S2801043 - Form 4D Recloser Control Communications - 2012
S2801043 - Form 4D Recloser Control Communications - 2012
S280-104-3
Form 4D Recloser Control
Communications
January 2012 • Supersedes 6/2011
Cooper Power Systems
2300 Badger Drive
Waukesha, WI 53188
P: (877) CPS-INFO
[email protected]
One Cooper | www.cooperpower.com | Online
Information in this document applies to version and is subject to change without notice.
Cooper Power Systems and ProView NXG are trademarks of Cooper Industries in the
U.S. and other countries. You are not permitted to use Cooper trademarks without the
prior written consent of Cooper Industries.
©2012 Cooper Industries. All Rights Reserved
Safety for Life
Cooper Power Systems products meet or exceed all applicable industry standards relating to
product safety. We actively promote safe practices in the use and maintenance of our products
through service literature, instructional training programs and the continuous efforts of all Cooper
Power Systems’ employees involved in product design, manufacture, marketing and service.
We strongly urge that you always follow all locally approved safety procedures and safety
instructions when working around high voltage lines and equipment and support our "Safety for
Life” mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a substitute for proper training or adequate
experience in the safe operation of the equipment described. Only competent technicians who
are familiar with the equipment should install, operate and service it.
A competent technician has these qualifications:
Is thoroughly familiar with these instructions.
Is trained in industry-accepted high- and low-voltage safe operating practices and
procedures.
Is trained and authorized to energize, de-energize, clear and ground power distribution
equipment.
Is trained in the care and use of protective equipment such as flash clothing, safety
glasses, face shield, hard hat, rubber gloves, hot stick, etc.
Following is important safety information. For safe installation and operation of this equipment be
sure to read and understand all cautions and warnings.
CAUTION: Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury.
CAUTION: Indicates a potentially hazardous situation that, if not avoided, may result
in equipment damage only.
WARNING: This equipment is not intended to protect human life. Follow all
locally approved procedures and safety practices when
installing or operating this equipment. Failure to comply can
result in death, severe personal injury and equipment damage.
G102.1
2 Communications Interfaces 3
2.1 Communications Interfaces ....................................................................... 3
2.1.1 USB Device Connectivity .............................................................. 3
2.1.2 USB Host Connectivity.................................................................. 3
2.1.3 Serial RS-232 Interface................................................................. 4
2.1.4 Serial RS-485 Interface................................................................. 4
2.1.5 Ethernet Interface – Copper Media............................................... 5
2.1.6 Ethernet Interface – Multi-Mode Fiber Media ............................... 5
2.1.7 Ethernet Interface – Single-Mode Fiber Media ............................. 6
2.1.8 Multi-Mode Fiber Optic Serial Interface ........................................ 6
2.2 Communications Media Selection ............................................................. 7
2.2.1 RS-485 Multi-Drop / Bus Media .................................................... 7
2.2.2 Copper Ethernet Media ................................................................. 7
2.2.3 Fiber Optic Media.......................................................................... 7
2.2.3.1 Fiber Media Selection ......................................... 8
2.2.3.2 Cooper Power Systems Fiber Optic
Transceivers 8
2.2.3.3 Fiber Optic Link Budgeting ................................. 9
2.2.3.3.1 Fiber Link Budget Example............................ 9
7 Support 79
1.1 Introduction
Congratulations on your selection of the Cooper Power Systems Form 4D recloser
control. You will find that the Form 4D control has been outfitted with many valuable
features to support local and remote communications, equipping it to serve as a versatile
component of your communicating distribution system, no matter the level of automation.
This manual serves to outline the communication functions available in the Form 4D
recloser control. This includes detailed set-up instructions in the areas of local service
communications, remote service communications, and digital SCADA communications.
