Ekdw1208 BD
Ekdw1208 BD
Units
Horizontal Unit
Model: EKDW020H~EKDW450H
Air flow: 2000m3/h ~ 45000m3/h
Vertical Unit
Model: EKDW040V ~ EKDW450V
Air flow: 4000m3/h ~ 45000m3/h
Air Jet Unit
Model: EKDW020S ~ EKDW120S
Air flow: 2000m3/h ~ 12000m3/h
Table Of Contents
Company Profile..............................................................................................................3
Overview.........................................................................................................................4
Nomenclature .................................................................................................................6
Specifications..................................................................................................................7
Unit Dimensions..............................................................................................................12
Installation ......................................................................................................................19
Optional Parts . ...............................................................................................................20
Quick Reference for Maximum Total External Pressure . ...............................................22
Measurement Conversion Table . ...................................................................................23
EUROKLIMAT possesses the most advanced technologies and manufacturing facilities/processes in the air
conditioning sector and has been forging ahead at the forefront of air conditioning products and technologies for
more than 40 years by enterprising innovation.
Launched by EK to meet market demand, EKDW series air handling units feature joggle structures and foamed
polyurethane plates for effective heat preservation and service life enhancement. Units of this series have 40
models and 560 standard specifications available for your choice, and can be widely used in central air conditioning
systems of hotels, shopping malls, hospitals, office buildings etc.
Customers
Design
EKDW series units feature a high total external pressure, large cooling capacity, compact
and simple structure and easy maintenance.
Easy maintenance: the bearing of the fan motor needs no lubricant refill.
Low sound: a quality fan motor with a low rev provides a large air flow with a low De
operation sound.
Clean and environment friendly: A nylon filter with primary efficiency is installed at the air
inlet. Customers can also choose to install a plate or bag filter and sterilization apparatus
(aluminum screen filter, electric cleaner and photocatalyst are available).
A high-efficiency forward-pitched fan with multiple wings provides a large air flow and
stable performance with a low operation sound. The bearing of the fan needs no lubricant
Com enient
refill, thus saving maintenance cost.
Con
A 30mm-thick strong cabinet wall made of foamed polyurethane ensures effective heat
pact
v
4 preservation and a long service life for the entire unit.
Mechanically expanded copper tubes with a thin wall and a new type of optimized wavy
anC
Com enient
fins produced using leading-edge manufacturing facilities ensure optimal heat exchange
d onv
efficiency and pave the way for a high EER. The coils feature multiple specifications and Customers
pact
different types of loops to work in concert with various other sections.
EKDW features a professional air jet solution that is suitable for areas that is super large
and
or high, areas where no air duct is installed, areas where air ducts cannot be installed
and areas where conditioned air cannot be supplied to the bottom of a building from the Customers
rooftop. Such areas include air ports, bus stations, exhibition centers, factory plants,
supermarkets, and lobbies, front doors and shafts of hotels.
EKDW air jet units use high-performance ball-shaped sprayer as the air outlet, and can
supply air over a maximum distance of 40 meters. The units can supply conditioned air
over a long distance without air duct, thus saving space and operation cost and lowering
the requirement on floor distance.
EKDW air jet units can supply air 360° and the air supply direction can be manually
adjusted. The air is similar to natural air and does not directly blow on people.
Conditioned air is supplied to specified locations in the most comfortable way.
