distance from control panel IP rating Operating temperature 1.2mm mild steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 3mm Clear Anti-Glare Acrylic M2 size - up to 24, M3 and S3 size - up to 56, S4 size - up to 88 230V AC +10% - 15% (100 Watts max.) T2A L250V Replace only with similar type 5.25 Amps total including battery charge 28V +/ 2V 200 millivolts Two 12 Volt sealed lead acid (7Ah maximum) 27.6VDC nominal (temperature compensated) 1.5A maximum 3 Amps. With mains power source disconnected See above 21 to 30V DC See above 0.5mm2 to 2.5mm2 solid or stranded wire Standard 901 key M2/M3 - standard 801 key, S3/S4 - standard KT3001 key RS485 Syncro/Syncro AS serial I/O bus protocol 1.2Km using RS485 data cable IP30 -5C to +50C - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels No. LEDs 24 56 88 Full Alarm Current 0.09 0.18 0.36 Batteries for 24 hours 0.88Ah 1.75Ah 2.8Ah Standby Current 0.026 0.052 0.078 Batteries for 48 hours 1.76Ah 3.5Ah 5.2Ah Max. number of LEDs = 56 Will house 1 x 8 Red LED driver PCB and 3 x 16 LED extension PCBs (Red, Green or Yellow) Enclosure Size Options Max. number of LEDs = 56 Will house 1 x 8 Red LED driver PCB and 3 x 16 LED extension PCBs (Red, Green or Yellow) Max. number of LEDs = 88 Will house 1 x 8 Red LED driver PCB and 5 x 16 LED extension PCBs (Red, Green or Yellow) Max. number of LEDs = 504 Will house 1 x 8 LED driver PCB (Red) and up to 31 x 16 LED extension PCBs (Red, Green or Yellow) Max. number of LEDs = 24 Will house 1 x 8 Red LED driver PCB and 1 x 16 LED extension PCBs (Red, Green or Yellow) DS52.03.2011 385mm x 310mm 90mm Deep 500mm x 355mm 117mm Deep 385mm x 520mm 110mm Deep 500mm x 650mm 137mm Deep Colour/Finish & Size to suit your requirements M2 S3 M3 S4 Bespoke Size 303 400 225 400 303 515 400 ? ? 185 Page 24 Syncro Networking Features Product Overview The fexibility of the Syncro system can be further enhanced by connecting control panels and repeaters together using a high integrity network. A simple 2-wire connection between each panel allows events to be transmitted to other parts of the system to provide indication or control on a system wide basis. Using the Loop Explorer confguration programme, up to 64 nodes can be programmed to respond in a variety of ways to any system events as required. This fexibility extends the comprehensive cause and efect programming capability of Syncro control panels to the entire network allowing actions, test modes or disablements to be started from any point. The fault tolerance of the network is such that any single open or short circuit fault will not result in any loss of information. Multiple faults are isolated and the network breaks into smaller networks which continue to work autonomously. Up to 64 nodes High integrity protocol Fully secure against short or open circuit faults Simple 2-wire loop connection Supports open ended networks for retroft applications Repeaters share network connection Network wide test and disablement functions Network wide cause and efect logic Flexible confguration options Panels confgurable to act on network events or not as required Apollo & Hochiki panels supported on single network Part No. K555 Net Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 25 Product code Protocol Connection Current Consumption Integrity Indicators Cable length
Cable type Compatible panels K555 RS485 Two wire loop 40mA Full isolation of faulty nodes or wiring segments Data In and Data Out communications status 1200 metres to adjacent nodes (subject to cable type) (see technical manual) Belden 9271, Belden 9860, FP200 Gold Syncro/Syncro AS (required for networking) Syncro Response/Syncro 6 & 8 loop, Syncro Focus (supplied with panel) - - - - - - - - - Technical Flexible network confguration options using simple to follow PC confguration programme Two core loop wiring ensures network integrity by providing full isolation of faulty wiring segments. Control Panel 2 Core 2 Core (Not tted on open ended networks) 2 Core Control Panel Control Panel DS23.07.2009 Page 26 Communications Module (modem) Features Product Overview The K556 communications module enables service companies to interrogate control panels remotely via a telephone link. The communications module is simple to install and requires a PSTN telephone line. The module mounts on existing pillars in the control panel and is supplied with all wiring and connections to enable speedy installation and commissioning. Once connected to the control panel via the Loop Explorer software, users can upload confguration data and event logs or take control of the system via the virtual panel interface. This allows the panel controls to be operated as if the user was standing at the panel. The Loop Explorer confguration programme (version 3.0 or higher) is used to dial into control panels but the dial up facility will not be available unless the PC calling the control panel is ftted with a registered dongle (part number B2158 for parallel port or B2158USB for USB version). View devices near calibration limits Plan maintenance visits Retrieve event log Dial in and observe reported faults Assist commissioning from remote location Ofer value added service to customers Check software version to see if updates are available Retrieve confguration Avoid unnecessary call outs Simple to install Dongle protected access, for customers security Comms Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 27 Module part number Size Supply voltage Current consumption Connection Dongle part number K556P (PSTN) 190mm(H) x 62mm(W) x 40mm(D) 21V to 30V DC 50 milliamps PSTN B2158 (parallel port) B2158USB (USB serial port) - - - - - - Technical Note: The Communications Module is compatible with Loop Explorer Software version 3 or above and Syncro Control Panel Firmware version 3 or above. PC running Loop Explorer Programme & tted with Dongle Public Telephone Network Syncro Control Panel tted with Communications Module DS31.07.2011 Note: One dongle required per user, to enable the dial in facility within the Loop Explorer program Page 28 Graphical User Interface for fre Detection Equipment Features Product Overview Syncro fre control panels can send data to, and be controlled by, the Guide system providing a single point of co-ordination for all alarms. The powerful 32 bit programme features a standard Windows look and feel and runs under Windows 2000 , XP, Vista or Windows 7 Professional. The system is highly confgurable in terms of the style of presentation so that the end user can be presented with maps, text, photographs, audio or a combination of all as required. User profles allow the system manager to control the facilities available to each individual system user. A comprehensive history logging and reporting system allows analysis of events and trends to be identifed to reduce unwanted alarms. Easy to programme and simple to use, Guide provides a cost efective solution for fre alarm management at many levels. Choice of text, graphic, event list display when an event occurs Versatile event analysis Total history archive Easy to programme Secure system Cost efective compared to other systems Simple to use Unlimited map linking & zoom facility Support for 100s of graphics Display and control for multiple panels Event history explore and export facility to text or HTML documents Powerful Event log fltering Virtual Panel - allows direct control GUI DE Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 29 Processor Operating system Memory Hard disk Graphics
Sound card Loudspeaker Monitor
Pointing device
Printer Parallel port Serial ports
CDROM drive
Backup drive Notes The faster the better Will operate under Windows 2000 The larger the better. The driver must allow this mode with large fonts. Separate Graphics card with 256MB graphics memory recommended
More convenient if built into PC. 17 inch minimum recommended, the larger the better. (1024 x 768) Third button and wheels are supported. Touch screen option supported Any type. Required if parallel printer to be used. Isolated converter supplied for connection to fre alarm system. Required for installation of software and updates. To back up history. Recommended Minimum Intel Pentium 1Ghz Windows XP/Vista , 7 Professional 1Gb minimum 10GB minimum 1024 x 768 16M colours
Any PC sound card Any PC speakers Any that supports above graphics driver Mouse essential
Optional Optional One RS232 per network Any
CD Writer Technical Range Product Code G1001 G1004 G1008 G1016 G1032 G1064 Description GUIDE software - Single panel package GUIDE software - 4 panel package GUIDE software - 8 panel package GUIDE software - 16 panel package GUIDE software - 32 panel package GUIDE software - 64 panel package Note: Guide will be operating 24 hours a day for many years. It may be desirable to include on site PC maintenance as part of the package. Note: The Syncro panel to which the Guide system is connected must not have a printer ftted. Note: Guide For use with Syncro Panels. Syncro 6 & 8 loop panels are considered 2 panels in the packages above. DS18.10.2009 Guide System Fire Control Panel Fire Control Panel Dongle tted RS485 Fire Control Panel Page 30 Providing Repeater Facility for any GUIDE System Features Product Overview Syncro GUIDE Repeater is an additional facility for the Syncro GUIDE fre alarm management system. GUIDE Repeater allows monitoring and limited control of the Syncro fre control system to be repeated on dedicated computers connected to the building Local Area Network. GUIDE Repeater is highly confgurable allowing replication of the main GUIDE system or alternative information to be given at the repeater Up to 16 GUIDE Repeaters may be connected to a single GUIDE system All monitoring options on GUIDE are supported on the GUIDE repeater. Device an zone disablements may also be performed from the Guide repeater. Choice of text, graphics, combined display when an event occurs. Easy to use Allows graphical information of fre events to be shown at alternative locations Unlimited map linking and zoom facility Display and control for up to 64-networked Syncro panels Repeat er Syncro Guide Repeater user interface GUI DE Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 31 DS45.02.2009 Range Product Code GR2001 GR2004 GR2016 Description GUIDE Repeater - single repeater package GUIDE Repeater - 4 repeater package GUIDE Repeater - 16 repeater package Processor Operating system Memory Hard disk Graphics
Sound card Loudspeaker Monitor
Pointing device
Printer Parallel port Network CDROM drive
Backup drive Notes The faster the better Will operate under Windows 2000 The larger the better. The driver must allow this mode with large fonts. Separate Graphics card with 256MB graphics memory recommended
More convenient if built into PC. 17 inch minimum recommended, the larger the better. (1024 x 768) Third button and wheels are supported. Touch screen option supported Any type. Required if parallel printer to be used.
Required for installation of software and updates. To back up history. Recommended Minimum Intel Pentium 1Ghz Windows XP/Vista / 7 Professional 256MB minimum 10GB minimum 1024 x 768 16M colours
Any PC sound card Any PC speakers Any that supports above graphics driver Mouse essential
Optional Optional One network port Any
CD Writer Technical Guide System Dongle tted RS485 Fire Control Panel LAN Page 32 Multi Input/Output Unit Product Overview - MIOU Occupying less than 20% of the space required by conventional I/O units, the MIOU replaces the large and expensive enclosures normally required for this application. With 8 opto-isolated inputs and 8 volt-free relay contacts (relay outputs individually selectable as normally open, normally closed or switched voltage outputs), the MIOU will fnd a multitude of uses in concentrated I/O applications. MI OU LIOU - Model No. K507 MIOU - Din rail mounting version (K559) LI OU( Lit e Version) Features - MIOU Multiple inputs and outputs at one address Opto isolated inputs Volt free contact or switched voltage outputs Considerable space and cost saving over discreet I/O units Easy clip-on din rail mounting method Compatible with Solo, Syncro AS and Syncro control equipment Low standby supply current Hochiki ESP protocol Product Overview - LIOU LIOU Lite provides 4 inputs and 4 outputs to a Hochiki analogue addressable detection loop in a compact and cost efective package. The LIOU Lite can replace up to four addressable modules in approximately the same space taken by one standard module and is ideal for applications where a concentration of I/O is needed in a limited space. The modules can be addressed with the Hochiki, hand held programmer in the range 1 to 127. All inputs and outputs are fully confgurable for any action and for cause and efect via the Syncro Loop Explorer confguration utility. The LIOU connects to the ESP loop as per all other ESP devices. Consider the maximum number of sub-addresses when using LIOU. Each unit has an integral short circuit isolator which provides further cost and space saving. Features - LIOU Four optically isolated inputs Four volt free changeover relay contact outputs 24V DC powered Small footprint Cost efective for concentrated I/O applications Built in short circuit isolator Compatible with Syncro and Syncro AS addressable fre control panels Hochiki ESP protocol Note: MIOU & LIOU are currently compatible with Solo, Syncro and Syncro AS control panels only. Note: MIOU & LIOU support Hochiki ESP protocol only. Note: Inputs on MIOU & LIOU are not monitored. Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 33 Boxed unit battery capacity Finish - lid & box Colour - lid & box Boxed unit IP rating Module mounting Communication protocol Supply voltage H6600001 Supply voltage H6675001 Quiescent supply current Input operated current Output operated current Input trigger resistance Output contact rating Switched -ve output Minimum recommended PSU Operating temperature Device sub-address count Address setting 2.6Ah 12V (2 per unit) Epoxy powder coated BS 00-A-05 grey - fne texture IP30 Symmetrical or asymmetrical din rail Hochiki ESP 24V DC 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) 10 milliamps 3 milliamps 18 milliamps 1k maximum 30V DC 1 Amp maximum 65 milliamps maximum per output 750 milliamps at 24V DC -5 to +40 deg. C 17 (of 800 permitted in Syncro / Syncro AS panel) Hochiki hand held programmer (see TB1010) - - - - - - - - - - - - - - - - - - Technical - MIOU Range Weight 0.3kg 3.6kg 6.8kg 0.2kg 3.6kg 6.8kg PSU - - 750mA - - 750mA Product Code K559 (Module Only) H66000M2 H66750M2 K507 (Module Only) HL66000M2 HL66750M2 Size (mm) 203(L) x 77(W) x 45(D) 385(L) x 310(H) x 90(D) 385(L) x 310(H) x 90(D) 119(L) x 99(W) 385(L) x 310(H) x 90(D) 385(L) x 310(H) x 90(D) DS21.09.2011 Module MIOU MIOU MIOU LIOU LIOU LIOU Boxed unit battery capacity Finish - lid & box Colour - lid & box Module mounting Communication protocol Supply voltage (K507 & HL6600M2) Supply voltage (HL66750M2) Mains fuse for HL67750M2 Quiescent supply current Input operated current Output operated current Input trigger resistance Output contact rating minimum recommended PSU Operating temperature Device sub-address count 2.6Ah 12V (2 per unit) Epoxy powder coated, BS 00 A 05 grey - fne texture 4 x 4mm holes in PCB Hochiki ESP 21 to 30V DC 230V AC 20mm ceramic 2A/250V fast acting 10 milliamps 3 milliamps 18 milliamps 1K maximum 30V DC/2A - 230V AC/0.5A 750 milliamps at 24V DC -5 to +40 deg. C 17 (of 800 permitted in Syncro / Syncro AS panel) - - - - - - - - - - - - - - - - Technical - LIOU FIRE PRESS HERE BREAK GLASS LIOU/ MIOU 24V DC CHQ-DIM CHQ-DRC Control Panel Page 34 16 Channel Input/Output Board Features Product Overview To add more I/O capability to the extensive options already ofered by the Syncro control panel, up to thirty two, sixteen channel I/O boards may be connected. The 16 channel boards may be mixed on the RS485 bus with 8 way sounder boards, 6 way sounder boards or 4 way conventional detection zone boards to provide a very fexible system of I/O to satisfy any requirement. When using a simple two wire RS485 communications protocol, these boards may be mounted locally to the control panel or distributed on a bus up to 1200 metres long by using a suitable cable. The fexibility of these boards is further enhanced by the fact that each of the channels is confgurable as either an input or and output. Each channel may also be confgured to produce a variety of input actions or respond to a variety of output types. All channels can contribute to, or respond to, system wide cause and efects logic. Typical uses for I/O boards include geographical LED mimic displays and plant alarm inputs. Standard Syncro control panels contain fxings for one sounder, relay, conventional detection or I/O board, which can easily be connected using four small signal wires to the power and comms bus within the panel. Consideration must be taken as to the loading on the main panel. 16 channels
Each channel confgurable as input or output
Inputs opto-isolated
Outputs open collector transistor Simple 2 wire connection to control panel
Up to 32 boards supported per panel (512 Input/Output Channels)
Inputs and outputs confgurable as per feld devices
Full cause and efects on all inputs and outputs Multi drop RS485 communications Can be used with other Syncro I/O modules on the same panel Compatible with Syncro AS panels Part No. K560 i O Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 35 Product code Supply voltage Quiescent current consumption Current per input Current per output Communications Maximum distance from panel PCB size Cable capacity Operating temperature Operating humidity K560 21 - 30V DC 20mA 3mA (maximum) 100mA (maximum) RS485 two wire 1.2Km (using correct type of cable) 190mm x 61mm 2.5mm per terminal -10C to +50C To 95% (non condensing) - - - - - - - - - - - Technical For full technical and application details see the Syncro I/O Board manual DS22.06.2009 B A T T .