In addition, optional accessory provisions are available to support a wide variety of third-
party communication and automation applications, including, but not limited to:
Cellular/GSM modems
Short-range wireless modules
Traditional point-to-point / point-to-multipoint radios
The Form 4D Recloser Control provides native support for the following digital SCADA
communications protocols:
DNP3 Serial
DNP3 IP
IEC 60870-5-101 (Serial)
IEC 60870-5-104 (Network)
Additional protocols are also supported with various ordering options:
Cooper 2179
MODBUS RTU (Serial)
IEC 61850
SNTP (Simple Network Time Protocol)
The Form 4D control will accommodate many different communications implementations,
ranging from single end point SCADA-only to multi end point SCADA with remote
configuration. The Form 4D control allows configuration of up to two remote SCADA
communications protocols, depending on the number of communications interfaces
installed. One protocol may be activated for each physical communications port that is
installed.
The ProView NXGTM software can communicate with the Form 4D control via the
dedicated front panel USB port or installed communications accessory cards. If an
Ethernet communications module is installed, simultaneous ProView NXG software and
SCADA connections are supported by way of a dedicated logical DNP device address
and IP port sharing a single IP address with any configured network-connected SCADA
protocols.
Note: Installation of communications accessories not included from the factory should
be conducted according to the Service Kit Installation Instructions included with
the kit.
where
Optical splices, amplifiers, combiners, and other fiber optic media devices should be
considered with their respective gains and losses, and added to the above formulation as
appropriate. Higher levels of link quality confidence can be achieved using larger safety
margin values for S.
Function Description
Code
1 Read Coil Status. Returns a specific portion of the coil RAM area.
2 Read Input Status. Returns a specific portion of the input status RAM area.
4 Read Input Registers. Returns a specific portion of the input register RAM
area.
5 Force Single Coil. Processes coil command and responds if the command
succeeds. (Note: If the command fails, a slave device failure exception
response is sent back to the master station).
Note: MODBUS and Cooper 2179 are only available on controls configured
with an expanded protocols ordering option.
The following protocols may be assigned to ANY Ethernet interface installed in EITHER
the top or bottom communications port:
DNP3 IP (network)
IEC 60870-5-104
The following protocols may be used with any Ethernet interface installed in ONLY in the
bottom communications port:
IEC 61850
SNTP
Note: IEC 61850 and SNTP are only available on controls configured with an
expanded protocols ordering option.
Note: The control must be removed from service prior to removing or replacing a
communication card. Refer to Service Instructions S280-104-1 Form 4D Control
Installation and Operation Instructions.
2. Identify the location of the communications port to be configured on the side of the
control module (Port 1 – Top, Port 2 – Bottom).
3. Open ProView NXG software; login and connect to desired control via USB Data
Port (or other previously-configured connection method).
4. Navigate to the Communication Ports Configuration dialog via Manage > Device
> Communications menu path.
5. For each port, select the appropriate port type to match the communications
implementation: Unused, Serial, or Ethernet.
6. For each port, select the desired SCADA communications protocol from the drop-
down list: DNP3, IEC 60870-5-101, IEC 60870-5-104, Cooper 2179, MODBUS, or
IEC 61850.
Note: IEC 61850 is only available for use with Port 2 (bottom port).
7. For each port, select the appropriate desired Point Map: Default, User Map 1, or
User Map 2. See the following protocol-specific configuration sections of this manual
for additional information on configuration of User Point Maps through the Discrete
Points Configuration dialogs.
8. If the side communication port(s) will be used for ProView NXG connections, select a
ProView NXG Address to match the configuration of the ProView NXG software on
the PC. For Ethernet or point-to-point connections, the Use Default option may be
used. Shared media serial networks (RS-485 multi-drop or serial fiber loop) require
custom ProView NXG addresses (DNP3 logical device addresses) to facilitate
addressing of multiple controls on a single serial connection to the ProView NXG
interface software. Valid address range is 0 – 65519.
Note: The ProView NXG Address settings in this dialog are per-port. The
ProView NXG Address set for Port 1 will affect the addressing of a
DNP3 logical device used for serial and Ethernet connections from the
ProView NXG software to this physical port location, independent of
the setting for Port 2, and vice versa. This logical device instance uses
a static point mapping to facilitate communications with the interface
software. The ProView NXG Address settings can be set to “Use
Default” for all point-to-point serial or Ethernet communications
topologies.
9. Click Apply when all settings have been entered as desired; changes will take effect
immediately.
