Annex To The Technical Catalogue Low Voltage Switch-Disconnectors and Automatic Circuit-Breakers For Direct Current Applications
Annex To The Technical Catalogue Low Voltage Switch-Disconnectors and Automatic Circuit-Breakers For Direct Current Applications
Annex To The Technical Catalogue Low Voltage Switch-Disconnectors and Automatic Circuit-Breakers For Direct Current Applications
1SDC200012D0201
Accessories ............................................................................................................................ 23
The SACE Emax range of low voltage automatic circuit-breakers is being enriched by the new series
SACE Emax DC of automatic circuit-breakers for direct current applications in compliance with the
international standard IEC60947-2.
Thanks to the exclusive technology of the new electronic SACE PR123/DC e PR122/DC the SACE Emax
DC range allows to cover all installation and automatic protection needs up to 1000V / 5000A DC.
By connecting three breaking poles in series it is possible to achieve a rated voltage of 750V DC,
while with four poles in series the limit rises 1000V DC.
The automatic circuit-breakers of SACE Emax DC range maintain the overall dimensions and fixing
points of the standard range circuit-breakers; they can be fitted with the various terminal kits and all
accessories common to the SACE Emax range.
The withdrawable circuit-breakers should be used together with the special version fixed parts for
applications at 750/1000 DC.
Common data
Voltages
Rated service voltage Ue [V–] 1000
Rated insulation voltage Ui [V] 1000
Rated impulse withstand voltage Uimp [kV] 12
Operating temperature [°C] -25....+70
Storage temperature [°C] -40....+70
Number of poles 3-4
Versions Fixed -
E2 E3 E4 E6
Performance levels B N N H S H H
Rated uninterrupted current (at 40 °C) Iu [A] 800 800
[A] 1000 1000
[A] 1250 1250
[A] 1600 1600 1600 1600 1600
[A] 2000 2000 2000
[A] 2500 2500 2500
[A] 3200 3200 3200
[A] 4000
[A] 5000
Rated ultimate breaking capacity under short-circuit Icu
@ 500 V DC (III) [kA] 35 50 60 85 75 100 100
@ 750 V DC (III) [kA] 25 25 40 40 65 65 65
@ 750 V DC (IV) [kA] 25 40 50 50 65 65 65
@ 1000 V DC (IV) [kA] 25 25 35 40 50 65 65
Rated service breaking capacity under short-circuit Ics [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Rated short-time withstand current Icw (0.5s)
@ 500 V DC (III) [kA] 35 50 60 65 75 100 100
@ 750 V DC (III) [kA] 25 25 40 40 65 65 65
@ 750 V DC (IV) [kA] 25 40 50 50 65 65 65
@ 1000 V DC (IV) [kA] 25 25 35 40 50 65 65
Rated making capacity under short-circuit Icm [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Utilization category (according to CEI EN 60947-2) B B B B B B B
Isolation behaviour (according to CEI EN 60947-2) ■ ■ ■ ■ ■ ■ ■
Overcurrent protection
Electronic trip units for DC applications ■ ■ ■ ■ ■ ■ ■
Operating times
Closing time (max) [ms] 80 80 80 80 80 80 80
Breaking time for I<Icw (max) (1) [ms] 70 70 70 70 70 70 70
Breaking time for I>Icw (max) [ms] 30 30 30 30 30 30 30
Overall dimensions
Fixed: H = 418 mm - D = 302 mm - W (3/4 poles) [mm] 296/386 296/386 404/530 404/530 566/656 566/656 782/908
Withdrawable: H = 461 mm - D = 396.5 mm - W (3/4 poles) [mm] 324/414 324/414 432/558 432/558 594/684 594/684 810/936
Weights
Fixed 3/4 poles [kg] 50/61 50/61 66/80 66/80 97/117 97/117 140/160
Withdrawable 3/4 poles (including fixed part) [kg] 50/61 50/61 66/80 66/80 147/165 147/165 210/240
ABB SACE has developed the SACE Emax/E MS range of switch-disconnectors for applications in
direct current up to 1000V in compliance with the international IEC 60947-3 Standard. These no-
automatic circuit-breakers are specially suitable for use as bus ties or main isolators in direct current
systems, such as in applications involving electric traction.