D I S C O N N . C H A R G E R
F A U L T E A R T H
F A U L T M A I N S
F A I L B A T T . L O W To Next I/O Board COMMS OUT CHANNEL I/O I/O OUT 0V 24V 0V 0V 0V 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 COMMS IN IN 0V TX RX 24V 0V REMOTE PSU OUT IN NETWORK NETWORK SNDR.2 SNDR.3 SNDR.4 SNDR.1 24V DC 8. 7. 6. 5. 4. 3. 2. 1. I/O BOARDS ADDITIONAL 24V AUX COMMS INPUTS AND AUX. CONTROL REMOTE PR3 PR2 PR1 0V SIL CNT INT RES FLT OUTPUT EXTINGUISHER FAULT ROUTING ROUTING FIRE Syncro 16 Channel I/O Board 0V 24V 2K2 EXAMPLE OUTPUT INPUT EXAMPLE 24V Out to next board only if powered from Power Supply & not Aux.24V at panel Syncro Main PCB Page 36 8 Way Relay Extender Board Features Product Overview To further enhance the versatility of the Syncro fre alarm system, additional relay output capability can be added using Syncro relay boards. These boards have 8 voltage free changeover relay contacts, each of which can be individually programmed. Up to 32 of these boards can be connected to the dedicated RS485 communications bus in the control panel giving the capability of up to 256 additional relay outputs. The relay boards may be mixed on the RS485 bus with 16 channel I/O boards, 6 way sounder boards or 4 way conventional detection zone boards to provide a very fexible system of I/O to satisfy any requirement. All outputs are confgurable in the same way as devices connected to the loops and all may be acted upon by cause and efect logic. These boards are typically used in applications which require more than the four standard relay outputs such as signalling to other systems or plant control. Standard Syncro control panels contain fxings for one sounder, relay, conventional detection or I/O board, which can easily be connected using four small signal wires to the power and comms bus within the panel. Consideration must be taken as to the loading on the main panel. 8 volt free changeover relay contacts (1Amp 30V DC)
Relay operated indications
Remote connection to panel via RS485 serial bus
Common footprint to other Syncro I/O board types All outputs programmable for cause and efects Can be used with other Syncro I/O modules on the same panel Compatible with Syncro AS panels i O Syncro Part No. K547 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 37 Product code Supply voltage range Quiescent current consumption Operating current (all outputs on) Output contact rating Communications Max. distance from panel PCB size Fixing centres Cable capacity Operating temperature Operating humidity K547 21 to 30 volts DC 10mA 250mA 30V DC 1 Amp RS485 two wire 1.2Km (using RS485 data cable) 190mm x 61mm 51.5mm x 180mm 2.5mm per terminal -5C to +50C To 95% (non condensing) - - - - - - - - - - - - Technical O/P 8 O/P 7 O/P 6 O/P 5 O/P 4 O/P 3 O/P 2 O/P 1 NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC COMMS OUT OUT 0V 24V 0V B A T T .
D I S C O N N . C H A R G E R
F A U L T E A R T H
F A U L T M A I N S
F A I L B A T T . L O W Data Out to other Boards Signal to other Systems 30V DC Max. 1 Amp Max. C O M M S
I N IN 0V TX RX 24V 0V REMOTE PSU OUT IN NETWORK NETWORK SNDR.2 SNDR.3 SNDR.4 SNDR.1 24V DC 8. 7. 6. 5. 4. 3. 2. 1. I/O BOARDS ADDITIONAL 24V AUX COMMS INPUTS AND AUX. CONTROL REMOTE PR3 PR2 PR1 0V SIL CNT INT RES FLT OUTPUT EXTINGUISHER FAULT ROUTING ROUTING FIRE Syncro 8 Way Relay Board Syncro Main PCB 24V Out to next board only if powered from Power Supply & not Aux.24V at panel DS33.05.2009 Page 38 6 way Sounder Extender Board Features Product Overview To further enhance the versatility of the Syncro fre alarm system, additional sounder output capability can be added using Syncro sounder boards. These boards have 6 monitored sounder outputs, each of which can be individually programmed. In addition to the sounder outputs each board has two general purpose, opto-isolated inputs and two volt-free changeover contact outputs. Up to 32 of these boards can be connected to the dedicated RS485 communications bus in the control panel giving the capability of 192 additional sounder outputs with 64 general purpose inputs and 64 general purpose outputs. The sounder boards may be mixed on the RS485 bus with 16 channel I/O boards, 8 way relay boards or 4 way conventional detection zone boards to provide a very fexible system of I/O to satisfy any requirement. All inputs and outputs are confgurable in the same way as devices connected to the loops and all may contribute to, or be acted upon by cause and efect logic. These boards are typically used in applications that require more than the four standard sounder outputs such as replacement of existing conventional systems. Standard Syncro control panels contain fxings for one sounder, relay, conventional detection or I/O board, which can easily be connected using four small signal wires to the power and comms bus within the panel. Consideration must be taken as to the loading on the main panel. 6 individually fused and monitored sounder outputs
Fault and operated indications
2 opto-isolated general purpose inputs 2 volt free contact general purpose outputs Remote connection to panel via RS485 serial bus Common footprint to other Syncro I/O board types All outputs and inputs programmable for cause and efects Can be used with other Syncro I/O modules on the same panel Compatible with Syncro AS panels i O Syncro Part No. K546 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 39 Product code Supply voltage range Quiescent current consumption Full alarm current consumption Sounder current monitoring resistor Current per input Current per sounder output Output contact rating Communications Max. distance from panel PCB size Fixing centres Cable capacity Operating temperature Operating humidity K546 21 to 30 volts DC 30mA 260mA 10k 3mA maximum 1 Amp maximum 30V DC 1 Amp RS485 two wire 1.2Km (using RS485 data cable) 190mm x 74mm 51.5mm x 180mm 2.5mm per terminal -5C to +50C To 95% (non condensing) - - - - - - - - - - - - - - - Technical DS34.05.2009 O/P 2 O/P 1 S1 NO C NC NO C NC S2 S3 S4 COMMS OUT OUT 0V 24V 0V S5 S6 I/P1 I/P2 B A T T .
D I S C O N N . C H A R G E R
F A U L T E A R T H
F A U L T M A I N S
F A I L B A T T . L O W Data Out to other Boards C O M M S
I N IN 0V TX RX 24V 0V REMOTE PSU OUT IN NETWORK NETWORK SNDR.2 SNDR.3 SNDR.4 SNDR.1 24V DC 8. 7. 6. 5. 4. 3. 2. 1. I/O BOARDS ADDITIONAL 24V AUX COMMS INPUTS AND AUX. CONTROL REMOTE PR3 PR2 PR1 0V SIL CNT INT RES FLT OUTPUT EXTINGUISHER FAULT ROUTING ROUTING FIRE Syncro Sounder Board Syncro Main PCB 24V Out to next board only if powered from Power Supply & not Aux.24V at panel Signal to other systems max. voltage 30V DC max. current 1 Amp Max. contact resistance 500 Ohms Unused outputs must be terminated with end of line resistor to prevent fault indication 1 0 K Polarised sounders max. 1 Amp. End of line resistor tted 1 0 K Page 40 4 Way Conventional Detection Zone Module Features Product Overview To further enhance the versatility of the Syncro fre alarm system, four conventional detection circuits can be connected with up to 30 detectors per circuit. Conventional control panels can be replaced with this simple module and existing conventional systems can be interfaced directly to modern analogue addressable control systems and networks. A fail safe mode ensures that the detection inputs will still operate the sounder outputs and fre contact if communication to the Syncro panel is lost. Up to 32 of these boards can be connected to the dedicated RS485 communications bus in the control panel giving the capability of up to 128 conventional zones with 64 sounder outputs. The detection zone boards may be mixed on the RS485 bus with 16 channel I/O Boards, 6 way sounder boards or 8 way relay boards to provide a very fexible system of I/O to satisfy any requirement. All inputs and outputs are confgurable in the same way as devices connected to the loops and all may be acted upon by cause and efect logic. Standard Syncro control panels contain fxings for one (four way) Detection Zone board, Sounder board, Relay board or I/O board, all of which can easily be connected using four signal wires to the power and comms bus within the panel. Consideration must be taken as to the loading on the main panel. 4 monitored detection zone inputs
2 monitored sounder outputs
Volt free fre contact Volt free fault contact Local power supply fault input RS485 comms connection to Syncro Fire Alarm Panel Individual fault and operated indications for inputs and outputs Directly replaces a conventional control panel when integrating into an analogue addressable system Can be used with other Syncro I/O modules on the same panel Compatible with Syncro AS panels i O Syncro Part No. K545 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 41 Product code Supply voltage range Quiescent current consumption Operating current (all outputs on) Output contact rating Detection zone monitoring resistor Sounder circuit monitoring resistor Communications Max. distance from panel PCB size Fixing centres Cable capacity Operating temperature Operating humidity K545 21 to 30 volts DC 70mA 250mA 30V DC 1 Amp 6k8 10k RS485 two wire 1.2Km (using RS485 data cable) 190mm x 74mm 51.5mm x 180mm 2.5mm per terminal -5C to +50C To 95% (non condensing) - - - - - - - - - - - - - - Technical DS35.05.2009 F A U L T S2 0V PF NO C NC S1 COMMS OUT OUT 0V 24V 0V B A T T .
D I S C O N N . C H A R G E R
F A U L T E A R T H
F A U L T M A I N S
F A I L B A T T . L O W Data Out to other Boards C O M M S
I N IN 0V TX RX 24V 0V REMOTE PSU OUT IN NETWORK NETWORK SNDR.2 SNDR.3 SNDR.4 SNDR.1 24V DC 8. 7. 6. 5. 4. 3. 2. 1. I/O BOARDS ADDITIONAL 24V AUX COMMS INPUTS AND AUX. CONTROL REMOTE PR3 PR2 PR1 0V SIL CNT INT RES FLT OUTPUT EXTINGUISHER FAULT ROUTING ROUTING FIRE Syncro 4 Way Conventional Detection Zone Board Syncro Main PCB 24V Out to next board only if powered from Power Supply & not Aux.24V at panel D D D CP F I R E NO C NC Z4 Z3 Z2 Z1 E O L D D CP E O L D D D CP E O L D D CP CP CP E O L S S S S E O L S S Page 42 I/O Board Enclosure Features Product Overview A range of new enclosures designed to house Syncro I/O modules with or with a power supply. The Syncro I/O enclosure ofers the installer the fexibility to create their own customised I/O panel. The standard Syncro I/O enclosure can hold up to 3 Syncro I/O modules or 2, if a power supply is incorporated. Matching design & colour scheme for Kentec new style control panel range Easy to install Incorporates Kentecs Quick Fit lid & equipment chassis Front panel mounted status led indication Space for 3.2Ah batteries Choice of power supplies Model No. K16001M2 Equipment Product Code K16001M2 K16750M2 K16250M2 K16400M2 Plug-Ins K560 K547 K546 K545 Description Syncro I/O enclosure without Charger Syncro I/O enclosure c/w 750mA Charger Syncro I/O enclosure c/w 2.5A Charger Syncro I/O enclosure c/w 5.25A Charger 16 Channel Input/Output Board 8 Way Relay Extender Board 6 Way Sounder Extender Board 4 Way Conventional Detection Zone Module 3x I/O boards without PSU 2x I/O boards with PSU 16 Channel Input/Output Board (K560) 8 Way Relay Extender Board (K547) 6 Way Sounder Extender Board (K546) 4 Way Conventional Detection Zone Module (K545) Choose any combination of I/O boards DS46.02.2011 i O Syncro The manufacturer reserves the right to amend specifcations without prior notice Page 43 Addressable Sounder Controller Unit Features Product Overview Syncro addressable sounder controller units enable additional, distributed power and control for sounder circuits in situations where there are insufcient circuits at the fre alarm control panel or where additional power is required to power heavily loaded sounder circuits. Sounder control modules for any of the protocols supported by Syncro are available in a steel enclosure designed to match the appearance of the Syncro fre alarm control panel. All units contain mains powered battery charger/power supply, they have space for up to 7 Ah batteries. Indicators are provided for power healthy and power fault conditions and power fault conditions are signalled to the Syncro fre alarm control panel as a sounder fault. Two, four or six way units available Apollo, Argus Vega or Hochiki protocols available Integral power supply Robust steel enclosure matches Syncro control panel styling Space for 7Ah batteries Power Healthy and Power Fault indicators DS46.04.2011 Construction Finish Colour - lid & box Colour - labels Mains voltage supply
Mains fuse Battery charge fuse Battery Operating temperature Operating humidity Protocol 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) 3A, 1 inch 20mm x 5mm, 500 milliamp 7Ah 12V (2 per panel) -5C to +50C To 95% (non condensing) Apollo XP95, Argus Vega or Hochiki ESP - - - - - - - - - - - Technical Panels Product Code A1725203 V1725203 H1725203 A1725403 V1725403 H1725403 A1725603 V1725603 H1725603 Sounder Outputs 2 2 2 4 4 4 6 6 6 PSU 2.5A 2.5A 2.5A 5.25A 5.25A 5.25A 5.25A 5.25A 5.25A Protocol Apollo XP95 Argus Vega Hochiki ESP Apollo XP95 Argus Vega Hochiki ESP Apollo XP95 Argus Vega Hochiki ESP Model No. #1725203 i O Syncro Size (mm) 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 Page 44 BMS Communications Interface Features Product Overview The all new OpenConnect system provides a simple means of integrating Apollo protocol, Syncro or Syncro AS fre panel networks with a wide range Building Management Systems using any of the commonly used communications protocols. A simple two wire connection from the fre panel network to the OpenConnect hardware interface and an exported fle from the Syncro Loop Explorer confguration programme is all that is needed to realise a working BMS interface simply and quickly. The OpenConnect system allows rapid deployment of a BMS interface due to the use of a standard protocol specifcally developed to allow fre panel integration without the need for expensive and time consuming specialist building integration engineering. Once the system is confgured, a report is generated containing all of the information on the BMS integrator requires to provide a rapid solution to all BMS integration requirements. Compatible with all existing Apollo Syncro or Syncro AS fre alarm systems Simple, two wire connection to fre panel Supports LonWorks, BACnet TM and Modbus protocols Easy to confgure interface via a standard web browser Confgurable to provide General (network wide) event reporting, event reporting from selected Syncro panels or event reporting from individual Detection Device addresses
Individual Syncro Event types (fres, pre- alarms, disablements, faults etc) can be confgured to be passed to the BMS, based on the selected panel reporting options above. Remote reporting only or remote reporting with control options Fully welded steel enclosure to match Syncro fre alarm control panels Simple 4 step process: 1. Connect OpenConnect hardware to a PC 2. Load confguration fle exported from Loop Explorer 3. Set up reporting options required (event types, by zone, by point etc) 4. Print report and hand to BMS integrator Open connect N E W ! The manufacturer reserves the right to amend specifcations without prior notice Page 45 DS66.02.2011 Operating temperature Operating humidity Supply Voltage - - - Technical 0C to +50C 5% to 95% (non condensing) 230V or 115V AC Contact Sales on +44 (0) 1322 222121 for product range Panels Product Code K8121110 K8121120 K8121111 K8121121 K8221110 K8221120 K8221111 K8221121 K8321110 K8321120 K8321111 K8321121 K8421110 K8421120 K8421111 K8421121 Ethernet 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 BMS Points provided 200 200 200 200 1600 1600 1600 1600 12000 12000 12000 12000 25000 25000 25000 25000 Size (mm) 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 500 x 355 x 117 BATTERY BATTERY Loops Loops Loops DC OUT ON HEART BEAT BATTERY LOW 24V DC F2 250V 3A N L E BATTERY DISCON. S406 AC NORMAL EARTH FLT CHARGER FLT 230VAC 115VAC 50Hz or 60Hz 24-29VDC 4A MAX EN54-4 (1997) + AC (1999) + A1 (2002) + A2 (2006) INPUT VOLTAGE FREQUENCY OUTPUT VOLTAGE POWER RATING - --- MODEL - Model: #80161M2 BS EN54-2 : 1998 BS EN54-4 : 1998 Fire AlarmControl 15:05 Tuesday 10 October 2006 KENTEC ELECTRONICS LIMITED 4 3 2 1 ? More Events Fires More Exit Enter Enable Control Function Evacuate Reset Buzzer Silence (Acknowledge) Silence Alarm Re-Sound Sounder Fault/Disabled SystemFault Power Fault General Fault General Disablement More Events Delay Active Buzzer Silenced On Test Pre-Alarm Power On Test Lamp Alarm Fire in Zone 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Fire Model: #80161M2 BS EN54-2 : 1998 BS EN54-4 : 1998 Fire AlarmControl 15:05 Tuesday 10 October 2006 KENTEC ELECTRONICS LIMITED 4 3 2 1 ? More Events Fires More Exit Enter Enable Control Function Evacuate Reset Buzzer Silence (Acknowledge) Silence Alarm Re-Sound Sounder Fault/Disabled SystemFault Power Fault General Fault General Disablement More Events Delay Active Buzzer Silenced On Test Pre-Alarm Power On Test Lamp Alarm Fire in Zone 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Fire Model: #80161M2 BS EN54-2 : 1998 BS EN54-4 : 1998 Fire AlarmControl 15:05 Tuesday 10 October 2006 KENTEC ELECTRONICS LIMITED 4 3 2 1 ? More Events Fires More Exit Enter Enable Control Function Evacuate Reset Buzzer Silence (Acknowledge) Silence Alarm Re-Sound Sounder Fault/Disabled SystemFault Power Fault General Fault General Disablement More Events Delay Active Buzzer Silenced On Test Pre-Alarm Power On Test Lamp Alarm Fire in Zone 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Fire OpenConnect Gateway Web based user interface Fire Alarm Control Panel Network BACnet TCP Modus TCP Lonworks FTT10 Automation Network/BMS R S 4 8 5 Interface PCB OpenConnect interface board (supplied with the OpenConnect kit) to be installed in any Syncro or Syncro AS panel. Note this panel cannot have a printer tted RS232 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 USB 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 RS485 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Lonworks FTT10 compatible No No Yes Yes No No Yes Yes No No Yes Yes No No Yes Yes Ports - Note: 1 x RS485 port is used to interface to the Syncro Panels Conventional Fire Detection Control Equipment Pages 48-61 EN54-4 Conventional Sounder Controller Units Page 55 Sigma Sounder Sigma CP Conventional Sounder Controller Units Page 54 Sigma CP EN54 Range Conventional Fire Alarm C/Ps Page 48-49 Sigma CP-A Alarmsense Compatible Conventional Fire Alarm C/Ps Page 50-51 Sigma CP-R Conventional Fire Alarm C/P Repeaters Page 52-53 K3000 Series Conventional Fire Alarm C/Ps Page 56-57 K3200 Series Conventional Fire Alarm C/P Repeaters Page 58 Sigma Matrix Conventional Fire Alarm Mimic System Page 60-61 LCMU Line Continuity Monitoring Unit Page 59 Conventional Fire Detection Control Equipment Pages 48-61 N E W ! Page 48 Conventional Fire Alarm Control Panels Features Product Overview The Sigma CP range consists of a series of conventional fre alarm control panels designed in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment. The range consists of 2, 4 and 8 zone control panels. All control panels are available in two versions: Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder circuits are provided). Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables. Commonly referred to as a two-wire system. Wiring sounders to the detection circuits eliminates the need to install sounder circuit cables and also ofers the ability to provide zoned or two stage sounder operation. (T series only) All control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of BS EN54-4. Fully certifed to BS EN54-2 and BS EN54-4 2-wire and standard versions in 2, 4 or 8 zones Compatible for use on BS5839: Part 1: 2002 installations 2-wire repeaters and ancillary boards Fully programmable using simple menu options Adjustable sounder delay time Sounder confguration options Zonal sounder delay detectors only Zonal sounder delay call points only Coincidence input selection
I.S Barrier selection by zone Short circuit fre by zone Non latching zones Silent zones Zone input delay General panel confguration Simple, single board construction Installer friendly Compatible with wide range of detection devices Two monitored sounder outputs 3 Amp power supply Auxiliary power output Model No. K11080M2 CP Sigma BS- EN54- 2 BS- EN54- 4 KM 73505 Note: For 2-wire T series panels, compatible detectors and call points must be used. All sounders must be polarised. Note: Also available is the Sigma Ancillary Board (K580) which is compatible with all Sigma CP and CP-R panels which have operating software version V2.0 or above. See DS39 (pages 52-53) for more details. Note: Also available is the Sigma Sounder Board (K461) which is compatible with all Sigma CP and CP-R panels which have operating software version V3.0 or above. See DS48 (page 54) for more details. Part No. K580 Part No. K461 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 49 Construction Finish Colour - lid & box Colour - controls plate & labels Supply voltage Mains supply fuse Power supply DC rating Maximum battery size Fault contact rating Local fre contact rating Fire contact rating Sounder output rating Detection zone current Detection zone EOL resistor Active EOL Sounder output EOL resistor Cable capacity Operating temperature Operating humidity 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC (+10%/-15%) 1.6 Amp 250V 24V 3 Amps 7Ah 12V (2 per panel) 30V DC 1 Amp 30V DC 1 Amp 30V DC 1 Amp 0.5A per output (max 1.6A over all outputs) 1.6 milliamps 6k8 5% K14606K (optional) 10k 5% 2.5mm per terminal -5C to +50C <95% (non condensing) - - - - - - - - - - - - - - - - - - - Panels Product Code K11020M2 K11040M2 K11080M2 T11020M2 T11040M2 T11080M2 K18002 Description 2 zone control panel 4 zone control panel 8 zone control panel 2 zone, 2 wire panel 4 zone, 2 wire panel 8 zone, 2 wire panel Tamper resistant Vision Window * Standby Current 0.065 Amps 0.075 Amps 0.093 Amps 0.065 Amps 0.075 Amps 0.093 Amps N/A * Vision Window can be easily retroftted to any Sigma CP panel Alarm Current 0.1 Amps 0.21 Amps 0.55 Amps 0.15 Amps 0.3 Amps 0.63 Amps N/A Technical DS37.08.2011 8 7 6 5 4 3 2 1 Model: K11080M 2 BS EN54-2 : 199 8 BS EN54-4 : 199 8 Fire Alarm Contro l KM73505 Zone Chart General System Status Disablemen t Sounder Fault/ 8 7 6 5 4 3 2 1 System Mode (+1) (+10) Zone Fault/Test/Disablement Zone Fault/Test/Disablement Enter Selec t Mode Reset Enable Contro l Fire Fire In Zone Fire In Zone Test Mode On Delay On Power On Warning Silenced Alarm/Faul t Power Fault Disablement Genera l System Fault General Faul t Test Lamp Alar m Silence/Sound Alarm/Fault Warning Silenc e 3 1 0 385 90 Size 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90 Page 50 CP-A Sigma AlarmSense compatible twowire conventional fre alarm control and indicating panels Features Product Overview The new Sigma CP-A AlarmSense range consists of a series of conventional, 2, 4 and 8 zone fre alarm control panels designed and approved in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment.