Port allows the user to select the communication port for which settings will be
viewed/modified.
IP Address sets the Internet Protocol (IPv4) address to be assigned to the Ethernet
interface, entered in dotted decimal format. IP addresses for the two network ports must
reside in separate IP subnets. (Default, Port 1: 10.10.10.10) (Default, Port 2: 10.10.1.10)
Subnet Mask sets the number of bits to be used for network and host portions of the IP
address, entered in dotted decimal format. (Default: 255.255.255.0)
Default Gateway defines an IP host to which traffic destined for hosts outside the
control’s own subnet/network will be addressed for routing. This is a global setting for the
device, and this setting is mirrored between Port 1 and Port 2. (Default: 10.10.10.11)
Note: The address entered for Default Gateway is used to route outbound messages
initiated from the control that must be routed through a gateway or router to
reach a destination on another subnet. If left blank, network communications
within the control’s own subnet will not be affected. Only one gateway is
configured for the control’s two network ports.
IMPORTANT: IP addresses for two network communications interface cards for Form
4D network interfaces must not reside in the same network subnet.
Installations requiring custom IP port number assignments can utilize the network
communications protocol configuration dialogs to assign custom port numbers. See the
Communications Configuration section of this manual for more information. Outbound
2. Click the Add button, and select Serial from the type drop-down. Click OK.
3. The Manage Connections – Add Serial Port dialog will open. Configure the
following settings for the new serial port connection:
Connection Name sets a descriptive name to identify the new serial connection in
the connection list.
Port allows selects the address of the hardware serial port on the local computer to
be used for the new serial connection.
Baud Rate selects the speed of serial communications established from ProView
NXG.
Data Bits sets the number of data bits used to represent each serial character;
options are 5, 6, 7, and 8 (default).
Stop Bits sets the number of bits to be sent at the end of each character; options
include 1 (default), 1.5, and 2.
Flow Control sets whether or not data transmission will be controlled by a hardware
or code-based flow control mechanism.
Connect Via Modem sets this serial connection to use the modem dialing
parameters in this dialog.
Use Hardware Handshaking forces the connected modem to use CD, DTR, and
RTS handshaking signals.
Phone Number is the number to be dialed to reach the modem connected to the
control.
Modem Init defines the initialization string to be sent to the modem upon opening the
communications port on the PC. This setting is dependent on the modem being used.
Pacing Interval specifies a delay period, in seconds, for which ProView NXG will
wait to begin sending data after the communications channel is detected as ready.
This setting can be left as “0” for most RS-232 applications; half-duplex RS-485
networks or other slow connections may require this delay to be inserted.
ProView NXG Address sets the address of the DNP3 logical device on the Form 4D
that will be connected to for ProView NXG configuration. This setting must match the
address set for the Form 4D serial port that this connection is used to connect to. See
the Port Configuration and Protocol Assignment section of this manual for more
information.
4. When all settings have been configured, click Save to store the settings for the new
serial port connection.
5. If no further connections are to be configured, click Close to close the Manage
Connections dialog.
2. Click the Add button, and select TCP/IP (Network) from the type drop-down. Click
OK.
3. The Manage Connections – Add TCP/IP Port dialog will open. Configure the
following settings for the new TCP/IP connection:
Connection Name sets a descriptive name to identify the new TCP/IP connection in
the connection list.
Port Number sets the IP port number to which this new connection will direct its
traffic. Port 19997 is not configurable in the control hardware; this setting is intended
to allow connection to controls behind a router or network address translator in a
NAT-enabled network.
ProView NXG Address sets the address of the DNP3 logical device on the Form 4D
that will be connected to for ProView NXG configuration. This setting must match the
address set for the Form 4D serial port that this connection is used to connect to. See
the Port Configuration and Protocol Assignment section of this manual for more
information.
2. Select the desired connection entry from the Configured Ports list.
3. Ensure that the necessary media is connected and properly configured between the
computer and Form 4D control, then click the Connect button. The interface software
will establish communications with the control.
