The document provides information on EuroKlimat's EKDW cabinet air handling units, including: - Models of horizontal, vertical, and air jet units with air flow ranges from 2000m3/h to 45000m3/h. - Units have a high total external pressure, large cooling capacity, and compact and simple structure for easy maintenance. - Features include a filter, efficient fan, insulated cabinet, and optional accessories. - Units can be used in central air conditioning systems for applications like hotels, malls, hospitals and offices.

Uploaded by

widya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
91 views24 pages

Ekdw1208 BD

The document provides information on EuroKlimat's EKDW cabinet air handling units, including: - Models of horizontal, vertical, and air jet units with air flow ranges from 2000m3/h to 45000m3/h. - Units have a high total external pressure, large cooling capacity, and compact and simple structure for easy maintenance. - Features include a filter, efficient fan, insulated cabinet, and optional accessories. - Units can be used in central air conditioning systems for applications like hotels, malls, hospitals and offices.

Uploaded by

widya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

EKDW (B Series) Cabinet Air Handling

Units
Horizontal Unit
Model: EKDW020H~EKDW450H
Air flow: 2000m3/h ~ 45000m3/h
Vertical Unit
Model: EKDW040V ~ EKDW450V
Air flow: 4000m3/h ~ 45000m3/h
Air Jet Unit
Model: EKDW020S ~ EKDW120S
Air flow: 2000m3/h ~ 12000m3/h

We help our customers


SUCCEED
www.euroklimat.com
Contents

Table Of Contents

Company Profile..............................................................................................................3
Overview.........................................................................................................................4
Nomenclature .................................................................................................................6
Specifications..................................................................................................................7
Unit Dimensions..............................................................................................................12
Installation ......................................................................................................................19
Optional Parts . ...............................................................................................................20
Quick Reference for Maximum Total External Pressure . ...............................................22
Measurement Conversion Table . ...................................................................................23

Manufactured in an ISO Certified Facility


Information covers EuroKlimat products at the time of publication
and we reserve the right to make changes in design and construction at anytime without prior notice.

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Company Profile

EUROKLIMAT Air Conditioner,


Environmental & Energy-saving Technology from Europe.

EUROKLIMAT (EK) was established in 1963 in


Italy. For the past half a century, it has become
famous as an energy-saving air-conditioning
manufacturer in Italy and globally. Continuous
innovation, new product development and top
EK Italy Headquarters manufacturing quality are the driving force behind
this growth.
EUROKLIMAT (EK) pursues the ideals of
protecting the environment, providing physical
comfort and adopting energy-saving into the
whole process of product R&D, manufacturing 3
3
and service. Our products covering residential,
commercial and close control air-conditioner are
manufactured according to the global generally
accepted standards.

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Overview

EUROKLIMAT possesses the most advanced technologies and manufacturing facilities/processes in the air
conditioning sector and has been forging ahead at the forefront of air conditioning products and technologies for
more than 40 years by enterprising innovation.
Launched by EK to meet market demand, EKDW series air handling units feature joggle structures and foamed
polyurethane plates for effective heat preservation and service life enhancement. Units of this series have 40
models and 560 standard specifications available for your choice, and can be widely used in central air conditioning
systems of hotels, shopping malls, hospitals, office buildings etc.

Customers
Design
EKDW series units feature a high total external pressure, large cooling capacity, compact
and simple structure and easy maintenance.
Easy maintenance: the bearing of the fan motor needs no lubricant refill.
Low sound: a quality fan motor with a low rev provides a large air flow with a low De
operation sound.
Clean and environment friendly: A nylon filter with primary efficiency is installed at the air
inlet. Customers can also choose to install a plate or bag filter and sterilization apparatus
(aluminum screen filter, electric cleaner and photocatalyst are available).
A high-efficiency forward-pitched fan with multiple wings provides a large air flow and
stable performance with a low operation sound. The bearing of the fan needs no lubricant

Com enient
refill, thus saving maintenance cost.

Con
A 30mm-thick strong cabinet wall made of foamed polyurethane ensures effective heat

pact
v
4 preservation and a long service life for the entire unit.
Mechanically expanded copper tubes with a thin wall and a new type of optimized wavy

anC
Com enient
fins produced using leading-edge manufacturing facilities ensure optimal heat exchange

d onv
efficiency and pave the way for a high EER. The coils feature multiple specifications and Customers

pact
different types of loops to work in concert with various other sections.
EKDW features a professional air jet solution that is suitable for areas that is super large

and
or high, areas where no air duct is installed, areas where air ducts cannot be installed
and areas where conditioned air cannot be supplied to the bottom of a building from the Customers
rooftop. Such areas include air ports, bus stations, exhibition centers, factory plants,
supermarkets, and lobbies, front doors and shafts of hotels.
EKDW air jet units use high-performance ball-shaped sprayer as the air outlet, and can
supply air over a maximum distance of 40 meters. The units can supply conditioned air
over a long distance without air duct, thus saving space and operation cost and lowering
the requirement on floor distance.
EKDW air jet units can supply air 360° and the air supply direction can be manually
adjusted. The air is similar to natural air and does not directly blow on people.
Conditioned air is supplied to specified locations in the most comfortable way.

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Overview

Design
All-round standard specifications for water flow, water
pressure drop, etc
All-purpose secondary design software
Complete design flow for non-standard units to
expand application scope

E
En fficie
erg nt
y S and
av
ing

Services Agents

Wide access door makes maintenance work very convenient.


Services 5
Optional accessories such as temperature/pressure drop alarms are available.
Agents
Both air inlet and outlet are equipped with a flange to facilitate air coil connection.
The unit can be mounted on the floor or hung from the ceiling.
gh
Hi
& y
o st bilit
C ta
o w dap
L A

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Nomenclature

Nomenclature

EKDW 080 H R 08 T - 4 L-F AB


1 2 3 4 5 6 7 8 9 10

1. EKDW Model code: EKDW series cabinet air handling units


2. 080 Air flow code: 080 - 8000 m3/h
3. H Type: H - horizontal; V - vertical
4. R Inlet air conditions: R - return air; F - fresh air
5. 08 Total external pressure: 08-80 Pa, 15-150 Pa, 22-220 Pa, 30-300 Pa
6. T Air supply direction: T - top; omitted for horizontal air supply
7. 4 Rows of coils: 4 - 4 row; 6 - 6 rows
8. L Pipe orientation: L - left oriented; R - right oriented (When you face toward the air outlet -
counter air current, connection pipes on the left are left oriented and vice versa)
9. F Power supply features: F: 380 V/3~/50 Hz
10. AB Detailed description on product specification changes

6
Flexible and convenient model selection software

A flexible, user-friendly and proprietary software


is specifically built for EKDW units for model
selection and pricing based on customer
requirements.