Design
All-round standard specifications for water flow, water
pressure drop, etc
All-purpose secondary design software
Complete design flow for non-standard units to
expand application scope
E
En fficie
erg nt
y S and
av
ing
Services Agents
Nomenclature
6
Flexible and convenient model selection software
EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
020H 030H 040H 050H 060H 070H 080H 090H 100H 120H 135H
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 9000 10000 12000 13500
I 80 80 80 80 80 80 80 80 ~ ~ ~
External
II 150 150 150 150 150 150 150 150 150 150 150
residual
III 220 220 220 220 220 220 220 220 220 220 220
pressure (Pa)
IV ~ ~ ~ 300 300 300 300 300 300 300 300
4 rows of coils (return air) 12 17 24 31 38 44 51 56 63 74 81
Nominal
4 rows of coils (fresh air) 29 42 57 69 83 94 113 127 142 169 175
cooling
6 rows of coils (return air) 15 23 33 39 48 55 63 72 78 94 107
capacity (kW)
6 rows of coils (fresh air) 35 53 69 88 105 122 137 155 173 208 237
4 rows of coils (return air) 19 30 41 50 61 71 83 93 103 122 140
Nominal
4 rows of coils (fresh air) 33 49 66 82 99 115 133 148 161 197 220
heating
6 rows of coils (return air) 23 36 48 60 72 84 96 108 120 144 162
capacity (kW)
6 rows of coils (fresh air) 38 57 77 95 114 132 150 169 188 224 255
4 rows of coils (return air) 0.57 0.81 1.14 1.48 1.81 2.10 2.43 2.67 3.00 3.52 3.86
Nominal
4 rows of coils (fresh air) 1.38 2.00 2.71 3.29 3.95 4.48 5.38 6.05 6.76 8.05 8.33
cooling water
6 rows of coils (return air) 0.71 1.10 1.57 1.86 2.29 2.62 3.00 3.43 3.71 4.48 5.10
flow (L/S)
6 rows of coils (fresh air) 1.67 2.52 3.29 4.19 5.00 5.81 6.52 7.38 8.24 9.90 11.29
4 rows of coils (return air) 0.43 0.68 0.92 1.13 1.37 1.71 1.87 2.24 2.32 2.75 3.37
Nominal
4 rows of coils (fresh air) 0.74 1.10 1.49 1.85 2.23 2.77 2.99 3.56 3.62 4.44 5.29
heating water
6 rows of coils (return air) 0.52 0.81 1.08 1.35 1.62 2.02 2.16 2.60 2.70 3.24 3.90
flow (L/S)
6 rows of coils (fresh air) 0.86 1.28 1.73 2.14 2.57 3.17 3.38 4.06 4.23 5.04 6.13
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6 7
Coil Size of inlet/outlet water
R1-1/2 R1-1/2 R1-1/2 R1-1/2 R1-1/2 R2 R2 R2 R2 R2 R2
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Downward horizontal/top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I 0.37(0.37) 0.55(0.75) 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.1) 1.1(1.5) 1.5(1.5) ~ ~ ~
Motor
Motor power II 0.55(0.55) 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.5) 1.1(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 3.0(3.0) 3.0(3.0)
(kW) III 0.55(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.1) 1.5(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 3.0(3.0) 3.0(4.0)
IV ~ ~ ~ 1.1(1.5) 1.5(2.2) 1.5(2.2) 2.2(2.2) 2.2(3.0) 2.2(3.0) 3.0(3.0) 4.0(4.0)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
Cabinet Type 30mm-thick double-layer plates filled with polyurethane material foamed under high pressure for heat preservation
Length (mm) 820 950 1010 1130 1260 1300 1500 1620 1650 1750 1940
Unit
Width (mm) 950 950 1050 1050 1050 1100 1100 1100 1050 1050 1050
Dimensions
Height (mm) 630 650 755 755 805 830 830 830 890 950 950
4 rows of coils (kg) 127 141 169 184 209 233 266 283 348 367 393
Unit weight
6 rows of coils (kg) 131 147 176 192 219 245 280 298 366 388 416
Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.
EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
150H 180H 200H 220H 250H 270H 300H 350H 400H 450H
Nominal air flow (m3/h) 15000 18000 20000 22000 25000 27000 30000 35000 40000 45000
I ~ ~ ~ ~ ~ ~ 220 220 220 220
External II 150 150 150 150 150 150 300 300 300 300
residual III 220 220 220 220 220 220 400 400 400 400
pressure (Pa) IV 300 300 300 300 300 300 500 500 500 500
V ~ ~ ~ ~ ~ ~ ~ 600 600 600
4 rows of coils (return air) 97 114 123 134 155 165 191 220 256 286
Nominal
4 rows of coils (fresh air) 211 248 270 290 337 361 418 481 558 620
cooling
6 rows of coils (return air) 120 147 160 175 199 218 239 276 318 354
capacity (kW)
6 rows of coils (fresh air) 268 321 347 375 434 459 526 596 686 754
4 rows of coils (return air) 153 186 202 225 253 277 310 358 408 460
Nominal
4 rows of coils (fresh air) 246 296 326 355 406 439 502 574 656 730
heating
6 rows of coils (return air) 183 215 238 264 298 312 366 424 484 542
capacity (kW)
6 rows of coils (fresh air) 287 338 375 412 469 507 574 666 766 854
4 rows of coils (return air) 4.62 5.43 5.86 6.38 7.38 7.86 9.10 10.48 12.19 13.62
Nominal
4 rows of coils (fresh air) 10.05 11.81 12.86 13.81 16.05 17.19 19.90 22.90 26.57 29.52
cooling water
6 rows of coils (return air) 5.71 7.00 7.62 8.33 9.48 10.38 11.38 13.14 15.14 16.86
flow (L/S)
6 rows of coils (fresh air) 12.76 15.29 16.52 17.86 20.67 21.86 25.05 28.38 32.67 35.90
4 rows of coils (return air) 3.44 4.19 4.55 5.07 5.70 6.24 7.48 8.64 9.84 11.10
Nominal
4 rows of coils (fresh air) 5.54 6.66 7.34 7.99 9.14 9.88 12.11 13.85 15.82 17.61
heating water
6 rows of coils (return air) 4.12 4.84 5.36 5.94 6.71 7.02 8.83 10.23 11.68 13.07
flow (L/S)
6 rows of coils (fresh air) 6.46 7.61 9.28 9.28 10.56 11.42 13.85 16.07 18.48 20.60
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
8 Working pressure (MPa) 1.6
Coil Size of inlet/outlet water
R2-1/2 R2-1/2 R2-1/2 R3 R3 R3 R3 R3 R3 R3
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Downward horizontal/top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I ~ ~ ~ ~ ~ ~ 7.5(7.5) 7.5(11) 11(11) 11(11)
Motor II 3.0(3.0) 4.0(4.0) 4.0(4.0) 4.0(5.5) 4.0(5.5) 5.5(5.5) 7.5(7.5) 11(11) 11(11) 11(15)
Motor power
III 3.0(4.0) 4.0(4.0) 4.0(5.5) 5.5(5.5) 5.5(5.5) 5.5(7.5) 11(11) 11(11) 15(15) 15(15)
(kW)
IV 4.0(4.0) 4.0(5.5) 5.5(5.5) 5.5(7.5) 5.5(7.5) 7.5(7.5) 11(11) 11(15) 15(15) 15(15)
V ~ ~ ~ ~ ~ ~ ~ 15(15) 15(15) 15(18.5)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
Cabinet Type 30mm-thick double-layer plates filled with polyurethane material foamed under high pressure for heat preservation
Length (mm) 2010 2060 2250 2300 2470 2620 2770 2770 2930 2930
Unit
Width (mm) 1090 1090 1250 1250 1250 1250 1650 1650 1650 1810
Dimensions
Height (mm) 1020 1140 1140 1200 1270 1270 1410 1570 1730 1890
4 rows of coils (kg) 447 477 565 589 703 722 972 1047 1196 1294
Unit weight
6 rows of coils (kg) 472 507 598 625 744 767 1025 1106 1266 1371
Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.
EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
040V 050V 060V 070V 080V 090V 100V 120V 135V 150V
Nominal air flow (m3/h) 4000 5000 6000 7000 8000 9000 10000 12000 13500 15000
External I 80 80 80 80 80 80 80 ~ ~ ~
residual II 150 150 150 150 150 150 150 150 150 150
pressure III 220 220 220 220 220 220 220 220 220 220
(Pa) IV 300 300 300 300 300 300 300 300 300 300
Nominal 4 rows of coils (return air) 23 30 37 44 50 56.3 63 74 84 95
cooling 4 rows of coils (fresh air) 55 70 83 94 111 121 137 167 190 202
capacity 6 rows of coils (return air) 32 40 47 53 62 69 78 96 112 120
(kW) 6 rows of coils (fresh air) 70 86 103 122 137 156 172 206 230 264
Nominal 4 rows of coils (return air) 40 50 60 71 82 91 102 122 139 155
heating 4 rows of coils (fresh air) 65 82 98 115 129 148 164 197 222 246
capacity 6 rows of coils (return air) 48 60 72 84 97 108 121 142 161 178
(kW) 6 rows of coils (fresh air) 77 94 113 132 152 169 191 224 257 280
Nominal 4 rows of coils (return air) 1.10 1.43 1.76 2.10 2.80 2.68 3.00 3.52 4.00 4.52
cooling 4 rows of coils (fresh air) 2.62 3.33 3.95 4.48 5.29 5.76 6.52 7.95 9.05 9.62
water flow 6 rows of coils (return air) 1.52 1.90 2.24 2.52 2.95 3.29 3.71 4.57 5.33 5.71
(L/S) 6 rows of coils (fresh air) 3.33 4.10 4.90 5.81 6.52 7.43 8.19 9.81 10.95 12.57
Nominal 4 rows of coils (return air) 0.96 1.21 1.45 1.71 1.98 2.19 2.46 2.94 3.34 3.74
heating 4 rows of coils (fresh air) 1.57 1.98 2.36 2.77 3.11 3.56 3.96 4.75 5.34 5.93
water flow 6 rows of coils (return air) 1.16 1.45 1.74 2.02 2.34 2.60 2.92 3.43 3.87 4.29
(L/S) 6 rows of coils (fresh air) 1.86 2.27 2.73 3.17 3.67 4.06 4.61 5.40 6.18 6.75
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6 9
Coil Size of inlet/outlet water
R 1-1/2 R 1-1/2 R 1-1/2 R2 R2 R2 R2 R2 R2 R 2-1/2
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.1) 1.1(1.5) 1.5(1.5) 1.5(2.2) ~ ~ ~
Motor Motor
II 0.75(1.1) 1.1(1.1) 1.1(1.5) 1.1(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 2.2(3.0) 3.0(3.0)
power
III 1.1(1.1) 1.1(1.1) 1.5(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 2.2(3.0) 3.0(3.0) 3.0(4.0)
(kW)
IV 1.1(1.5) 1.1(1.5) 1.5(2.2) 1.5(2.2) 2.2(2.2) 2.2(3.0) 2.2(3.0) 3.0(3.0) 3.0(4.0) 4.0(4.0)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
30mm-thick double-layer plates filled with polyurethane material foamed under high pressure for heat
Cabinet Type
preservation
Length (mm) 920 1030 1200 1230 1280 1290 1330 1440 1580 1870
Unit
Width (mm) 650 650 650 810 810 810 900 900 900 810
Dimensions
Height (mm) 1270 1335 1385 1490 1550 1610 1800 1860 1860 1680
4 rows of coils (kg) 172 203 236 274 306 323 386 423 435 482
Unit weight
6 rows of coils (kg) 179 211 246 286 321 339 404 444 458 507
Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.
Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.
EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
020S 030S 040S 050S 060S 070S 080H 090S 100S 120S
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 9000 10000 12000
Nominal 4 rows of coils (return air) 12 17 24 31 38 44 51 56 63 74
cooling 4 rows of coils (fresh air) 29 42 57 69 83 94 113 127 142 169
capacity 6 rows of coils (return air) 15 23 33 39 48 55 63 72 78 94
(kW) 6 rows of coils (fresh air) 35 53 69 88 105 122 137 155 173 208
Nominal 4 rows of coils (return air) 19 30 41 50 61 71 83 93 103 122
heating 4 rows of coils (fresh air) 33 49 66 82 99 115 133 148 161 197
capacity 6 rows of coils (return air) 23 36 48 60 72 84 96 108 120 144
(kW) 6 rows of coils (fresh air) 38 57 77 95 114 132 150 169 188 224
Nominal 4 rows of coils (return air) 0.57 0.81 1.14 1.48 1.81 2.10 2.43 2.67 3.00 3.52
cooling 4 rows of coils (fresh air) 1.38 2.00 2.71 3.29 3.95 4.48 5.38 6.05 6.76 8.05
water flow 6 rows of coils (return air) 0.71 1.10 1.57 1.86 2.29 2.62 3.00 3.43 3.71 4.48
(L/S) 6 rows of coils (fresh air) 1.67 2.52 3.29 4.19 5.00 5.81 6.52 7.38 8.24 9.90
Nominal 4 rows of coils (return air) 0.43 0.68 0.92 1.13 1.37 1.71 1.87 2.24 2.32 2.75
heating 4 rows of coils (fresh air) 0.74 1.10 1.49 1.85 2.23 2.77 2.99 3.56 3.62 4.44
water flow 6 rows of coils (return air) 0.52 0.81 1.08 1.35 1.62 2.02 2.16 2.60 2.70 3.24
(L/S) 6 rows of coils (fresh air) 0.86 1.28 1.73 2.14 2.57 3.17 3.38 4.06 4.23 5.04
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6
Coil Size of inlet/outlet water
R 1-1/2 R 1-1/2 R 1-1/2 R 1-1/2 R 1-1/2 R2 R2 R2 R2 R2
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
11
Fanning direction Downward horizontal/top
I 10~20m(1) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) ~ ~
4 rows of heat
II 20~30m(1) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2)
Rang exchangers
III ~ ~ ~ 30~40m(1) 30~40m(2) 30~40m(1) 30~40m(1) 30~40m(1) 30~40m(2) 30~40m(2)
(number of
I 10~20m(1) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) ~ ~
nozzles) 6 rows of heat
II 20~30m(1) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2)
exchangers
III ~ ~ ~ 30~40m(1) 30~40m(2) 30~40m(1) 30~40m(1) 30~40m(1) 30~40m(2) 30~40m(2)
I 0.55 0.75 0.75 1.1 1.5 1.5 1.5 2.2 ~ ~
4 rows of heat
II 0.75 1.1 1.1 1.5 2.2 2.2 2.2 3.0 3.0 4.0
exchangers
Motor III ~ ~ ~ 2.2 3.0 3.0 3.0 4.0 5.5 5.5
power (kW) I 0.75 1.1 1.1 1.1 1.5 1.5 1.5 3.0 ~ ~
6 rows of heat
II 1.1 1.5 1.5 1.5 2.2 2.2 2.2 3 3.0 4.0
exchangers
III ~ ~ ~ 2.2 3.0 3.0 3.0 4.0 5.5 5.5
Type Thickness (mm)
Filter
Thickness (mm) 8/21
30mm-thick double-layer plates filled with polyurethane material foamed under
Cabinet Type
high pressure for heat preservation
Length (mm) 820 950 1010 1130 1260 1300 1500 1620 1650 1750
Unit
Width (mm) 1450 1450 1550 1550 1550 1600 1600 1600 1550 1550
Dimensions
Height (mm) 630 650 755 755 805 830 830 830 890 950
Unit weight 4 rows of heat exchangers 135 149 179 195 222 247 282 300 369 389
(kg) 6 rows of heat exchangers 139 156 187 204 232 260 297 316 388 411
Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.
