7UM62 Generator Protection Relay
7UM62 Generator Protection Relay
7UM62 Generator Protection Relay
6 and 7
Communication
8 and 9
10 to 16
17 to 23
Technical data
24 to 35
36
~ Advantages to you
n Cost-effectiveness n High degree of automation n User-friendly operation n Low planning and engineering effort n Fast, flexible mounting, reduced wiring n Simple, short commissioning n Simple spare part stocking n High flexibility n High reliability and availability n State-of-the-art technology n Compliance with international standards n Integration in a control system
Accessories
37
Connection diagrams
38 to 41
Dimension drawings
42 and 43
Protection functions
Abbreviation I
ANSI-N
Generator Basic X X X X X X X X X X X X X 4 X X X X X X X
Motor Asynchronous X X X X X X X X X X X X X 4 X X X X X X
Transformer X X X X X X X X X X X X X 4 X X
Current differential protection Stator earth-fault protection non-directional, directional Sensitive earth-fault protection (also rotor earth-fault protection) Stator overload protection Definite time-overcurrent protection with undervoltage seal-in Definite time-overcurrent protection, directional Inverse time-overcurrent protection Overvoltage protection Undervoltage protection Frequency protection Reverse-power protection Overexcitation protection (Volt/Hertz) Fuse failure monitor External trip coupling Trip circuit supervision Forward-power protection Underexcitation protection (loss-of-field protection) Negative sequence protection Breaker failure protection Motor starting time supervision Restart inhibit for motors Rotor earth-fault protection (fn, R-measuring) Inadvertent energization protection 100% stator earth-fault protection with 3rd harmonics Impedance protection with (I>+V<) pick-up DC voltage / DC current time protection Overcurrent protection during start-up (for gas turbines)2) Earth-current differential protection2) Out-of-step protection Rotor earth-fault protection ( 1 to 3 Hz square wave voltage)2) 100 % stator earth-fault protection with 20 Hz voltage2) Rate-of-frequency-change protection2) Vector jump supervision (voltage) Supervision of phase rotation Undercurrent via CFC External temperature monitoring via serial interface2)
2)
87G/87T/ 87M 59N, 64G 67G 50/51GN (64R) 49 51 50/51/67 51V 59 27 81 32R 24 60FL 74TC 32F 40 46 50BF 48 66, 49 Rotor 64R (fn) 50/27 59TN, 27TN 3rd h 21 59N (DC) 51N (DC) 51 87GN/TN 78 64R (1 3 Hz) 64G (100%) 81R 47 37 38
t = f (I)+V< V> V<, t=f(V) f<, f> P V/f V2/V1, I2/I1 Incoup. T.C.S. P>, P< 1/xd I2>, t =f(I2) Imin> Istart2t I2t R<
I>, V< V0(3rd harm.)
RREF< RSEF<
df/dt > > A, B, C I< (RTD)
X X X
1) Optional for all function groups 2) Available as of version V4.1 and higher Siemens SIP 6.2 2001
n Operation User-friendly local operation Many advantages are already to be found on the clear and user-friendly front panel: n Positioning and grouping of the keys supports the natural operating process n Large non-reflective back-lit display n Programmable (freely assignable) LEDs for important messages
n Arrows arrangement of the keys for easy navigation in the function tree n Operator-friendly input of the setting values via the numeric keys or DIGSI 4 n Four programmable keys for frequently used functions >at the press of a button< Local operation All operator actions can be executed and information displayed on an integrated user interface:
Fig. 1 SIPROTEC 4 7UM62
On the LCD display, process and device information can be displayed as text in various lists. Frequently displayed information includes protection setting values, metered values, protection information, general indications and alarms as well as binary information on inputs and outputs.
t
Fourteen configurable (parameterizable) LEDs are used to display any process or device information. The LEDs can be labeled based on user requirements. An LED reset key resets the LEDs.
LSP2287-afpen.eps
s s s
Four configurable function keys permit the user to execute frequently used actions fast and simple. Typical applications include jumps to certain points in the menu tree to display the operational measured values or indications.
DIGSI 4 matrix The DIGSI 4 matrix allows the user to see the overall view of the unit configuration at a glance. For example, you can display all the LEDs that have binary inputs or show any indication that are connected to the relay. And with one click of the button connections can be switched. By utilizing filter functions, only allocated information is rendered visible. In addition, it is possible to alter the viewing modes. In Binary Output viewing mode (output relays), the tripping matrix is clearly displayed.
LSP295-afpen2.tif
LSP2294-afpen.tif
Simple protection setting The protection functions required can be selected from the wide range of functions provided (Fig. 3). This means that transparency in subsequent menus is enhanced. The newly introduced primary display (settings are related to nominal values of the object to be protected) permits standardization of the setting values. Pressing a button effects conversion to secondary values and loading into the protection unit.
LSP2293-afpen.tif
CFC: Reduced time and planning for programming logic With the help of the CFC (Continuous Function Chart), you can configure interlocks and switching sequences simply by drawing the logic sequences; no special knowledge of software is required. Logical elements, such as AND, OR and time elements, measured limit values, etc. are available. Commissioning Special attention has been paid to commissioning. All binary inputs and outputs can be read and set directly. This can simplify the wire checking process significantly for the user. For primary testing, it is possible to activate a transmission lockout to prevent any information being transmitted via the interface to the control room. On the other hand, indications can be transmitted intentionally for test purposes. SIGRA 4: Universal program for fault recording evaluation Fault recordings stored in the protection system can be visually displayed and evaluated in clear form. It is easily possible to calculate harmonics, to view individual measuring points, to display vector and locus diagrams etc. The Comtrade format makes it possible to analyze any desired fault recordings.
I4
learn n Easy to matrix f routing t r layout o n Clea equipmen eder and tion, fe n Substa nagement data ma on d protecti TIC Passwor n AM/SIMA ith the SICent w n Linked e environm ar softw tandards indows s nW
LSP2182f.tif
LSP2181f.tif
Fig. 7 IEC 60870-5-103 star-type RS232 copper conductor connection or fibre-optic connection
OLM1)
System solution SIPROTEC 4 is tailor-made for use in SIMATIC-based automation systems. Via the PROFIBUS-DP, indications (pickup and tripping) and all relevant operational measured values are transmitted from the protection unit. Via modem and service interface, the protection engineer has access to the protection devices at all times. This permits remote maintenance and diagnosis (cyclic testing). Parallel to this, local communication is possible, for example during a major inspection. Analog output 0 to 20 mA Alternatively to the serial interfaces up to two analog output modules (4 channels) can be installed in the 7UM62. Several operational measured values (I1, I2, V, P, Q, f, PF (cos ), stator, rotor) can be selected and transmitted via the 0 to 20 mA interfaces.
LSP2162f.eps
LSP2163f.eps
LSP2207f.eps
LSP2164f.eps
Earth-current differential protection (ANSI 87GN, 87TN) The earth current differential protection permits high sensitivity to single-pole faults. The zero currents are compared. On the one hand, the zero sequence current is calculated on the basis of the phase currents and on the other hand, the earth current is measured directly at the star point current transformer.
The differential and restraint quantity is generated and is fitted into the restraint characteristic (see Fig. 16). DC components in particular are suppressed by means of specially dimensioned filters. A number of monitoring processes avoid unwanted operation in the event of external short-circuits. In the case of a sensitive setting, multiple measurement ensures the necessary reliability.
However, attention must be drawn to the fact that the sensitivity limits are determined by the current transformers. The protection function is only used on generators when the neutral point is earthed with a low impedance. In the case of transformers, it is connected on the neutral side. Lowimpedance or solid earthing is also required.