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Specifications

Specifications for EKDW-H Series Horizontal Air Handling Units

EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
020H 030H 040H 050H 060H 070H 080H 090H 100H 120H 135H
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 9000 10000 12000 13500
I 80 80 80 80 80 80 80 80 ~ ~ ~
External
II 150 150 150 150 150 150 150 150 150 150 150
residual
III 220 220 220 220 220 220 220 220 220 220 220
pressure (Pa)
IV ~ ~ ~ 300 300 300 300 300 300 300 300
4 rows of coils (return air) 12 17 24 31 38 44 51 56 63 74 81
Nominal
4 rows of coils (fresh air) 29 42 57 69 83 94 113 127 142 169 175
cooling
6 rows of coils (return air) 15 23 33 39 48 55 63 72 78 94 107
capacity (kW)
6 rows of coils (fresh air) 35 53 69 88 105 122 137 155 173 208 237
4 rows of coils (return air) 19 30 41 50 61 71 83 93 103 122 140
Nominal
4 rows of coils (fresh air) 33 49 66 82 99 115 133 148 161 197 220
heating
6 rows of coils (return air) 23 36 48 60 72 84 96 108 120 144 162
capacity (kW)
6 rows of coils (fresh air) 38 57 77 95 114 132 150 169 188 224 255
4 rows of coils (return air) 0.57 0.81 1.14 1.48 1.81 2.10 2.43 2.67 3.00 3.52 3.86
Nominal
4 rows of coils (fresh air) 1.38 2.00 2.71 3.29 3.95 4.48 5.38 6.05 6.76 8.05 8.33
cooling water
6 rows of coils (return air) 0.71 1.10 1.57 1.86 2.29 2.62 3.00 3.43 3.71 4.48 5.10
flow (L/S)
6 rows of coils (fresh air) 1.67 2.52 3.29 4.19 5.00 5.81 6.52 7.38 8.24 9.90 11.29
4 rows of coils (return air) 0.43 0.68 0.92 1.13 1.37 1.71 1.87 2.24 2.32 2.75 3.37
Nominal
4 rows of coils (fresh air) 0.74 1.10 1.49 1.85 2.23 2.77 2.99 3.56 3.62 4.44 5.29
heating water
6 rows of coils (return air) 0.52 0.81 1.08 1.35 1.62 2.02 2.16 2.60 2.70 3.24 3.90
flow (L/S)
6 rows of coils (fresh air) 0.86 1.28 1.73 2.14 2.57 3.17 3.38 4.06 4.23 5.04 6.13
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6 7
Coil Size of inlet/outlet water
R1-1/2 R1-1/2 R1-1/2 R1-1/2 R1-1/2 R2 R2 R2 R2 R2 R2
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Downward horizontal/top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I 0.37(0.37) 0.55(0.75) 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.1) 1.1(1.5) 1.5(1.5) ~ ~ ~
Motor
Motor power II 0.55(0.55) 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.5) 1.1(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 3.0(3.0) 3.0(3.0)
(kW) III 0.55(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.1) 1.5(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 3.0(3.0) 3.0(4.0)
IV ~ ~ ~ 1.1(1.5) 1.5(2.2) 1.5(2.2) 2.2(2.2) 2.2(3.0) 2.2(3.0) 3.0(3.0) 4.0(4.0)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
Cabinet Type 30mm-thick double-layer plates filled with polyurethane material foamed under high pressure for heat preservation
Length (mm) 820 950 1010 1130 1260 1300 1500 1620 1650 1750 1940
Unit
Width (mm) 950 950 1050 1050 1050 1100 1100 1100 1050 1050 1050
Dimensions
Height (mm) 630 650 755 755 805 830 830 830 890 950 950
4 rows of coils (kg) 127 141 169 184 209 233 266 283 348 367 393
Unit weight
6 rows of coils (kg) 131 147 176 192 219 245 280 298 366 388 416
Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Specifications

Specifications for EKDW-H Series Horizontal Air Handling Units

EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
150H 180H 200H 220H 250H 270H 300H 350H 400H 450H
Nominal air flow (m3/h) 15000 18000 20000 22000 25000 27000 30000 35000 40000 45000
I ~ ~ ~ ~ ~ ~ 220 220 220 220
External II 150 150 150 150 150 150 300 300 300 300
residual III 220 220 220 220 220 220 400 400 400 400
pressure (Pa) IV 300 300 300 300 300 300 500 500 500 500
V ~ ~ ~ ~ ~ ~ ~ 600 600 600
4 rows of coils (return air) 97 114 123 134 155 165 191 220 256 286
Nominal
4 rows of coils (fresh air) 211 248 270 290 337 361 418 481 558 620
cooling
6 rows of coils (return air) 120 147 160 175 199 218 239 276 318 354
capacity (kW)
6 rows of coils (fresh air) 268 321 347 375 434 459 526 596 686 754
4 rows of coils (return air) 153 186 202 225 253 277 310 358 408 460
Nominal
4 rows of coils (fresh air) 246 296 326 355 406 439 502 574 656 730
heating
6 rows of coils (return air) 183 215 238 264 298 312 366 424 484 542
capacity (kW)
6 rows of coils (fresh air) 287 338 375 412 469 507 574 666 766 854
4 rows of coils (return air) 4.62 5.43 5.86 6.38 7.38 7.86 9.10 10.48 12.19 13.62
Nominal
4 rows of coils (fresh air) 10.05 11.81 12.86 13.81 16.05 17.19 19.90 22.90 26.57 29.52
cooling water
6 rows of coils (return air) 5.71 7.00 7.62 8.33 9.48 10.38 11.38 13.14 15.14 16.86
flow (L/S)
6 rows of coils (fresh air) 12.76 15.29 16.52 17.86 20.67 21.86 25.05 28.38 32.67 35.90
4 rows of coils (return air) 3.44 4.19 4.55 5.07 5.70 6.24 7.48 8.64 9.84 11.10
Nominal
4 rows of coils (fresh air) 5.54 6.66 7.34 7.99 9.14 9.88 12.11 13.85 15.82 17.61
heating water
6 rows of coils (return air) 4.12 4.84 5.36 5.94 6.71 7.02 8.83 10.23 11.68 13.07
flow (L/S)
6 rows of coils (fresh air) 6.46 7.61 9.28 9.28 10.56 11.42 13.85 16.07 18.48 20.60
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
8 Working pressure (MPa) 1.6
Coil Size of inlet/outlet water
R2-1/2 R2-1/2 R2-1/2 R3 R3 R3 R3 R3 R3 R3
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Downward horizontal/top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I ~ ~ ~ ~ ~ ~ 7.5(7.5) 7.5(11) 11(11) 11(11)
Motor II 3.0(3.0) 4.0(4.0) 4.0(4.0) 4.0(5.5) 4.0(5.5) 5.5(5.5) 7.5(7.5) 11(11) 11(11) 11(15)
Motor power
III 3.0(4.0) 4.0(4.0) 4.0(5.5) 5.5(5.5) 5.5(5.5) 5.5(7.5) 11(11) 11(11) 15(15) 15(15)
(kW)
IV 4.0(4.0) 4.0(5.5) 5.5(5.5) 5.5(7.5) 5.5(7.5) 7.5(7.5) 11(11) 11(15) 15(15) 15(15)
V ~ ~ ~ ~ ~ ~ ~ 15(15) 15(15) 15(18.5)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
Cabinet Type 30mm-thick double-layer plates filled with polyurethane material foamed under high pressure for heat preservation
Length (mm) 2010 2060 2250 2300 2470 2620 2770 2770 2930 2930
Unit
Width (mm) 1090 1090 1250 1250 1250 1250 1650 1650 1650 1810
Dimensions
Height (mm) 1020 1140 1140 1200 1270 1270 1410 1570 1730 1890
4 rows of coils (kg) 447 477 565 589 703 722 972 1047 1196 1294
Unit weight
6 rows of coils (kg) 472 507 598 625 744 767 1025 1106 1266 1371

Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Specifications

Specifications for EKDW-V Series Vertical Air Handling Units

EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
040V 050V 060V 070V 080V 090V 100V 120V 135V 150V
Nominal air flow (m3/h) 4000 5000 6000 7000 8000 9000 10000 12000 13500 15000
External I 80 80 80 80 80 80 80 ~ ~ ~
residual II 150 150 150 150 150 150 150 150 150 150
pressure III 220 220 220 220 220 220 220 220 220 220
(Pa) IV 300 300 300 300 300 300 300 300 300 300
Nominal 4 rows of coils (return air) 23 30 37 44 50 56.3 63 74 84 95
cooling 4 rows of coils (fresh air) 55 70 83 94 111 121 137 167 190 202
capacity 6 rows of coils (return air) 32 40 47 53 62 69 78 96 112 120
(kW) 6 rows of coils (fresh air) 70 86 103 122 137 156 172 206 230 264
Nominal 4 rows of coils (return air) 40 50 60 71 82 91 102 122 139 155
heating 4 rows of coils (fresh air) 65 82 98 115 129 148 164 197 222 246
capacity 6 rows of coils (return air) 48 60 72 84 97 108 121 142 161 178
(kW) 6 rows of coils (fresh air) 77 94 113 132 152 169 191 224 257 280
Nominal 4 rows of coils (return air) 1.10 1.43 1.76 2.10 2.80 2.68 3.00 3.52 4.00 4.52
cooling 4 rows of coils (fresh air) 2.62 3.33 3.95 4.48 5.29 5.76 6.52 7.95 9.05 9.62
water flow 6 rows of coils (return air) 1.52 1.90 2.24 2.52 2.95 3.29 3.71 4.57 5.33 5.71
(L/S) 6 rows of coils (fresh air) 3.33 4.10 4.90 5.81 6.52 7.43 8.19 9.81 10.95 12.57
Nominal 4 rows of coils (return air) 0.96 1.21 1.45 1.71 1.98 2.19 2.46 2.94 3.34 3.74
heating 4 rows of coils (fresh air) 1.57 1.98 2.36 2.77 3.11 3.56 3.96 4.75 5.34 5.93
water flow 6 rows of coils (return air) 1.16 1.45 1.74 2.02 2.34 2.60 2.92 3.43 3.87 4.29
(L/S) 6 rows of coils (fresh air) 1.86 2.27 2.73 3.17 3.67 4.06 4.61 5.40 6.18 6.75
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6 9
Coil Size of inlet/outlet water
R 1-1/2 R 1-1/2 R 1-1/2 R2 R2 R2 R2 R2 R2 R 2-1/2
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I 0.75(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.1) 1.1(1.5) 1.5(1.5) 1.5(2.2) ~ ~ ~
Motor Motor
II 0.75(1.1) 1.1(1.1) 1.1(1.5) 1.1(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 2.2(3.0) 3.0(3.0)
power
III 1.1(1.1) 1.1(1.1) 1.5(1.5) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 2.2(3.0) 3.0(3.0) 3.0(4.0)
(kW)
IV 1.1(1.5) 1.1(1.5) 1.5(2.2) 1.5(2.2) 2.2(2.2) 2.2(3.0) 2.2(3.0) 3.0(3.0) 3.0(4.0) 4.0(4.0)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
30mm-thick double-layer plates filled with polyurethane material foamed under high pressure for heat
Cabinet Type
preservation
Length (mm) 920 1030 1200 1230 1280 1290 1330 1440 1580 1870
Unit
Width (mm) 650 650 650 810 810 810 900 900 900 810
Dimensions
Height (mm) 1270 1335 1385 1490 1550 1610 1800 1860 1860 1680
4 rows of coils (kg) 172 203 236 274 306 323 386 423 435 482
Unit weight
6 rows of coils (kg) 179 211 246 286 321 339 404 444 458 507

Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Specifications

Specifications for EKDW-V Series Vertical Air Handling Units

EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW


Model
180V 200V 220V 250V 270V 300V 350V 400V 450V
Nominal air flow (m3/h) 18000 20000 22000 25000 27000 30000 35000 40000 45000
I ~ ~ ~ ~ ~ 220 220 220 220
External II 150 150 150 150 150 300 300 300 300
residual III 220 220 220 220 220 400 400 400 400
pressure (Pa) IV 300 300 300 300 300 500 500 500 500
V ~ ~ ~ ~ ~ ~ 600 600 600
4 rows of coils (return air) 115 123 138 157 170 191 220 256 286
Nominal
4 rows of coils (fresh air) 246 272 302 342 369 418 481 558 620
cooling
6 rows of coils (return air) 142 160 173 197 211 239 276 318 354
capacity (kW)
6 rows of coils (fresh air) 317 350 379 428 454 526 596 686 754
4 rows of coils (return air) 187 202 230 255 275 310 358 408 460
Nominal
4 rows of coils (fresh air) 293 326 362 406 439 502 574 656 730
heating
6 rows of coils (return air) 215 238 266 300 325 366 424 484 542
capacity (kW)
6 rows of coils (fresh air) 339 377 418 474 507 574 666 766 854
4 rows of coils (return air) 5.48 5.86 6.57 7.48 8.10 9.10 10.48 12.19 13.62
Nominal
4 rows of coils (fresh air) 11.71 12.95 14.38 16.29 17.57 19.90 22.90 26.57 29.52
cooling water
6 rows of coils (return air) 6.76 7.62 8.24 9.38 10.05 11.38 13.14 15.14 16.86
flow (L/S)
6 rows of coils (fresh air) 15.10 16.67 18.05 20.38 21.62 25.05 28.38 32.67 35.90
4 rows of coils (return air) 4.51 4.87 5.55 6.15 6.63 7.48 8.64 9.84 11.10
Nominal
4 rows of coils (fresh air) 7.07 7.86 8.73 9.79 10.59 12.11 13.85 15.82 17.61
heating water
6 rows of coils (return air) 5.19 5.74 6.42 7.24 7.84 8.83 10.23 11.68 13.07
flow (L/S)
6 rows of coils (fresh air) 8.18 9.09 10.08 11.43 12.23 13.85 16.07 18.48 20.60
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6
10 Coil Size of inlet/outlet water
R 2-1/2 R 2-1/2 R3 R3 R3 R3 R3 R3 R3
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
Fanning direction Top
Power supply 380V/3~/50Hz
Type 3-phase asynchronous motor; insulation grade of F and protection grade of IP54
I ~ ~ ~ ~ ~ 7.5(7.5) 7.5(11) 11(11) 11(11)
Motor Motor II 4.0(4.0) 4.0(4.0) 4.0(5.5) 4.0(5.5) 5.5(5.5) 7.5(7.5) 11(11) 11(11) 11(15)
power III 4.0(4.0) 4.0(5.5) 5.5(5.5) 5.5(5.5) 5.5(7.5) 11(11) 11(11) 15(15) 15(15)
(kW) IV 4.0(5.5) 5.5(5.5) 5.5(7.5) 5.5(7.5) 7.5(7.5) 11(11) 11(15) 15(15) 15(15)
V ~ ~ ~ ~ ~ ~ 15(15) 15(15) 15(18.5)
Type Thickness (mm)
Filter
Thickness (mm) 8/21
30mm-thick double-layer plates filled with polyurethane material foamed under high pressure
Cabinet Type
for heat preservation
Length (mm) 2060 2250 2310 2480 2630 2770 2770 2930 3090
Unit
Width (mm) 810 900 900 900 900 1010 1010 1010 1170
Dimensions
Height (mm) 1740 1860 1920 1990 1990 2270 2590 2750 2810
4 rows of coils (kg) 537 649 674 779 807 968 1040 1196 1384
Unit weight
6 rows of coils (kg) 567 682 710 820 851 1021 1099 1267 1461

Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Specifications

Specifications for EKDW-S Jet Air Handling Unit

EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
020S 030S 040S 050S 060S 070S 080H 090S 100S 120S
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 9000 10000 12000
Nominal 4 rows of coils (return air) 12 17 24 31 38 44 51 56 63 74
cooling 4 rows of coils (fresh air) 29 42 57 69 83 94 113 127 142 169
capacity 6 rows of coils (return air) 15 23 33 39 48 55 63 72 78 94
(kW) 6 rows of coils (fresh air) 35 53 69 88 105 122 137 155 173 208
Nominal 4 rows of coils (return air) 19 30 41 50 61 71 83 93 103 122
heating 4 rows of coils (fresh air) 33 49 66 82 99 115 133 148 161 197
capacity 6 rows of coils (return air) 23 36 48 60 72 84 96 108 120 144
(kW) 6 rows of coils (fresh air) 38 57 77 95 114 132 150 169 188 224
Nominal 4 rows of coils (return air) 0.57 0.81 1.14 1.48 1.81 2.10 2.43 2.67 3.00 3.52
cooling 4 rows of coils (fresh air) 1.38 2.00 2.71 3.29 3.95 4.48 5.38 6.05 6.76 8.05
water flow 6 rows of coils (return air) 0.71 1.10 1.57 1.86 2.29 2.62 3.00 3.43 3.71 4.48
(L/S) 6 rows of coils (fresh air) 1.67 2.52 3.29 4.19 5.00 5.81 6.52 7.38 8.24 9.90
Nominal 4 rows of coils (return air) 0.43 0.68 0.92 1.13 1.37 1.71 1.87 2.24 2.32 2.75
heating 4 rows of coils (fresh air) 0.74 1.10 1.49 1.85 2.23 2.77 2.99 3.56 3.62 4.44
water flow 6 rows of coils (return air) 0.52 0.81 1.08 1.35 1.62 2.02 2.16 2.60 2.70 3.24
(L/S) 6 rows of coils (fresh air) 0.86 1.28 1.73 2.14 2.57 3.17 3.38 4.06 4.23 5.04
Type Copper tube with a new type of wavy aluminum fins
Piece/inch 13
Working pressure (MPa) 1.6
Coil Size of inlet/outlet water
R 1-1/2 R 1-1/2 R 1-1/2 R 1-1/2 R 1-1/2 R2 R2 R2 R2 R2
pipe connector
Size of condensate water
R1-1/4
pipe connector
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/zinc-plated steel plates
Fan Transmission V-belt transmission
11
Fanning direction Downward horizontal/top
I 10~20m(1) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) ~ ~
4 rows of heat
II 20~30m(1) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2)
Rang exchangers
III ~ ~ ~ 30~40m(1) 30~40m(2) 30~40m(1) 30~40m(1) 30~40m(1) 30~40m(2) 30~40m(2)
(number of
I 10~20m(1) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) 10~20m(2) ~ ~
nozzles) 6 rows of heat
II 20~30m(1) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2) 20~30m(2)
exchangers
III ~ ~ ~ 30~40m(1) 30~40m(2) 30~40m(1) 30~40m(1) 30~40m(1) 30~40m(2) 30~40m(2)
I 0.55 0.75 0.75 1.1 1.5 1.5 1.5 2.2 ~ ~
4 rows of heat
II 0.75 1.1 1.1 1.5 2.2 2.2 2.2 3.0 3.0 4.0
exchangers
Motor III ~ ~ ~ 2.2 3.0 3.0 3.0 4.0 5.5 5.5
power (kW) I 0.75 1.1 1.1 1.1 1.5 1.5 1.5 3.0 ~ ~
6 rows of heat
II 1.1 1.5 1.5 1.5 2.2 2.2 2.2 3 3.0 4.0
exchangers
III ~ ~ ~ 2.2 3.0 3.0 3.0 4.0 5.5 5.5
Type Thickness (mm)
Filter
Thickness (mm) 8/21
30mm-thick double-layer plates filled with polyurethane material foamed under
Cabinet Type
high pressure for heat preservation
Length (mm) 820 950 1010 1130 1260 1300 1500 1620 1650 1750
Unit
Width (mm) 1450 1450 1550 1550 1550 1600 1600 1600 1550 1550
Dimensions
Height (mm) 630 650 755 755 805 830 830 830 890 950
Unit weight 4 rows of heat exchangers 135 149 179 195 222 247 282 300 369 389
(kg) 6 rows of heat exchangers 139 156 187 204 232 260 297 316 388 411