W
N
Hoist hole: 4-ɸ20
E A
L
M
K
R
chilled water
B
Q
J
80
P
Drain pipe C for condensate water
12
W
N
L
M
K
B S E A
Outlet pipe D for chilled water
W
N
Hoist hole: 4-ɸ20
E A T A
L
M
K
R
G
chilled water
B
Q
J
80
13
W
N
L
M
K
B S E A T A
Outlet pipe D for chilled water
H
G
Inlet/outlet Drain
Size of return Size of air Size of connection pipe for pipe for
Dimensions Length Width Height Hoist size
air inlet supply inlet pipes chilled condensate
water water
Model L W H F G A B K M N J S E T P Q R D C
EKDW100H 1650 1050 810 1595 755 312 344 1830 1770 983 101 217 177 241 55 131 561 R2 R1-1/4
EKDW120H 1750 1050 870 1695 815 312 344 1930 1870 983 101 217 252 241 55 131 625 R2 R1-1/4
EKDW135H 1940 1050 870 1885 815 398 344 2120 2060 983 101 218 215 321 55 131 625 R2 R1-1/4
EKDW150H 2010 1090 940 1955 885 375 407 2190 2130 1023 101 258 244 292 55 139 672 R2-1/2 R1-1/4
EKDW180H 2060 1090 1060 2005 1005 375 407 2240 2180 1023 101 248 294 292 55 139 799 R2-1/2 R1-1/4
EKDW200H 2250 1250 1060 2195 1005 432 478 2430 2370 1183 107 309 298 341 55 139 799 R2-1/2 R1-1/4
EKDW220H 2300 1250 1120 2245 1065 432 478 2480 2420 1183 106 309 298 341 55 145 850 R3 R1-1/4
EKDW250H 2470 1250 1190 2415 1135 559 481 2650 2590 1183 106 309 156 456 55 145 913 R3 R1-1/4
EKDW270H 2620 1250 1190 2565 1135 559 481 2800 2740 1183 106 309 307 456 55 145 913 R3 R1-1/4
W
E A T A
L
80
J
P
Drain pipe C for condensate water
F
14
W
B S E A T A
Outlet pipe D for chilled water
Note: "D" in the above figure is the diameter of inlet/out water pipe for units (EKDW020H ~ EKDW350H) with a single coil;
For units (EKDW400H ~ EKDW450H) with double coils, there are two sets of inlet/outlet water pipes with a diameter of "D".
B S E A
P
80
B S A T A E
P
80
Measurement: mm
B S A T A E
chilled water
G
Measurement: mm
Size of return Size of air Size of connection Inlet/outlet pipe for Drain pipe for
Dimensions Length Width Height Hoist size
air inlet supply inlet pipes chilled water condensate water
Model L W H F G A B E T S P D C
EDW300V 2770 1010 2190 2710 1270 559 481 262 456 206 100 R3 R1-1/4
EDW350V 2770 1010 2510 2710 1405 572 572 274 446 132 100 R3 R1-1/4
EDW400V 2930 1010 2670 2870 1565 572 572 354 446 132 100 R3 R1-1/4
EDW450V 3090 1170 2730 3030 1565 638 638 353 500 197 100 R3 R1-1/4
Note: "D" in the above figure is the diameter of inlet/out water pipe for units (EKDW040V ~ EKDW350V) with a single coil;
For units (EKDW400V ~ EKDW450V) with double coils, there are two sets of inlet/outlet water pipes with a diameter of "D".