The AlarmSense system enables all devices in a given zone to be wired to the same pair of cables thus greatly reducing the cabling and installation requirements and hence costs.
The AlarmSense range of devices includes smoke and heat detectors, call points, base sounders, base sounder/beacons and relay units all wired to the same pair of cables.
Having sounders and sounder beacons installed on the same cabling as detectors and call points allows all systems to be confgured for common, zonal or two stage alarm by simply setting one of the panels confguration options.
Selection of the AlarmSense local alarm feature at sounder or sounder beacon bases invokes the alarm verifcation feature. This is particularly useful in Houses of Multiple Occupation such as student accommodation or nursing homes. When sounder or sounder beacon bases are selected for local alarm mode, any alarm sounders are restricted such that only the sounder connected to the activated detector will operate initially. The panel will attempt to reset the activated detector after a time delay and if successful no further alarms are sounded. If the detector re-activates after being reset, a general alarm will sound throughout the premises. Activation of a second detector or a call point will sound the general alarm immediately
All control panels have an integral, mains powered battery charger and power supply designed and approved in accordance with the requirements of BS EN54-4. Fully compliant with BS EN54-2 and BS EN54-4
Allows systems to be installed in accordance with BS5838: Part 6
2 wire systems, reduces installation cabling
2-wire repeaters and ancillary boards via serial bus
Fully programmable using simple menu options
Adjustable sounder delay time
Sounder confguration options
Zonal sounder delay for detectors only
Zonal sounder delay for call points only
Coincidence output via ancillary board
Short circuit fre selectable by zone
Non latching selection by zone
Silent zones (common sounder outputs)
Zone input delay for sprinkler system connection
AlarmSense local alarm feature supported
Simple, single board construction
Installer friendly
Compatible with all AlarmSense devices
Two conventional monitored sounder outputs
3 Amp power supply
Auxiliary power output Ancillary PCB Part No. K580 Model No. A11080M2 Sounder PCB Part No. K461 N E W ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 51 DS65.02.2011 Construction Finish Colour - lid & box Colour - controls plate & labels Supply voltage Mains supply fuse Power supply DC rating Maximum battery size Fault contact rating Local fre contact rating Fire contact rating Common Sounder output rating AlarmSense Sounder output rating Detection zone current Detection zone EOL resistor Sounder output EOL resistor Cable capacity Operating temperature Operating humidity - - - - - - - - - - - - - - - - - - - Technical 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC (+10%/-15%) 1.6 Amp 250V 24V 3 Amps 7Ah 12V (2 per panel) 30V DC 1 Amp 30V DC 1 Amp 30V DC 1 Amp 0.5A per output 0.2A per output 1.6 milliamps 3K3 5% 10k 5% 2.5mm per terminal -5C to +50C <95% (non condensing) Panels Product Code KA11020M2 KA11040M2 KA11080M2 Description 2 zone control panel 4 zone control panel 8 zone control panel Standby Current 0.065 Amps 0.075 Amps 0.093 Amps Alarm Current 0.1 Amps 0.21 Amps 0.55 Amps Options Product Code K580 K461 M2FCLGT K02000M2 K02750M2 K18002 Description Stand alone ancillary board Sounder PCB Bezel for semi fushing panel to wall Boxed ancillary board Boxed ancillary board with 0.75A PSU Tamper resistant Vision Window * * Vision Window can be easily retroftted to any Sigma CP-A panel 8 7 6 5 4 3 2 1 Model: KA11080M2 Fire Alarm Control Zone Chart General System Status Disablemen t Sounder Fault/ 8 7 6 5 4 3 2 1 System Mode (+1) (+10) Zone Fault/Test/Disablement Zone Fault/Test/Disablement Enter Selec t Mode Reset Enable Contro l Fire Fire In Zone Fire In Zone Test Mode On Delay On Power On Warning Silenced Alarm/Faul t Power Fault Disablement Genera l System Fault General Faul t Test Lamp Alar m Silence/Sound Alarm/Fault Warning Silenc e 3 1 0 385 90 Size (mm) 385 x 310x 90 385 x 310 x 90 385 x 310 x 90 Page 52 Conventional Fire Alarm Control Panel Repeaters Sigma CP-R Features Ancillary PCB Product Overview The Sigma Ancillary Board is compatible with all Sigma CP and CP-R panels which have operating software version V2.0 or above. The board provides common fre, common fault, coincidence and zonal fre, volt free contacts allowing control of sub-systems, graphical mimics and plant, remotely from the main panel over a two wire data bus. Mains powered Ancillary boards require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source. A mixture of Ancillary boards, Sounder boards or Repeaters up to a maximum of 7 of each type can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres. Two wire serial connection Up to 7 panels per system 230V AC or 24V DC powered versions Full control over main panel Volt free fre and fault contact outputs Model No. E01080M2 Sigma CP-R Product Overview The Sigma CP-R Repeater is compatible with all Sigma CP control panels which have operating software version V2.0 or above. Repeaters are available with 2, 4 or 8 zones and in mains powered (K versions) or 24V powered (E versions). Mains powered repeaters require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source. A mixture of Repeaters, Ancillary boards or Sounder Boards up to a maximum of 7 of each type can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres. Ancillary PCB Features Two wire serial connection Up to 7 boards per system 230V AC or 24V DC powered versions Open collector zonal fault outputs Volt free fre, coincidence and common fault contact outputs Part No. K580 CP-R & Anc i l l ar y PCB Sigma Note: Also available is the Sigma Sounder Board (K461) which is compatible with all Sigma CP and CP-R panels which have operating software version V3.0 or above. See DS48 (page 54) for more details. Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 53 Equipment Construction Finish Colour - lid & box Colour - Controls plate & labels Supply voltage (K models) Supply voltage (E models) Mains supply fuse Power supply DC rating Maximum battery size Fault contact rating Fire contact rating Cable capacity Operating temperature Operating humidity 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC (+10%/-15%) 20-30V DC 1.6A 250V 24V 1 Amps 7Ah 12V (2 per panel) 30V DC 1 Amp 30V DC 1 Amp 2.5mm per terminal -5C to +50C <95% (non condensing) - - - - - - - - - - - - - - Sigma CP-R Technical Product Code E01020L2 E01040L2 E01080L2 K01020M2 K01040M2 K01080M2 K580 K02000M2 K02750M2 K18002 Description 2 zone Sigma CP-R repeater panel 4 zone Sigma CP-R repeater panel 8 zone Sigma CP-R repeater panel 2 zone Sigma CP-R repeater panel with PSU 4 zone Sigma CP-R repeater panel with PSU 8 zone Sigma CP-R repeater panel with PSU Stand alone ancillary board Boxed ancillary board Boxed ancillary board with 0.75A PSU Tamper resistant Vision Window * Standby Current 0.075 Amps 0.075 Amps 0.075 Amps 0.075 Amps 0.075 Amps 0.075 Amps
0.020 Amps 0.020 Amps 0.020 Amps N/A * Vision Window can be easily retroftted to any Sigma CP-R panel Alarm Current 0.094 Amps 0.098 Amps 0.11 Amps 0.094 Amps 0.098 Amps 0.11 Amps
0.2 Amps 0.2 Amps 0.2 Amps N/A Supply Voltage 24V DC 24V DC 24V DC 230V AC 230V AC 230V AC
24V DC 24V DC 230V AC N/A Construction (boxed) Finish Colour - lid & box Colour - controls plate & labels Supply voltage (K02750M2) Supply voltage (K02000M2) Mains supply fuse Power supply DC rating Maximum battery size Standby current Full alarm current Fault contact rating Fire contact rating Coincidence contact rating Zonal contact rating Cable capacity Operating temperature Operating humidity 1.2mm mild steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC (+10%/-15%) 20-30V DC 1.6A 250V 24V 750mA 2.6Ah 12V (2 per panel) 20mA 190mA 30V DC 1 Amp 30V DC 1 Amp 30V DC 1 Amp 30V DC 1 Amp 2.5mm per terminal -5C to +50C <95% (non condensing) - - - - - - - - - - - - - - - - - - Ancillary PCB Technical Processor Reset Switch Data Connection Zonal Volt Free Contacts Power Connection Address Switch ADDRESS PROCESSOR RESET FUSE FAIL OK COMMS 24V DC - + - + - + RS485 OUT RS485 IN NO NC C NO NC C NO NC C COINC RELAY FAULT RELAY FIRE RELAY Z8 FIRE Z7 FIRE Z6 FIRE Z5 FIRE Z4 FIRE Z3 FIRE Z2 FIRE Z1 FIRE K580 Sigma CP Ancillary PCB DS39.05.2011 Size (mm) 385 x 310 x 60 385 x 310 x 60 385 x 310 x 60 385 x 310 x 90 385 x 310 x 90 385 x 310 x 90
155 x 136 385 x 310 x 90 385 x 310 x 90 Page 54 Sigma CP Conventional Sounder Controller Units Features Product Overview The Sigma CP Sounder Board is compatible with all Sigma CP control panels which have operating software version V3.0 or above. The board provides 8 additional sounder outputs which can be confgured as zoned, 2-stage or common alarm. All sounder outputs are open and short circuit monitored and any faults on the sounder outputs will be announced at the main fre alarm panel as a sounder fault. A class change input is provided which, when activated by a volt free contact closing, will switch all sounder outputs on. Mains powered units require only a two core data cable from the main control panel. 24V DC versions require an additional two cores from another 24V DC source which is suitably rated to supply the total sounder current. 230V versions have their own power supply which is rated to supply sounder loads up to 5.25 Amps. Up to 7 Sounder boards can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. Sounder boards may be connected to the Sigma CP serial bus in addition to Sigma CP ancillary boards and Sigma CP-R repeater panels. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres. Once Sounder boards have been recognised by the main panel, a fault will be announced at the main panel if any become disconnected. Two wire serial connection Up to 7 sounder boards per system 230V AC or 24V DC powered versions Zoned, 2-stage or common alarm All outputs monitored for open and short circuit faults Individual open and short circuit fault indicators Fully monitored by main control panel Class change input facility Up to 8 outputs with 1A available from each Can be connected to serial bus with Ancillary boards and repeaters Boxed units in enclosure to match Sigma CP control panels Power fault input for monitoring remote power supplies Construction (Boxed) Finish Colour - lid & box Supply Voltage (K04400M2) Supply Voltage (K04000M2) Mains supply fuse Power supply DC rating Sounder output rating Class change input Cable capacity Operating temperature Operating humidity 1.2mm mild steel Epoxy powder coated BS 00 A 05 grey - fne texture 230V AC (+10%/-15%) 20-30V DC 1.6A 250V 24V 5.25 Amp 1A per output Volt free NOC 2.5mm per terminal -5C to +50C <95% (non condensing) - - - - - - - - - - - - Technical Panels Product Code K461 K04000M2 K04400M2 Description Stand alone sounder PCB Boxed sounder PCB Boxed sounder PCB with 5.25 Amp PSU PSU 24V DC 24V DC 230V DC Model No. K04400M2 Sounder Sigma Size (mm) 155 x 136 385 x 310 x 90 385 x 310 x 90 The manufacturer reserves the right to amend specifcations without prior notice Page 55 Conventional Sounder Controller Units Features Product Overview Conventional Sounder controllers enable additional, distrib- uted power and control for sounder circuits in situations where there are insufcient circuits at the fre alarm control panel or where additional power is required to power heavily loaded sounder circuits. The Sounder Controller Unit connects to conventional sounder circuits and any faults on its outputs are transmitted to the fre control panel via the incoming, triggering sounder circuit thus maintaining full fault monitoring. All units contain a mains powered battery charger/power supply. There is space for up to 7 Ah batteries. Indicators are provided for power healthy, power fault and sounder fault conditions and power fault conditions are signalled to the fre alarm control panel as a sounder fault. Two four or six way units available Integral power supply Robust steel enclosure Space for 7Ah batteries Power Healthy, Power Fault and Sounder Fault indicators Full fault monitoring and integrity maintained DS48.05.2011 Construction Finish Colour - lid & box Supply voltage Mains fuse Battery charge fuse Power output Battery Operating temperature Operating humidity 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 230V AC (+10%/-15%) 3A, 1 inch 20mm x 5mm, 500 milliamp 24V at 2.5A 7Ah -5C to +50C To 95% (non condensing) - - - - - - - - - - Technical Panels Product Code K1740203 K1740403 K1740603 Description 2 Way Sounder Controller Unit 4 Way Sounder Controller Unit 6 Way Sounder Controller Unit PSU 5.25A 5.25A 5.25A Model No. K1725203 Sounder Cont r ol l er Size (mm) 500 x 355 x 108 500 x 355 x 108 500 x 355 x 108 Page 56 Conventional Fire Alarm Control Panels Features Product Overview The K3000 Series exceeds the requirements of BS5839: Part 4: 1988 in several areas. Inclusion of zone isolate, zonal one man test, zonal contacts, shop unit interface and zoned or two stage alarm outputs are all standard features. A wide range of detectors are supported by the equipment, ensuring that the K3000 Series control panels can be used with existing installations without the need to change the feld devices. Front panel controls and indicators are kept to a minimum to simplify user operation and to maintain clarity of indication. High intensity, twin bar LED indicators are used on all front panels. All panels are supplied with suitable power supply and generous battery space to give extended battery standby if required. Ample cable entries and removable chassis assist in ease of installation. All panels are available as true fush or surface mounting and in two tone grey or cream and brown. Other colours are available to special order. Arrangements can be made for special badging or special fnishes such as brass or stainless steel. K3000 Series control panels allow continued operation of call points and detectors upon removal of a device from the detec- tion line. This can be achieved either by ftting an active end of line device or by using special line clamping bases. Complies with BS5839: Part 4: 1988 Can be used on pre BS5839 type systems 12 - 48 zones as standard more available on request Class change input Common fre and fault contacts Line continuity upon detector removal Remote signal contact and isolate Shop interface input Zonal one man test Zonal selection for operation with intrinsically safe barriers Zonal volt free contacts Zone isolate facility Compatible with most popular detectors Option for plug-in two stage sounder cards Model No. K3024005 3000 Series Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 57 Panels Construction Finish Standard colour Sounder outputs Isolatable fre contact Auxiliary alarm contact Fault contact Zonal contacts Auxiliary DC output Detection zone monitoring resistor Sounder circuit monitoring resistor Remote control inputs
Mains supply