Note:
■ The above parameters are for standard units. However, EK can ■ Weight listed in the above table are net weight of units. Operation
customize these parameters to meet special requirements from weight may post an increase of 20%.
customers. ■ Parameters inside ( ) are the power of units with 6 rows of coils.
■ Working conditions for cooling under nominal return air flow: dry bulb ■ The coil loops for units with full return air ("R") and units with full fresh
27°C, wet bulb 19.5°C; working conditions for cooling under nominal air ("F") may be different. Please specify the inlet air conditions while
fresh air flow: dry bulb 34°C, wet bulb 28°C; water temperature placing orders. EK can provide computer-aided model selection to
under nominal cooling capacity: inlet water 7°C, outlet water 12°C. meet special requirements. For detailed parameters, please refer to
■ Working conditions for heating under nominal return air flow: dry bulb the model selection results.
21°C; Working conditions for heating under nominal fresh air flow:
dry bulb 0°C; water temperature under nominal heating capacity:
inlet water 60°C, outlet water 50°C.

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Unit Dimensions

Dimensions of Horizontal Air Handling Units (EKDW020H ~ EKDW080H)


F

W
N
Hoist hole: 4-ɸ20

E A
L
M
K

Outlet pipe D for chilled water

Inlet pipe D for


G

R
chilled water
B

Q
J

80

P
Drain pipe C for condensate water

EKDW-H horizontal air supply

12
W
N

Hoist hole: 4-ɸ20

L
M
K

B S E A
Outlet pipe D for chilled water

Inlet pipe D for chilled water


G

1. Outlet pipe D for chilled water


Q

2. Inlet pipe D for chilled water


80

3. Drain pipe C for condensate water


Drain pipe C for condensate water
P

EKDW-H top air supply Measurement: mm

Size of Drain pipe for


Size of return Size of air Inlet/outlet pipe
Dimensions Length Width Height Hoist size connection condensate
air inlet supply inlet for chilled water
pipes water
Model L W H F G A B K M N J S E P Q R D C
EKDW020H 820 950 550 765 495 262 231 1000 940 883 95 148 145 55 123 297 R1-1/2 R1-1/4
EKDW030H 950 950 570 895 515 290 259 1130 1070 883 93 162 203 55 123 348 R1-1/2 R1-1/4
EKDW040H 1010 1050 675 955 620 333 292 1190 1130 983 101 201 168 55 123 449 R1-1/2 R1-1/4
EKDW050H 1130 1050 675 1075 620 312 344 1310 1250 983 101 245 250 55 123 449 R1-1/2 R1-1/4
EKDW060H 1260 1050 725 1205 670 398 344 1440 1380 983 101 217 304 55 123 500 R1-1/2 R1-1/4
EKDW070H 1300 1100 750 1245 695 375 407 1480 1420 1033 101 248 348 55 131 498 R2 R1-1/4
EKDW080H 1500 1100 750 1445 695 375 407 1680 1620 1033 101 246 449 55 131 498 R2 R1-1/4
EKDW090H 1620 1100 750 1565 695 473 407 1800 1740 1033 101 258 449 55 131 498 R2 R1-1/4

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Unit Dimensions

Dimensions of Horizontal Air Handling Units (EKDW100H ~ EKDW270H)


F

W
N
Hoist hole: 4-ɸ20

E A T A
L
M
K

Outlet pipe D for chilled water

Inlet pipe D for


H

R
G

chilled water
B

Q
J

80

Drain pipe C for condensate water P


EKDW-H horizontal air supply

13
W
N

Hoist hole: 4-ɸ20

L
M
K

B S E A T A
Outlet pipe D for chilled water
H
G

Inlet pipe D for chilled water

1. Outlet pipe D for chilled water


Q
80

2. Inlet pipe D for chilled water


Drain pipe C for condensate water
P

3. Drain pipe C for condensate water


Measurement: mm
EKDW-H top air supply

Inlet/outlet Drain
Size of return Size of air Size of connection pipe for pipe for
Dimensions Length Width Height Hoist size
air inlet supply inlet pipes chilled condensate
water water
Model L W H F G A B K M N J S E T P Q R D C
EKDW100H 1650 1050 810 1595 755 312 344 1830 1770 983 101 217 177 241 55 131 561 R2 R1-1/4
EKDW120H 1750 1050 870 1695 815 312 344 1930 1870 983 101 217 252 241 55 131 625 R2 R1-1/4
EKDW135H 1940 1050 870 1885 815 398 344 2120 2060 983 101 218 215 321 55 131 625 R2 R1-1/4
EKDW150H 2010 1090 940 1955 885 375 407 2190 2130 1023 101 258 244 292 55 139 672 R2-1/2 R1-1/4
EKDW180H 2060 1090 1060 2005 1005 375 407 2240 2180 1023 101 248 294 292 55 139 799 R2-1/2 R1-1/4
EKDW200H 2250 1250 1060 2195 1005 432 478 2430 2370 1183 107 309 298 341 55 139 799 R2-1/2 R1-1/4
EKDW220H 2300 1250 1120 2245 1065 432 478 2480 2420 1183 106 309 298 341 55 145 850 R3 R1-1/4
EKDW250H 2470 1250 1190 2415 1135 559 481 2650 2590 1183 106 309 156 456 55 145 913 R3 R1-1/4
EKDW270H 2620 1250 1190 2565 1135 559 481 2800 2740 1183 106 309 307 456 55 145 913 R3 R1-1/4

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Unit Dimensions

Dimensions of Horizontal Air Handling Units (EKDW300H ~ EKDW450H)