F F
N
W
W
L
L
M
M
K K
18
G
H
Q
P
80
chilled water
Drain pipe C for
condensate water
Measurement: mm
■ Please specify the model, specification, quantity, working ■ How to Tell Right-oriented Connection Pipes from Left-
conditions of the unit (s) and any special requirements in oriented Ones
detail while placing orders. Please specify the orientation of inlet/outlet water pipes
■ Besides standard total external pressure, the total external while placing orders. When you face toward the air outlet
pressure of this series of units can also be customized (counter air current), connection pipes on the left are left
as per requirements from customers. Please specify your oriented and vice versa, as shown in Figure 1 ~ 3. For
requirement on total external pressure while placing orders. cooling water pipes, L represents "left" and R represents
"right". The condensate water pipes are on the same side
with cooling water pipes.
Left connection pipe Left connection pipe
Figure 1 EKDW-H horizontal units with horizontal air supply Figure 2 EKDW-H horizontal units with top air supply
Inlet air
During unit installation, a proper water seal is needed to ensure smooth discharge of condensate water, as shown in Figure 4.
■ A high-voltage static dedusting technology is applied to effectively filter all sorts of dust, bacteria,
virus and harmful gas;
■ Multi-layered filtering provides multi-layered protection;
■ A modular design can meet various air flow requirements.
■ The sterilamp can effectively dampening the growth of bacteria and mildew and thereby
eliminating odor caused by such growth;
■ The photocatalyst itself is stable and unconsumed, and therefore can be effective for a long
time;
■ The sterilamp can effectively degrade contaminants such as formaldehyde, toluene and
ammonia into harmless and nontoxic materials, and does not cause secondary contamination.
Water distributor
Humidifying material
Tap water purified by the solenoid valve flows directly into the water distributor at the top of the Humidifying air Inlet air
humidifier through water pipes and then flows down to wet the wet film under the pull of gravity.
Residual water collected by the water collector flows into the sewage through the drainpipe (water
will not be recycled). Hot air passing through the wet film is dampened and cooled (equal enthalpy
wetting). During this course, some water in the wet film is evaporated without consuming additional
energy. The work principle of wet film humidifier with direct water flow is shown in the figure on the
right side.
Water discharge
office buildings.
Fresh air handling unit & fan coil system consists of two components, namely
the indoor fan coil unit which is used for indoor cooling/heating and the fresh Fresh Air Handling
Fresh Air Handling
Unit PAU Indoor environment
Indoor environment
air handling unit which is used for pre-cooling and preheating of outdoor fresh Fresh Air Handling Unit PAU
Unit PAU Type b Indoor environment
air (only processes fresh air). Some fresh air handling units can be equipped Type b
Type b
with humidifiers and air purification/sterilization apparatus to meet high
requirements on indoor air quality.
Fresh air can be supplied in two ways, namely direct supply which directly Fresh Air Handling
Fresh Air Handling
supplies processed fresh air into rooms (a in the figure on the right) and Fresh Air Handling Unit PAU
Unit PAU
indirect supply which supplies processed fresh air into rooms through terminal Unit PAU
Type a
Type a
Dual Pipe Proportional Integral Control for Fresh Air Handling Units
Code Description