The range covers all installation needs up to 1000V DC /6300A.
They are available in fixed and withdrawable, three-pole and four-pole versions.
By connecting three breaking poles in series, it is possible to achieve a rated voltage of 750V DC,
while with four poles in series the limit rises to 1000V DC.
The switch-disconnectors of the SACE Emax/E MS range maintain the overall dimensions and fixing
points of the standard range circuit-breakers. They can be fitted with the various terminal kits and all
the accessories common to the SACE Emax range. They cannot, of course, be associated with the
electronic trip units, CSs and accessories for determining currents and for AC applications.
The withdrawable circuit-breakers should be used together with the special version fixed parts for
applications at 750/1000V DC.
Rated current (at 40 °C) Iu [A] 800 1250 1250 3200 5000
[A] 1250 1600 1600 4000 6300
[A] 2000 2000
[A] 2500
[A] 3200
Poles 3 4 3 4 3 4 3 4 3 4
Rated service voltage Ue [V] 750 750 750 750 750 750 750 750 750 750
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp [kV] 12 12 12 12 12 12 12 12 12 12
Rated short-time withstand current Icw (1s) [kA] 20 20* 25 25* 40 40* 65 65 65 65
Rated making capacity Icm
750 V DC [kA] 42 42 52.5 52.5 105 105 143 143 143 143
1000 V DC [kA] 42 52.5 105 143 143
Note: the breaking capacity Icu, by means of external protection relay, with 500 ms maximum timing, is equal to the value of Icw (1s).
* The performances at 750 V are:
for E1B/E MS Icw=25kA
for E2N/E MS Icw=40kA
for E3H/E MS Icw=50kA
1. Emergency supply or auxiliary services: the use of direct current is due to the need to employ a
back-up energy source which allows the supply of essential services such as protection services,
emergency lighting, alarm systems, hospital and industrial services, data-processing centres etc.,
using accumulator batteries
2. Electrical traction: the advantages offered by the use of dc motors in terms of regulation and of
single supply lines lead to the widespread use of direct current for railways, underground railways,
trams, lifts and public transport in general
3. Particular industrial installations: there are some electrolytic process plants and applications which
have a particular need for the use of electrical machinery
Here below the typical distribution systems used in direct current are described:
– Fault a: the fault, without negligible impedance, between the two polarities sets up a short-circuit
current to which both polarities contribute to the full voltage, according to which the breaking
capacity of the breaker must be selected.
– Fault b, c: the fault between the polarity and earth has no consequences from installation func-
tioning point of view.
– Fault a: the fault between the two polarities sets up a short-circuit current to which both polari-
ties contribute to the full voltage U, according to which the breaking capacity of the breaker is
selected.
– Fault b: the fault on the polarity not connected to earth sets up a current which involves the
over-current protection according to the resistance of the ground.
– Fault c: the fault between the polarity connected to earth and earth has no consequences from
the point of view of the function of the installation.
All the poles of the breaker necessary for protection must be connected in series on the non-earthed
polarity.
– Fault a: the fault between the two polarities sets up a short-circuit current to which both polari-
ties contribute to the full voltage U, according to which the breaking capacity of the breaker is
selected.
– Fault b: the fault between the polarity and earth sets up a short-circuit current less than that of
a fault between the two polarities, as it is supplied by a voltage equal to 0.5 U.
– Fault c: the fault in this case is analogous to the previous case, but concerns the negative polarity.
