Modular Data Center

FusionModule800 Smart Small Data Center

Introduction Electrical cable tray(Optional)

Data cable tray(optional)


FusionModule800 Smart Small Data Center is a new-generation data Spring to open Camera(optional)
center solution. It is integrated with PDU, UPS, monitoring , cooling and the door(rear)
Spring to open
the door(front)
rack system in a comprehensive rack in order to save space. IT racks Indicator light

can be deployed flexibly on both sides. A single module can support PDU
Glass door
maximum12 racks and 25kW IT load (T3: IT Load≤21kW), the maximum
UPS Touch
power density for each rack is 7kW/ R(T3:≤6kW). Cold and hot aisle Transformer
screen

(optional))
containment to saving Energy and reduce noise. Monitoring module
Aisle

Application Scenarios Air conditioners

• Finance, Education, Health Care, Public Security, SMEs, Retailing &


Merchandising, Edge DC, etc.
• Indoor modular data center
FusionModule800 Architecture

Features & Value


Simple
• Integrated cooling ,PDU,UPS and monitoring system in one rack,
footprint saving.
• All components are prefabricated in factories. only need to be
combined onsite, hardware are installed in 4 hours, 2 days business
on line.
• The local PAD supports facial recognition , easy login without
password.
• Support online maintenance through hot swap switches, local PAD
indicates the PUE through intelligent power distribution(only for BC6
FusionModule800 Application
and BC7).

Efficient
• Rack-mounted air conditioner saves at least one rack footprint.
600 to 7400mm
• Cold and hot aisle containment, saving energy and reducing noise.
• Improve the efficiency of cooling system through DC variable
frequency compressor, wet film humidification ,cold and hot aisle Hot aisle
containment. PDU
1100mm

Network IT IT ATS IT IT IT IT IT Battery Battery


UPS
• Real-time monitoring of mobile apps, centralized monitoring of cabinet cabinet cabinet
Monitoring
IT cabinet cabinet cabinet cabinet cabinet cabinet cabinet
multiple sits. cabinet (A/C:#3
A/C
#4)

Reliable
250mm

• Dehumidifying at min. 10% IT load avoids condensation risk. Cold aisle


• Automatic shutdown to prevent fire caused by battery overheating.
• Open rack doors automatically in case of cooling failure and the Maximum configuration:IT load 17~25KW(T1/LT),14kW~21kW(T3)
temperature exceeds the limit.
• When detect the fire alarm automatically open the rear door to let the
fire extinguishing gas enters.
Specifications
System features Centralized management for multiple DCs
Power system 380/400/415Vac, 50Hz, 3Ph+N+PE
Aisle containment Cold and hot aisle containment
System protection level IP20
T1*:-20℃~+45℃;
Ambient temperature T3*:-10℃~+55℃;
LT*:-40℃~+45℃;
Maximum cabinet quantity
12 LTE
for a module
Quantity of IT cabinets 0~10
25kW (T1* & LT*)
Maximum IT load
21kW (T3*) TCP/IP
7kW (T1* & LT*)
Max power density /Rack
6kW (T3*)
Mobile operation
IT cabinet weight Static load 1500kg, Dynamic load 1000kg
Total Dimensions
2000×(600-7400)×1350 Module1
(H×W×D mm) Management for
Cooling system single module ……
Power system 220/230/240Vac, 50Hz, 1Ph+N+PE
Cooling capacity 12.5kWa APP (local) Module 2 Module N
Operating temperature of T1*:-20℃~+45℃;
T3*:-10℃~+55℃;
the outdoor unit LT*:-40℃~+45℃;
Configuration N, N+1 WiFi
ECC800 data acquisition
Cooling mode Direct expansion air-cooled
Installation Rack- mounted
Air volume 2600m³/h
Air supply mode Front supply, rear return Battery UPS Cooling Temperature Water Door status Video
Power Supply and Distribution System and humidity sensor sensor
SPD CLASSII/C, In 20kA, Imax 40kA, 8/20us
Input power Single or dual inputs 7 Basic Configurations for T1/T3/LT
UPS capacity 10kVA 20kVA ≤8.5KW(T1/LT) 8.5KW~17kW(T1/LT)
UPS configuration N, N+1 IT load
≤7KW(T3) 7KW~14kW(T3)
UPS output power factor 0.9
Basic configuration BC1* BC2 BC3* BC4*
UPS rated input voltage 380/400/415Vac, 50/60HZ, 3Ph+N+PE
UPS input voltage range 138~485Vac, 40~70Hz, 3Ph+N+PE Aisle type Single row, cold & hot aisle containment
220/230/240Vac 380/400/415Vac UPS(KVA) 10+0 10+10 20+0 20+20
UPS rated output voltage
50/60Hz, 1Ph+N+PE 50/60Hz, 3Ph+N+PE
Smart cooling 1+0 1+1 2+0 2+0
UPS efficiency 94.5% 95%
Power input Single input is default (ATS optional)
Battery backup mode Battery pack, battery cabinet, battery rack
Backup time 15min/30min IT output 4 12 12 12
No-Intelligent rPDU: IEC or GB,on site installation Intelligent Power
rPDU (Optional) NO NO NO NO
Intelligent rPDU:IEC,on site installation distribution
ATS (Optional) On site installation
Maintenance bypass Standard
17~25KW(T1/LT) ≤8.5KW(T1/LT) 8.5~17kW(T1/LT)
Intelligent battery IT load
Optional 14kW~21kW(T3) ≤7KW(T3) 7~14kW(T3)
monitoring system
Monitoring system Basic configuration BC5* BC6* BC7*
Mobile phone APP, SMS alarm, Web access,
Monitoring system Aisle type Single row, cold&hot sealed
centralized management for multi-DCs
10 inched Pad Standard UPS(KVA) 20*2+0 10+10 20+20
Water sensor Optional Smart cooling 3+0 1+1 2+0
Camera Optional
Power input Single input is default (ATS optional)
Smoke sensor Standard
Intelligent door lock Standard IT output 20 12 12
Facial recognition Standard Intelligent Power
NO Yes Yes
Temperature and humidity distribution
Standard
sensor
Local app on the mobile phone,SMS alarm Note:
Mobile O&M NetEco remote app on the mobile 1, Basic configuration 1, 3,4,5,7 are only applicable to TierI DC.
2, The cooling capacity 12.5kW is obtained when the indoor dry bulb temperature is
phone(optional) 37.8℃, and outdoor dry bulb temperature is 35℃,relative humidity 20%.
3, ATS is optional and can be installed on site
4, T1:-20℃~ +45℃,LT:-40℃~ +45℃;T3:-10℃~ +55℃
5, BC1 cooling without heating and humidification, the others are all have one
cooling with heating and humidification
6, BC6 & BC7 are intelligient power distribution.
7, The Converged cabinet part number don't include cooling out door unit.three
type of outdoor unites are freely configured with the converged cabinet.
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.