10
Definite time-overcurrent protection I>, I>> (ANSI 50, 51, 67) This protection function comprises the short-circuit protection for the generator and also the backup protection for upstream devices such as transformers or power system protection. An undervoltage stage at I> maintains the pickup when during the fault the current drops below the threshold. In the case of a voltage drop on the generator terminals, the static excitation system can no longer be sufficiently supplied. This is one reason for the decreasing of the short-circuit current. The I>> stage can be implemented as high-set instantaneous trip stage. With the integrated directional function it can be used as backup protection on the transformer high voltage side. With the information of the directional element, impedance protection can be controlled via the CFC. Inverse time-overcurrent protection (ANSI 51V) This function also comprises short-circuit and back-up protection and is used for power system protection with current dependent protection devices. IEC and ANSI characteristics can be selected (Table 2). By evaluating the generator terminal voltage, the current function can be controlled. The controlled version releases the sensitive set current stage. With the restraint version the pickup value of the current is lowered linearly with decreasing voltage. The fuse-failure-monitor prevents unwanted operation.
Stator overload protection (ANSI 49) The task of the overload protection is to protect the stator windings of generator and motors from high, continuous overload currents. All load variations are evaluated by a mathematical model. The thermal effect of the rms current value forms the basis of the calculation. This conforms to IEC 60255-8. In dependency of the current the cooling time constant is automatically extended. If the ambient temperature or the temperature of the coolant are injected via a transducer (TD2) or PROFIBUS-DP, the model automatically adapts to the ambient conditions; otherwise a constant ambient temperature is assumed. Negative sequence protection (ANSI 46) Asymmetrical current loads in the three phases of a generator cause a temperature rise in the rotor because of the negative sequence field produced. This protection detects an asymmetrical load in threephase generators. It functions on the basis of symmetrical components and evaluates the negative sequence of the phase currents. The thermal processes are taken into account in the algorithm and form the inverse characteristic. In addition, the negative sequence is evaluated by an independent stage (alarm and trip) which are supplemented by a time-delay element (see Fig. 17). In the case of motors, the protection function is also used to monitor a phase failure.
IEC characteristic Normal inverse 0.14 t= Tp 0 , 02 I 1 I p Very inverse 13.5 t= Tp 1 I 1 I p Extremely inverse 80 t= Tp 2 I I 1 p
ANSI characteristic Inverse 8.9341 t= + 0.17966 D 2 . 0938 I 1 I p Moderately inverse 0.0103 t= + 0.0228 D 0 . 02 I 1 Ip Very inverse 3.922 t= + 0.0982 D 2 I 1 I p Extremely inverse 5.64 t = + 0.02434 D 2 I 1 I p Definite inverse 0.4797 t= + 0.21359 D 1. 5625 I 1 Ip
11
12
Overvoltage protection (ANSI 59) This protection prevents insulation faults that result when the voltage is too high. Either the maximum line-to-line voltages or the phase-to-earth voltages (for low-voltage generators) can be evaluated. The measuring results of the line-to-line voltages are independent of the neutral point displacement caused by earth faults. This function is implemented in two stages. Frequency protection (ANSI 81) The frequency protection prevents an unpermissible stress of the equipment (e.g. turbine) in case of under or overfrequency. It also serves as an monitoring and control element. The function has four stages; the stages can be implemented either as underfrequency or over-frequency protection. Each stage can be delayed separately. Even in the case of voltage distortion, the frequency measuring algorithm reliably identifies the fundamental waves and determines the frequency extremely precise. Frequency measurement can be blocked by using an undervoltage stage. Overexcitation protection Volt/Herz (ANSI 24) The overexcitation protection serves for detection of an unpermissible high induction (proportional to V/f) in generators or transformers, which leads to a thermal overloading. This may occur when starting up, shutting down under full load, with weak systems or under isolated operation. The inverse characteristic can be set via eight points derived from the manufacturer data. In addition, a definite-time alarm stage and an instantaneous stage can be used. For calculation of the V /f ratio, frequency and also the highest of the three line-to-line voltages are used. The frequency range that can be monitored comprises 11 to 69 Hz.
90 % stator earth-fault protection, non-directional, directional (ANSI 59N, 64G, 67G) Earth faults manifest themselves in generators that are operated in isolation by the occurance of a displacement voltage. In case of unit connections, the displacement voltage is an adequate, selective criterion for protection. For the selective earth-fault detection, the direction of the flowing earth-current has to be evaluated too, if there is a direct connection between generator and busbar. The protection relay measures the displacement voltage at a v.t. located at the transformer star point or at the broken delta-winding of a v.t. As an option it is also possible to calculate the zero-sequence voltage from the phase-to-earth voltages. Depending on the load resistor selection 90 to 95 % of the stator winding of a generator can be protected. A sensitive current input is available for the earth current measurement. This input should be connected to a core-balance current transformer. The fault direction is deduced from the displacement voltage and earth current. The directional characteristic (straight line) can be easily adapted to the system conditions. Effective protection for direct connection of a generator to a busbar can therefore be created. During startup, it is possible to switch over from the directional to the displacement voltage measurement via an externally injected signal. Depending on the protection setting, various earth-fault protection concepts can be implemented with this function (see Figs. 23 to 26).
Sensitive earth-fault protection (ANSI 50/51GN, 64R) The sensitive earth-current input can also be used as separate earth-fault protection. It is of two-stage form. Secondary earth currents of 2 mA or higher can be reliably handled. Alternatively, this input is also suitable as rotor earth-fault protection. A voltage with rated frequency (50 or 60 Hz) is connected in the rotor circuit via the interface unit 7XR61. If a higher earth current is flowing, a rotor earth fault has occurred. Measuring circuit monitoring is provided for this application (see Fig. 29). 100% stator earth-fault protection with 3rd harmonic (ANSI 59TN, 27TN (3rdH.)) Owing to the design, the generator produces a 3rd harmonic that forms a zero phasesequence system. It is verifiable by the protection on a broken delta winding or on the neutral transformer. The magnitude of the voltage amplitude depends on the generator and its operation. In the event of an earth fault in the vicinity of the neutral point there is a change in the amplitude of the 3rd harmonic voltage (dropping in the neutral point and rising at the terminals).
Depending on the connection the protection must be set either as undervoltage or overvoltage protection. It can also be delayed. So as to avoid overfunction, the active power and the positive sequence voltage act as enabling criteria. The final protection setting can be made only by way of a primary test with the generator. Breaker failure protection (ANSI 50BF) In the event of scheduled downtimes or a fault in the generator, the generator can remain on line if the circuitbreaker is defective and could suffer substantial damage. Breaker failure protection evaluates a minimum current and the circuit-breaker auxiliary contact. It can be started by internal protective tripping or externally via binary input. Two-channel activation avoids overfunction (see Figure 20).
13
tTrip Istart
Tripping time Permissible start-up current tstart max Permissible start-up time Measured rms current Irms value Calculation is not started until the current Irms lies above an adjustable response value (e.g. 2 IN, MOTOR). If the permissible locked-rotor time is less than the permissible start-up time (motors with a thermally critical rotor), a binary signal is set to detect a locked rotor by means of a tachometer generator. This binary signal releases the set locked-rotor time, and tripping occurs after it has elapsed.
14
DC voltage time protection/DC current time protection (ANSI 59N (DC) 51N(DC)) Hydroelectric generators or gas turbines are started by way of frequency starting converters. An earth fault in the intermediate circuit of the frequency starting converter causes DC voltage displacement and thus a direct current. As the neutral or earthing transformers have a lower ohmic resistance than the voltage transformers, the largest part of the direct current flows through them, thus posing a risk of destruction from thermal overloading. As shown in Fig. 28, the direct current is measured by means of a shunt transformer (measuring transducer) connected directly to the shunt. Voltages or currents are fed to the 7UM62 depending on the version of the measuring transducer. The measurement algorithm filters out the DC component and takes the threshold value decision. The protection function is active as from 0 Hz. If the measuring transducer transmits a voltage for protection, the connection must be interference-free and must be kept short. The implemented function can also be used for special applications. Thus, the rms value can be evaluated for the quantity applied at the input over a wide frequency range. Overcurrent protection during start-up (ANSI 51) Gas turbines are started by means of frequency starting converters. Overcurrent protection during start-up measures shortcircuits in the lower frequency range (as from about 5 Hz) and is designed as independent overcurrent-time protection. The pick-up value is set below the rated current. The function is only active during start-up. If frequencies are higher than 10 Hz, sampling frequency correction takes effect and the further shortcircuit protection functions are active.