Call points Alarm threshold Short circuit threshold Maximum zone quiescent current Active end of line Operating temperature Operating humidity 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 2 outputs each fused at 1 amp each (0.5A E3002001) Volt free changeover 1A at 30V DC Volt free changeover 1A at 30V DC Volt free changeover 1A at 30V DC Volt free normally open 1A at 30V DC Fused at 500mA 6k8 10k Alarm input, Silence input, Reset input (option for pulsed alarm input [Security Alert]) 230V AC (+10%/-15%) (other voltages upon request) Require 470 OHM series resistor 100 to 900 Ohms 0 to 100 Ohms 1.6mA K1406K (optional) -5C to +40C To 95% (non condensing) - - - - - - - - - - - - - - - - - - - - Technical Product Code E3012003 K3016005 E3016005 K3024005 E3024005 K3032007 E3032007 K3040007 K3048009 Zones 12 16 16 24 24 32 32 40 48 Standby Current 0.2A 0.22A 0.22A 0.31A 0.31A 0.38A 0.38A 0.45A 0.52A Flush mounting versions are available to order. All weights quoted are less standby batteries Alarm Current 0.34A 0.38A 0.38A 0.45A 0.45A 0.52A 0.52A 0.59A 0.66A Sounder Load per Circuit 1.0A 1.0A 1.0A 1.0A 1.0A 1.0A 1.0A 1.0A 1.0A Sounder Load total 1.5A 1.5A 1.0A 1.5A 1.0A 1.5A 1.0A 1.5A 1.5A Minimum Battery (24h standby) 7.0Ah 7.0Ah 7.0Ah 12.0Ah 12.0Ah 12.0Ah 12.0Ah 15.0Ah 17.0Ah PSU 2.5A 4.0A 2.5A 4.0A 2.5A 4.0A 2.5A 4.0A 4.0A Weight (approx) 8.6kg 11.0kg 11.0kg 11.5kg 11.5kg 20.0kg 20.0kg 20.5kg 24.0kg Size (mm) 500 x 355 x 108 570 x 420 x 110 570 x 420 x 110 570 x 420 x 110 570 x 420 x 110 600 x 700 x 140 600 x 700 x 140 600 x 700 x 140 700 x 1000 x 145 Control Panel Wall Flush mount cross section DS01.11.2011 Page 58 Conventional Fire Alarm Control Panel Repeaters Model No. K3212001 3200 Series Equipment Product Code K3212001 K3216001 K3224001 K3232003 K3240005 K3248005 Weight 3.5kg 6.0kg 6.0kg 8.0kg 10.5kg 10.5kg Size (mm) 365 x 290 x 88 365 x 290 x 88 365 x 290 x 88 500 x 355 x 108 570 x 420 x 110 570 x 420 x 110 Flush mounting versions are available to order, see price guide Zones 12 16 24 32 40 48 Construction Finish Colour Voltage Power consumption Operating temperature Operating humidity 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 20V - 30V DC 20mA per zone -5 to +50 deg. C To 95% (non condensing) - - - - - - - Technical DS02.11.2011 Features Product Overview The K3200 series repeater panel uses a similar layout to the main control panel and is ftted with the same high quality indicators. In their discrete enclosure, they are well suited to areas where space is limited and aesthetics are an important consideration. As well as zonal fre indicators, system fault, system healthy and buzzer muted indicators are provided. Controls are kept to the practical minimum of lamp test and buzzer mute. Subsequent alarm or fault conditions whilst the buzzer is muted will resound the buzzer to alert personnel to changing conditions. Repeat panels are available as true fush or surface mounting and in two tone grey or cream and brown as standard. Other colours are available to special order. Arrangements can be made for special badging or special fnishes such as brass or stainless steel. Special repeater panels can be made to order. Zonal fre indicators Common fault and power on indicators Lamp test push button Internal buzzer with mute facility Buzzer resound facility The manufacturer reserves the right to amend specifcations without prior notice Page 59 DS20.09.2011 Finish Colour Normal current Fault condition current Max. zone cable resistance Panel capacitor Operating voltage Terminal connections Max. detectors supported Lead colours Conformal powder coating Blue 5mA at 28V 750uA 50V 20 ohms 47uF 50V 15V to 30V Bootlace ferrules 20 per zone K1406K - pink/black K1406C - orange/black K1406N - red/black - - - - - - - - - - Technical Panels Product Code K14060 NF14060 KID14060 Description Line Continuity Monitoring Unit 6k8 Line Continuity Monitoring Unit 5k6 Line Continuity Monitoring Unit 3k9 47uF Not required on K3000 series or Sigma CP panels 470R Z Z LCMU DETECTOR POINTS CALL 470R DETECTOR POINTS CALL ON ZONE LAST DEVICE CONTROL PANEL LCMU Size (m) 25 x 20 x 8 25 x 20 x 8 25 x 20 x 8 Line Continuity Monitoring Unit Product Overview To use this method of monitoring, the breaking connection of the detector base must be ftted with a diode. To ensure correct operation over a wide supply voltage range and with up to 20 detectors removed, a Schottky type BYV-1060 is recommended. These devices are, however, very sensitive to electrostatic discharge and extra care should be taken when handling or cable testing. It is also necessary to ft a 47uF capacitor to the detection line terminals on some of the control panels (not K3000 series or Sigma CP). Extreme care should be taken when ftting the capacitor in the panel as they are polarity conscious. The LCMU itself is also polarity conscious and the polarity is indicated in the normal manner i.e. black wire is always negative. A wrongly connected LCMU will produce a short circuit fault condition. Due to the use of surface mount technology components, the LCMU is probably the smallest device of its kind on the market. This enables the device to be ftted either within the last device on a zone or in the back box, eliminating the need for an additional wiring point. Features Easy to install No additional wiring point Low cost Sub-miniature design Environmentally sealed Page 60 Conventional Fire Alarm Mimic System Features Product Overview The Sigma Matrix system uses fexible, fbre optic light guides to illuminate areas on a foor plan, laid over a high resolution grid. This unique system dispenses completely with wiring and ena- bles indicators to be moved, removed or added on site without the need for any wiring. All indicators can be confgured to operate via switched positive or negative inputs providing compatibility with a wide range of input/output boards. Sigma Matrix can be supplied with or without common LEDs and controls. Optional LEDs indicate Power on, Fire and Fault and optional controls are for Buzzer silence and Lamp test. Housed in attractive, slimline enclosures to match Sigma fre alarm panels and with high quality, full colour or monochrome foor plans, Sigma Matrix provides a clear, geographical indication of fre alarm activation enabling speedy identifcation of the source of an alarm. Up to 320 LEDs can be controlled Full colour printing Available in a range of standard enclosures to suit any application Bespoke sized units can be made upon request Choice of Red, Green or Yellow LEDs Available with or without controls Same look and feel as Sigma range Sigma Matrix can easily be upgraded on site with minimal cost and efort EN54-4 approved PSU (optional) M3 size Sigma Matrix View showing mimic mounted on inner door View showing LED grid View showing internal layout Mat r i x Sigma PSU opt ional Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 61 Construction Finish Colour - lid & box Colour - controls plate & labels Mimic Number of indicators (standard models) Mains supply* Mains supply fuse* Power supply rating* Maximum ripple current* Battery type* (Yuasa NP) Battery charge voltage* Battery charge current* Max. current draw from batteries* Supply voltage (24V versions) Terminal capacity Cabinet locks Maximum distance from control panel IP rating Operating temperature 1.2mm mild steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 3mm Clear Anti-Glare Acrylic M2 size - up to 32, M3 and S3 size - up to 64, S4 size - up to 96 230V AC +10% - 15% (100 Watts max.) T2A L250V Replace only with similar type 5.25 Amps total including battery charge 28V +/ 2V 200 millivolts Two 12 Volt sealed lead acid (7Ah maximum) 27.6VDC nominal (temperature compensated) 1.5A maximum 3 Amps. With mains power source disconnected 18 to 30V DC 0.5mm2 to 2.5mm2 solid or stranded wire M2/M3 - standard 801 key, S3/S4 - standard KT3001 key 1km with 1.5mm2 cable IP30 -5C to +50C - - - - - - - - - - - - - - - - - - - - Technical Max. number of LEDs = 64 Will house 1 x LED driver PCB and 1 x 32 LED extension PCBs (Red, Green or Yellow) Enclosure Size Options Max. number of LEDs = 64 Will house 1 x 32 LED driver PCB and 1 x 32 LED extension PCBs (Red, Green or Yellow) Max. number of LEDs = 96 Will house 1 x 32 LED driver PCB and 2 x 32 LED extension PCBs (Red, Green or Yellow) Max. number of LEDs = 320 Will house 1 x 32 LED driver PCB and up to 9 x 32 LED extension PCBs (Red, Green or Yellow) Max. number of LEDs = 32 Will house 1 x 32 LED driver PCB (Red, Green or Yellow) 385mm x 310mm 90mm Deep 500mm x 355mm 117mm Deep 385mm x 520mm 110mm Deep 500mm x 650mm 137mm Deep Colour/Finish & Size to suit your requirements M2 S3 M3 S4 Bespoke Size 303 400 225 400 303 515 400 ? ? 185 DS59.02.2011 * 230 V Versions only Extinguishant System Control Equipment Pages 64-81 Sigma Si Status Units and hold of switch for use with Sigma XT/XT+ Page 70-71 Syncro XT+ Multi Area Addressable Extinguishant Control Panels Page 74-75 Sigma XT Ancillary PCB Extinguishant Ancillary PCB Page 72-73 Sigma A-Si Status Units and abort switch for use with Sigma A-XT Page 78-79 C O M I N G S O O N Extinguishant System Control Equipment Pages 64-81 Sigma XT EN12094 Extinguishant Control Panels Page 64-65 Sigma XT+ Multi Area Extinguishant Control Panels Page 66-67 Sigma XT+ Extinguishant Coincidence Unit Page 68-69 Sigma A-XT UL Listed FM Approved Extinguishant Control Panels Page 76-77 Sigma A-XT Ancillary PCB UL Listed FM Approved Extinguishant Ancillary PCB Page 80-81 N EW ! N EW ! N EW ! Page 64 Extinguishant Control Panel Features Product Overview Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the Sigma XT extinguishant releasing panel ofers outstanding value and performance for all small to medium fxed frefghting installations. With three detection zones as standard, extinguishant release can be confgured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and foor void applications. The extensive confguration options of the Sigma XT allow the functionality of the system to be extensively modifed while still complying with the requirements of the controlling standard for the equipment (EN12094-1). The panel contains a large LED display to enable easy confguration and control which also displays the time remaining until extinguishant release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status. With all of the electronics mounted on a single, easily removable, steel plate Sigma XT panels are both robust and easy to install. Sigma XT is supplied in an enclosure that matches the design and colour of the Sigma CP range. Complies with EN12094-1 Three detection zones as standard Any single zone or any combinations of zones can be confgured to release Confgurable frst stage sounder delays Confgurable detection delays Zero time delay upon manual release option Compatible with I.S. barriers Non-latching zone input option to receive signals from other systems such as aspirating equipment Confgurable extinguishant delays up to 60 seconds in 5 second steps Confgurable extinguishant duration up to 5 minutes in 5 second steps Countdown timer shows time remaining until release Supports up to seven, four wire status indicators Built in Extract Fan control Programmable Functions Access Level 2 Test Zones 1 to 3 Disable Zones 1 to 3 Disable 1st Stage Alarms Disable Pre-activated 1st Stage Relay Disable Pre-activated 2nd Stage Relay Disable Extract Fan Output Disable Manual Release Input Disable Extinguishant Sub System Activate Extract Fan Output Activate Alarm Delays Access Level 3 Sounder Delay Coincidence Detection Disable Panel Features Zone Alarm Delays (Detectors) Zone Alarm Delay (Call Points) Confgure Zone for I.S Barrier Use Zone Short Circuit Alarm Zone Non Latching Zone Inputs Delay Extinguishant Release Time Delay Extinguishant Release Duration Timer Extinguishant Reset Delay Timer Model No. K11031M2 XT Sigma BS- EN12094- 1 KM 96761 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 65 Panels Construction Finish Colour - lid & box Colour - controls plate & labels Mains supply Mains supply fuse Power supply rating Maximum ripple current Battery type (Yuasa NP) Battery charge voltage Battery charge current Battery fuse Maximum current draw from batteries Quiescent current of panel in mains fail R0V output Sounder outputs Fault relay contact rating Fire relay contact rating Local fre relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of detectors per zone Number of sounders per circuit Detection circuit end of line Monitored input end of line Sounder circuit end of line Extinguishant output EOL No. of detection circuits No. of sounder circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Zone normal threshold Detector alarm threshold Call point alarm threshold Short circuit threshold Head removal condition Cabling Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC +10%/-15% (100 Watts maximum) 1.6 Amp (F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 200 millivolts Two 12 Volt 7Ah sealed lead acid in series 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 3 Amps 0.095A Fused at 500mA with electronic fuse 24V Fused at 500mA with electronic fuse 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 2mA maximum 0.5mm to 2.5mm solid or stranded wire Dependent on type (maximum 32) Dependent on type (max. 0.5A per sounder circuit) 6K8 5% Watt resistor 6K8 5% Watt resistor 10K 5% Watt resistor 1N4004 Diode 3 2 x 1st Stage, 1 x 2nd Stage Fused at 1 Amp Adjustable 0 to 60 seconds (in 5 second steps) Adjustable 60 to 300 seconds (in 5 second steps) Switched -ve, max resistance 100 Ohms 8K ohms to 1K ohm 999 ohms to 400 ohms 399 ohms to 100 ohms 99 ohms to 0 ohms 15.5 to 17.5 volts FP200 or equivalent 8K ohms to 1K ohm 999 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection Fused at 500mA with electronic fuse - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Product Code K11031M2 K11031F2 Description Surface mounting panel Flush mounting panel Size (mm) 385 x 310 x 90 415 x 315 x 86 EXTRACT REL PRESS. SWI TCH LOW PRES. SWI TCH EXTI NG. HOLD RELEASE MAN. SELECT MODE 2ND STAGE 1ST STAGE SOUNDER 2ND POWER DATA STATUS UNI TS REMOTE CONTROL AUX 24V C NO NO C NC NO C NC ZONE 3 E ZONE 1 ZONE 2 S2 S1 RST R0V SI L AL FLT NO C NC NO C NC NO C NC FI RE RELAY LOCAL FI RE FAULT RELAY S S S S S S S S 4 7 0 R 4 7 0 R 4 7 0 R 4 7 0 R 6 K 8 6 K 8 6 K 8 6 K 8 6 K 8 D I O D E 4 7 0 R S O L 10K 6 K 8 6 K 8 6 K 8 10K 10K To St at us Unit s Remot e Cont rol I nput s 1st St age Sounders 2nd St age Sounders Auxiliary Signalling Relays S t o p
A i r
C o n d i t i o n i n g R e m o t e
A u t o / M a n u a l S e l e c t
S w i t c h R e m o t e
M a n u a l R e l e a s e
S w i t c h R e m o t e
H o l d
S w i t c h E x t i n g u i s h a n t
R e l e a s e d P r e s s u r e
S w i t c h R e l e a s i n g
S o l e n o i d E x t i n g u i s h a n t
L o w P r e s s u r e
S w i t c h R e l e a s i n g D e t e c t o r s P e r i p h e r a l D e t e c t o r s E x t r a c t
F a n
P o w e r S h u t d o w n
P o w e r Sigma XT PCB DS40.06.2011 Page 66 Multi- Area Extinguishant Control Panels Features Product Overview Sigma XT+ control panels are multi-area extinguishant control panels complying with EN12094-1. Up to 8 zones of conventional detection with up to 4 extinguishant areas are available. Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fre detection control panels or addressable modules. Each extinguishant area has a comprehensive set of inputs and outputs and is confgurable via a simple programming interface. All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable. The versatility of the control panel can be enhanced further by the ftting of up to 7 Sigma CP Ancillary boards (K580) or Sigma CP Sounder boards (K461) to the RS485 serial bus. See data sheet DS39 (page 52-53) and DS48 (page 53-54). For compatible status units see Sigma Si data sheet DS41 (page 70-71). Complies with EN12094-1 2, 4 or 8 detection zones 1 to 4 extinguishant areas Dual extinguishant outputs for each area (confgurable as Main/Reserve) First and second stage sounder outputs for each area First and second stage volt free changeover contacts for each area Released volt free contact per area Fault volt free contact per area Programmable extinguishant delays Programmable output duration Extract fan control Countdown indicator shows time until release in seconds Mode select and manual release controls per area Monitored remote manual release input Monitored remote Hold input Monitored remote Mode select (door interlock) input Monitored remote Released pressure switch input Monitored remote Low Pressure switch input Monitored Abort input Serial connection for Sigma Si status units and ancillary boards. (K588) Sigma XT Ancillary Board - K588 Sigma CP Ancillary Board - K580 Sigma CP Sounder Board - K461 XT+ Sigma Model No. K21082M3 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 67 Construction Finish Colour - lid & box Colour - controls plate & labels Mains supply Mains supply fuse Power supply rating (1 & 2 area units) Power supply rating (3 & 4 area units) Maximum ripple current Battery charge voltage Battery charge current Battery fuse Current draw in mains fail condition Max. current draw from batteries
Sigma XT+ module Aux 24V output Sigma CP Aux 24V output 1st and 2nd stage Sounder outputs Fault relay contact rating Fire relay contact rating Local fre relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of detectors per zone Number of sounders per circuit Detection circuit end of line Monitored input end of line Sounder circuit end of line Extinguishant output end of line No. of detection circuits No. of sounder circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Zone normal threshold (Allowable EOL) Detector alarm threshold Call point alarm threshold Short circuit threshold Head removal condition Cabling Monitored inputs normal threshold (Allowable EOL) Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC, 50Hz +10% - 15% (100 Watts maximum) 1.6 Amp ( F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 5.25 Amps including battery charge 28V +/- 2V 200 millivolts 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 54 milliamps per module 3A (K21021, K21041, K21042, K21081, K21082) 4A (K21083, K21084) Fused at 500mA with electronic fuse - 1 per extinguishant area Fused at 2.5A - not available to user 21 to 28V DC Fused at 1A with electronic fuse 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 0mA minimum, 2mA maximum 0.5mm2 to 2.5mm2 solid or stranded wire Dependent on type - typically 20 Dependent on type and current consumption - typically 20+ 6K8 +/- 5% Watt resistor 6K8 +/- 5% Watt resistor 10K +/- 5% Watt resistor 1N4004 Diode Two to eight. 21 to 28V DC Dependent on model 21 to 28V DC 21 to 28V DC. Fused at 1 Amp Adjustable 0 to 60 seconds (+/- 10%) Adjustable 60 to 300 seconds Switched -ve, min resistance 0 ohms, max resistance 100 Ohms 10K ohm to 2K ohm 1K ohms to 390 ohms 370 ohms to 150 ohms 130 ohms to 0 ohms 15.5 to 17.5 volts FP200 or equivalent (max capacitance 1uF max inductance 1 mH 10K ohm to 2K ohm