F

W
E A T A
L

Outlet pipe D for chilled water

Inlet pipe D for chilled water


Outlet pipe D for chilled water
G

Inlet pipe D for chilled water


B

80
J

P
Drain pipe C for condensate water

EKDW-H horizontal air supply

F
14
W

B S E A T A
Outlet pipe D for chilled water

Inlet pipe D for chilled water


Outlet pipe D for chilled water
G

Inlet pipe D for chilled water


80

Drain pipe C for condensate water


Measurement: mm
EKDW-H top air supply

Drain pipe for


Size of return air Size of air Size of Inlet/outlet pipe
Dimensions Length Width Height Hoist size condensate
inlet supply inlet connection pipes for chilled water
water
Model L W H F G A B E T J S P D C
EDW300H 2770 1650 1330 2710 1270 557 478 262 458 70 330 100 R3 R1-1/4
EDW350H 2770 1650 1490 2710 1430 569 569 277 450 270 315 100 R3 R1-1/4
EDW400H 2930 1650 1650 2870 1590 569 569 357 450 270 315 100 R3 R1-1/4
EDW450H 2930 1810 1810 2870 1750 638 638 273 500 275 430 100 R3 R1-1/4

Note: "D" in the above figure is the diameter of inlet/out water pipe for units (EKDW020H ~ EKDW350H) with a single coil;
For units (EKDW400H ~ EKDW450H) with double coils, there are two sets of inlet/outlet water pipes with a diameter of "D".

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Unit Dimensions

Dimensions of Vertical Air Handling Units (EKDW40V ~ EKDW120V)

B S E A

Outlet pipe D for


chilled water
15
H
G

Inlet pipe D for


chilled water
Q

P
80

N Drain pipe C for M


condensate water
W L

EKDW-V top air supply


Measurement: mm

Inlet/outlet Drain pipe for


Size of return Size of air
Dimensions Length Width Height Hoist size Size of connection pipes pipe for condensate
air inlet supply inlet
chilled water water
Model L W H F G A B M N S E P Q R D C
EKDW040V 920 650 1190 865 640 333 292 890 620 143 448 50 131 510 R1-1/2 R1-1/4
EKDW050V 1030 650 1255 975 640 312 344 1000 620 70 517 50 131 510 R1-1/2 R1-1/4
EKDW060V 1200 650 1305 1145 690 398 344 1170 620 70 517 50 131 573 R1-1/2 R1-1/4
EKDW070V 1230 810 1410 1175 720 375 407 1200 780 146 515 50 131 561 R2 R1-1/4
EKDW080V 1280 810 1470 1225 785 375 407 1250 780 145 516 50 131 625 R2 R1-1/4
EKDW090V 1290 810 1530 1235 840 473 407 1260 780 146 514 50 131 688 R2 R1-1/4
EKDW100V 1330 900 1720 1275 910 432 481 1300 870 103 572 50 131 752 R2 R1-1/4
EKDW120V 1440 900 1780 1385 970 559 481 1410 870 103 622 50 131 815 R2 R1-1/4
EKDW135V 1580 900 1780 1525 970 559 481 1550 870 103 622 50 131 815 R2 R1-1/4

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Unit Dimensions

Dimensions of Vertical Air Handling Units (EKDW150V ~ EKDW270V)

B S A T A E

16 Outlet pipe D for


chilled water
H
G

Inlet pipe D for


chilled water
Q

P
80

Drain pipe C for


N M
condensate water
W L

EKDW-V top air supply

Measurement: mm

Inlet/outlet Drain pipe for


Size of return Size of air Size of connection
Dimensions Length Width Height Hoist size pipe for chilled condensate
air inlet supply inlet pipes
water water
Model L W H F G A B M N S E T P Q R D C
EKDW150V 1870 810 1600 1815 910 375 407 1840 780 145 131 292 50 139 736 R2-1/2 R1-1/4
EKDW180V 2060 810 1660 2005 970 375 407 2030 780 145 339 292 50 139 799 R2-1/2 R1-1/4
EKDW200V 2250 900 1780 2195 970 432 481 2220 870 104 379 341 50 139 799 R2-1/2 R1-1/4
EKDW220V 2310 900 1840 2255 1030 432 481 2280 870 104 358 341 50 139 850 R3 R1-1/4
EKDW250V 2480 900 1910 2425 1105 559 481 2450 870 103 160 456 50 139 913 R3 R1-1/4
EKDW270V 2630 900 1910 2575 1105 559 481 2600 870 104 310 456 50 139 913 R3 R1-1/4

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Unit Dimensions

Dimensions of Vertical Air Handling Units (EKDW300V ~ EKDW450V)

B S A T A E

Outlet pipe D for


chilled water
17

Inlet pipe D for


H

chilled water
G

Outlet pipe D for chilled water

Inlet pipe D for chilled water


Q
P
80

Drain pipe C for


N M
condensate water
90 W L

EKDW-V top air supply

Measurement: mm

Size of return Size of air Size of connection Inlet/outlet pipe for Drain pipe for
Dimensions Length Width Height Hoist size
air inlet supply inlet pipes chilled water condensate water
Model L W H F G A B E T S P D C
EDW300V 2770 1010 2190 2710 1270 559 481 262 456 206 100 R3 R1-1/4
EDW350V 2770 1010 2510 2710 1405 572 572 274 446 132 100 R3 R1-1/4
EDW400V 2930 1010 2670 2870 1565 572 572 354 446 132 100 R3 R1-1/4
EDW450V 3090 1170 2730 3030 1565 638 638 353 500 197 100 R3 R1-1/4

Note: "D" in the above figure is the diameter of inlet/out water pipe for units (EKDW040V ~ EKDW350V) with a single coil;
For units (EKDW400V ~ EKDW450V) with double coils, there are two sets of inlet/outlet water pipes with a diameter of "D".

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Unit Dimensions

Dimensions of Jet Air Handling Unit (EKDW020S~EKDW120S)

F F

N
W

W
L
L
M
M
K K

Outlet pipe D for


chilled water

18
G

H
Q
P

Outlet pipe D for


80

80
chilled water
Drain pipe C for
condensate water

Measurement: mm

Size of return air Inlet/outlet pipe Drain pipe for


Dimensions Length Width Height Hoist size Size of connection pipes
inlet for chilled water condensate water
Model L W H F G K M N J P Q R D C
EKDW020S 820 1450 550 765 495 1000 940 1383 95 55 123 297 R1-1/2 R1-1/4
EKDW030S 950 1450 570 895 515 1130 1070 1383 93 55 123 348 R1-1/2 R1-1/4
EKDW040S 1010 1550 675 955 620 1190 1130 1483 101 55 123 449 R1-1/2 R1-1/4
EKDW050S 1130 1550 675 1075 620 1310 1250 1483 101 55 123 449 R1-1/2 R1-1/4
EKDW060S 1260 1550 725 1205 670 1440 1380 1483 101 55 123 500 R1-1/2 R1-1/4
EKDW070S 1300 1600 750 1245 695 1480 1420 1533 101 55 131 498 R2 R1-1/4
EKDW080S 1500 1600 750 1445 695 1680 1620 1533 101 55 131 498 R2 R1-1/4
EKDW090S 1620 1600 750 1565 695 1800 1740 1533 101 55 131 498 R2 R1-1/4
EKDW100S 1650 1550 810 1595 755 1830 1770 1483 101 55 131 561 R2 R1-1/4
EKDW120S 1750 1550 870 1695 815 1930 1870 1483 101 55 131 625 R2 R1-1/4