Out-of-step protection (ANSI 78) This protection function serves to measure power swings in the system. If generators feed to a system short-circuit for too long, low frequency transient phenomena (active power swings) between the system and the generator may occur after fault clearing. If the center of power swing is in the area of the block unit, the active power surges lead to unpermissible mechanical stressing of the generator and the turbine. As the currents and voltages are symmetrical, the positive sequence impedance is calculated on the basis of their positive-sequence components and the impedance trajectory is evaluated. Symmetry is also monitored by evaluation of the negative-phase-sequence current. Two characteristics in the R/X diagram describe the active range (generator, unit transformer or power system) of the out-of-step protection. The associated counters are incremented depending on the range of the characteristic in which the impedance vector enters or departs. Tripping occurs when the set counter value is reached. The counters are automatically reset if power swing no longer occurs after a set time. By means of an adjustable pulse, every power swing can be signaled. Expansion of the characteristic in the R direction defines the power swing angle that can be measured. An angle of 120 is practicable. The characteristic can be tilted over an adjustable angle to adapt to the conditions prevailing when several parallel generators feed into the system.
Inverse undervoltage protection (ANSI 27) Motors tend to fall out of step when their torque is less than the breakdown torque. This, in turn, depends on the voltage. On the one hand, it is desirable to keep the motors connected to the system for as long as possible while, on the other hand, the torque should not fall below the breakdown level. This protection task is realized by inverse undervoltage protection. The inverse characteristic is started if the voltage is less than the pick-up threshold Vp<. The tripping time is inversely proportional to the voltage dip (see equation). The protection function uses the positive-sequence voltage, for the protection decision.
System disconnection E.g., in-plant generators feed directly into a system. The incoming line is generally the legal entity boundary between the system owner and the in-plant generator. If the incoming line fails as the result of auto-reclosure, for instance, a voltage or frequency deviation may occur depending on the power balance at the feeding generator. Asynchronous conditions may arise in the event of connection, which may lead to damage on the generator or the gearing between the generator and the turbine. Besides the classic criteria such as voltage and frequency, the following two criteria are also applied (vector jump, rate-of-frequencychange protection, see page 16).
t TRIP =
I I
V Vp
T M
tTRIP V Vp TM
15
Fig. 22 Temperature characteristic at rotor and in thermal replica of the rotor (multiple start-ups)
As the fan provides no forced cooling when the motor is off, it cools down more slowly. Depending on the operating state, the protection function controls the cooling time constant. A value below a minimum current is an effective changeover criterion. External trip coupling For recording and processing of external trip information there are 4 binary inputs. They are provided for information from the Buchholz relay or generator-specific commands and act like a protective function. Each input initiates a fault event and can be individually delayed by a timer. Trip circuit supervision (ANSI 74TC) One or two binary inputs can be used for monitoring the circuit-breaker trip coil including its incoming cables. An alarm signal occurs whenever the circuit is interrupted. Phase rotation reversal If the relay is used in a pumped-storage power plant, matching to the prevailing rotary field is possible via a binary input (generator/motor operation via phase rotation reversal).
2 pre-definable parameter groups In the protection the setting values can be stored in two datasets. In addition to the standard parameter group, the second group is provided for certain operating conditions (pumped-storage power stations). It can be activated via binary input, local control or DIGSI 4. Lockout (ANSI 86) All binary outputs (alarm or trip relays) can be stored like LEDs and reset using the LED reset key. The lockout state is also stored in the event of supply voltage failure. Reclosure can only occur after the lockout state is reset.
Fuse failure and other monitoring The relay comprises high-performance monitoring for the hardware and software. The measuring circuits, analog-digital conversion, power supply voltages, memories and software sequence (watchdog) are all monitored. The fuse failure function detects failure of the measuring voltage due to short-circuit or open circuit of the wiring or v.t. and avoids overfunction of the undervoltage elements in the protection functions. The positive and negative-sequence system (voltage and current) are evaluated. Filter time All binary inputs can be subjected to a filter time (indication suppression).
16
Connections/Typical applications Direct generator-bus connection Fig. 23 illustrates the recommended standard connection if several generators supply one busbar. Phase-to-earth faults are disconnected by employing the directional earth-fault criterion. The earth-fault current is driven through the cables of the system. If this is not sufficient, an earthing transformer connected to the busbar supplies the necessary current (maximum approximately 10 A) and permits a protection range of up to 90 %. The earth-fault current should be detected by means of core-balance current transformers in order to achieve the necessary sensitivity. The displacement voltage can be used as earth-fault criterion during starting operations until synchronization is achieved. Differential protection embraces protection of the generator and of the outgoing cable. The permissible cable length and the current transformer design (permissible load) are mutually dependent. Recalculation is advisable as from lengths of more than 100 m.
Fig. 23
17
Fig. 24
18
Unit connection with isolated star point This configuration of unit connection is a variant to be recommended (see Figure 25). Earth-fault detection is effected by means of the displacement voltage. In order to prevent unwanted operation in the event of earth faults in the system, a load resistor must be provided at the broken delta winding. Depending on the plant, a voltage transformer with a high power (VA) may in fact be sufficient. If not, an earthing transformer should be employed. The available measuring winding can be used for the purpose of voltage measurement. In the application example, differential protection is intended for the generator. The unit transformer is protected by its own differential relay (e.g. 7UT612). As indicated in the figure, additional protection functions are available for the other inputs. They are used on larger generator/transformer units (see also Figs. 28 and 30).
Fig. 25
19
Fig. 26
20
Voltage transformer in open delta connection (V-connection) Protection can also be readily implemented on voltage transformers in open delta connection. Fig. 27 shows the connection involved. If necessary, the operational measured values for the phase-to-earth voltages can be slightly asymmetrical. If this is undesirable, the neutral point (R16) can be connected to earth via a capacitor. In the case of open delta connection, it is not possible to calculate the displacement voltage from the secondary voltages. It must be passed to the protection unit along a different path (for example, voltage transformer at the generator neutral point or from the earthing transformer). 100% stator earth-fault protection, earth-fault protection during start-up With reference to the example of the neutral transformer, Fig. 28 shows interfacing of 100% stator earth-fault protection with voltage injection of 20 Hz. The same interfacing connection also applies to the broken delta winding of the earthing transformer. The 20 Hz generator can be connected both to the DC voltage and also to a powerful voltage transformer (>100 VA). The load of the current transformer 4NC1225 should not exceed 0.5 . The 7XT33, 7XT34 and load resistance connection must be established with a low resistance (RConnection < RL). If large distances are covered, the devices are accommodated in the earthing cubicle. Connection of the DC voltage protection function (TD 1) is shown for systems with a starting converter. Depending on the device selection, the 7KG6 boosts the measured signal at the shunt to 10 V or 20 mA. The TD 1 input can be jumpered to the relevant signal.
Fig. 27
Fig. 28
21
Fig. 29
Fig. 30
22
Protection of an asynchronous motor Fig. 31 shows typical connection of the protection function to a large asynchronous motor. Differential protection embraces the motor including the cable. Recalculation of the permissible current transformer burden is advisable as from lengths of more than 100 m. The voltage for voltage and displacement voltage monitoring is generally tapped off the busbar. If several motors are connected to the busbar, earth faults can be detected with the directional earth-fault protection and selective tripping is possible. A core balance current transformer is used to detect the earth current. The chosen pickup value must be slightly higher if there are several cables in parallel. The necessary shutdown of the motor in the event of idling can be realized with active power monitoring.