2K ohms to 150 ohms +/- 5% 140 ohms to 0 ohms +/- 5% Two wire RS485 connection (EIA-485 specifcation) 21 to 28V DC. Fused at 500mA with electronic fuse - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels Product Code K21021M3 K21041M3 K21042M3 K21081M3 K21082M3 K21083M4 K21084M4 Areas 1 1 2 1 2 3 4 Size (mm) 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 700 x 145 385 x 700 x 145 Zones 2 4 4 8 8 8 8 DS50.03.2011 Page 68 Extinguishant Coincidence Unit Features Product Overview The Sigma XT+ ECD coincidence unit has two fully monitored inputs for connection to fre detection control equipment or addressable control modules to provide an EN12094-1 compliant extinguishant control system. Its many programmable features and extensive range of inputs and outputs make the Sigma XT+ ECD coincidence unit suitable for all extinguishing applications where a fully featured control device is required. Among the many features of the Sigma XT+ ECD are serially connected status units for reduced wiring and reduced installation cost, dual extinguishant outputs that may be confgured for main/reserve applications and a countdown timer which displays the time until discharge of the extinguishant in seconds. All units are independently confgurable via a simple, code based programming interface to suit the desired application. Complies with EN12094-1 Dual extinguishant outputs First and second stage sounder outputs First and second stage relay contacts Main reserve facility Serial connection to status units Discharge countdown time indicator Model No. K21001M2 XT+ Sigma Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 69 Product Code Size Construction Finish Colour - lid & box Colour - controls plate & labels Areas Mains supply Mains supply fuse Power supply rating
Maximum ripple current Battery type (Yuasa NP) Maximum Battery Capacity within Enclosure Battery charge voltage Battery charge current Battery fuse Current draw in mains fail condition Maximum current draw from batteries Aux 24V output 1st and 2nd stage Sounder outputs Fault relay contact rating Fire relay contact rating K21001M2 385mm(W) x 310mm(H) x 90mm(D) 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 1 230V AC, 50Hz +10% - 15% (100 Watts max.) 1.6 Amp ( F1.6A L250V) 5.25 Amps total including battery charge 28V +/- 2V 200 millivolts 12 Volt sealed lead acid in series Yuasa 2.3Ah 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 54 milliamps 4 Amps Fused at 500mA with electronic fuse 21 to 28V DC Fused at 1A with electronic fuse 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each - - - - - - - - - - - - - - - - - - - - - - - Technical Local fre relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of sounders per circuit Monitored input end of line Sounder circuit end of line Extinguishant output end of line Extinguishant release output Extinguishant release delay Extinguishant release duration Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 0mA minimum, 2mA maximum 0.5mm2 to 2.5mm2 solid or stranded wire Dependent on type and current consumption 6K8 +/- 5% Watt resistor 10K +/- 5% Watt resistor 1N4004 Diode 21 to 28V DC. Fused at 1 Amp Adjustable 0 to 60 seconds (+/- 10%) Adjustable 60 to 300 seconds (Allowable EOL) 10K ohm to 2K ohm 2K ohms to 150 ohms +/- 5% 140 ohms to 0 ohms +/- 5% Two wire RS485 connection (EIA-485 specifcation) 21 to 28V DC, Fused at 500mA with electronic fuse - - - - - - - - - - - - - - - - - - DS55.04.2011 230V RS485 Sigma CP Ancillary Board (S580) Sigma CP Sounder Board (S461) 24V Power Supply EN54-4 : 1998 L4 L5 L3 L E N
1. 2. 3. 4. 5. 6. FUSE-T2A 250V HRC KENTEC ELECTRONICS LTD LOAD 28V DC L2 L1 24V BATT. TIME DELAYTYPET2A250V 230V AC ENS400 REPLACE FUSE ONLYWITH 20mm 2A INPUT CURRENT - L5 - CHGR. FAULT L4 - EARTH FAULT L3 - BATTERY LOW L2 - BATT DISCON. L1 - MAINS FAIL CHARGER FAIL BATT. DISCONN. 6. 5. 4. 3. 2. 1. COMMON FAULT EARTH FAULT BATTERY LOW MAINS FAILED 112W 28V DC 50 - 60Hz - MODEL --- - POWER RATING OUTPUTVOLTAGE FREQUENCY INPUT VOLTAGE L5 L4 L1 L2 L3 K588 Ancillary Board System Status & Control K588 Ancillary Board System Status & Control Up to 4 Sigma XT+ coincidence units may be tted 1 Sigma CP-R Repeater Panel (Up to 7) Sigma CP Control Panel RS485 RS485 Up to 7 Ancillary Boards Up to 7 Status Units Up to 7 Ancillary Boards Up to 7 Status Units 230V K588 Ancillary Board System Status & Control K588 Ancillary Board System Status & Control Sigma XT+ Coincidence Unit Sigma XT+ Coincidence Unit Sigma XT+ Coincidence Unit Sigma XT+ Coincidence Unit Syncro Control Panel RS485 RS485 Up to 7 Ancillary Boards Up to 7 Status Units Up to 7 Ancillary Boards Up to 7 Status Units Loop Module Loop Module Example Schematic 1 Example Schematic 2 Page 70 Extinguishant Status Indicators Sigma Si Product Overview The Sigma Si range of status indicators provide detailed status information for Sigma XT/XT+ extinguishant release control equipment. All models provide high brightness, LED indication of Manual Only, Automatic and Manual, Hold operated, Disabled, Imminent and Released conditions. Models are also available with zonal fre indicators and a common fault indicator. For systems where local control of the Automatic/Manual mode and or a Manual extinguishant release control are required, units are available with these controls ftted. All models have monitored inputs for the remote connection of Automatic/ Manual mode and Hold switches. All units contain a large, LED display which shows a countdown of the time remaining until the extinguishant is released in seconds. Hold of Product Overview Available with red or green actuators (BS 7273-1 recommends white with red button) Shrouded push button to prevent accidental operation Fitted with normally open and normally closed contacts to allow operation with monitored and unmonitored systems Robust all steel enclosure Model No. K911113M8 Model No. K911000M8 Model No. K911100M8 Model No. K911111M8 Model No. K911110M8 Sigma Si Features Certifed compliant with BS EN12094-1 when used with Sigma XT control equipment High brightness LEDs Detailed indication of the status of the control panel Monitored data connection Countdown timer shows time remaining until release Manual only and Automatic & Manual mode select keyswitch option Four wire connection (data and power) Protected dual action manual release switch option Option for zonal fre and common fault indication with buzzer Robust, high quality enclosure Easy access to terminals Remote Auto/Manual door interlock input (monitored) Remote Hold input (monitored) Internal fault diagnosis indicators Weatherproof IP65 versions available Internal buzzer Model No. K91000M10 Si & Hol d Sw i t c h Sigma Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 71 256mm 1 7 0 m m Construction Colour - lid & box Contacts Trigger resistor 1.2mm mild sheet steel White 1 N.O and 1 N.C 470R 1 Watt - - - - Equipment Product Code
K91000M10 KB91000M10 Description 6 lamp status unit surface 6 lamp status unit fush 6 lamp status unit with mode select keyswitch surface 6 lamp status unit with mode select keyswitch fush 6 lamp status unit with manual release surface 6 lamp status unit with manual release fush 6 lamp status unit with mode select keyswitch and manual release surface 6 lamp status unit with mode select keyswitch and manual release fush 10 lamp status unit with mode select keyswitch and manual release surface 10 lamp status unit with mode select keyswitch and manual release fush
IP65 - 6 lamp status unit surface IP65 - 6 lamp status unit with mode select keyswitch surface IP65 - 6 lamp status unit with mode select keyswitch and manual release surface IP65 - 10 lamp status unit with mode select keyswitch and manual release surface
Extinguishant hold of switch unit - green button Extinguishant hold of switch unit - red button Construction Colour - lid & box Power supply Maximum current draw Max. number of status units Quiescent current Cable capacity Monitored inputs end of line resistor Monitored inputs normal threshold Monitored inputs trigger threshold Monitored inputs Short circuit threshold Data connection 1.2mm mild sheet steel BS 00 A 05 grey - fne texture 21 to 30 V DC 0.07A 7 0.033A 2.5mm per terminal 6K8 0.5W Resistor 8K ohm to 1K ohm
700 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection (max 1200 metres) - - - - - - - - - - - Hold of Technical Sigma Si Technical Fire Zone 3 Fire Zone 2 Fire Zone 1 Fault Released Imminent Disabled Hold Activated Auto/Manual Manual Only available on 10 lamp units only DS41.04.2011 Weatherproof Version Model No. W911113W8* * Not suitable for Sigma XT+ / Syncro XT+ or Sigma XT+ ECU products Size (mm) 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 186 x 132 x 50 186 x 132 x 55 256 x 170 x 60 256 x 170 x 60 256 x 170 x 60 256 x 170 x 60 97 x 97 x 45 97 x 97 x 45 Page 72 Extinguishant Ancillary PCB Ancillary PCB Product Overview The Sigma XT Ancillary Board is compatible with all Sigma XT control panels which have operating software version SIGXT_11A.HEX or above. The board provides volt free normally open contacts allowing control of sub-systems and plant remotely from the main panel over a two wire data bus. Mains powered, boxed Ancillary boards require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source. Up to 7 Ancillary boards can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres. A mixture of status units and Ancillary boards, up to a maximum of 7 of each type, can be connected to the serial data bus. Ancillary PCB Features Two wire serial connection Up to 7 per system 230V AC or 24V DC powered versions Volt free relay outputs for fre and extinguishing system status
Relay operated LED indicators Model No. K1822 R S 4 8 5 2 4 V
D C I N O U T M O D E H O L D Status PCB 6K8 6K8 470R 470R To next Status Unit if tted From previous status unit or control panel To next Status Unit if tted From previous status unit or control panel Equipment Product Code
K588 K03000M2 K03750M2 Description Stand alone ancillary PCB Boxed ancillary PCB Boxed ancillary PCB with 0.75A PSU Size (mm) 155 x 136 385 x 310 x 90 385 x 310 x 90 Construction (Boxed) Colour - lid & box Supply voltage (K03750M2) Supply voltage (K03000M2) Mains supply fuse Power supply DC rating Maximum battery size Contact ratings Cable capacity Operating temperature Operating humidity 1.2mm mild sheet steel BS 00 A 05 grey - fne texture 230V AC (+10%/-15%) 20-30V DC 1.6A 250V 24V 0.75 Amp 2Ah 24V (2 per panel) 30V DC 1 Amp 2.5mm per terminal -5C to +50C <95% (non condensing) - - - - - - - - - - Ancillary PCB Technical Si Anc i l l ar y PCB Sigma Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 73 DS75.01.2011 ADDRESS PROCESSOR RESET FUSE FAIL OK Z1 Z2 Z3 MAN DISAB REL ACT EXTR HOLD MAN REL - + 24V DC 24V DC - + - + PF Z1 FIRE Z2 FIRE Z3 FIRE MAN MODE DISAB REL ACT HOLD EXTR MAN REL - + RS485 OUT RS485 IN System Status and Control System Status and Control System Status and Control EN12094-1 Approved Control Unit Detection Zone 1 Detection Zone 2 Detection Zone 3 1 s t
S t a g e
S o u n d e r s 2 n d
S t a g e
S o u n d e r s H o l d M a n u a l
R e l e a s e D o o r
I n t e r l o c k 4 Core Ancillary Board Ancillary Board BMS Interface Addressable House Fire Alarm Activate Extinguisher Released Pressure Switch Low Pressure Switch 4 Core Example System Schematic Page 74 Multi-Area, Addressable Extinguishant Control Panels Features Product Overview Syncro XT+ control panels are multi-area extinguishant control panels complying with EN12094-1. Up to 16 zones of addressable detection over 1 or 2 loops ensure every detector is able to contribute to extinguishant release. Up to 4 extinguishant areas are available. Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fre detection control panels or addressable modules. Each extinguishant area has a comprehensive set of inputs and outputs and is confgurable via a simple programming interface. All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable. For compatible status units see Sigma Si data sheet DS41 (page 70-71). Complies with EN12094-1 16 detection zones Up to 4 extinguishant areas Dual extinguishant outputs for each area (confgurable as Main/Reserve) First and second stage sounder outputs for each area First and second stage volt free changeover contacts for each area Released volt free contact per area Fault volt free contact per area Programmable extinguishant delays Programmable output duration Countdown indicator shows time until release in seconds Mode select and manual release controls per area Monitored remote manual release input Monitored remote hold input Monitored remote mode select (door interlock) input Monitored remote released pressure switch input Monitored Abort input Serial connections for Sigma Si status units and ancillary boards. (K588) Model No. #32162M3 C O M I N G S O O N XT+ Syncro Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 75 Construction Finish Colour - lid & box Colour - controls plate & labels Mains supply Mains supply fuse Power supply rating (1 & 2 area units) Power supply rating (3 & 4 area units) Maximum ripple current Battery charge voltage Battery charge current Battery fuse Current draw in mains fail condition Max. current draw from batteries
Sigma XT+ module Aux 24V output Syncro AS Aux 24V output 1st and 2nd stage Sounder outputs Fault relay contact rating Fire relay contact rating Local fre relay contact rating First stage contact rating Second stage contact rating Extract contact rating Terminal capacity Number of sounders per circuit Monitored input end of line Sounder circuit end of line Extinguishant output end of line Number of detection loops Number of zones No. of sounder circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Cabling Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 230V AC, 50Hz +10% - 15% (100 Watts maximum) 1.6 Amp ( F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 4 Amps including battery charge 28V +/- 2V 200 millivolts 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 54 milliamps per extinguishing module 3A (#31161M3, #32161M3, #31162M3, #32162M3) 5.25A (#31163M4, #32163M4, #31164M4, #32164M4) Fused at 500mA with electronic fuse - 1 per extinguishant area Fused at 2.5A - not available to user 21 to 28V DC Fused at 1A with electronic fuse 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 5 to 30VDC 1A Amp maximum for each 0.5mm2 to 2.5mm2 solid or stranded wire Dependent on type and current consumption - typically 20+ 6K8 +/- 5% Watt resistor 10K +/- 5% Watt resistor 1N4004 Diode 1 or 2 16 Dependent on model 21 to 28V DC 21 to 28V DC. Fused at 1 Amp Adjustable 0 to 60 seconds (+/- 10%) Adjustable 60 to 300 seconds Switched -ve, min resistance 0 ohms, max resistance 100 Ohms FP200 or equivalent (max capacitance 1uF max inductance 1 mH 10K ohm to 2K ohm 2K ohms to 150 ohms +/- 5% 140 ohms to 0 ohms +/- 5% Two wire RS485 connection (EIA-485 specifcation) 21 to 28V DC. Fused at 500mA with electronic fuse - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Panels Product Code