For additional information on the use of the ProView NXG application software for
configuration of the Form 4D control, refer to Service Instructions S280-104-2, Form 4D
Recloser Control Programming Guide.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Master (Destination of URBE data) sets the DNP3 device number to be used as the
destination for any unsolicited reports generated by DNP3 events.
Slave (Address of this IED) sets the DNP3 device number to be assigned to the
connected Form 4D control.
Note: The DNP3 Master and Slave addresses in this dialog are also presented
in the DNP3 Network Configuration dialog. A change to these settings in
the Basic Configuration dialog will also change the value shown in the
Network Configuration dialog.
Collision Avoidance determines if the control will honor the DCD serial signal during
communications to detect and avoid data collisions.
Fixed Delay sets the fixed portion of the Collision Avoidance back-off timer, in
milliseconds.
Max Random Delay sets a high threshold for the random component added to the fixed
delay to generate the Collision Avoidance back-off time, in milliseconds.
Baud Rate sets the speed of DNP3 serial communications on the chosen
communications port.
CTS Support determines if CTS/RTS handshaking will be used to control the serial
communications channel.
Transmit Enable Delay sets a delay beginning when RTS is asserted and ending when
the DNP3 message begins; must not be set to "0" when connected to a DCE device, in
milliseconds.
Note: When both Transmit Enable Delay and Transmit Disable Delay are Non-
Zero, RTS is asserted to transmit a message.
Port allows the user to select the port for which settings will be viewed/modified.
Data Link Confirm determines if the control will request Data Link confirmations during
its responses. “Sometimes” will cause confirmations to be requested when an exchange
includes multi-segment messages; “Always” will request confirms for every exchange.
Number of Data Link Layer Retries sets the number of Data Link retries to be
attempted.
Data Link Timeout sets the length of time the control waits for Data Link confirmation
when requested from the master, in milliseconds x 10 (entry of 10 = 100ms).
Application Confirm Timeout is the length of time that the control waits for application
confirmation from the master after sending an unsolicited message, in milliseconds x 10.
SBO Select Timeout determines the amount of time that can elapse between a “select”
and “operate” command for systems that employ select-before-operate, in seconds.
Write Time Request Interval determines how often the Form 4D will set the DNP3 Need
Default variation for Binary Input, Binary Input Change, Analog Input, Analog Input
Change, Running Counter, and Running Counter Change set the default DNP3 object
variations to be used when variation 0 is requested by the master.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Unsolicited Notification Delay sets a time delay after any event before the control will
generate an unsolicited response, in milliseconds x 10 (entry of 10 = 100ms). A setting of
zero will cause the control only to generate reports based on the settings for Minimum
Number of Events, as seen below.
Minimum Number of Events to Generate URBE for Class 1, Class 2, and Class 3 set
the number of times that analog event generation must take place for data in each class
before an URBE report is generated and transmitted to the master without a request; the
lowest number that is met will cause report generation.
Delivery Attempts sets the number of times the URBE report will be transmitted to the
master before being discarded if not acknowledged.
Flush Events after delivery attempts exhausted determines whether or not the control
will clear or keep events sent in an URBE report that was not successfully transmitted to
and acknowledged by the master.
Minimum Delivery Back Off Time sets the minimum amount of time the initial
Back Off Time Increment Method determines if the unsolicited back off time is constant
(minimum delivery + max random), variable, or random (minimum delivery + t, where t is
≤ max random).
Max Random Back Off Time is the maximum amount of time the initial unsolicited
response back-off period increments each time following the failed unsolicited response
transmission causing the device to re-enter back-off mode, in milliseconds.
Absolute Back Off Time is the capped maximum period of unsolicited response back-off
period that can be incremented; once this value has been reached, successive
increments of the unsolicited response back-off period will be capped to this value, in
seconds.
Any Messages terminates any unsolicited messages if any message is sent from the
Master.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Master (Destination of URBE data) sets the DNP3 device number to be used as the
destination for any unsolicited reports generated by DNP3 events.
Note: The DNP3 Master and Slave addresses in this dialog are also present in
the DNP3 Basic Configuration dialog. A change to these settings in the
Network Configuration dialog will also change the value shown in the
Basic Configuration dialog.