Fig. 31
23
IEE1 Sensitive earth-fault protection Directional stator earth-fault protection Rotor earth-fault protection (fn, R-measuring) 100% stator earth-fault protection with 20 Hz voltage Earth-current differential protection
1) optional (eitherIEE1 or IEE2) Table 3: Multiple use of analog inputs
IEE2 X1) X
VE
X1)
X X X
X X X1) X1)
TD1 Injection of excitation voltage DC voltage time/DC current time protection Injection of a temperature Rotor earth-fault protection (1 to 3 Hz) Processing of analog values via CFC
Table 4: Multiple use of measuring transducers
TD2
TD3 X
X X X X X X X
R BC + R Ct K *ALF R BN + R Ct
Knee-point voltage
IEC British Standard ANSI
V = K ALF (R Ct + R BN )I sN
Ktd IpSSC IpN
V=
(R
Ct
+ R BN )I sN 1,3
K ALF
rated transient dimensioning factor primary symmetrical short-circuit current rated primary current transformer current connected burden resistance rated burden resistance secondary winding resistance short-circuit voltage (impedance voltage) subtransient reactance rated secondary current transformer current network time constant
24
Technical data
Hardware
Analog input Rated frequency Rated current IN Earth current, sensitive IEmax Rated voltage VN (at 100 V) Measuring transducer Power consumption with IN = 1 A with IN = 5 A for sensitive earth current voltage inputs (with 100 V) Capability in CT circuits thermal (rms values) 50 or 60 Hz 1 or 5 A 1.6 A 100 to 125 V - 10 to + 10 V (Ri = 1 M) or - 20 to + 20 mA (Ri = 10 ) approx. 0.05 VA approx. 0.3 VA approx. 0.05 VA approx. 0.3 VA 100 IN for 1 s 30 IN for 10 s 4 IN continuous 250 IN (one half cycle) 300 A for 1 s 100 A for 10 s 15 A continuous 750 A (one half cycle) 230 V continuous 60 V continuous 100 mA continuous 24 to 48 V DC 60 to 125 V DC 110 to 250 V DC and 115 V AC with 50/60 Hz 20 to +20 % 15 % approx. 5.3 W approx. 5.5 W approx. 12 W approx. 15 W 50 ms 20 ms 7 15 14 to 19 V DC or 66 to 88 V DC 300 V DC approx. 1.8 mA 12 (1 NO; 4 optional as NC via jumper) 21 (1 NO; 5 optional as NC via jumper) 1000 W / VA 30 VA 40 W 25 VA 250 V 5 A continuous 30 A for 0.5 seconds 1 1 14
dynamic (peak) Earth current, sensitive dynamic (peak) Capability in voltage paths Capability of measuring transducer as voltage input as current input Power supply Rated auxiliary voltage
Permitted tolerance Superimposed (peak to peak) Power consumption during normal operation 7UM621 7UM622 during pickup with all inputs and outputs activated 7UM621 7UM622 Bridging time during auxiliary voltage failure at Vaux = 48 V and Vaux 110 V at Vaux = 24 V and Vaux = 60 V Binary inputs Number 7UM621 7UM622 2 pickup thresholds Range is selectable with jumpers Maximum permissible voltage Current consumption, energized Number 7UM621 7UM622 Switching capacity make break break (for resistive load) break (for L/R 50 ms) Switching voltage Permissible current Number RUN (green) ERROR (red) Assignable LED (red)
Output relays
LED
25
Unit version
7XP20 housing Degree of protection acc. to EN 60529 For surface-mounting housing For flush-mounting housing front rear For the terminals Weight Flush-mounting housing 7UM621 (1/2 x 19 ) 7UM622 (1/1 x 19l) Surface-mounting housing 7UM621 (1/2 x 19) 7UM622 (1/1 x 19)
Serial interfaces
Operating interface for DIGSI 4 Connection Baud rate Time synchronization IRIG B / DCF 77 signal Connection Voltage levels Service/modem interface (Port C) for DIGSI 4 / Modem / Service System interface (Port B) IEC 60870-5-103 PROFIBUS DP MODBUS RTU Isolated RS232/RS485 Test voltage Distance for RS232 Distance for RS485 Isolated RS232/RS485 Baud rate Test voltage Permissible distance for RS232 Permissible distance for RS485 PROFIBUS RS485 Test voltage Baud rate Permissible distance PROFIBUS fiber-optic cable Baud rate Optical wavelength Permissible path attenuation Bridgeable distance Analog output module (electrical) Non-isolated, RS232, front panel; 9-pin subminiature connector 4800 to 115200 Bauds 9-pin subminiature connector, terminal with surface-mounting case selectable 5 V, 12 V or 24 V 9-pin subminiature connector 500 V / 50 Hz Max. 15 m Max. 1000 m 9-pin subminiature connector 4800 to 115200 Bauds 500 V / 50 Hz Max. 15 m Max. 1000 m 500 V / 50 Hz Max. 12 MBauds 1000 m at 93,75 kBauds; 100 m at 12 MBauds Integrated ST-connector; Single or double ring Max. 1.5 MBauds = 820 nm Max. 8 dB for glass-fiber 62.5/125 m Max. 1.5 km 2 ports with 0 to 20 mA
Electrical tests
Specifications Standards IEC 60255 (product standards) ANSI/IEEE C37.90.0/.1/.2 UL 508 DIN 57435 part 303 For further standards see below IEC 60255-5 2.5 kV (rms.), 50/60 Hz
Insulating tests
Standards Voltage test (100 % test) All circuits except for auxiliary supply, binary inputs communication and time synchronization interfaces Voltage test (100 % test) Auxiliary voltage and binary inputs Voltage test (100 % test) only isolated communication interfaces and time synchronization interface Surge voltage test (type test) All circuits except for communication interfaces and time synchronization interface, class III
3.5 kV DC 500 V (rms value), 50/60 Hz 5 kV (peak); 1.2/50 s; 0.5 J; 3 positive and 3 negative surges at intervals of 5 s
26
Standards
High frequency test IEC 60255-22-1, class III and DIN 57435 part 303, class III Discharge of static electricity IEC 60255-22-2 class IV EN 61000-4-2, class IV Exposure to RF field, non-modulated IEC 60255-22-3 (report), class III Exposure to RF field, amplitude-modulated IEC 61000-4-3, class III Exposure to RF field, pulse-modulated IEC 61000-4-3/ ENV 50204, class III Fast transient interference bursts IEC 60255-22-4, IEC 61000-4-4, class IV High-energy surge voltages (SURGE), IEC 61000-4-5 installation class III Auxiliary supply Measurement inputs, binary inputs and relay outputs Conducted RF, amplitude-modulated IEC 61000-4-6, class III Magnetic field with power frequency IEC 61000-4-8, class IV; IEC 60255-6 Oscillatory surge withstand capability ANSI/IEEE C37.90.1 Fast transient surge withstand capability ANSI/IEEE C37.90.1 Radiated electromagnetic interference ANSI/IEEE C37.90.2 Damped oscillations IEC 60894, IEC 61000-4-12 EMC tests for interference emission (type tests) Standard Radio interference voltage on lines only auxiliary supply IEC-CISPR 22 Interference field strength IEC-CISPR 22