385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 520 x 110 385 x 700 x 145 385 x 700 x 145 385 x 700 x 145 385 x 700 x 145 # - replace with: A for Apollo protocol, H for Hochiki protocol V for Argus Vega protocol DS58.02.2011 Page 76 Extinguishant Control Panel Features Product Overview Designed and manufactured to the highest standards in a quality controlled environment and with UL and FM approvals, the Sigma A-XT releasing panel ofers outstanding value and performance for all small to medium fxed frefghting installations. With three initiation circuits as standard, release can be confgured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and foor void applications. The extensive confguration options of the Sigma A-XT allow the functionality of the system to be extensively modifed. The panel contains a large LED display to enable easy confguration and control which also displays the time remaining until release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the system status. With all of the electronics mounted on a single, easily removable, steel plate Sigma A-XT panels are both robust and easy to install. Sigma A-XT is supplied in an enclosure that matches the design and color of the Elite RS range and is available in standard red or optional gray. UL864 and FM listed Three initiation circuits as standard Any single zone or any combinations of zones can be confgured to release Confgurable frst stage NAC delays Confgurable detection delays Zero time delay upon manual release option Compatible with I.S. barriers Non-latching zone input option to receive signals from other systems such as aspirating equipment Confgurable releasing delays up to 60 seconds in 5 second steps Confgurable releasing duration up to 5 minutes in 5 second steps Countdown timer shows time remaining until release Supports up to seven, four wire status indicators Built in Extract Fan control Programmable Functions Access Level 2 Test Zones 1 to 3 Disable Zones 1 to 3 Disable 1st Stage Alarms Disable Pre-activated 1st Stage Relay Disable Pre-activated 2nd Stage Relay Disable Extract Fan Output Disable Manual Release Input Disable Releasing Sub System Activate Extract Fan Output Activate Alarm Delays Access Level 3 Sounder Delay Coincidence Detection Disable Panel Features Zone Alarm Delays (Detectors) Zone Alarm Delay (Call stations) Confgure Zone for I.S Barrier Use Zone Short Circuit Alarm Zone Non Latching Zone Inputs Delay Extinguishant Release Time Delay Extinguishant Release Duration Timer Extinguishant Reset Delay Timer Model No. K1810-10 A-XT Sigma N E W ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 77 Panels Construction Finish Colour - lid & box Mains supply Mains supply fuse Power supply rating Maximum ripple current Battery type (Yuasa NP) Battery charge voltage Battery charge current Battery fuse Maximum current draw from batteries Quiescent current of panel in mains fail R0V output Sounder outputs Fault relay contact rating Fire relay contact rating Local fre relay contact rating First stage contact rating Second stage contact rating Extract contact rating Zone quiescent current Terminal capacity Number of detectors per zone NAC rating Detection circuit end of line Monitored input end of line Sounder circuit end of line Extinguishant output EOL No. of initiating circuits No. of NAC circuits Extinguishant release output Extinguishant release delay Extinguishant release duration SIL, AL, FLT, RST inputs Zone normal threshold Detector alarm threshold Call point alarm threshold Short circuit threshold Monitored inputs normal threshold Monitored inputs alarm threshold Monitored inputs Short circuit threshold Status unit/Ancillary board connection Status unit power output 1.2mm mild sheet steel Epoxy powder coated Red RAL 3002 (optional grey BS 00 A 05 semi-matt) 230V AC or 115V AC 1.6 Amp (F1.6A L250V) 3 Amps total including battery charge 28V +/- 2V 200 millivolts Two 12 Volt 7Ah sealed lead acid in series 27.6VDC nominal (temperature compensated) 0.7A maximum 20mm, 3.15A glass 3 Amps 0.095A Fused at 500mA with electronic fuse 24V Fused at 500mA with electronic fuse 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 30VDC 1A Amp maximum 2mA maximum 12 AWG Dependent on type (maximum 32) 0.5A per circuit 6K8 5% Watt resistor 6K8 5% Watt resistor 10K 5% Watt resistor 1N4004 Diode 3 2 x 1st Stage, 1 x 2nd Stage Fused at 1 Amp Adjustable 0 to 60 seconds (in 5 second steps) Adjustable 60 to 300 seconds (in 5 second steps) Switched -ve, max resistance 100 Ohms 8K ohms to 1K ohm 999 ohms to 400 ohms 399 ohms to 100 ohms 99 ohms to 0 ohms 8K ohms to 1K ohm 999 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection Fused at 500mA with electronic fuse - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Product Code K1810-12 K1810-13 K1810-44 K1810-43 Description Surface mounting panel - Red 115V Surface mounting panel - Red 230V Surface mounting panel - Grey 115V Surface mounting panel - Grey 203V Size (mm) 368 x 310 x 90 368 x 310 x 90 368 x 310 x 90 368 x 310 x 90 DS72.01.2011 Page 78 Extinguishant Status Indicators Sigma A-Si Product Overview The Sigma A-Si range of status indicators provide detailed status information for Sigma A-XT releasing control equipment. All models provide high brightness, LED indication of Manual Only, Automatic and Manual, Abort operated, Disabled, Imminent and Released conditions. Models are also available with zonal fre indicators and a common trouble indicator. For systems where local control of the Automatic/Manual mode and or a Manual extinguishant release control are required, units are available with these controls ftted. All models have supervised inputs for the remote connection of Automatic/ Manual mode and abort switches. All units contain a large, LED display which shows a countdown of the time remaining until release in seconds. Abort Switch Product Overview The Sigma A-XT Abort switch connects to the Abort terminals of the Sigma A-XT releasing panel. Any number of Sigma A-XT Abort switches may be connected to the circuit. The last switch must have the end of line device from the Abort circuit terminals of the Sigma A-XT releasing panel ftted across its connections to provide open and short circuit supervision. The unit is supplied mounted to a rugged steel enclosure but may also be fush mounted to a single gang electrical box. Model No. K1821-19 Model No. K1821-11 Model No. K1821-13 Model No. K1821-15 Model No. K1821-17 Sigma A-Si Features UL864 and FM listed High brightness LEDs Detailed indication of the status of the control panel Supervised data connection Countdown timer shows time remaining until release Manual only and Automatic & Manual mode select keyswitch option Four wire connection (data and power) Protected dual action manual release switch option Option for zonal fre and trouble indication with buzzer Robust, high quality enclosure Easy access to terminals Remote Auto/Manual door interlock input (supervised) Remote Abort input (supervised) Internal trouble diagnosis indicators Model No. K1823-10 A-Si & Abor t Sw i t c h Sigma N E W ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 79 Equipment Product Code
K1821-11 K1821-41 K1821-12 K1821-42 K1821-13 K1821-43 K1821-14 K1821-44 K1821-15* K1821-45* K1821-16* K1821-46* K1821-17* K1821-47* K1821-18* K1821-48* K1821-19* K1821-49* K1821-20* K1821-50* K1823-10 K1823-40 Description 6 lamp status unit surface mount - red 6 lamp status unit surface mount - gray 6 lamp status unit fush mount - red 6 lamp status unit fush mount - gray 6 lamp status unit with mode select keyswitch surface mount - red 6 lamp status unit with mode select keyswitch surface mount - gray 6 lamp status unit with mode select keyswitch fush mount - red 6 lamp status unit with mode select keyswitch fush mount - gray 6 lamp status unit with manual release surface mount - red 6 lamp status unit with manual release surface mount - gray 6 lamp status unit with manual release fush mount - red 6 lamp status unit with manual release fush mount - gray 6 lamp status unit with mode select keyswitch & manual release surface mount - red 6 lamp status unit with mode select keyswitch & manual release surface mount - gray 6 lamp status unit with mode select keyswitch & manual release fush mount - red 6 lamp status unit with mode select keyswitch & manual release fush mount - gray 10 lamp status unit with mode select keyswitch & manual release surface mount - red 10 lamp status unit with mode select keyswitch & manual release surface mount - gray 10 lamp status unit with mode select keyswitch & manual release fush mount - red 10 lamp status unit with mode select keyswitch & manual release fush mount - gray Elite Extinguishing Abort switch surface mount - red Elite Extinguishing Abort switch surface mount - gray Construction Colour - lid & box Power supply Maximum current draw Max. number of status units Quiescent current Cable capacity Monitored inputs end of line resistor Monitored inputs normal threshold Monitored inputs trigger threshold Monitored inputs Short circuit threshold Data connection 1.2mm mild sheet steel Red (optional grey) 21 to 30 V DC 0.07A 7 0.033A 2.5mm per terminal 6K8 0.5W Resistor 8K ohm to 1K ohm 700 ohms to 100 ohms 99 ohms to 0 ohms Two wire RS485 connection (max 1200 metres) - - - - - - - - - - - - Sigma A-Si Technical DS73.01.2011 * Not UL/FM Listed Size (mm) 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 186 x 132 x 50 186 x 132 x 50 186 x 132 x 55 186 x 132 x 55 98 x 98 x 59 98 x 98 x 59 Trouble Released Imminent Disabled Abort Activated Auto/Manual Manual Only Fire Zone 3 Fire Zone 2 Fire Zone 1 Construction Colour Switch rating Trigger resist End of line resistor 1.2mm mild sheet steel Red (optional grey) 1A at 30V DC 470R 1W 6K8 1/2 W - - - - - Abort Switch Technical Page 80 Extinguishant Ancillary PCB R S 4 8 5 2 4 V
D C I N O U T M O D E A B O R T Status PCB 6K8 6K8 470R 470R To next Status Unit if tted From previous status unit or control panel To next Status Unit if tted From previous status unit or control panel A-XT Anc i l l ar y PCB Sigma N E W ! Ancillary PCB Product Overview The Sigma A-XT Ancillary Board is compatible with all Sigma A-XT control panels. The board provides volt free normally open contacts allowing control of sub-systems and plant remotely from the main panel over a two wire data bus. Ancillary boards require only a two core data cable from the main control panel and a two core power cable from the main panel. Up to 7 Ancillary boards can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 4000 feet. A mixture of status units and Ancillary boards, up to a maximum of 7 of each type, can be connected to the serial data bus. Ancillary PCB Features UL864 and FM listed Two wire serial connection Up to 7 per system Volt free relay outputs for fre and releasing system status
Relay operated LED indicators Model No. K1822 Equipment Product Code
K1822-00 K1822-10 K1822-40 Description Sigma A-XT Ancillary Board Sigma A-XT Ancillary Board with cabinet - red Sigma A-XT Ancillary Board with cabinet - gray Size (mm) 155 x 136 385 x 310 x 90 385 x 310 x 90 Construction (Boxed) Colour - lid & box Supply voltage Contact ratings Cable capacity Operating temperature Operating humidity 1.2mm mild sheet steel Red (optional grey) 20-30V DC 30V DC 1 Amp 2.5mm per terminal -5C to +50C <95% (non condensing) - - - - - - - Ancillary PCB Technical Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 81 DS74.01.2011 ADDRESS PROCESSOR RESET FUSE FAIL OK Z1 Z2 Z3 MAN DISAB REL ACT EXTR HOLD MAN REL - + 24V DC 24V DC - + - + PF Z1 FIRE Z2 FIRE Z3 FIRE MAN MODE DISAB REL ACT HOLD EXTR MAN REL - + RS485 OUT RS485 IN System Status and Control System Status and Control System Status and Control Sigma A-XT Control Panel Detection Zone 1 Detection Zone 2 Detection Zone 3 1 s t
S t a g e
S o u n d e r s 2 n d
S t a g e
S o u n d e r s H o l d M a n u a l
R e l e a s e D o o r
I n t e r l o c k 4 Core Ancillary Board Ancillary Board BMS Interface Addressable House Fire Alarm Activate Extinguisher Released Pressure Switch Low Pressure Switch 4 Core Example System Schematic Power Supplies Pages 84-88 C O M I N G S O O N Power Supplies Pages 84-88 PSU EN54-4 Approved Fire Alarm Power Supplies Page 84-85 PSU EN54-4 Approved Switched Mode Power Supply / Charger Page 86-87 PSU EN54-4 Compliant 10.25 Amp Power Supply Page 88 Page 84 EN54-4 Approved Fire Alarm Power Supplies Features Product Overview Syncro Power fully certifed to EN54-4 power supplies provide a stable and fully regulated, true 24V output for fre alarm system applications under all power conditions. The unique regulation techniques ensure that even when running on standby batteries, a stable 24V supply is available to all parts of the system ensuring that all 24V powered devices connected are supplied with optimum power. The powerful onboard micocontroller ensures that all battery types are conditioned with optimum, temperature compensated charging algorythms to maximise battery life and maintain batteries in top condition. Syncro Power EN54-4 compliant power supplies can be ftted with an optional dual fused output monitoring module to ensure compliance with European standards when supplying fre control panels with an external power supply. Enclosed units are available to match both Sigma and Syncro equipment ranges and all are fnished with matching livery and provide power on and power fault indications. Optional dual output path (KD) variant available, to provide two independent supply paths between the power supply unit and the control panel in accordance with EN54-4 clause 6.4 and BS5839 pt1, clause 12.2.2.m requirements. 2.5A and 5.25A versions Chassis only or enclosure mounted with battery space 110V or 230V input Regulated, true 24V output Intelligent battery charging and temperature compensation House up to 26Ah batteries Status indicators for monitored faults Dual output option for powering fre alarm control panels remotely Chassis versions have same mounting points Fully enclosed and robust construction Boxed Power Supply to match Syncro Style Boxed Power Supply to match Sigma CP and Syncro AS Style PSU BS- EN54- 4 KM 73505 Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 85 Construction Finish colour - lid & box Mains input supply voltage Mains supply fuse Load output voltage Maximum load current K25400 models Maximum load current K25250 models Maximum ripple Load fuse Maximum current draw from batteries Battery charge output voltage Battery charge current Deep discharge prevention Compatible batteries Operating temperature Common fault output Battery disconnected output Battery low output Charger fault output Earth fault output Mains failed output Fault output connector Mains connector Load connector Battery connector Front panel Power On indicator Front panel Fault indicator Power output 1.2 mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 230V AC 50/60Hz or 110V AC 50/60Hz (link selectable) 250V, 3A, SB, 5mm X 20mm 19- 30V DC +/- 1% 5.25 Amps continuous with maximum battery charge output of 1.25A 2.5 Amps continuous with maximum battery charge output of 1.0A 200 milliamps 5 Amp, self resetting Polyfuse 5 Amps 27.4V DC nominal at 20 degrees C (temperature compensated from -5 to 45 degrees C Two stage, constant voltage. 1.25 Amps maximum Battery disconnects at 19V Yuasa NP7-12, NP12-12, NP17-12, NP24-12 Powersonic PS-1270, PS-12120, PS-12170, PS12260 -5 to 45 degrees C Normally energised volt free changeover relay 30V DC 1 Amp Open collector 50 milliamps Open collector 50 milliamps Open collector 50 milliamps Open collector 50 milliamps Open collector 50 milliamps 14 way DIL header 0.1 spacing 3 way terminal, 7.62mm spacing, 2.5mm maximum cable size 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size Green LED Yellow LED Dual 24V supply terminals with EN54-4 clause 6.4 interface (when ftted with optional dual fused output monitoring module) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Technical Size (mm) 365 x 310 x 90 385 x 520 x 110 500 x 355 x 117 385 x 520 x 110 500 x 355 x 117 500 x 460 x 190 365 x 310 x 90 385 x 520 x 110 500 x 355 x 117 385 x 520 x 110 500 x 355 x 117 500 x 460 x 117 Panels Product Code K25250M2 K25250M3 K2525003 K25400M3 K2540003 K2540015 KD25250M2 KD25250M3 KD2525003 KD25400M3 KD2540003 KD2540015 PSU 2.5 Amp 2.5 Amp 2.5 Amp 5.25 Amp 5.25 Amp 5.25 Amp 2.5 Amp 2.5 Amp 2.5 Amp 5.25 Amp 5.25 Amp 5.25 Amp Batteries up to 7Ah up to 12Ah up to 12Ah up to 17.2Ah up to 12Ah up to 26Ah up to 7Ah up to 12Ah up to 12Ah up to 17.2Ah up to 12Ah up to 26Ah DS61.04.2011 With Dual Output Board With Dual Output Board With Dual Output Board With Dual Output Board With Dual Output Board With Dual Output Board Page 86 EN54-4 Approved Switched Mode Power Supply/Charger S406 Features Product Overview The S407/S406 power supply/battery charger has been developed using switched mode technology to produce an efcient and lightweight power unit for a host of fre alarm applications. Suited to almost any application, the S407/S406 is designed to be a universal power source which will reduce spares stock holding and increase serviceability of systems. The comprehensive monitoring features of the S407/S406 include true battery present detection, low battery voltage warning, battery overcharge warning, high battery impedance monitoring and low battery shut of. These features combined with the temperature compensated charger output will increase the service life of sealed lead acid batteries. Complies with EN54-4 Fully enclosed construction Small & lightweight True 5.25 Amp continuous output Comprehensive fault monitoring Microprocessor controlled Temperature compensated charger Wide input supply voltage Low battery shut of to prevent deep discharge of battery S407 Features Complies with EN54-4 Fully enclosed construction Small & lightweight True 2.5 Amp continuous output Comprehensive fault monitoring Temperature compensated charger Wide input supply voltage Low battery shut of to prevent deep discharge of battery S407 - 2.5 Amp PSU BS- EN54- 4 KM 73505 PSU S406 - 5.25 Amp PSU Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 87 Construction Finish Colour Size Weight Supply voltage Output voltage Total output current Battery charge current Load current Fault outputs rating Mains fuse Load fuses Mains failed warning Battery disconnected warning Battery low warning Battery overcharge warning Earth fault warning Common fault output Operating temperature Aluminium base - sheet steel cover Epoxy powder coated Black 226mm x 120mm x 55mm 0.9Kg 230V AC (+10%/-15%) 27.5V DC (temperature compensated) 5.25 Amps (continuous) 1.25 Amps max. 4.0 Amps (with fat battery) 50mA max. 3 Amp 20mm HRC 5 Amp (self resetting) Switched -ve output Switched -ve output Switched -ve output Switched -ve output Switched -ve output Switched -ve output -5 to +50 deg. C - - - - - - - - - - - - - - - - - - - - S406 Technical Formula C min
