This document provides instructions for connecting OMRON CJ/CS/CP PLCs to an HMI. It outlines the recommended HMI settings for communication with the PLC over RS232 or RS485 and lists the device address formats and ranges supported. It also describes how to export tags from the PLC programming software and import them into the HMI project to map addresses. Wiring diagrams are included for RS232 and RS485 4W connections.

Uploaded by

Vu Minh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
146 views4 pages

Omron CJ CS CP

This document provides instructions for connecting OMRON CJ/CS/CP PLCs to an HMI. It outlines the recommended HMI settings for communication with the PLC over RS232 or RS485 and lists the device address formats and ranges supported. It also describes how to export tags from the PLC programming software and import them into the HMI project to map addresses. Wiring diagrams are included for RS232 and RS485 4W connections.

Uploaded by

Vu Minh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

PLC Connection Guide

OMRON CJ/CS/CP
Supported Series: OMRON CP1E, CP2E, CP1L, CP1H, CJ1M, CJ2M, CJ1H, CJM1G,
CS1H and CS1G. (Host Link Protocol FINS command), this driver supports Extend
Addressing Mode.
Website: http://www.omron.com/

HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON CJ/CS/CP
PLC I/F RS232 RS232, RS422, RS485
Baud rate 9600 9600~115200
Data bits 7 7 or 8
Parity Even Even, Odd, None
Stop bits 2 1 or 2
PLC sta. no. 0 0-31 Host Link Station No.

Online simulator YES Extend address YES


Broadcast NO mode
command
*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

PLC Setting:
Communication Host Link Protocol
mode

Device Address:
Bit/Word Device type Format Range Memo
B CIO_Bit DDDDDdd 0 ~ 3276715 Channel I/O (CIO)
B W_Bit DDDDDdd 0 ~ 3276715 Work Area (WR)
B H_Bit DDDDDdd 0 ~ 3276715 Holding Area (HR)
B D_Bit DDDDDdd 0 ~ 3276715 Data Memory (DM)
B A_Bit DDDDDdd 0 ~ 3276715 Auxiliary Relay (AR)
B T_Bit DDDDDdd 0 ~ 3276715 Timer (TIM)
B C_Bit DDDDDdd 0 ~ 3276715 Counter (CNT)
B C_flag DDDD 0 ~ 4095
PLC Connection Guide
Bit/Word Device type Format Range Memo
B T_flag DDDD 0 ~ 4095
B LR_Bit DDDdd 0 ~ 19915
B EM0_Bit ~ DDDDDdd 0 ~3276715 Extend Memory
EM18_Bit

W T DDDDD 0 ~ 32767 Timer (TIM)


W H DDDDD 0 ~ 32767 Holding Area (HR)
W D DDDDD 0 ~ 32767 Data Memory (DM)
W A DDDDD 0 ~ 32767 Auxiliary Relay (AR)
W W DDDDD 0 ~ 32767 Work Area (WR)
W C DDDDD 0 ~ 32767 Counter (CNT)
W CIO DDDDD 0 ~ 32767 Channel I/O (CIO)
W EM0 ~ EM18 DDDDD 0 ~ 32767 Extend Memory
W LR DDD 0 ~ 199
PLC Connection Guide

Import Tags:
1. Export the *.cxr file in cx-programmer -> variables
[Important]: Only addresses with tag name can be imported, and address type is required

2. Open EasyBuilder Pro, and set the drive parameters in [System Parameter Settings],
click [Import Tags].

3. Select *.cxr file

4. Check the TAG that the project needs to use.

5. Imported tag information successfully.


PLC Connection Guide

Wiring Diagram:
Diagram 1
RS-232
The serial port pin assignments may vary between HMI models, please click the following
link for more information.

HMI PLC

RS232 9P
Link
D-Sub Male

Rx 2 SD

Tx 3 RD

GND 9 GND

4 RS

5 CS

Diagram 2
RS-485 4W (CP1H/CP1L CP1W-CIF11 RS485 4W : 9P D-Sub to Termainals)
The serial port pin assignments may vary between HMI models, please click the following
link for more information.

HMI PLC

CP1W-CIF11
Link
RS485 4W Terminal

Rx- SDA

RX+ SDB

Tx- RDA

Tx+ RDB

GND FG
CP1W-CIF11: SW1 ON, others OFF.