IEC 60255-6, IEC 60255-22 (product standards) EN 50082-2 (generic standard) DIN 57 435 part 303 2.5 kV (peak value), 1 MHz; = 15 ms 400 pulses per s; duration 2 s 8 kV contact discharge; 15 kV air discharge; both polarities; 150 pF; Ri = 330 10 V/m; 27 to 500 MHz 10 V/m; 80 to 1000 MHz; 80 % AM; 1 kHz 10 V/m; 900 MHz; repetition frequency 200 Hz; duty cycle 50 % 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms; repetition frequency 300 ms; both polarities; Ri = 50 ; test duration 1 min Impulse: 1.2/50 s common (longitudinal) mode: 2 kV; 12 , 9 F differential (transversal) mode:1 kV; 2 , 18 F common (longitudinal) mode: 2 kV; 42 , 0.5 F differential (transversal) mode: 1 kV; 42 , 0.5 F 10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz 30 A/m continuous; 300 A/m for 3 s; 50 Hz 0.5 mT; 50 Hz 2.5 to 3 kV (peak); 1 to 1.5 MHz damped wave; 50 surges per second; Duration 2 s; Ri = 150 to 200 4 to 5 kV; 10/150 ns; 50 impulses per second; both polarities; duration 2 s ; Ri = 80 35 V/m; 25 to 1000 MHz 2.5 kV (peak value), polarity alternating 100 kHz, 1 MHz, 10 and 50 MHz, Ri = 200 EN 50081-1 (generic standard) 150 kHz to 30 MHz class B 30 to 1000 MHz class B
Shock IEC 60255-21-2, class 1 IEC 60068-2-27 Vibration during earthquake IEC 60255-21-2, class 1 IEC 60068-3-3
27
Shock IEC 60255-21-2, class 1 IEC 60068-2-27 Continuous shock IEC 60255-21-2, class 1 IEC 60068-2-29 Climatic stress Temperatures Standards Recommended temperature during operation Temporary permissible temperature limit during operation Limit temperature during storage Limit temperature during transport Storage and transport with standard factory packaging Humidity
IEC 60255-21 and IEC 60068-2 Sinusoidal 5 to 8 Hz: 7,5 mm amplitude; 8 to 150 Hz: 2 g acceleration Frequency sweep 1 octave/min 20 cycles in 3 orthogonal axes Half-sinusoidal Acceleration 15 g, duration 11 ms, 3 shocks each in both directions 3 axes Half-sinusoidal Acceleration 10 g, duration 16 ms, 1000 shocks in both directions of the 3 axes IEC 60255-6 - 5 to +55 C 25 to 131 F - 20 to +70 C - 4 to 158 F (The legibility of the display may be affected above 55 C/131 F) 25 to +55 C -13 to 131 F 25 to +70 C -13 to 158 F
Permissible humidity stress Annual average 75 % relative humidity; on 56 We recommend arranging the units in such a way days a year up to 93 % relative humidity; condenthat they are not exposed to direct sunlight or pronounced sation during operation is not permitted temperature changes that could cause condensation
Functions
Common Definite time-overcurrent protection, directional ANSI 50, 51, 67 Frequency range Setting ranges Overcurrent I>, I>> Time delay T Undervoltage seal-in V< Seal-in time of V< Angle of the directional element (at I>>) Times Pickup time I>, I>> at 2 times of set value at 10 times of set value Drop-off time I>, I>> Drop-off ratio Drop-off ratio V< Tolerances Current pickup (starting) I>, I>> Undervoltage seal-in V< Angle of the directional element Time delays Setting ranges Pickup overcurrent IP Time multiplier IEC-characteristics T Time multiplier ANSI- characteristics D Undervoltage release V< Trip characteristics IEC ANSI Pickup threshold Drop-off threshold Tolerances Pickup threshold IP Pickup threshold V< Time for 2 I/IP 20 11 to 69 Hz 0.05 to 20 A (steps 0.01 A); 5 times at IN= 5 A 0 to 60 s (steps 0.01 s) or indefinite 10 to 125 V (steps 0.1 V) 0.1 to 60 s (steps 0.01 s) 90 to + 90 (steps 1)
approx. 35 ms approx. 25 ms approx. 50 ms I>: 0.95; I>>: 0.9 to 0.99 (steps 0.01) approx. 1.05 1 % of set value or 10/50 mA 1 % of set value or 0.5 V 1 1 % or 10 ms 0.1 to 4 A (steps 0.01 A); 5 times at IN = 5A 0.05 to 3.2 s (steps 0,01 s) or indefinite 0.5 to 15 (steps 0.01) or indefinite 10 to 125 V (steps 0.1 V) Normal inverse; very inverse; extremely inverse Inverse; moderately inverse; very inverse; extremely inverse; definite inverse approx. 1.1 IP approx. 1.05 IP for IP/IN 0.3 1 % of set value or 10/50 mA 1 % of set value or 0.5 V 5 % of nominal value + 1 % current tolerance or 40 ms
28
Setting ranges Factor k according to IEC 60255-8 Time constant Time delay factor at stand still Alarm overtemperature Alarm/Trip Overcurrent alarm stage IAlarm Temperature at IN Scaling temperature of cooling medium Limit current ILimit Reset time at emergency start Drop-off ratio / Trip / Alarrm I/IAlarm Tolerances regarding k x IN regarding trip time
0.5 to 2.5 (steps 0.01) 30 to 32000 s (steps 1 s) 1 to 10 (steps 0.01) 70 to 100 % related to the trip temperature (steps 1 %) 0.1 to 4 A (steps 0.01 A); 5 times at IN = 5 A 40 to 200 C (steps 1 C) or 104 to 392 F (steps 1 F) 40 to 300 C (steps 1 C) or 104 to 572 F (steps 1 F) 0.5 to 8 A (steps 0.01), 5 times at IN = 5 A 20 to 150000 s (steps 1 s) Drop-off with Alarrn approx. 0.99 approx. 0.95 2 % or 10/50 mA; class 2 % according to IEC 60255-8 3 % or 1 s: class 3 % according to IEC 60255-8 for I/(k IN)>1.25 3 to 30 % (steps 1 %) 10 to 100 % (steps 1 %) 0 to 60 s (steps 0.01 s) or indefinite 2 to 40 s (steps 0.1 s) 0 to 50000 s (steps 1 s) approx. 50 ms approx. 50 ms approx. 0.95 Drop-off at fall below of I2 perm. 3 % of set value or 0.3 % negative sequence 1 % or 10 ms 5 % of set point +1 % current tolerance or 600 ms 0.25 to 3.0 (steps 0.01) 50 to 120 (steps 1 ) 0 to 50 s (steps 0.01 s) or indefinite 10 to 125 V (steps 0.1 V) approx. 60 ms approx. 50 ms approx. 0.95 approx. 1.1 3 % of set value 1 electrical 1 % or 0.5 V 1 % or 10 ms - 0.5 to 30 % (steps 0.01 %) 0 to 60 s (steps 0.01 s) or indefinite approx. 360 ms (50 Hz); approx. 300 ms (60 Hz) approx. 360 ms (50 Hz); approx. 300 ms (60 Hz) approx. 0.6 0.25 % SN 3 % set value 1 % or 10 ms