Port Type defines the IP-connected DNP3 outstation as a TCP Listening End Point, UDP
End Point, or Dual End Point.
Keep-Alive Timeout sets the time after which a DNP3 data Link Layer status request will
be sent if no message is received from the master, in seconds (enter 0 to disable).
Keep-Alive Timer Retries sets the number of times the DNP3 Data Link Layer status
request will be reattempted before the connection is closed.
Accept from any IP address controls whether or not DNP3 requests will be honored
from hosts other than the one defined in the next set of fields.
Accept from IP address allows the user to input a specific IP address from which to
accept DNP3 requests. This is also used as the destination IP to establish a connection
when a Dual End Point connection is initiated by the control.
Destination Port Number defines the IP port number to which outgoing DNP3
messages are addressed when a UDP End Point is configured, unless Use source port
from request is checked. This port number is also used for outgoing TCP connections
when a Dual End Point is configured.
Listening Port Number defines the IP port number that will be monitored for incoming
DNP3 requests when a TCP Listening End Point is configured; responses will be sent
using the source port from the incoming request.
Use source port from request sets the control to use the source IP port number from
the last request as the destination port number.
Listening UDP Port allows the user to set the IP port number to be monitored for DNP3
requests over UDP when a UDP End Point is configured.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Scale Factor sets the analog scaling value to be applied to the value of the
chosen data source for transmission.
Low and High Threshold set the trigger values for URBE reporting when
reports are set to be generated by Thresholds (threshold values apply to
engineering units; scale factor is applied after thresholds).
Event Class sets the event class value for the selected data point (Class 0
only or Class 0 & Classes 1-3).
Unit lists the engineering unit type for the selected data point; this value is
updated automatically as the Assigned Source Data is selected and is not
user-configured.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Event Class sets the event class value for the selected data point (Class 0
only or Class 0 & Classes 1-3).
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Operation Type lists the type of operation associated with the selected
Assigned Resource Data setting. Self-Resetting points are activated or
toggled with each momentary or pulsed input from the SCADA master;
Latched points are set to either on ON or OFF, with this state maintained
until the next local or remote command interacts with the selected mode or
function.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Event Class sets the event class value for the selected data point (Class 0
only or Class 0 & Classes 1-3).
5. When finished, click Apply to send the new point map definitions to the control.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Link Address assigns a unique identifier to the individual slave instance running on the
device.
Common Address identifies the station address, where the station is comprised of all of
a device’s links.
Baud Rate sets the speed of IEC 60870-5-101 serial communications on the chosen
communications port.
Parity sets the type of parity bit calculation to be used on the serial communications
channel between None, Even, or Odd.
CTS Support determines if CTS/RTS handshaking will be used to control the serial
communications channel.
Transmit Enable Delay sets a delay beginning when RTS is asserted and ending when
the IEC 60870-5-101 message begins; must not be set to "0" when connected to a DCE
device, in milliseconds.
Transmit Disable Delay sets a delay beginning when the IEC 60870-5-101 message is
complete and ending when RTS is de-asserted; must not be set to "0" when connected to
a DCE device, in milliseconds.
Single Command Operation Mode defines if the control will respond directly (Direct
mode) to Single Command Operation commands or if a “select” is required before
“execution” (SBE mode).
Select Before Execute Timeout determines the amount of time that can elapse between
a “select” and “execute” command for Single Command Operations in systems that
employ a select-before-execute mode, in milliseconds.
Link Address Size sets the number of octets to be used for the value of the link address.
Common Address Size sets the number of octets to be used for the value of the
common address.
Object Address Size sets the number of octets to be used for the value of the object
address.
Cause of Transmission Size sets the number of octets to be used for the cause of
transmission indication.
Re-Synchronization Time Interval sets the time that will elapse between clock
synchronizations, in seconds.
Port allows the user to select the communication port for which settings will be
Single Point Base Address identifies the starting address for single input objects,
entered as an unsigned integer.
Double Point Base Address identifies the starting address for double input objects,
entered as an unsigned integer.