Where: C min
T 1
I 1
I 2
D 1.25 (T 1 I 1 + D I 2 /2)
Minimum capacity of the battery when new at the 20 hour discharge rate and at 20 C in ampere-hours; Total battery stand by period in hours; Total battery stand by load in amperes; Total battery alarm load in amperes; a de-rating factor. (1.75) Battery Calculation BS 5839-1:2002 =
=
= = = = DS19.09.2011 Construction Finish Colour Size Weight Supply voltage Output voltage Total output current Battery charge current Load current Fault outputs rating Mains fuse Load fuses Mains failed warning Battery disconnected warning Battery low warning Battery overcharge warning Earth fault warning Common fault output Operating temperature Aluminium base - sheet steel cover Epoxy powder coated Black 226mm x 120mm x 55mm 0.9Kg 230V AC (+10%/-15%) 27.5V DC (temperature compensated) 3.5 Amps (continuous) 1.25 Amps max. 2.5 Amps (with fat battery) 50mA max. 3 Amp 20mm HRC 3 Amp (self resetting) Switched -ve output Switched -ve output Switched -ve output Switched -ve output Switched -ve output Switched -ve output -5 to +50 deg. C - - - - - - - - - - - - - - - - - - - - S407 Technical Page 88 Boxed Power Supply to match Syncro Style PSU C O M I N G S O O N EN54-4 Compliant 10.25 Amp Power Supply Features Product Overview The S408 is an EN54-4 compliant, universal input switching power supply capable of delivering a full 290W of continuous power for fre alarm systems. Suitable for charging a range of sealed lead acid batteries from 7Ah to 45Ah, the S408 power supply features complete monitor- ing of primary and secondary power sources with fully tempera- ture compensated battery charging and battery high impedance monitoring. The S408 power supplies are available as chassis only units or mounted in a range of enclosures suitable for various sizes of battery. Continuous 8A load output while charging fully depleted batteries Charges up to 45Ah batteries Complies with EN54-4 94V to 253V AC input Mains fail monitoring with LED indication and output Battery disconnection monitoring with LED indication and output Low battery monitoring with LED indication and output Earth fault monitoring with LED indication and output Low battery cut out Temperature compensated battery charging Lightweight construction Panels Product Code S408 (Chassis only) K25800M3 K2580003 K2580015 K25800D3 KD25800M3* KD2580003* KD2580015* KD25800D3* Batteries N/A Up to 17Ah Up to 17Ah Up to 45Ah Up to 45Ah Up to 17Ah Up to 17Ah Up to 45Ah Up to 45Ah Construction Finish Colour Input voltage Output voltage Total output current Battery charge current Load current Fault outputs rating Mains fuse Load fuses Mains failed warning Battery disconnected warning Battery low warning Battery overcharge warning Earth fault warning Common fault output Operating temperature 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 94 to 253V AC 50/60 Hz 24V DC 10.25A 2.25A 8.0A (with fat battery) 50mA max. 5A 20mm HRC 10A (self resetting) Switched -ve output Switched -ve output Switched -ve output Switched -ve output Switched -ve output Switched -ve output -5 to +50 deg. C - - - - - - - - - - - - - - - - - - Technical DS67.02.2011 *With Dual Output Board Size (mm) 120 x 260 x 65 385 x 520 x 110 500 x 355 x 117 500 x 460 x 190 385 x 520 x 200 385 x 520 x 110 500 x 355 x 117 500 x 460 x 190 385 x 520 x 200 A new era in life safety alarm management Come and join us on our Journey All New Control Systems Innovative Annunciator ranges Market leading data storage and access facilities Unique system management tools Power, Intelligence...... with a sense of feeling Miscellaneous Items Pages 92-101 Remote Indicator Remote Fire Detector Indicator Units Page 96-97 Audio Visual Audible and Visual Indicator Units Page 98 N EW ! N EW ! N EW ! Miscellaneous Items Pages 92-101 Sigma DocBox Document Enclosure Page 92 Warning Signs Illuminated signs using high intensity LED indicators Page 94-95 Realy Boards Single (RL1) and Four (RL4) Way Relay PCB Page 99 Hydrosense Water Detection System Page 100-101 Vision Window Tamper Resistant Vision Window Page 93 Page 92 Sigma Doc Box DS42.04.2011 Features Product Overview Another addition to the Kentec range, the document box is designed to complement the design & colour of the Sigma CP range of control panels. The standard version Document Box will hold up to 50 A4 sheets of information on the Fire Detection or other security systems within a premises. The deep version will hold up to 100 sheets. The Doc Box also doubles up as a Key Box providing 7 easily accessible formed key hooks inside the enclosure. Matches design & colour scheme for standard Sigma CP/XT & Syncro AS control panel ranges Easy to install Key Lockable Designed for versatility Choice of small or large capacity enclosure Part Number Size Part Number Size Construction Finish Colour - lid & box Weight K16000L2 (Standard version) 385mm(W) x 310mm(H) x 60mm(D) K16000M2 (Deep version) 385mm(W) x 310mm(H) x 90mm(D) 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 3.0Kg - - - - - - - - Technical Internal VIew Model No. K16000L2 Doc Box Sigma Product code: K18002 The manufacturer reserves the right to amend specifcations without prior notice Page 93 Retroft Tamper Resistant Vision Window DS56.03.2011 Features Product Overview The Tamper Resistant Vision Window is perfect for public areas where restricted access is necessary to prevent damage and unauthorised operation of the control panel. The cover fea- tures a fully welded steel construction and key lockable inner door making it robust and secure. The Vision Window is available from stock, fully assembled, and can be ftted on site in minutes by simply taking out the hinge pins on the existing enclosure, removing the lid before ftting the new Vision Window cover and hinge pins. Control panels can also be supplied pre-ftted with the Vision Window. This applies to any M2 size Sigma CP, Sigma CPA, Sigma CP-R, Sigma XT, Sigma A-XT or Syncro AS control panels. Please contact our sales department for prices. 2 minutes to ft on site
Kit available from stock Colour to match standard Control Panel ranges Special colours available on request Fits any M2 sized Sigma CP, Sigma CP-R, Sigma XT or Syncro AS panel
Attractive design Key lockable Product code Size Construction Finish Colour - lid & box Colour - controls plate & labels Weight K18002 385mm(W) x 310mm(H) x 35mm(D) 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture RAL 7047 light grey - satin 2.0 Kg - - - - - - - Technical Fit the Vision Window, then re-ft both hinge pins Take out both hinge pins & remove lid Tamper Resi st ant Vi si on Wi ndow Page 94 Illuminated signs using high intensity LED indicators Features Product Overview The new range of illuminated warning signs employ the very latest in LED technology to provide a high reliability, high brightness, audio/ visual warning indication unit. The brightness of the sign remains constant over its entire operating range of 15 to 30 volts DC due to the unique power boost circuitry employed. This ensures that even with a system running on depleted batteries, all signs remain at full intensity. A range of standard text signs are available and customised text and languages are easily accommodated due to the unique method employed to apply the lettering. The split level design allows one message to be displayed in the top half of the sign and an additional message to be displayed in the bottom half of the sign allowing for two stage warnings for systems such as extinguishing protection systems. The signs are now also available in split colours. Red, green or yellow acrylic can be mounted in the top section and the bottom section in any confguration. Text can be printed in black or alternatively can be reversed so the letters appear in the colour of the acrylic. High brightness white LED indicators for reliability and low power consumption Standard or easily customisable wording and language variants Split level function - allows top half and bottom half of sign to be illuminated independently with no light spillage between halves Internal buzzer with disable and external silence facility Available in red illuminated or yellow illuminated as standard, other colours available on request Connects to standard fre alarm sounder circuits Two wire 2 - stage (top half/ bottom half ) voltage reversing input provided Voltage reversing, silenceable sounder output provided Model No. K27102 Split level function War ni ng Si gns N E W ! Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 95 DS64.03.2011 Construction Finish Colour - lid & box Power Consumption Operating temperature Operating humidity Operating Voltage - - - - - - - Technical Panels Product Code K27102 K27101 K27202 X2710 X2720 X2730 Description Illuminated sign - FIRE ALARM DO NOT ENTER Illuminated sign - FIRE ALARM EVACUATE AREA Illuminated sign - EXTINGUISHANT SYSTEM ACTIVATED Special Designation (specify text) Special Designation (specify text) Special Designation (specify text) 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 140 milliamps max at 24V DC -5C to +50C To 95% non-condensing -15 to 30V DC Colour Red on black Red on black Black on yellow Red on black Black on yellow Black on green ON LEV1 FLASH LEV2 FLASH SING/DUAL DISABLE BUZZ ENABLE SILENCE 2 WIRE CONTROL 3 WIRE CONTROL SILENCE BUTTON MOUNTED REMOTELY C O M M O N
+ 2 4 V S W I T C H E D
- V E
S T A G E
1 V O L T A G E
R E V E R S I N G
I N P U T
+
T O
- V O L T A G E
R E V E R S I N G
I N P U T
-
T O
+ C O M M
+ L E V
1 L E V
2 2 WIRE I/P SILENCE TO ADDITIONAL SIGNS OR SOUNDERS SOUNDER OUTPUT C O M M O N
+ 2 4 V S W I T C H E D
- V E
S T A G E
1 S W I T C H E D
- V E
S T A G E
2 C O M M
+ L E V
1 L E V
2 2 WIRE O/P SOUNDER Size (mm) 300 x 195 x 50 300 x 195 x 50 300 x 195 x 50 300 x 195 x 50 300 x 195 x 50 300 x 195 x 50 For dual background versions, contact sales on +44 (0) 1322 222121 Model No. K27102 Special designations example ALARMA DE INCENDIOS NO ENTRAR EXTINGUISHANT RELEASE SYSTEM NORMAL ENTER DO NOT ENTER Special designations example Dual background example Page 96 Remote Fire Detector Indicator Units Features Product Overview The K24000 Remote Indicator LED Units allow the LED associated with a fre detector to be extended to a visible location in areas where the detector itself is concealed. Two bright, alternately fashing LED indicators with wide angle difusers ensure that the indicators are immediately visible in any sized room. Special ceiling mounting clip available. Fixing screws supplied with each unit. The round version fts into a BESA box and the square version fts into a standard electrical single gang back box. Connections for both conventional and addressable detectors. High brightness red LED indicators for reliability and low power consumption Wide viewing angle LEDs fash alternately to easily attract attention Units to ft to standard gang or round electrical back boxes Compatible with conventional and addressable detectors Printed with FIRE ALARM IN CONCEALED SPACE as standard Custom printing and languages available on request Model No. K24001 Model No. K24000 Remot e I ndi c at or Uni t N E W ! Ceiling Mounting Clip Product Overview Our new and unique ceiling mounting clip provides fast and secure fxing of our round Remote Indicator unit to ceilings. Particularly good for fragile ceilings such as suspended ceil- ings. Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 97 Construction Finish Colour Current Consumption Operating temperature Operating humidity Voltage 1.5mm mild sheet steel Epoxy powder coated White 20 milliamps max at 24V DC -5C to +50C <95% (non condensing) 15 to 30V DC - - - - - - - Panels Product Code K24000 K24001 M24000 Description Round Remote Indicator Square Remote Indicator Ceiling Mounting Clip (fts Round Remote Indicator only) Technical DS68.02.2011 Always refer to the detector manufacturers detector base instructions before connecting the K24000 Remote Indicator Unit and only use the connections described. Remote indicators that are not connected as per the instructions may cause the detector to be inoperative. Connection Details + + A - 100R 1K Detector + Supply Addressable Detector Remote Indicator Output Conventional Detector Remote Indicator Output Flashing Red LEDs Ceiling Mounting Clip M24000* Fixing Details A A B B C C D D 1. Make a hole in the ceiling using the most suitable method below: a) Using a standard 64mm diameter hole saw. b) Use an open ended saw to cut a 62mm X 28mm slot. c) If fxing to a ceiling tile, gently push the clip through the tile and use a stanley knife to cut between points C and D (both sides). 2. Fold back the two tabs marked A into position B, locking the ceiling clip into position. 3. Use the 2 self tapping screws provided to ft the Remote Lamp plate. * Fits Round Remote Indicator Only (K24000) Size (mm) 85 x 85 x 30 85 x 85 x 30 85 x 85 x 30 Page 98 Audible and visual indicator units Providing remote indication of the status of the fre alarm system Features Product Overview A range of indicator units with either red or yellow indicators to provide audible and visual status of alarms, isolations or other functions associated with the fre alarm or other systems. These units are available with a keyswitch to silence the internal buzzer or a keyswitch to illuminate the indicator and buzzer and provide a volt free contact for ancillary control functions when the keyswitch is operated. All units mount to a UK style, single gang back box or can mount to standard surface or fush single gang mounting boxes. Available with red or yellow high brightness, fashing LED indicators Can be used for Fire alarm warning, activated by a sounder circuit or to indicate and initiate an active isolation Optional silence buzzer keyswitch Disable buzzer option via internal jumper link Optional keyswitch to perform isolation Terminations for incoming and outgoing wiring Fits onto standard, single gang UK back box for fush mounting (use M10FCLGT) Surface mounting box supplied Construction Finish Colour - lid & box Voltage Power Consumption Operating temperature Operating humidity - - - - - - - Technical 1.2mm mild sheet steel Epoxy powder coated BS 00 A 05 grey - fne texture 18 to 30 V DC 25 milliamps at 24V -5C to +50C To 95% non-condensing DS63.03.2011 Model No. K24210-M10 Model No. K24110-M10 Panels Product Code K24100-M10 K24110-M10 K24200-M10 K24210-M10 M10FCLGT Description Red Fire alarm indicator Red Fire alarm indicator with buzzer silence keyswitch Yellow alarm indicator Yellow alarm indicator with control keyswitch Flush Mounting Collar (will ft single gang deep fush back box) Size (mm) 97 x 97 x 48 97 x 97 x 48 97 x 97 x 48 97 x 97 x 48 Audi o Vi sual N E W ! The manufacturer reserves the right to amend specifcations without prior notice Page 99 Single (RL1) and Four (RL4) Way Relay PCB Features K375 - RL1 Single Way Relay PCB Product Overview This simple board contains a single 24V DC relay, which can be used for any extra low voltage switching applications. It has two changeover contacts, an LED indicator to show when the coil is energised and a polarising diode to prevent damage to the power source by reverse polarity connection.
The contacts are suitable for switching a maximum of 30V DC and 2 Amps. Voltages or currents that exceed these values should not be connected under any circumstances.
The current consumption of the unit when operated from a 24V supply is approximately 25mA.
The PCB has four 4mm mounting holes, which will accept the self adhesive standofs supplied. The use of self adhesive standofs should be carefully considered however due to their tendency to become detached over a period of time and a more permanent fxing method is recommended. 24V DC operated LED indicator shows relay operated Two changeover contacts per relay Built in suppression diodes Spring leaf 2.5mm capacity terminals Small footprint 2 Amp 30V DC contact rating Low current consumption DS26.03.2011 K376 - RL4 Four Way Relay PCB Product Overview This simple board contains four 24V DC relays, which can be used for any extra low voltage switching applications.
Each relay has two changeover contacts, and an LED indicator to show when the coil is energised. The coils of the relays are commoned to the positive supply and the relays can be operated individually by switching a negative to the numbered coil inputs.
The contacts are suitable for switching a maximum of 30V DC and 2 Amps. Voltages or currents that exceed these values should not be connected under any circumstances.
The current consumption of the unit when operated from a 24V supply is approximately 25mA per relay.