To correctly select the devices for the protection of a direct current network the following factors
must be considered:
• The type of network - earthing connection
• Rated Current
• Voltage Current
• The prospective short-circuit current at the point of installation
Here below the rating plate of an Emax DC air circuit-breaker for direct current application:
Characteristics
The PR122/DC is the new electronic protection trip unit for the SACE Emax DC series suitable for
direct current installation wherein the basic protections are enough.
(1) The minimum trip value is 1 s, regardless of the type of curve set (self-protection)
(2) These tolerances are valid in the following conditions:
- fully powered release by voltage module and/or auxiliary power supply (without start-up)
- trip time set ≥ 100 ms
The following tolerance values apply in all cases not covered by the above:
Trip threshold Trip time
Power Supply
The PR122/DC trip unit does not normally require an auxiliary power supply being self-supplied from
the measurement module PR120/V always supplied as standard in PR122/DC (only for power supply,
no voltage and power based protection/measurements available in PR122/DC).
On request it is possible to supply the PR122/DC with a special version of measurements module
suitable for very low DC rated voltage 24/48V DC, called PR120/LV, typically railway and mine in-
stallations.
An external auxiliary power supply is however required in case of the PR120/LV module is present.
When an auxiliary power supply is present, refer to the below table for the overall electronic power
consumption.
The Emax DC is supplied as standard for incoming power from the bottom terminals: PR120/V
- PR120/LV internal connection on bottom terminals – “U rear connection kit” mounted on upper
terminals.
Refer to Ordering Codes Section for incoming power from the upper terminals.
t=k
Functions L-S-I
I2t = k
Characteristics
The PR123/DC is the new electronic protection trip unit for the SACE Emax DC series; the complete
range of protection functions together with the wide combination of thresholds and trip times offered
make it suitable for protecting a wide range of direct current installation.
(1) The minimum trip value is 1 s, regardless of the type of curve set (self-protection)
(2) These tolerances hold in the following conditions:
- fully powered release by voltage module and/or auxiliary power supply (without start-up)
- trip time set ≥ 100 ms
The following tolerance values apply in all cases not covered by the above:
Power Supply
The PR123/DC trip unit does not normally require an auxiliary power supply being self-supplied from
the measurement module PR120/V always supplied as standard in PR123/DC.
On request it is possible to supply the PR123/DC with a special version of measurements module
suitable for very low DC rated voltage 24/48V DC, called PR120/LV, typically railway and mine in-
stallations.
An external auxiliary power supply is however required in case of the PR120/LV module is present.
When an auxiliary power supply is present, refer to the below table for the overall electronic power
consumption.
The Emax DC is supplied as standard for incoming power from the bottom terminals: PR120/V
- PR120/LV internal connection on bottom terminals – “U rear connection kit” mounted on upper
terminals.
Refer to Ordering Codes Section for incoming power from the upper terminals.
t=k
Functions L-S-I
I2t = k
Function G
k
t=
I2
t=k
1SDC200112F0001
Function U
1SDC200122F0001
RP
1SDC200126F0001
Function UV
UV
1SDC200123F0001
Function OV
OV
1SDC200124F0001
The automatic circuit-breakers of SACE Emax DC range are supplied of an internal back-up protection
called Override Protection made by the Module PR120/DC always supplied with the PR122/DC
and PR123/DC electronic trip units.
The Override Protection ensures the protection of the electrical plant against instantaneous short-
circuit in case of any loss of power supply of the protection unit PR122/DC and PR123/DC.
The Override protection threshold depends on the circuit breaker size; as standard neither connec-
tions nor settings are in user’ care.
(1) PR120/V Measurements Module always supplied with the trip units PR123/DC and PR122/DC
(2) Extracode to be specified with the circuit-breaker code to have the low voltage measuring module PR120/LV
(3) Not to be specified, always supplied with the electronic trip unit
PR122/DC
The following measurements are available
• Current;
• Instantaneous current value over a given time interval;
• Maintenance: number of operations, percentage of contact wears, opening data storage (latest
20 trips and 80 events);
• The protection records the historical data of the maximum current read.