Measured Value Base Address identifies the starting address for measured value
objects, entered as an unsigned integer.
Single Command Base Address identifies the starting address for single command
objects, entered as an unsigned integer.
Floating Point Base Address identifies the starting address for floating point input
objects, entered as an unsigned integer.
Class 2 Base (TF) millisecond specifies the base frequency at which the internal
database of objects is updated for each object type specified below, in milliseconds
IEC Transmission Mode allows the user to specify Unbalanced or Balanced mode
operation. Balanced mode allows for either the control or master station to initiate
messages; Unbalanced mode requires traditional sequential polling of outstations by the
master.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Scale Factor sets the analog scaling value to be applied to the value of the
chosen data source for transmission.
Units lists the engineering unit type for the selected data point; this value is
updated automatically as the Assigned Source Data is selected and is not
user-configured.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Server Listen Port is the IP port number that will be monitored for connections.
Common Address identifies the station address, where the station is comprised of all of
a device’s links.
Single Command Operation Mode defines if the control will respond directly (Direct
mode) to Single Command Operation commands or if a “select” is required before
“execution” (SBE mode).
Select Before Execute Timeout determines the amount of time that can elapse between
a “select” and “execute” command for Single Command Operations in systems that
employ a select-before-execute mode, in milliseconds.
Re-Synchronization Time Interval sets the time that will elapse between clock
synchronizations, in seconds.
Response Timeout - [t1] sets a timeout value for the transmission of data or test
messages.
Ack / No Data - [t2] sets a timeout for sending an ACK APDU if no data ACKs are
received.
Idle Test - [t3] sets the amount of time allowed to lapse before a test APDU is generated.
Max Transmit - [k] sets the maximum number of unacknowledged data frames that are
allowed to be in transit.
Max Receive - [w] sets the maximum number of data frames to wait before
acknowledging if no data ACKs are received (w should normally not exceed 2k/3).
Port allows the user to select the communication port for which settings will be
viewed/modified.
Single Point Base Address identifies the starting address for single input objects,
entered as an unsigned integer.
Double Point Base Address identifies the starting address for double input objects,
entered as an unsigned integer.
Measured Value Base Address identifies the starting address for measured value
objects, entered as an unsigned integer.
Single Command Base Address identifies the starting address for single command
objects, entered as an unsigned integer.
Floating Point Base Address identifies the starting address for floating point input
objects, entered as an unsigned integer.
Class 2 Base (TF) millisecond specifies the base frequency at which the internal
database of objects is updated for each object type specified below, in milliseconds
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Scale Factor sets the analog scaling value to be applied to the value of the
chosen data source for transmission.
Units lists the engineering unit type for the selected data point; this value is
updated automatically as the Assigned Source Data is selected and is not
user-configured.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Enable Remote Control Commands determines if remote commands received from the
communications master will be honored, causing a state change in the Form 4D control.
Device Address specifies the address, from 0 to 2047, of the RTU instance on the
control.
Ignore Master Address allows the device to accept commands and requests from
masters other than that listed in the Master Device Address field; check the box to allow
data from all master devices.
Master Address sets the address, from 0 to 31, of the master station controlling and
polling the RTU.
Select Timeout determines the amount of time that can elapse between a “select” and
“operate” command for systems that employ select-before-operate commands, entered in
milliseconds.
Baud Rate sets the speed of 2179 serial communications on the chosen communications
port.
CTS Support determines if CTS/RTS handshaking will be used to control the serial
communications channel.
Tx Enable Delay sets a delay beginning when RTS is asserted and ending when the
2179 message begins; must not be set to "0" when connected to a DCE device, in
milliseconds.
Tx Disable Delay sets a delay beginning when the 2179 message is complete and
ending when RTS is de-asserted; must not be set to "0" when connected to a DCE
device, in milliseconds.
Note: When both Tx Enable Delay and Tx Disable Delay are Non-Zero, RTS is
asserted to transmit a message.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
Scale Factor sets the analog scaling value to be applied to the value of the
chosen data source for transmission.
Units lists the engineering unit type for the selected data point; this value is
updated automatically as the Assigned Source Data is selected and is not
user-configured.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Port allows the user to select the communication port for which settings will be
viewed/modified.