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Installation

Considerations for Placing Orders

■ Please specify the model, specification, quantity, working ■ How to Tell Right-oriented Connection Pipes from Left-
conditions of the unit (s) and any special requirements in oriented Ones
detail while placing orders. Please specify the orientation of inlet/outlet water pipes
■ Besides standard total external pressure, the total external while placing orders. When you face toward the air outlet
pressure of this series of units can also be customized (counter air current), connection pipes on the left are left
as per requirements from customers. Please specify your oriented and vice versa, as shown in Figure 1 ~ 3. For
requirement on total external pressure while placing orders. cooling water pipes, L represents "left" and R represents
"right". The condensate water pipes are on the same side
with cooling water pipes.
Left connection pipe Left connection pipe

Outlet air Inlet air Inlet air

Right connection pipe


Right connection pipe

Figure 1 EKDW-H horizontal units with horizontal air supply Figure 2 EKDW-H horizontal units with top air supply

Left connection pipe


19

Inlet air

Right connection pipe

Figure 3 EKDW-V horizontal units with top air supply

Considerations for Installation

During unit installation, a proper water seal is needed to ensure smooth discharge of condensate water, as shown in Figure 4.

Connected to the drain pipe

P - Max. internal negative pressure - PaH ≥ P/10+20 (mm)

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Optional Parts

Available Combinations of Optional Functional Sections


Standard configuration Optional functional section
Functional section Primary Wet film Electric Bag-type filter with Blending
Cooled coil Fan Heating coil
efficiency filter humidifier heater medium efficiency section
Combination 1 √ √ √ √
Combination 2 √ √ √ √
Combination 3 √ √ √ √
Combination 4 √ √ √ √
Combination 5 √ √ √ √
Combination 6 √ √ √ √ √
Combination 7 √ √ √ √ √
Combination 8 √ √ √ √ √ √
Combination 9 √ √ √ √ √
Combination 10 √ √ √ √ √
Combination 11 √ √ √ √ √ √
Combination 12 √ √ √ √ √
Combination 13 √ √ √ √ √
Combination 14 √ √ √ √ √ √
Note:
1. Non-woven fabric filters are available for your choice (nylon screen filter is the standard configuration).
2. Unit power and total external pressure may be changed.
3. The width of the unit "W" may be increased as necessary.

Purification and Sterilization Apparatus (Optional)


Aluminum Screen Filter
20
■ Used to filter large particles, such as smog;
■ The aluminum frame helps to reduce maintenance cost;
■ The precision aluminum screen is easy to install and clean.

Electronic Purification Apparatus

■ A high-voltage static dedusting technology is applied to effectively filter all sorts of dust, bacteria,
virus and harmful gas;
■ Multi-layered filtering provides multi-layered protection;
■ A modular design can meet various air flow requirements.

Photocatalyst Ultraviolet Sterilamp

■ The sterilamp can effectively dampening the growth of bacteria and mildew and thereby
eliminating odor caused by such growth;
■ The photocatalyst itself is stable and unconsumed, and therefore can be effective for a long
time;
■ The sterilamp can effectively degrade contaminants such as formaldehyde, toluene and
ammonia into harmless and nontoxic materials, and does not cause secondary contamination.

Water distributor

Humidifying material

Wet film humidifier Inlet water

Tap water purified by the solenoid valve flows directly into the water distributor at the top of the Humidifying air Inlet air

humidifier through water pipes and then flows down to wet the wet film under the pull of gravity.
Residual water collected by the water collector flows into the sewage through the drainpipe (water
will not be recycled). Hot air passing through the wet film is dampened and cooled (equal enthalpy
wetting). During this course, some water in the wet film is evaporated without consuming additional
energy. The work principle of wet film humidifier with direct water flow is shown in the figure on the
right side.
Water discharge

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Optional Parts

Fresh Air Handling Unit & Fan Coil System


It is flexible and space effective, and can modulate indoor air independently. Fan coil
Fan coil FCU
As customers attached more importance to indoor air quality, this system has Fan coil FCU
found its way into various types of buildings, such as guest houses, hotels and FCU

office buildings.
Fresh air handling unit & fan coil system consists of two components, namely
the indoor fan coil unit which is used for indoor cooling/heating and the fresh Fresh Air Handling
Fresh Air Handling
Unit PAU Indoor environment
Indoor environment
air handling unit which is used for pre-cooling and preheating of outdoor fresh Fresh Air Handling Unit PAU
Unit PAU Type b Indoor environment
air (only processes fresh air). Some fresh air handling units can be equipped Type b
Type b
with humidifiers and air purification/sterilization apparatus to meet high
requirements on indoor air quality.
Fresh air can be supplied in two ways, namely direct supply which directly Fresh Air Handling
Fresh Air Handling
supplies processed fresh air into rooms (a in the figure on the right) and Fresh Air Handling Unit PAU
Unit PAU

indirect supply which supplies processed fresh air into rooms through terminal Unit PAU
Type a
Type a

equipment (b in the figure on the right). Type a

Dual Pipe Proportional Integral Control for Fresh Air Handling Units

Air supply Air supply


Air supply Air supply
Air supply Air supply

Code Description
TC-1 Proportional integral temperature controller
TV-1 Electric 2-way valve 21
DPS-1 Differential pressure switch Connected to alarm
Closed
Open
Water supply
Return water

Connected to alarm
Closed
Open
Water
Return

TE-1 Air duct temperature sensor Connected to alarm


Closed
Openwater
Water supply
Return water

supply

Work Principle:

This air supply temperature control system consists of the temperature sensor Blue
TE-1, the proportional integral temperature controller TC-1 and the electric 2-way Blue
Red
Red
Blue
valve TV-1. TE-1 is installed in the air supply duct and used to send temperature Red Power supply
Power supply
signals to TC-1 which compares the signal with the set value and outputs signals to Bluesupply Yellow
Power
Blue Yellow
continuously modulate the openness of TV-1 so that the temperature detected by Blue Yellow

TE-1 always falls into the set range.


The differential pressure switch DPS-1 detects the pressure drop of the filter and
compares it with the set value. An alarm is triggered if the value detected exceeds the
set value.