PR123/DC
• Current;
• Maintenance: number of operations, percentage of contact wears, opening data storage (latest
20 trips and 80 events);
• Voltage;
• Instantaneous current/voltage value over a given time interval (data logger);
• Power;
• Energy;
• The protection records the historical data of the maximum current read, the maximum and minimum
voltage, the total maximum and mean value of power.
Measurement Functions
The measurements available on electronic trip units PR122/DC and PR123/DC fitted by the Modbus
Communication module PR120/D-M and the protocol converter for Profibus and Devicenet FieldBus
EP010-FBP are listened on the following table.
Measuring functions
Currents ■ ■ ■
Ground current ■ ■ ■
Voltage ■ on demand (1)
Power ■ on demand (1)
Energy ■ on demand (1)
Available data
Circuit-breaker status (open, closed) ■ ■ ■
Circuit-breaker position (racked-in, racked-out) ■ ■ ■
Mode (local, remote) ■ ■ ■
Protection parameters set ■ ■ ■
Load control parameters ■ ■ ■
Alarms
Protection L ■ ■ ■
Protection S ■ ■ ■
Protection I ■ ■ ■
Protection G ■ ■
Fault release mechanism failure ■ ■ ■
Undervoltage, overvoltage (timing and trip) protection ■ on demand (1)
Reverse power protection (timing and trip) ■ on demand (1)
Maintenance
Total number of operations ■ ■ ■
Total number of trips ■ ■ ■
Number of trip tests ■ ■ ■
Number of manual operations ■ ■ ■
Number of separate trips for each protection function ■ ■ ■
Contact wear (%) ■ ■ ■
Record data of last trip ■ ■ ■
Operating mechanisms
Circuit-breaker open/close ■ ■ ■
Reset alarms ■ ■ ■
Setting of curves and protection thresholds ■ ■ ■
Synchronize system time ■ ■ ■
Events
Status changes in circuit-breaker, protections and all alarms ■ ■ ■
Accessories
The SACE Emax DC family can be fitted by the same electrical and mechanical accessories already
available on the standard alternative current family.
CAPTION
(1) For automatic circuit-breakers, four auxiliary contacts to electrically signal circuit-breaker
open/closed are included in the supply as standard.
■ Accessory on request for fixed circuit-breaker or moving part
(2) Incompatible with the E6/f versions with full-size neutral
■ Accessory on request for fixed part (3) Incompatible with the range of circuit-breakers for applications up to 1150V AC
■ Accessory on request for moving part
For Emax DC circuit-breakers accessories please refer to the same accessories codes of standard Emax AC circuit-breakers.
Basic version
with rear terminals INCOMING POWER FROM UPPER TERMINALS 6
4 POLES E2 - E4 E3 - E6
3 POLES
3 POLES
4 POLES
Caption
148
A B C D 98
78
45
188
188
98 98
78 78
180 180
Iu=1600A
150 Iu=2000A
252
242 177
60
M10 10
45 10 10
49
50
Max. 40 98
78
510
757
65 65
45
188 188
98 98
78 78
180 180
Iu=1600A
252
242 177
150 Iu=2000A
60
M10 10
45 10 10
49
Max. 40 50
98
78
690
211
415
95
126 126
Iu=2000A
E3 III Iu=2500A 114
View A 96
168
148
98 78 98
78
126 126
177
Iu=800A
96
242 Iu=1000A
12
252 10
Iu=1250A
M10 10
12 12
Iu=1600A
49
50
Max. 40 98
78
348
Basic version
with rear terminals
541
168 148
98 78 98 78
96
12
252
177 10 10 Iu=800A
242 Iu=1000A
M10 12 12 Iu=1250A
63
49
Iu=1600A
50
Max. 40 98
78
474
793
252 252
E6 III 410
View A
222 79,5 85
56
208
98 222
78 56 56
70
12
10 10
177 12 12
252
242
M10 50
98
78
49
Max. 40
63
726
1045
56 85 85
208
222
98 56 70 56
78
12
10 10
177
12 12
252
242
M10 50
98
78
49
Max. 40
63
978
A B
E2 400 490
E3 500 630
E4 700 880
E6 1000 1260
Depth
3 POLES
4 POLES
4 POLES
E2-E4 E3-E6
3 POLES
3 POLES
4 POLES
Caption
Iu=3200A
65 65
143 143
103
53 33 53 33
122
120
E4 IV 777
View A 180 180 180
65 65
143 143
103
53 53 33
33
708
0 180 180 180
Ø1 45
33
10 10
393,5 40 700
7
10 10 10 10
Iu=1600A