Enable Remote Control Commands determines if remote commands received from the
communications master will be honored, causing a state change in the Form 4D control.
Device Address specifies the address, from 1 to 247, of the RTU instance on the
Baud Rate sets the speed of MODBUS serial communications on the chosen
communications port.
Parity sets the data parity parameter to be used on the serial communications channel
between None, Even, or Odd.
CTS Support determines if CTS/RTS handshaking will be used to control the serial
communications channel.
Tx Enable Delay sets a delay beginning when RTS is asserted and ending when the
MODBUS message begins; must not be set to "0" when connected to a DCE device, in
milliseconds.
Tx Disable Delay sets a delay beginning when the MODBUS message is complete and
ending when RTS is de-asserted; must not be set to "0" when connected to a DCE
device, in milliseconds.
Note: When both Tx Enable Delay and Tx Disable Delay are Non-Zero, RTS is
asserted to transmit a message.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Scale Factor sets the analog scaling value to be applied to the value of the
chosen data source for transmission.
Unit lists the engineering unit type for the selected data point; this value is
updated automatically as the Assigned Source Data is selected and is not
user-configured.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Discrete Point displays the point identifier for the selected data point. To
add a point, right-click in the edit table and choose Insert New Point; the new
point will be inserted below the currently selected line and the point indices
will be updated automatically. To delete a point, select the desired point,
right-click in the edit table and choose Delete Point; the point indices will be
updated automatically.
Enable Remote Control Commands determines if remote commands received from the
communications master will be honored, causing a state change in the Form 4D control.
Inactivity Timeout defines the number of milliseconds the slave instance will wait after
the last valid data link layer frame is received, before resetting the communications link.
Integrity Report Scan Interval sets the number of milliseconds to wait before verifying
whether an integrity report is to be sent.
Request Timeout defines the number of milliseconds to wait for the master response to
the previous request
MMS Message Size is the maximum number of bytes for the MMS message used to
communicate with the master. This setting is negotiated during the association, and
whichever MMS message size is smaller - slave or master - is used.
Max In Requests defines the maximum number of incoming requests. This setting is
negotiated during the association, and whichever maximum number of incoming requests
is smaller - slave or master - is used.
TPDU Size sets the size of the packet to be used in the transport layer.
AP Title sets the client application process title. A string consisting of at-most 16 space-
separated entries. Used for validation in the ISO stack.
AE Qualifier is the client application-entity qualifier of the application process. Used for
validation in the ISO stack
Accept from any IP chooses whether or not to disable incoming IP validation per the
settings set in the next element.
Accept from IP allows the user to specify a valid incoming IP host or subnet address.
Listening Port Number sets the listening IP port number for the 61850 slave instance.
Presentation is the client presentation layer selector. This is a string consisting of at-
most 4 space-separated entries. Each entry represents a byte. Used for validation in the
ISO stack.
Session is the client session layer selector. Used for validation in the ISO stack. This is a
string consisting of at most 4 space-separated entries. An entry represents a byte.
Transport is the client transport layer selector. Used for validation in the ISO stack. This
is a string consisting of at most 2 space-separated entries. An entry represents a byte.
Destination Address is the destination MAC address where GOOSE messages will be
sent.
Enable Port 2 (Bottom) set whether or not GOOSE messaging will be enabled for an
IEC 61850 instance running on the bottom communications interface port (IEC
61850/GOOSE not available on Port 1).
VLAN Priority sets the 3-bit user priority setting for the specified VLAN.
Event Tx Interval sets the amount of time, in milliseconds, to wait between message
transmissions resulting from event occurrences.
Event Tx Quantity sets the number of messages that will be sent on the Event Tx
Interval schedule before returning to the normal Tx Interval after an event occurrence.
4.9.5 Create 61850 ICD File and Create GOOSE ICD File
The ProView NXG application may be used to dynamically generate IED Capability
Description (ICD) files, in XML format, as required for system configuration in
accordance with IEC 61850 standards. Files may be generated from opened Form 4D
settings (*.f4d) files or from settings obtained from a connected control; however, care
should be taken when using GOOSE ICD files generated from saved settings files as
information specific to individual controls will be omitted, such as the network MAC
address.