The unit can be equipped with temperature controllers, water valves,


pressure gauges and differential pressure switches (optional)

Temperature controller Differential pressure switch

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


Quick Reference for Maximum Total External Pressure

Motor Power of EKDW Series Cabinet Air Handling Units -


Quick Reference for Maximum Total External Pressure
EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
020H 030H 040H 050H 060H 070H 080H 090H 100H 120H 135H 150H 180H 200H 220H 250H 270H
3
Nominal air flow (m /h) 2000 3000 4000 5000 6000 7000 8000 9000 10000 12000 13500 15000 18000 20000 22000 25000 27000
Rows of coils Motor power (kW) Total external pressure (Pa)
0.37 140
0.55 280 115
0.75 420 235 200 129
1.1 550 415 380 329 160 180
1.5 615 540 509 320 340 245 180
4 2.2 680 809 550 590 485 360 315
3.0 829 680 820 785 570 515 380 230 270
4.0 725 600 400 450 295 240 170 155
5.5 775 850 630 700 525 430 50 315 255
7.5 780 815 660 580 485 445
11 930 705 705
0.37
0.55 215
0.75 355 159 125
1.1 465 339 305 243
1.5 539 465 423 240 260 170 110
6 2.2 610 723 470 510 410 290 245
3.0 743 600 740 710 500 445 305 160 200
4.0 655 525 330 380 220 170
5.5 705 775 560 630 450 360 280 245 180
7.5 710 740 590 510 415 370
11 860 635 630

EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW EKDW
Model
040V 050V 060V 070V 080V 090V 100V 120V 135V 150V 180V 200V 220V 250V 270V
22 3
Nominal air flow (m /h) 4000 5000 6000 7000 8000 9000 10000 12000 13500 15000 18000 20000 22000 25000 27000
Rows of coils Motor power (kW) Total external pressure (Pa)
0.37
0.55
0.75 180 115
1.1 360 315 165 185 100
1.5 520 495 325 345 250 185 125
4 2.2 795 555 595 490 365 315 245 150
3.0 815 685 825 790 575 545 415 340 275
4.0 805 585 520 455 295 240 170 155
5.5 765 750 705 525 430 350 315 255
7.5 785 815 660 580 485 445
11 930 705 705
0.37
0.55
0.75 95 140
1.1 275 340 115
1.5 435 520 250 275 180 110
6 2.2 820 480 525 420 290 245 170
3.0 840 610 755 720 500 475 340 270 200
4.0 735 510 450 380 220 170 100
5.5 690 680 630 450 360 280 245 180
7.5 710 740 590 510 415 370
11 860 635 630

Model EKDW300H EKDW350H EKDW400H EKDW450H EKDW300V EKDW350V EKDW400V EKDW450V


Nominal air flow (m3/h) 30000 35000 40000 45000 30000 35000 40000 45000
Rows of coils Motor power (kW) Total external pressure (Pa)
5.5 180 180
7.5 370 250 370 250
4 11 650 520 365 320 650 520 365 320
15 830 685 600 830 685 600
18.5 790 790
5.5 120 120
7.5 310 180 310 180
6 11 590 450 300 250 590 450 300 250
15 760 620 530 760 620 530
18.5 720 720

EKDW (B Series) Cabinet Air Handling Units www.euroklimat.com


Measurement Conversion Table

Measurement Conversion Table

M mm in ft mile
1 1x103 39.37 3.281 6.214x10-4
0.3048 304.8 12 1 1.578x10-5
Length -3 -3
1x10 1 0.0394 3.281x10 6.214x10-7
0.0254 25.4 1 0.08333 1.578x10-5
3 6 4
1.609x10 1.609x10 6.336x10 5280 1
m2 hm2 in2 ft2 milk2
1 1x10-4 1.55x103 10.76 3.861x10-7
Area -6
0.0929 9.29x10 144 1 3.587x10-8
6 9 7
2.59x10 258.9 4.0145x10 2.7878x10 1
m3 L US gal UK gal ft3
1 1000 264.17 219.97 35.315
1x10-3 1 0.2642 0.22 0.0353
Volume
3.785x10-3 3.7854 1 0.8327 0.1337
4.546x1-3 4.546 1.20095 1 0.1605
2.832x10-2 28.316 7.481 6.229 1
G kg t lb Slug
1 1x10-3 1x10-6 2.205x10-3 0.0353
3 -3
1x10 1 1x10 2.205 35.274
Weight
1x106 1x103 1 2.205x103 3.527x104
453.592 0.4536 4.536x10-4 1 16
28.35 0.0283 2.83x10-5 0.0625 1
Pa mmH2O atm lb/in2 in.Hg 23
1 0.102 9.8692x10-6 1.4504x10-4 2.953x10-4
9.807 1 9.678x10-5 1.422x10-3 2.89x10-3
Pressure
101325 10332 1 14.696 29.921
6894.8 703.06 0.068 1 2.036
3386.39 345.32 0.0334 0.4911 1
J kJ kW•h kcal Btu
1 1x10-3 2.778x10-7 2.389x10-4 9.478x10-4
3 -4
1x10 1 2.778x10 0.2389 0.9478
Energy
3.6x106 3600 1 860.1 3411
4186.8 4.1868 1.163x10-3 1 3.968
1055.1 1.0551 2.93x10-4 0.252 1
W kW kcal/h Btu/h RT
1 1x10-3 0.8604 3.412 2.843x10-4
1x103 1 860.4 3412 0.2843
Power
1.163 1.1622x10-3 1 3.9657 3.30x10-4
0.293 2.93x10-4 0.2522 1 8.33x10-5
3517 3.517 3024 12000 1
L/s m3/s m3/h ft3/s UK gal/s
1 1x10-3 3.6 0.0353 0.22
1x103 1 3600 35.3147 219.97
Flow
0.2778 2.778x10-4 1 9.81x10-3 0.611
28.317 0.0283 101.941 1 6.2288
4546 4.546x10-3 16.416 0.1605 1

www.euroklimat.com EKDW (B Series) Cabinet Air Handling Units


www.euroklimat.com ISO9001: 2008 ISO14001: 2004

EKDW1208-Catalog-BD-E
 Illustrations in this document may be different from real products. Please check real products while making a purchase.
 Product specifications, features, performance parameters, structures and exteriors are subject to change without further notice. Please refer to the nameplate
of the product for detailed information.
 Data in this document has been carefully checked and reviewed. EUROKLIMAT cannot be held responsible for any consequence arising from print errors and
omissions.
 Euroklimat reserves the ultimate right to interpret this document.