TC-1 Proportional integral temperature controller
TV-1 Electric 2-way valve 21
DPS-1 Differential pressure switch Connected to alarm
Closed
Open
Water supply
Return water
Connected to alarm
Closed
Open
Water
Return
supply
Work Principle:
This air supply temperature control system consists of the temperature sensor Blue
TE-1, the proportional integral temperature controller TC-1 and the electric 2-way Blue
Red
Red
Blue
valve TV-1. TE-1 is installed in the air supply duct and used to send temperature Red Power supply
Power supply
signals to TC-1 which compares the signal with the set value and outputs signals to Bluesupply Yellow
Power
Blue Yellow
continuously modulate the openness of TV-1 so that the temperature detected by Blue Yellow
EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
040V 050V 060V 070V 080V 090V 100V 120V 135V 150V 180V 200V 220V 250V 270V
22 3
Nominal air flow (m /h) 4000 5000 6000 7000 8000 9000 10000 12000 13500 15000 18000 20000 22000 25000 27000
Rows of coils Motor power (kW) Total external pressure (Pa)
0.37
0.55
0.75 180 115
1.1 360 315 165 185 100
1.5 520 495 325 345 250 185 125
4 2.2 795 555 595 490 365 315 245 150
3.0 815 685 825 790 575 545 415 340 275
4.0 805 585 520 455 295 240 170 155
5.5 765 750 705 525 430 350 315 255
7.5 785 815 660 580 485 445
11 930 705 705
0.37
0.55
0.75 95 140
1.1 275 340 115
1.5 435 520 250 275 180 110
6 2.2 820 480 525 420 290 245 170
3.0 840 610 755 720 500 475 340 270 200
4.0 735 510 450 380 220 170 100
5.5 690 680 630 450 360 280 245 180
7.5 710 740 590 510 415 370
11 860 635 630
M mm in ft mile
1 1x103 39.37 3.281 6.214x10-4
0.3048 304.8 12 1 1.578x10-5
Length -3 -3
1x10 1 0.0394 3.281x10 6.214x10-7
0.0254 25.4 1 0.08333 1.578x10-5
3 6 4
1.609x10 1.609x10 6.336x10 5280 1
m2 hm2 in2 ft2 milk2
1 1x10-4 1.55x103 10.76 3.861x10-7
Area -6
0.0929 9.29x10 144 1 3.587x10-8
6 9 7
2.59x10 258.9 4.0145x10 2.7878x10 1
m3 L US gal UK gal ft3
1 1000 264.17 219.97 35.315
1x10-3 1 0.2642 0.22 0.0353
Volume
3.785x10-3 3.7854 1 0.8327 0.1337
4.546x1-3 4.546 1.20095 1 0.1605
2.832x10-2 28.316 7.481 6.229 1
G kg t lb Slug
1 1x10-3 1x10-6 2.205x10-3 0.0353
3 -3
1x10 1 1x10 2.205 35.274
Weight
1x106 1x103 1 2.205x103 3.527x104
453.592 0.4536 4.536x10-4 1 16
28.35 0.0283 2.83x10-5 0.0625 1
Pa mmH2O atm lb/in2 in.Hg 23
1 0.102 9.8692x10-6 1.4504x10-4 2.953x10-4
9.807 1 9.678x10-5 1.422x10-3 2.89x10-3
Pressure
101325 10332 1 14.696 29.921
6894.8 703.06 0.068 1 2.036
3386.39 345.32 0.0334 0.4911 1
J kJ kW•h kcal Btu
1 1x10-3 2.778x10-7 2.389x10-4 9.478x10-4
3 -4
1x10 1 2.778x10 0.2389 0.9478
Energy
3.6x106 3600 1 860.1 3411
4186.8 4.1868 1.163x10-3 1 3.968
1055.1 1.0551 2.93x10-4 0.252 1
W kW kcal/h Btu/h RT
1 1x10-3 0.8604 3.412 2.843x10-4
1x103 1 860.4 3412 0.2843
Power
1.163 1.1622x10-3 1 3.9657 3.30x10-4
0.293 2.93x10-4 0.2522 1 8.33x10-5
3517 3.517 3024 12000 1
L/s m3/s m3/h ft3/s UK gal/s
1 1x10-3 3.6 0.0353 0.22
1x103 1 3600 35.3147 219.97
Flow
0.2778 2.778x10-4 1 9.81x10-3 0.611
28.317 0.0283 101.941 1 6.2288
4546 4.546x10-3 16.416 0.1605 1
EKDW1208-Catalog-BD-E
Illustrations in this document may be different from real products. Please check real products while making a purchase.
Product specifications, features, performance parameters, structures and exteriors are subject to change without further notice. Please refer to the nameplate
of the product for detailed information.
Data in this document has been carefully checked and reviewed. EUROKLIMAT cannot be held responsible for any consequence arising from print errors and
omissions.
Euroklimat reserves the ultimate right to interpret this document.