380 580
84 Iu=2000A
53 33 50
122
120
435
126 126
211 211
E3 III 158 114
View A Iu=2000A
95 95
Iu=2500A
123 103
53 53
33 33
183
0
126 126
Ø1
33
393,5 40
7 240 12
380 225 10 10
84 183
12 12 Iu=800A
122 Iu=1000A
63 33 50
49 70 Iu=1250A
Iu=1600A
6 200
400
10
Ø
126 126 126
33
393,5
380
40 7 225 Iu=800A
84 63 240 12 Iu=1000A
10 10 Iu=1250A
122 12 12
Iu=1600A
49 70
53 33 50
6 325
370
490
813
463
E6 III
410
View A
252 252 85
163
53 33
222
744 182
Ø10
33 12
393,5 40 10 10
380 7
84 12 12
750
53 50
33
122
63
620
1065
463
E6 IV
View A 410 410
163
53 222
33
182
12
10 10
33
393,5
40 12 12
380 7
84 53 50
33
122
63
866
A B
E2 400 490
E3 500 630
E4 700 880
E6 1000 1260
Depth
3 POLES
4 POLES
Mechanical
compartment
door lock
Holes in compartment door Minimum distance between circuit-breakers and switchboard wall
Fixed version Withdrawable version
A
3 POLES 4 POLES
E2 180 180
E3 234 234
E4 270 360
E6 360 486
Warning
Before installing the circuit-breaker, carefully read note F on the circuit diagrams.
Versions
Though the diagram shows a circuit-breaker in withdrawable version, it can be applied to a fixed version circuit-breaker
as well.
Fixed version
The control circuits are fitted between terminals XV (connector X is not supplied).
With this version, the applications indicated in figures 31 and 32 cannot be provided.
Withdrawable version
The control circuits are fitted between the poles of connector X (terminal box XV is not supplied).
Version with PR122/DC electronic trip unit
Version with PR123/DC electronic trip unit
Caption
= Circuit diagram figure number
* = See note indicated by letter
A1 = Circuit-breaker accessories
A3 = Accessories applied to the fixed part of the circuit-breaker (for withdrawable version only)
A4 = Example switchgear and connections for control and signalling, outside the circuit-breaker
D = Electronic time-delay device of the undervoltage release, outside the circuit-breaker
F1 = Delayed-trip fuse
K51 = PR122/DC, PR123/DC electronic trip unit with the following protection functions:
- L overload protection with inverse long time-delay trip - setting I1
- S short-circuit protection with inverse or definite short time-delay trip - setting I2
- I short-circuit protection with instantaneous time-delay trip - setting I3
- G earth fault protection with inverse short time-delay trip - setting I4
K51/1...8 = Contacts of the PR021/K signalling unit
K51/GZin = Zone selectivity: input for protection G (only with Uaux. and PR123/DC trip unit)
K51/GZout = Zone selectivity: output for protection G (only with Uaux. and PR123/DC trip unit)
K51/IN1 = Digital programmable input (available only with Uaux and PR122/DC or PR123/DC trip unit with indicator
module PR120/K)
K51/P1...P4 = Programmable electrical signalling (available only with Uaux and PR122/DC or PR123/DC trip unit with
indicator module PR120/K)
K51/SZin = Zone selectivity: input for protection S (only with Uaux. And PR123/DC trip unit)
K51/SZout = Zone selectivity: output for protection S (only with Uaux. And PR123/DC trip unit)
K51/YC = Closing control from PR122/DC or PR123/DC electronic trip unit with communication module PR120/D-M
K51/YO = Opening control from PR122/DC or PR123/DC electronic trip unit with communication module PR120/D-M
M = Motor for charging the closing springs
Q = Circuit-breaker
Q/1...27 = Circuit-breaker auxiliary contacts
S33M/1...3 = Limit contacts for spring-charging motor
S43 = Switch for setting remote/local control
S51 = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release. The
circuit-breaker may be closed only after pressing the reset pushbutton, or after energizing the coil for
electrical reset (if available).