Setting ranges Permissible negative sequence I2 perm. /IN Definite time trip stage I2 >>/IN Time delays TAlarm; TI2>> Negative sequence factor K Cooling down time TCooling Times Pickup time (definite stage) Drop-off time (definite stage) Drop-off ratios I2 perm.; I2 >> Drop-off ratio thermal stage Tolerances Pickup values I2 perm.; I2 >> Time delays Thermal characteristic Time for 2 I2/I2 perm. 20 Setting ranges Conductance thresholds 1/xd characteristic (3 characteristics) Inclination angle 1, 2, 3 Time delay T Undervoltage blocking V< Times Stator criterion 1/xd characteristic; Undervoltage blocking Drop-off ratio Stator criterion 1/xd characteristic; Undervoltage blocking Tolerances Stator criterion 1/xd characteristic Stator criterion Undervoltage blocking Time delays T Setting ranges Reverse power PRev.>/SN Time delays T Times Pickup time Drop-off time Drop-off ratio PRev.> Tolerances Reverse power PRev.> Time delays T
29
Setting ranges Forward power PForw.</SN Forward power PForw.>/SN Time delays T Times Pick-up time (accurate measuring) Pick-up time (fast measuring) Drop-off time (accurate measuring) Drop-off time (fast measuring) Drop-off ratio PForw.< Drop-off ratio PForw.> Tolerances Active power PForw.<, PForw.>
0.5 to 120 % (steps 0.1 %) 1 to 120 % (steps 0.1 % 0 to 60 s (steps 0.01 s) or indefinite approx. 360 ms (50 Hz); approx. 300 ms (60 Hz) approx. 60 ms (50 Hz); approx. 50 ms (60 Hz) approx. 360 ms (50 Hz); approx. 300 ms (60 Hz) approx. 60 ms (50 Hz); approx. 50 ms (60 Hz) 1.1 or 0.5 % of SN approx. 0.9 or 0,5 % of SN 0.25 % SN 3 % of set value at Q < 0.5 SN at accurate measuring 0.5 % SN 3 % of set value at Q < 0.5 SN at fast measuring 1 % or 10 ms 0.1 to 20 A (steps 0.01 A); 5 times at IN = 5A 10 to 125 V (steps 0.1V) 0.05 to 130 (steps 0.01 ) 0.05 to 65 (steps 0.01 ) 0.05 to 65 (steps 0.01 ) 0 to 60 s (steps 0.01 s) or indefinite approx. 40 ms approx. 50 ms approx. 0.95 approx. 1.05 1 % of set value or 10/50 mA 1 % of set value or 0.5 V |Z/Z| 5 % for 30 K 90 1% or 10 ms 10 to 125 V (steps 0.1 V) 0 to 60 s (steps 0.01 s) or indefinite 0.1 to 5 s (steps 0.01 s) approx. 50 ms approx. 50 ms 1.01 or 0.5 V 1 % of set value or 0.5 V 1 % or 10 ms 1 % of measured value of voltage 30 to 170 V (steps 0.1 V) 0 to 60 s (steps 0.01 s) or indefinite approx. 50 ms approx. 50 ms 0.9 to 0.99 (steps 0.01) 1 % of set value 0.5 V 1 % or 10 ms 4 40 to 65 Hz (steps 0.01 Hz) 3 stages 0 to 100 s, 1 stage up to 600 s (steps 0.01 s) 10 to 125 V (steps 0.1 V) approx. 100 ms approx. 100 ms approx. 20 mHz approx. 1.05 10 mHz (at V> 0.5 VN) 1 % of set value or 0.5 V 1 % or 10 ms
Time delays T Impedance protection ANSI 21 Setting ranges Overcurrent pickup I> Undervoltage seal-in V< Impedance Z1 (related to IN =1 A) Impedance Z1B (related to IN =1 A) Impedance Z2 (related to IN =1 A) Time delays T Times Shortest tripping time Drop-off time Drop-off ratio Overcurrent pickup I> Undervoltage seal-in V< Tolerances Overcurrent pickup I> Undervoltage seal-in V< Impedance measuring Z1, Z2 Time delays T Setting range Undervoltage pickup V<, V<<, Vp< (positive sequence as phase-to-phase values) Time delays T Time multiplier TM Times Pickup time V<, V<< Drop-off time V<, V<< Drop-off ratio V<, V<<, Vp< Tolerances Voltage limit values Time delays T Inverse-time characteristic Setting ranges Overvoltage pickup V>, V>> (maximum phase-to-phase voltage or phase-to-earth-voltage) Time delays T Time Pickup times V>, V>> Drop-off times V>, V>> Drop-off ratio V>, V>> Tolerances Voltage limit value Time delays T Setting ranges Steps; selectable f>, f< Pickup values f>, f< Time delays T Undervoltage blocking V1< Times Pickup times f>, f< Drop-off times f>, f< Drop-off difference f Drop-off ratio V1< Tolerances Frequency Undervoltage blocking Time delays T
30
Setting ranges Pickup threshold alarm stage Pickup threshold V/f>>-stage Time delays T Characteristic values of V/f and assigned times t(V/f ) Cooling down time TCooling Times (Alarm and V/f>>-stage) Pickup times at 1.1 of set value Drop-off times Drop-off ratio (alarm, trip) Tolerances V/f-Pickup Time delays T Thermal characteristic (time) Setting ranges Displacement voltage V0 > Earth current 3I0> Angle of direction element Time delays T Times Pickup times V0>, 3I0> Drop-off times V0>/ 3I0> Drop-off ratio V0>, 3I0> Drop-off difference angle Tolerances Displacement voltage Earth current Time delays T Setting ranges Earth current pickup IEE>, IEE>> Time delays T Measuring circuit supervision IEE< Times Pickup times Drop-off times Measuring circuit supervision Drop-off ratio IEE>, IEE>> Drop-off ratio measuring circuit supervision IEE< Tolerances Earth current pickup Time delays T Setting ranges Displacement voltage V0 (3rd harm.)>, V0 (3rd harm.)< Time delay T Active power release Positive sequence voltage release Times Pickup time Drop-off time Drop-off ratio Undervoltage stage V0 (3rd harm.)< Overvoltage stage V0 (3rd harm.)> Active power release Positive sequence voltage release Tolerances Displacement voltage Time delay T Setting ranges Current thresholds I>BF Time delay BF-T Time Pickup time Drop-off time Tolerances Current threshold I>BF/IN Time delay T
1 to 1.2 (steps 0.01) 1 to 1.4 (steps 0.01) 0 to 60 s (steps 0.01 s) or indefinite 1.05/1.1/1.15/1.2/1.25/1.3/1.35/1.4 0 to 20000 s (steps 1s) 0 to 20000 s (steps 1s) approx. 60 ms approx. 60 ms 0.95 3 % of set value 1 % or 10 ms 5 % rated to V/f or 600 ms 2 to 125 V (steps 0.1 V) 2 to 1000 mA (steps 1 mA) 0 to 360 (steps 1 ) 0 to 60 s (steps 0,01 s) or indefinite approx. 50 ms approx. 50 ms 0.7 10 directed to power system 1 % of set value or 0.5 V 1 % of set value or 0.5 mA 1 % or 10 ms 2 to 1000 mA (steps 1 mA) 0 to 60 s (steps 0.01 s) or indefinite 1.5 to 50 mA (steps 0.1 mA) approx. 50 ms approx. 50 ms approx. 2 s 0.95 or 1 mA approx. 1.1 or 1 mA 1 % of set value or 0.5 mA 1 % or 10 ms 0.2 to 40 V (steps 0.1 V) 0 to 60 s (steps 0.01 s) or indefinite 10 to 100 % (steps 1 %) or indefinite 50 to 125 V (steps 0.1 V) or indefinite approx. 80 ms approx. 80 ms approx. 1.4 approx. 0.6 approx. 0.9 approx. 0.95 3 % of set value or 0.1 V 1 % or 10 ms 0.04 to 1 A (steps 0.01 A) 0.06 to 60 s (steps 0.01 s) or indefinite approx. 50 ms approx. 50 ms 1 % of set value or 10/50 mA 1 % or 10 ms
100 % stator earth-fault protection with 3rd harmonic ANSI 59TN, 27TN (3rd H.)