The PCB has four 4mm mounting holes, which will accept the self adhesive standofs supplied. The use of self adhesive standofs should be carefully considered however due to their tendency to become detached over a period of time and a more permanent fxing method is recommended. RL4- Four Way Relay PCB (K376) RL1- Single Way Relay PCB (K375) Example sounder interface of two K3000S re panels R 4 R 3 R 2 R 1 D 4 D 3 D 2 D 1 S E R IA L N U M B E R RELAY 4 RELAY 3 RELAY 2 RELAY 1 NO C NC 4 NO C NC 3 NO C NC 2 NO C NC 1 L K 1 R E L A Y 2 R E L A Y 1 NO C NC NO C NC R E L A Y 4 R E L A Y 3 NO C NC NO C NC RL4 RL3 RL2 RL1 X1 L4 L3 L2 L1 RL4 CONTACT 2 CONTACT 1 COIL C NC NO NO C NC CONTACT ALARM INPUT ALARM S2 S1 0V AL NO C NC RL1 L1 CONTACT 2 CONTACT 1 COIL NO C NC NO C NC CONTACT ALARM INPUT ALARM S2 S1 0V AL NO C NC RL1 L1 Rel ay Boar ds Page 100 Hydrosense Water Detection System System Features System Overview A Hydrosense Water Detection System installed in vulnerable areas will continuously monitor the potential hazards around the clock, year in year out. The Hydrosense system has a range of attractive and unobtrusive control panels containing the alarm circuitry, power supply and has the facility for 24 hour battery standby. A Hydrosense System has two methods of leak or moisture detection, Linear or Point detection. Linear detection is provided by Hydrowire moisture sensitive cables which are connected to the control panel via a special Connection Box, by simple two core leader cable making installation quick and inexpensive. Point detection is provided by Floor or Drip Tray Probes also connected to the control panel by simple two core leader cable. The Hydrowire and Probes are continuously monitored. Any disconnection or fault is immediately indicated on the control panel. All monitoring indicators can be repeated to remote repeater panels or via volt free contacts to a BMS. Hydrosense Floor and Drip Tray Mounting Probes The Floor Probe is simply fxed to the foor and adjusted to give the required detection level and connected to the control panel via a simple junction box. The Drip Tray Probe has exactly the same facilities as the foor mount- ing probe but has a bracket for mounting onto the side of an ACU drip tray. Hydrowire Available as standard 5 and 10 metre lengths pre-terminated with DIN plugs, Hydrowire is a fexible cable which will continuously monitor large areas. When even a small amount of water or moisture comes into contact with Hydrowire it will trigger an alarm. Hydrowire will dry out in around 20 minutes for use again. Each zone requires a junction box and an end of line plug. Hydr oSense Linear detection with Hydrowire Point detection with probes Zonal repeat contacts Easy to install Easy to service and maintain Auxillary alarm contacts Monitored alarm outputs Battery backup Remote monitoring Model No. HSCP-S-8 Control Panels Two types of control panel are available. The Hydrosense HSCP is available in 2, 4 and 8 Zone confgurations and the Hydrosense K200000 range for 12 Zones or greater. Flush versions and special fnishes are also available. Repeater panels and ancillary PCBs are available to provide common alarm, common fault, coinci- dence and zonal alarm, VFCs allowing control of sub-systems, graphical mimics and plant, remotely from the main panel over a two wire data bus. Model No. K2024005 St ar Lane, Great Wakering Essex, SS3 0PJ. England Tel: + 44 (0)1702 216999 Fax: + 44 (0)1702 216699 Email: [email protected] Web: www.vimpex.co.uk Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 101 Equipment Product Code K2012003 K2016005 K2024005 HSCP-S-2 HSCP-S-4 HSCP-S-8 HSCPR-S-2 HSCPR-S-4 HSCPR-S-8 K2101 K2102 K2103 K2104 K2105 K2106 K2110 K2111 K2112 S 9615/A F/A/1W Description 12 zone control panel 16 zone control panel 24 zone control panel 2 zone Control Panel 4 zone Control Panel 8 zone Control Panel 2 zone Repeater Panel 4 zone Repeater Panel 8 zone Repeater Panel Floor mounted probe Drip tray probe Remote indicator 5 metre Hydrowire 10 metre Hydrowire Hydrowire connection box End of line plug Leader cable 50M Fixing clips (100) Protection Cage for Floor Mounted Probe Fire-Cryer with water leakage alarm Size Indicator Connection Material 95mm (max.) 80mm (min.)H x 45mmD x 100mmW Green LED 4 pin din fying lead (1 metre) Black nylon - - - - Hydrosense Probes Technical Larger control panels are available on request DS03.14.2011 Model No. K2101 Fully compliant with & tested to BS EN54-2 and BS EN54-4 Available in 2, 4 or 8 zones 2 wire repeaters and ancillary boards Fully programmable using simple menu options For more Features, Product Overview and Technical details see Sigma CP page 48 and Sigma CP-R page 52 HSCP Control Panel Features 12 - 48 zones as standard, more available on request Common fre and fault contacts Remote signal contact and isolate Zonal one man test For more Features, Product Overview and Technical details see Series 3000 page 56 K200000 Control Panel Features Up to 320 LEDs can be controlled Full colour printing Available in a range of standard enclosures to suit any application Bespoke sized units can be made upon request For more Features, Product Overview and Technical details see Sigma Matrix page 60 Matrix Control Panel Features Custom Engineered Solutions Pages 104-109 Custom Engineered Solutions Pages 104-109 The Custom Specialists Our In-house Facilities Page 104-105 Custom Engineered Solutions Page 106-109 Page 104 From the initial design process
To sheet metal fabrication To painting and printing
To panel construction We have full control at every stage allowing us to ofer industry leading delivery times and with quality you can have confdence in. The Custom Specialists Our in-house Facilities Cust om One of the key areas of our business is the design and manufac- ture of bespoke equipment. Kentec has considerable expertise in this feld with over 25 years experience, so you can be certain that all custom engineered product will be designed and built in accordance with your exact requirements and our strict ISO 9001 approved quality procedures. Many in-house facilities are at our disposal: Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 105 All custom built equipment is project managed by our engineering department, using the latest software to produce electrical, mechanical and construction drawings to the customers specifcations. We have a dedicated area for the construction of bespoke product and this was enlarged in the frst quarter of 2011 to allow us to increase our capacity and ofer better service to our customers including factory acceptance testing. Our skilled and dedicated production engineers build each bespoke product to very high standards and to specifcations driven by our customers. Page 106 Custom Engineered Solutions Facilities Expert design advice Mechanical engineering design Artwork and printing design Documentation Electrical engineering Electronic engineering Sheet metal fabrication Powder coat fnishing Metal fnishing Silk screen printing Wire looming Electrical safety testing Technical support Geographical foor plan with LED indications. Analogue Addressable fre control panel with plant controls. Floor standing fre detection control panel with geographical foor plan & plant controls. Cust om Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 107 Unit is then assembled, fully tested and dispatched to address of your choosing! Firemans Override AUTO OFF ON GENERATOR FAULT LWR. GRD. SMOKE CLEAR ASSIST AUTO SHUT SHUT GAS VALVE AUTO OFF ON CLEAR ASSIST AUTO AUTO OFF ON STAIR PRESSURISATION BUILDING SMOKE ATRIUM LOUVRE OPEN WARNING ENCLOSED WITHIN 240V AC SHUT OPEN OPEN Dwg. No: DATE: CLIENT: R.NOTE: CHK. BY DWN. BY REV: SCALE: S.P. 1:1 01 PM BLUE TRIANGLE 1.2.06 R31611/1 K7903-02 Detailed electrical schematic diagrams are produced for production and record purposes Silk screen artworks are generated in house for use in our printing shop From Concept . . . . . . . . To Product Conceptual drawing produced and sent to client for approval On approval, parts are engineered & sent to sheet metal shop for fabrication before going to paint shop (choice of fnishes) Special Firemans Control Panel DS38.03.2009 REV REVSON REL/C NOTE DATE 01 RELEASE TTLE: CLENT: DATE DRAWN W/O No. DRAWN BY CHECKED BY PSU/BATT DRG No. R31611/2 Various 06/02/2006 06/02/2006 N/A K7903-04 'FREMAN'S OVERRDE' CONTROL PANEL ~ nternal Circuit Wiring. Contact 1 02 03 com on 04 auto 06 07 com on 09 auto 10 11 com on 12 auto Off On Lwr. Grd. Smoke Clear Assist Auto Off On Stair Pressurisation Auto 13 14 com on 16 auto 17 18 com on 20 auto Off On Building Smoke Clear Assist Auto Open Atrium Louvre Open Auto 21 22 com open 23 auto Shut Gas Valve Shut Auto 101 102 com shut 103 auto 93 94 +v -v Open LED 201 202 +v -v 203 204 +v -v Shut LED Generator Fault LED Contact 2 Contact 3 240Vac 24Vdc 24Vdc NOTE: Termination Numbers are NOT consecutive. [numbers match that of existing equipment] Lwr. Grd. Smoke Clear Assist Building Smoke Clear Assist Atrium Louvre Open Gas Valve Shut Stair Pressurisation E E E = use 'end stop' as divider Off On Stair Pressurisation Auto Off On Lwr. Grd. Smoke Clear Assist Auto Shut Gas Valve Shut Auto Off On Building Smoke Clear Assist Auto Open Atrium Louvre Open Auto Shut *24Vdc* Open *240Vac* Generator Fault TEST: Switches . Check continuity of all switch positions at the respective DN terminals . a) Stair Pressurisation ~ Contact 1 T02/03 = 'closed' in AUTO only; T02/04 = 'closed' in ON only. Contact 2 T06/07 = 'closed' in AUTO only; T06/08 = 'closed' in ON only. Contact 3 T10/11 = 'closed' in AUTO only; T10/12 = 'closed' in ON only. b) Lwr Gnd Smoke Assist ~ Contact = T13/14 = 'closed' in AUTO only; T13/16 = 'closed' in ON only. c) Building Smoke Assist ~ Contact = T17/18 = 'closed' in AUTO only; T17/20 = 'closed' in ON only. d) Atrium Louvre Open ~ Contact = T21/22 = 'closed' in AUTO only; T21/23 = 'closed' in OPEN only. e) Gas Valve Shut ~ Contact = T101/102 = 'closed' in AUTO only; T101/103 = 'closed' in SHUT only. LED's ... a) apply 24Vdc to T201[+v]/202[-v] ~ 'SHUT' LED shall illuminate. b) apply 24Vdc to T203[+v]/204[-v] ~ 'GENERATOR FAULT' LED shall illuminate. c) apply 240Vac to T93/94 ~ 'OPEN' LED shall illuminate. CONSTRUCTION: Mount length of DN rail c/w terminals across the width of the internal chassis plate .. ENSURE TERMNALS DO NOT CLASH WTH FRONT PANEL EQUPMENT. Mount Rotary Switches & LED's to the front panel . NOTE VOLTAGES ON GREEN LED's. Wire all switches & LED's to DN terminals as detailed ~ use 32/0.2 mm2. Wire Earth terminals to enclosure earth studs & ensure that lid, box, chassis & terminals are all bonded together. Fit 240Vac Warning Labels to the rear of door & to chassis plate. Fit Lockable Vision Window to overall enclosure. DRAWING No. PROJECT: CLIENT: REV DWN BY: CHK BY: SCALE: DATE: REV REVISION REL/C.NOTE No. DATE W/O No. NOTES: CL N D4 WELD & FULLY CLEAN CORNERS, SURFACE TO BE FLAT, SMOOTH & SQUARE BEFORE FINISHING UNLESS OTHERWISE STATED ALL DIMENSIONS IN MILLIMETRES, TOLERANCES AS FOLLOWS: x.x = +- 0.3 x.xx = +- 0.05 E CL L L L L L L L L MATERIAL: 18SWG MILD STEEL FINISH: EPC - WHITE 01 FOR PRODUCTION R31611/1 1.2.06 SPECIAL FIREMANS CONTROL PANEL C/WVISION WINDOWCOVER INNER LID DETAIL TRIANGLE INTERGRATED FIRE 1.2.06 31611 NTS PM K7903-03 01 355.0 500.0 45.0 35.0 12.0 18.5 7.0 97.5 90.0 90.0 90.0 30.0 130.0 80.0 DATE: SCALE: W/O No. DRAWING No. REV: CHK BY: PROJECT: NOTES: R./C. NOTE No. DATE REV REVISION DWN BY: CLIENT: A K7903-01 C NTS PM MATERIAL: FINISH: Firemans Override AUTO OFF ON GENERATOR FAULT LWR. GRD. SMOKE CLEAR ASSIST AUTO SHUT SHUT GAS VALVE AUTO OFF ON CLEAR ASSIST AUTO AUTO OFF ON STAIR PRESSURISATION BUILDING SMOKE ATRIUM LOUVRE OPEN WARNING ENCLOSED WITHIN 240V AC 18SWG MILD STEEL EPC - WHITE FOR APPROVAL 24.1.06 FASCIA DRAWING TRIANGLE INTERGRATED FIRE 24.1.06 31611 SCREENING - BLUE SHUT OPEN OPEN B 26.1.06 FOR INFORMATION C FOR INFORMATION 1.2.06 SPECIAL FIREMANS CONTROL PANEL C/WVISION WINDOWCOVER 398.0 35.0 543.0 130.0 YOUR LOGO Page 108 Custom Engineered Solutions Applications Smoke Damper Control Panels Composite Relay Units (c/w Resettable Latching Relay & Firemans Switch) Sprinkler System Indicator Panels Pump Status Indicator Panels Firemans Control Switch Panels Analogue/Addressable Interface Units (with or without integral PSU) Mimic Repeat Indicator Panels (perspex/metal, metal only, black & white or multi-coloured) . . . . choose your fnish . . . . choose your colour . . . . choose your specifcation Cust om Specifcation The manufacturer reserves the right to amend specifcations without prior notice Page 109 Floor standing triple width enclosure with glazed doors. Unit features geographical foor plan layouts and 3rd party voice alert system. Bespoke Fire Alarm Control Panel housed in a special compact enclosure to suit customers building layout. Are you In the loop? Kentecs popular In the loop e-mail bulletin has now been a regular feature for over six years, providing articles on a variety of subjects including news about new products, enhancements to existing products and many other subjects relating to our products and services along with general industry information. If you would like to be In the loop you or a colleague can register for free on our web site by visiting www.kentec.co.uk For the more technical user we also produce the technically biased In the technical loop e-mail bulletin, which can also be subscribed to by visiting www.kentec.co.uk For back issues of either publication please visit our web site. Enhanced Training from Kentec Due to the success of the Regional Syncro Training Seminars that have been running for the past two years throughout the UK, we have now extended this to 2011. Each course is split over two days. The rst day is the Syncro Foundation Course and the second day builds on this by providing hands-on training on networking, expansion cards and conguring complex systems. We can also provide product training on the Guide graphics system and our Extinguishing control panels, either at our oces or at customer locations in the UK and Internationally by prior arrangement. For more information on training or to register, please visit our web site www.kentec.co.uk and click on the Training tab. Alternatively please email [email protected]. Syncro ASM analogue addressable, re detection systems are available from Kentec Electronics Limited, for a wide range of marine re alarm system applications. Syncro ASM re control panels can be networked to provide scalable re alarm systems, suitable for many classes of vessel. For more information please visit our web site www.kentec.co.uk and click on the Marine tab. Alternatively please contact our sales department on 01322 222121. Marine approvals for Syncro ASM 0086/11 How to nd us? Train The nearest station is Dartford which is served by trains from Charing Cross, London Victoria. Journey time approximately 40 minutes from Central London. From M25 Clockwise Leave M25 at Junction1b (signed Dartford & A225). At the roundabout, take the third exit onto the A225. Continue straight across the next roundabout and continue to a set of trac lights. Turn left at lights onto Darenth Road. Turn right onto Powder Mill Lane. Turn left into Fawkes Avenue. We are located on the right. From M25 Anti-Clockwise Leave M25 at Junction 2 (signed London, Canterbury, A2 (M2) & Dartford (A225). At the roundabout, take second exit and follow slip road towards Junction 1b, At roundabout take rst exit onto the A225. Continue straight across the next roundabout and continue to a set of trac lights. Turn left at lights onto Darenth Road. Turn right onto Powder Mill Lane. Turn left into Fawkes Avenue. We are located on the right. Are you In the loop? Kentecs popular In the loop e-mail bulletin has now been a regular feature for over six years, providing articles on a variety of subjects including news about new products, enhancements to existing products and many other subjects relating to our products and services along with general industry information. If you would like to be In the loop you or a colleague can register for free on our web site by visiting www.kentec.co.uk For the more technical user we also produce the technically biased In the technical loop e-mail bulletin, which can also be subscribed to by visiting www.kentec.co.uk For back issues of either publication please visit our web site. Enhanced Training from Kentec Due to the success of the Regional Syncro Training Seminars that have been running for the past two years throughout the UK, we have now extended this to 2011. Each course is split over two days. The rst day is the Syncro Foundation Course and the second day builds on this by providing hands-on training on networking, expansion cards and conguring complex systems. We can also provide product training on the Guide graphics system and our Extinguishing control panels, either at our oces or at customer locations in the UK and Internationally by prior arrangement. For more information on training or to register, please visit our web site www.kentec.co.uk and click on the Training tab. Alternatively please email [email protected]. Syncro ASM analogue addressable, re detection systems are available from Kentec Electronics Limited, for a wide range of marine re alarm system applications. Syncro ASM re control panels can be networked to provide scalable re alarm systems, suitable for many classes of vessel. For more information please visit our web site www.kentec.co.uk and click on the Marine tab. Alternatively please contact our sales department on 01322 222121. Marine approvals for Syncro ASM 0086/11 How to nd us? Train The nearest station is Dartford which is served by trains from Charing Cross, London Victoria. Journey time approximately 40 minutes from Central London. From M25 Clockwise Leave M25 at Junction1b (signed Dartford & A225). At the roundabout, take the third exit onto the A225. Continue straight across the next roundabout and continue to a set of trac lights. Turn left at lights onto Darenth Road. Turn right onto Powder Mill Lane. Turn left into Fawkes Avenue. We are located on the right. From M25 Anti-Clockwise Leave M25 at Junction 2 (signed London, Canterbury, A2 (M2) & Dartford (A225). At the roundabout, take second exit and follow slip road towards Junction 1b, At roundabout take rst exit onto the A225. Continue straight across the next roundabout and continue to a set of trac lights. Turn left at lights onto Darenth Road. Turn right onto Powder Mill Lane. Turn left into Fawkes Avenue. We are located on the right.