S75E/1...4 = Contacts for electrical signalling of circuit-breaker in racked-out position (only with withdrawable circuit-
breakers)
S75I/1...5 = Contacts for electrical signalling of circuit-breaker in racked-in position (only with withdrawable circuit-
breakers)
S75T/1..4 = Contacts for electrical signalling of circuit-breaker in test isolated position (only with withdrawable circuit-
breakers)
SC = Pushbutton or contact for closing the circuit-breaker
SO = Pushbutton or contact for opening the circuit-breaker
SO1 = Pushbutton or contact for opening the circuit-breaker with delayed trip
SO2 = Pushbutton or contact for opening the circuit-breaker with instantaneous trip
SR = Pushbutton or contact for electrical circuit-breaker reset
W1 = Serial interface with control system (external bus): EIA RS485 interface (see note E)
W2 = Serial interface with the accessories of PR122/DC and PR123/DC trip units (internal bus)
X = Delivery connector for auxiliary circuits of withdrawable version circuit-breaker
X1...X7 = Connectors for the accessories of the circuit-breaker
XF = Delivery terminal box for the position contacts of the withdrawable circuit-breaker (located on the fixed
part of the circuit-breaker)
XK1 = Connector for power circuits of PR122/DC and PR123/DC trip units
XK2 - XK3 = Connectors for auxiliary circuits of PR122/DC and PR123/DC trip units
XK4 = Connector signalling open/closet contact
XK5 = Connector for PR120/V module
XO = Connector for YO1 release
XV = Delivery terminal box for the auxiliary circuits of the fixed circuit-breaker
YC = Shunt closing release
YO = Shunt opening release
YO1 = Overcurrent shunt opening release
YO2 = Second shunt opening release (see note Q)
YR = Coil to electrically reset the circuit-breaker
YU = Undervoltage release (see notes B and Q)
Description of figures
Fig. 1 = Motor circuit to charge the closing springs.
Fig. 2 = Circuit of shunt closing release.
Fig. 4 = Shunt opening release.
Fig. 6 = Instantaneous undervoltage release (see notes B and Q).
Fig. 7 = Undervoltage release with electronic time-delay device, outside the circuit-breaker (see notes B and Q)
Fig. 8 = Second shunt opening release (see note Q).
Fig. 11 = Contact for electrical signalling of springs charged.
Fig. 12 = Contact for electrical signalling of undervoltage release energized (see notes B and S).
Fig. 13 = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release. The
circuit-breaker may be closed only after pressing the reset pushbutton.
Fig. 14 = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release and elec-
trical reset coil. The circuit-breaker may be closed only after pressing the reset pushbutton or energizing
the coil.
Fig. 21 = First set of circuit-breaker auxiliary contacts.
Fig. 22 = Second set of circuit-breaker auxiliary contacts (see note V).
Fig. 23 = Third set of supplementary auxiliary contacts outside the circuit-breaker.
Fig. 31 = First set of contacts for electrical signalling of circuit-breaker in racked-in, test isolated, racked-out position.
Fig. 32 = Second set of contacts for electrical signalling of circuit-breaker in racked-in, test isolated, racked-out
position.