31
Setting ranges Current pickup I>>> Voltage release V1< Time delay Drop-off time Times Reaction time Drop-off time Drop-off ratio I>>> Drop-off ratio V1< Tolerances Current pickup Undervoltage seal-in V1< Time delay T Setting ranges Differential current IDiff>IN High-current stage IDiff>>IN Inrush stabilization ratio I2fN/IN Harmonic stabilization ratio InfN/IN (n=3rd or 4rd or 5rd harmonics) Additional trip time delay T Times Pickup time (IDiff 1.5 setting value IDiff >) Pickup time (IDiff 1.5 setting value IDiff>>) Drop-off time Drop-off ratio Tolerances Pickup characteristic Inrush stabilization Additional time delays
0.1 to 20 A (steps 0.1 A); 5 times at IN= 5 A 10 to 125 V (steps 1 V) 0 to 60 s (steps 0.01 s) or indefinite 0 to 60 s (steps 0.01 s) or indefinite approx. 25 ms approx. 35 ms approx. 0.8 approx. 1.05 5 % of set value or 20/100 mA 1 % of set value or 0.5 V 1 % or 10 ms 0.05 to 2 (steps 0.01) 0.8 to 12 (steps 0.1) 10 to 80 (steps 1 %) 10 to 80 (steps 1 %) 0 to 60 s (steps 0.01 s) or indefinite approx. 35 ms approx. 20 ms approx. 35 ms approx. 0.7 3 % of set value or 0.01 I/IN 3 % of set value or 0.01 I/IN 1% or 10 ms 0.01to 1 (steps 0.01) 0 to 60 s (steps 0.01 s) or indefinite approx. 50 ms approx. 50 ms approx. 0.7 3 %of set value 1 % or 10 ms 3 to 30 k (steps 1 k) 1.0 to 5.0 k (steps 0,1 k) 0 to 60 s (steps 0,01 s) or indefinite - 15 to + 15 (steps 1 ) 80 ms 80 ms approx. 1.25 approx. 5 % of set value approx. 10 % of set value 1% or 10 ms 0.15 to 3 F
Setting ranges Differential current IE-Diff >/IN Additional trip time delay Times Pickup time (IE-Diff 1.5 setting value IE-Diff >) Drop-off time Drop-off ratio Tolerances Pickup characteristic Additional time delay
Setting ranges Alarm stage RE, Alarrn < Trip stage RE, Trip < Time delays T Correction angle Times Pickup time Drop-off time Drop-off ratio Tolerances Trip stage RE, Trip <, Alarm stage RE, Alarm < Time delays T Permissible rotor earth capacitance
32
Setting ranges Alarm stage RE,Alarrn < Trip stage RE, Trip < Time delays T Pickup value of meas. circuit supervision QC< Times Pickup time Drop-off time Drop-off ratio RE Drop-off ratio QC < Tolerances Trip stage (RE,Trip <; Alarm stage RE, Alarm<) Time delays T Permissible rotor earth-capacitance
5 to 80 k (steps 1 k) 1 to 10 k (steps 1 k) 0 to 60 s (steps 0.01 s) or indefinite 0.01 to 1 mAs (steps 0.01 mAs) approx. 1 to 1.5 s (depends on frequency of 7XT71) approx. 1 to 1.5 s approx 1.25 1.2 or 0.01 mAs approx. 5 % or 0.5 k at 0.15 F CE < 1F approx. 10 % or 0.5 k at 1 F CE < 3 F 1% or 10 ms 0.15 to 3 F 20 to 500 (steps 1 ) 10 to 300 (steps 1 ) 0.02 to 1.5 A (S steps 0.01 A) 0 to 60 s (steps 0.01 s) or indefinite 0.3 to 15 V (steps 0.1 V) 5 to 40 mA (steps 1 mA) - 60 to + 60 (steps 1 ) 1.3 s 250 ms 0.8 s 120 ms approx. 1.2 to 1.7 ca. 5 % or 2 3 % or 3 mA 1 % or 10 ms 0.2 to 4 I1/IN (steps 0.1 I1/IN ) 0.05 to 1 I2/IN (steps 0.01 I2/IN ) 0.05 to 130 (steps 0.01 ) 60 to 90 (steps 1 ) 1 to 4 1 to 8 0.2 to 60 s (steps 0.01 s) 0.02 to 0.15 s (steps 0.01s) Depending from the out-of-step-frequency |Z/Z| 5 % for 30 SC 90 or 10 m 1 % to 10 ms 0.1 to 8.5 V (steps 0.1 V) 0.2 to 17 mA (steps 0.1 mA) 0 to 60 s (steps 0.01 s) or indefinite approx. 60 ms approx. 200 ms approx. 60 ms or 200 ms 0.9 or 1.1 1 % of set value, or 0.1 V 1 % of set value, or 0.1 mA 1 % or 10 ms
Setting ranges Alarm stage RSEF < Trip stage RSEF << Earth current stage ISEF > Time delays T Supervision of 20 Hz generator V20 Hz I20 Hz Correction angle Times Pickup times RSEF<, RSEF<< Pickup time ISEF> Drop-off times RSEF<, RSEF<< Drop-off time ISEF> Drop-off ratio Tolerances Resistance (RSEF Earth current stage (ISEF >) Time delays T
Setting ranges Positive sequence current pickup I1> Negative sequence current pickup I2< Impedances Za to Zd (based on IN =1 A) Inclination angle of polygon P Number of out-of-step periods characteristic 1 Number of out-of-step periods characteristic 2 Holding time of pickup tH Holding time for out-of-step annuncation Times Typical trip time Tolerances Impedance measurement Time delays T
DC voltage time / DC current time protection ANSI 59N (DC) ; 51N (DC)
Setting ranges Voltage pickup V = >,< Current pickup I = >, < Time delays T Times Pickup time (operational condition 1) Pickup time (operational condition 0) Drop-off time Drop-off ratio Tolerances Voltage Current Time delays T
33
Setting ranges Motor starting current IStart max /IN Starting current pickup IStart, pickup. /IN Permissible starting time T Start max Permissible locked rotor time T Blocking Times Drop-off ratio Tolerances Current threshold Time delays T
1.0 to 16.0 (steps 0.01) 0.6 to 10.0 (steps 0.01) 1.0 to 180.0 s (steps 0.1 s) 0.5 to 120.0 s (steps 0.1 s) or indefinite Depending on the settings approx. 0.95 1 % of set value, or 1 % of IN 5 % or 30 ms 3.0 to 10.0 (steps 0.01) 3.0 to 120.0 s (steps 0.1 s) 0 to 60.0 min (steps 0,1 min) 0.2 to 120.0 min (steps 0.1 min) 1 to 4 1 to 2 1.0 to 100.0 1 % or 0.1 ms 4 0.2 to 10 Hz/s (steps 0.1 Hz/s); 0 to 60 s (steps 0.01 s) or indefinite 10 to 125 V (steps 0.1 V) approx. 200 ms approx. 200 ms approx. 0.95 or 0.1 Hz/s approx. 1.05 approx. 0.1 Hz/s at V> 0.5 VN 1 % of set value or 0.5 V 1% or 10 ms 0.5 to 15 (steps 0.1 ) 0 to 60 s (steps 0.01 s) or indefinite 10 to 125 V (steps 0.1 V) 0.3 at V> 0.5 VN 1 % of set value or 0.5 V 1 % or 10 ms 6 or 12 40 to 250 C or 100 to 480 F (steps 1 C or 1 F) T100; Ni 100, Ni 120 4 1
Setting ranges Motor starting current IStart max /IN Permissible starting time T Start max Rotor temperature equalization time T Equali. Minimum restart inhibit time T Restart, min Permissible number of warm starts nW Difference between warm- and cold starts nK-nW Extensions of time constants (running and stop) Tolerances Time delays T
Setting ranges Steps, selectable +df/dt >; - df/dt Pickup value df/dt Time delays T Undervoltage blocking V1< Times Pickup times df/dt Drop-off times df/dt Drop-off ratio df/dt Drop-off ratio V< Tolerances Rate of frequency change Undervoltage blocking Time delays T
Setting ranges Stage Time delay T Undervoltage blocking V1< Tolerances Vector jump Undervoltage blocking Time delay T
34
Description Currents Tolerance Differential protection currents Tolerances Phase angles of currents Tolerances Voltages Tolerance Impedance Tolerance Power Tolerance Phase angle Tolerance Power factor Tolerance Frequency Tolerance Overexcitation Tolerance Thermal measurement Tolerance Memory Reset manual
Primary; secondary or per unit (%) IL1, S1; IL2, S1; IL3, S1; IL1, S2; IL2, S2; IL3, S2; IEE1; IEE2; I1; I2 0.2 % of measurement values or 10 mA 1 digit IDiffL1; IDiffL2; IDiffL3; IRestL1; IRestL2; IRestL3; 0.1 % of measured or 10 mA 1 digit IL1,S1; IL2,S1; IL3,S1; IL1,S2; IL2,S2; IL3,S2; < 0.5 VL1; VL2; VL3; VE; VL12; VL23; VL31; V1; V2 0.2 % of measured values or 0.2 V 1 digit R, X 1% S; P; Q 1 % of measured values or 0.25 % SN <0.1
cos (p.f.) 1% 1 digit f 10 mHz (at V> 0.5 VN; 40 Hz < f < 65 Hz) V/f;
1% L1; 5%
L2, L3, I2, , V/f
RTDs
Min./max. memory
Measured values with date and time via binary input via key pad via communication
Values Positive sequence voltage Positive sequence current Active power Reactive power Frequency Displacement voltage (3rd harmonics) Energy metering Fault records Meter of 4 quadrants Tolerance Number of fault records Instantaneous values Storage time Sampling interval Channels Rms values Storage period Sampling interval Channels Additional functions Fault event logging
Operational indications Elapsed-hour meter Switching statistics CE conformity The product meets the stipulations of the guideline of the council of the European Communities for harmonization of the legal requirements of the member states on electro-magnetic compatibility (EMC directive 89/336/EEC) and product use within certain voltage limits (low-voltage directive 73,23/EEC). The product conforms with the international standard of the IEC 60255 series and the German national standard DIN VDE 57 435,Part 303. The unit has been developed and manufactured for use in industrial areas in accordance with the EMC standard.