When one of these two menu items is selected, the application presents a Save ICD File
dialog. The user may choose a path and desired filename and click Save, at which time
ProView NXG will generate and save the selected ICD file to the chosen location. Once
saved, this file may be retrieved from the specified save location and used for IEC 61850
system configuration using third-party tools.
Note: When ICD files are generated from a connected control, additional IEC
61850 dialog windows may open and remain open after the file save
operation is complete. This is normal behavior; the user may close the
opened dialogs and resume normal use of the application.
Enable SNTP Client allows the user to activate or deactivate time synchronization via
the SNTP protocol.
Refresh Rate sets the frequency, in minutes, at which the Form 4D will send an SNTP
query to the time server to be resynchronized.
Recovery Refresh sets the frequency, in minutes, at which the Form 4D will attempt to
reconnect to an SNTP server that previously failed to respond to a query. This value must
be less than the normal Refresh Rate.
Maximum Time Variance sets the maximum allowed time difference between the new
time being returned by the SNTP server and the current time on the Form 4D. If the
resulting time difference from a synchronization would yield a time change outside this
maximum delta, the synchronization is ignored.
Note: HTML files may be exported from Form 4D settings files or a connected
Form 4D control using the ProView NXG application. User Map HTML
files exported from connected controls will contain information regarding
the connected control’s Firmware version, while files exported from an
open settings file will contain the settings file name in the exported
HTML document.
To export a Form 4D Discrete Points Configuration User Map using ProView NXG
software:
1. Open a valid Form 4D settings file using the File menu or connect to a Form 4D
control with the ProView NXG software.
3. Choose the appropriate User Map for which the Export operation will be completed,
using the Point Map selection drop-down box.
4. Once the desired point map is displayed in the table, click on the Export to Html
File… button located below the point map table.
As outlined throughout this manual, the Form 4D control supports a wide variety of
communications infrastructures, each with their respective topologies and implementation
details. The examples in this section represent some of the most common
communications implementations used by our customers. While not intended to provide
in-depth technical details, they are suitable for familiarization with the various supported
methodologies for those users who may not have an extensive communications
background.
In most, but not all applications, straight-through serial cables may be used for all RS-232
connections to the Form 4D control except for connections made directly to a computer
for configuration or SCADA emulation.
Note: The control must be removed from service prior to removing or replacing a
communication card. Refer to Service Instructions S280-104-1 Form 4D Control
Installation and Operation Instructions.
Item Description
Note: The terminating resistors included on the Form 4D control RS-485 interface card
have been specified for +/- 5 Volt DC RS-485 installations. For RS-485
applications using a voltage supply greater than 5VDC, external terminating
resistors must be used.
Note: The control must be removed from service prior to removing or replacing a
communication card. Refer to Service Instructions S280-104-1 Form 4D Control
Installation and Operation Instructions.
Note: The control must be removed from service prior to removing or replacing a
communication card. Refer to Service Instructions S280-104-1 Form 4D Control
Installation and Operation Instructions.
5.4.1 Auto-Negotiation
The Form 4D control Ethernet interface is auto-negotiating, meaning that it will
automatically detect the type of device connected to the control’s 8P8C and adjust its pin-
out accordingly. This is commonly referred to as Auto MDI/MDIX capability.
In practice, Auto MDI/MDIX allows all Ethernet connections—control to PC, control to
switch, control to router, etc.—to be made with either straight-through or crossover
Ethernet cabling, without the need to keep separate cables for different connection types.
The Form 4D control Ethernet interface is also able to automatically detect and connect
to either 10Mbps or 100Mbps Ethernet networks.
6.1 Overview
Cooper Power Systems recognizes the need for flexible communications options to meet
a variety of needs arising from different distribution automation and smart grid
deployments. We are pleased to offer communications accessories for the Form 4D
control that allow connection to communications devices and supporting equipment to
facilitate wired and wireless communications.
Measurement Value