Fig. 42 = Auxiliary circuits of PR122/DC and PR123/DC trip units (see notes F, M and V).
Fig. 45 = Circuits of the communication module PR120/D-M of the PR122/DC and PR123/DC trip units (optional,
see note E).
Fig. 46 = Circuits of the indicator module PR120/K of the PR122/DC and PR123/DC trip units - connection 1
(optional; see note V).
Fig. 47 = Circuits of the indicator module PR120/K of the PR122/DC and PR123/DC trip units - connection 2
(optional; see note V).
Fig. 62 = Circuits of the PR021/K signalling module (outside the circuit-breaker)
Incompatibilities
The circuits indicated in the following figures cannot be supplied simultaneously on the same circuit-breaker:
6-7-8
13 - 14
22 - 46 - 47
Operating status
A1 C1 B1 A1 C1 D1 B1
K51 K51
Q Q
>
XK10 XK10
A1I 1 A1I 1
>> >>
2 2
A1E XO A1E XO
>> 1 >> 1
>>
> >>>
1
1
Y01 Y01
XO XO
2
2
>> 2 >> 2
PR122/DC PR122/DC
XK11 XK11
B1I 1 B1I 2
2 1
B1E B1E
PR123/DC PR123/DC
a1 c1 b1 a1 c1 d1 b1
Three-pole circuit-breaker with PR122/DC or PR123/DC electronic trip Four-pole circuit-breaker with PR122/DC or PR123/DC electronic trip
units units
A1 A2 C1 C2 D1 D2 B1 B2
K51
Q
>
>>
XK10 XO
A1I 1 >> 1
2 >>>
A1E
1
Y01
XO
2
>> 2
XK10
A2I 3
4
A2E
PR122/DC PR122/DC
XK11
B1I 1
B1E 2
XK11
B2I 3
4
B2E
PR123/DC
PR123/DC
a1 a2 c1 c2 d1 d2 b1 b2
Three-pole circuit-breaker with PR122/DC or PR123/DC electronic Four-pole circuit-breaker with PR122/DC or PR123/DC electronic trip
trip units units
Signalling contacts
PR122/DC
PR123/DC
PR122/DC
PR123/DC
(+)
(+)
(+)
PR122/DC PR122/DC
PR123/DC PR123/DC
(-)
(-)
(-)
PR122/DC
PR123/DC
PR122/DC PR123/DC
1SDA......R1 1SDA......R1
3 Poles 4 Poles 3 Poles 4 Poles
E2 08 Iu (40 °C) = 800 A
VR = Vertical rear terminals
Fixed (F)
B 064580 064585 064668 064673
E2 10 Iu (40 °C) = 1000 A
VR = Vertical rear terminals
Fixed (F)
B 064581 064586 064669 064674
E2 12 Iu (40 °C) = 1250 A
VR = Vertical rear terminals
Fixed (F) B 064582 064587 064670 064675
E2 16 Iu (40 °C) = 1600 A
VR = Vertical rear terminals
Fixed (F) B 064583 064588 064671 064676
N 064584 064589 064672 064677
E3 08 Iu (40 °C) = 800 A
VR = Vertical rear terminals
Fixed (F)
N 064600 064609 064688 064697
E3 10 Iu (40 °C) = 1000 A
VR = Vertical rear terminals
Fixed (F)
N 064601 064610 064689 064698
E3 12 Iu (40 °C) = 1250 A
VR = Vertical rear terminals
Fixed (F)
N 064602 064611 064690 064699
E3 16 Iu (40 °C) = 1600 A
VR = Vertical rear terminals
Fixed (F)
N 064603 064612 064691 064700
H 064606 064615 064694 064703
E3 20 Iu (40 °C) = 2000 A
VR = Vertical rear terminals
Fixed (F)
N 064604 064613 064692 064701
H 064607 064616 064695 064704
E3 25 Iu (40 °C) = 2500 A
VR = Vertical rear terminals
Fixed (F)
N 064605 064614 064693 064702
H 064608 064617 064696 064705
1SDA......R1
Extracode
PR120/LV Low Voltage measuring module 24-48 V DC 065223*
PR120/V - PR120/LV Internal connection on upper terminals 058251**
* extracode to be specified with the circuit breaker code to have the low voltage measuring module PR120/LV
** The Emax DC is supplied ad standard for incoming power from the bottom terminals (PR120/V internal connection on bottom terminals – “U rear
connection kit” mounted on upper terminals).