35
Designation Multifunction generator protection SIPROTEC 4 Housing, binary inputs and binary outputs Housing 1/2 19", 7 BI, 11 BO, 1 live status contact Housing 1/1 19", 15 BI, 20 BO, 1 live status contact Current transformer IN 1 A, IEE (sensitive) 5 A, IEE (sensitive) Auxiliary voltage (power supply, indication voltage) 24 to 48 V DC, threshold binary input 17 V 60 to 125 V DC, threshold binary input 17 V 110 to 250 V DC, 115 V AC, threshold binary input 73 V
Order No.
ss s s s s s s s s
Order Code
sss
7UM62--0
1 2
1 5
2 4 5
Unit version with Surface-mounting housing, 2 tier screw-type terminals top/bottom Flush-mounting housing, plug-in terminals (2-/3 pin AMP-connector) Flush-mounting housing, screw-type terminal (direct connection, ring-type cable lugs) Region-specific default setting/function and language settings Region DE, 50 Hz, IEC characteristics, language: German, (language can be adjusted) Region World, 50/60 Hz, IEC/ANSI characteristics, language: English, (language can be adjusted) Region US, 60 Hz, ANSI characteristics, language: American, (language can be adjusted) Port B (System Interface) No system interface IEC protocol, electric RS232 IEC protocol, electric RS485 IEC protocol, optical 820 nm, ST-connector Analog output 2 x 0 to 20 mA Further protocols Port B PROFIBUS-DP slave, electric RS485 PROFIBUS-DP slave, optical 820 nm, double ring, ST-connector MODBUS, electric RS485 MODBUS, optical 820 nm, ST-connector Only Port C (Service Interface) DIGSI 4 / modem, electric RS232 DIGSI 4 / modem, RTD module, electric RS485 Port C (Service interface) and Port D (Additional Interface) Port C (Service Interface) DIGSI 4 / modem, electric RS232 DIGSI 4 / modem, RTD module, electric RS485 Port D (Additional Interface) RTD module, optical 820 nm, ST connector RTD module, electric RS485 Analog outputs 2 x 0 to 20 mA Measuring functions without extended measuring functions min./max. values, energy metering Functions1) Generator Basic Generator Standard Generator Full Asynchronous Motor Transformer Functions (additional functions)1) without Sensitive rotor earth-fault protection and 100 % stator earth-fault protection Network decoupling (df/dt and vector jump) all additional functions
B D E
A B C
0 1 2 3 7 9 9 9 9 L L L L 0 0 0 0 A B D E
1 2 9
Mo o
1 2
A F K
0 3
A B C F H
A B E G
36
Accessories
LSP2288f.eps
Mounting rail for 19 rack 2-pin connector 3-pin connector Short-circuit link for current contacts Short-circuit link for voltage contacts
LSP2093f.eps
LSP2090f.eps
LSP2091f.eps
LSP2092f.eps
Fig. 33
Fig. 34
Fig. 35
Fig. 36
Description Connector Crimp connector 2-pin 3-pin CI2 0.5 to 1 mm2 CI2 1 to 2.5 mm2 Type III + 0.75 to 1.5 mm2 Crimping tool for Type III + and matching female for CI2 and matching female
Order No. C73334-A1-C35-1 C73334-A1-C36-1 0-827039-1 0-827396-1 0-827040-1 0-827397-1 0-163083-7 0-163084-2 0-539635-1 0-539668-2 0-734372-1 1-734387-1 C73165-A63-D200-1 for current terminals for other terminals large small
Tel.: +49 6103 709-0 Fax: +49 6103 709-223
Supplier Siemens Siemens AMP 1) AMP 1) AMP 1) AMP 1) AMP 1) AMP 1) AMP 1) AMP 1)
Fig. 33 34
32 35 36
Product description DIGSI 4 Software for configuration and operation of Siemens protection units MS Windows program, running under MS Windows (version MS Windows 95 and higher). Unit templates, COMTRADE Viewer, electronic manual included
Variants Basis Full version with license for 10 computers, on CD-ROM (authorization with license number). Additional: CD-ROM with DIGSI 3 Demo Demo version on CD-ROM Professional Complete version: Basis and all optional packages on CD-ROM Additional: CD-ROM with DIGSI 3 between PC and relay (9-pin female connector to 9-pin male connector)
7XS5401-0AA00 7XS5402-0AA00
Coupling device for rotor earth-fault protection (rated frequency voltage) Series resistor for rotor earth-fault protection (fn) Voltage devider (10:1, 20:1) Voltage devider (5:1, 5:2) 20 Hz generator 20 Hz band pass filter Current transformer (400 A/ 5 A) Controlling unit f. rotor earth-fault protection (1 to 3 Hz) Resistor for 1 to 3 Hz rotor earth-fault protection Temperature monitoring device (RTD module) Instruction manual 7UM62; V4.0 Advertising brochures English 7UM61/62 German 7UM61/62
37
38
39
40
41
Fig. 41 Side view of flush-mounting housing With screw-type terminals With plug-in terminals
Panel cutout
Rear view
Panel cutout
Rear view
42
(without sloped FO case) Fig. 44 Front view in 1/2 surface-mounting housing 7XP20 Fig. 45 Side view
Fig. 46 Front view in 1/1 surface-mounting housing 7XP20 (without sloped FO case)
43
Conditions of Sale and Delivery Subject to the General Conditions of Supply and Delivery for Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs. n The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are for reference only. We reserve the right to adjust the prices and shall charge the price applying on the date of delivery
Export Regulations In accordance with present provisions of the German Export List and the US Commercial Control List, export licences are not required for the products listed in this catalog. An export licence may however be required due to country-specific application and final destination of the products. Relevant are the export criteria stated in the delivery note and the invoice regarding a possible export and reexport licence. Subject to change without notice.
Trademarks All product designations used are trademarks or product names of Siemens AG or of other suppliers.
Responsible for Technical contents: Dr. Hans-Joachim Herrmann Siemens AG, PTD PA 13, Nuernberg General editing: Claudia Khn-Sutiono Siemens AG, PTD CC T, Erlangen
44
Order No.: E50001-K4406-A121-A1-7600 Printed in Germany KGK 0701 5.0 44 En 101753 6101/D6111
Published by Siemens Aktiengesellschaft Power Transmission and Distribution Power Automation Division Postfach 48 06 90026 Nuernberg Germany www.ptd.siemens.de
Order No.: E50001-K4406-A121-A1-7600