In case of incoming power from the upper terminals an extracode must be specified: 1SDA058251R1 (PR120/V internal connection on upper
terminals – “U rear connection kit” mounted on bottom terminals).
PR122/DC PR123/DC
1SDA......R1 1SDA......R1
3 Poles 4 Poles 3 Poles 4 Poles
E2 08 Iu (40 °C) = 800 A
VR = Vertical rear terminals
Withdrawable (W) - MP
B 064590 064595 064678 064683
E2 10 Iu (40 °C) = 1000 A
VR = Vertical rear terminals
Withdrawable (W) - MP
B 064591 064596 064679 064684
E2 12 Iu (40 °C) = 1250 A
VR = Vertical rear terminals
Withdrawable (W) - MP B 064592 064597 064680 064685
E2 16 Iu (40 °C) = 1600 A
VR = Vertical rear terminals
Withdrawable (W) - MP B 064593 064598 064681 064686
N 064594 064599 064682 064687
E3 08 Iu (40 °C) = 800 A
VR = Vertical rear terminals
Withdrawable (W) - MP
N 064618 064627 064706 064715
E3 10 Iu (40 °C) = 1000 A
VR = Vertical rear terminals
Withdrawable (W) - MP
N 064619 064628 064707 064716
E3 12 Iu (40 °C) = 1250 A
VR = Vertical rear terminals
Withdrawable (W) - MP
N 064620 064629 064708 064717
E3 16 Iu (40 °C) = 1600 A
VR = Vertical rear terminals
Withdrawable (W) - MP
N 064621 064630 064709 064718
H 064624 064633 064712 064721
E3 20 Iu (40 °C) = 2000 A
VR = Vertical rear terminals
Withdrawable (W) - MP
N 064622 064631 064710 064719
H 064625 064634 064713 064722
E3 25 Iu (40 °C) = 2500 A
VR = Vertical rear terminals
Withdrawable (W) - MP
N 064623 064632 064711 064720
H 064626 064635 064714 064723
1SDA......R1
Extracode
PR120/LV Low Voltage measuring module 24-48 V DC 065223*
PR120/V - PR120/LV Internal connection on upper terminals 058251**
* extracode to be specified with the circuit breaker code to have the low voltage measuring module PR120/LV
** The Emax DC withdrawable mobile part is supplied ad standard for incoming power from the bottom terminals (PR120/V internal connection on
bottom terminals).
In case of incoming power from the upper terminals an extracode must be specified: 1SDA058251R1 (PR120/V internal connection on upper
terminals).
750 V DC 1000 V DC
1SDA......R1
3 Poles 4 Poles
E2 FP = Fixed part
VR 059895 059906
Withdrawable (W) - FP
E3 FP = Fixed part
VR 059896 059907
Withdrawable (W) - FP
E4 FP = Fixed part
VR 059897 059137
Withdrawable (W) - FP
E6 FP = Fixed part
VR 059140 059143
Withdrawable (W) - FP
1SDA......R1
Extracode*
U rear Connection kit FP E2-E6 DC on upper terminals 065169**
U rear Connection kit FP E2-E6 DC on upper terminals 065169***
* extracode to be specified with the fixed part whenever used with Emax DC to include the mandatory U rear connection kits
** extracode to be specified for incoming power from the bottom terminals
*** extracode to be specified for incoming power from the upper terminals