Camarines Norte State College
Camarines Norte State College
Camarines Norte State College
COLLEGE OF ENGINEERING
EE 28 – Professional Elective 2 (Power System Analysis and Design)
EE117
MODULE 2
Title: Fundamentals
I. Introduction
The objective of this chapter is to review basic concepts and establish terminology and notation.
II. Phasors
A sinusoidal voltage or current at constant frequency is characterized by two parameters: a maximum value
and a phase angle. A voltage
has a maximum value 𝑉𝑚𝑎𝑥 hand a phase angle 𝛿 when referenced to cos(𝜔𝑡). The root-mean-square (rms) value,
also called the effective value, of the sinusoidal voltage is
𝑉𝑚𝑎𝑥
𝑉= (2.1.2)
√2
Euler’s identity, (𝑒 𝑗∅ ) = cos ∅ + 𝑗𝑠𝑖𝑛∅, can be used to express a sinusoidal in terms of phasor. For the above
voltage above,
Where 𝑗 = √−1and Re denotes “real part of”. The rms phasor representation of the voltage is given in three
forms – exponential, polar and rectangular:
(2.1.4)
A phasor can be easily converts from one form to another. Conversion from polar to rectangular is shown in
the phasor diagram of Figure 2.1. Euler’s identity can be used to convert from exponential to rectangular form.
Activity 1: Given the sinusoid 𝑣(𝑡) = 169.7cos(𝜔𝑡 + 60°) volts. (a) Compute its rms value and (b) express the given
sinusoids as phasors.
Activity 2: Given the sinusoids 𝑖(𝑡) = 100 cos(𝜔𝑡 + 45°) amperes. a) Compute its rms value and (b) express the given
sinusoids as phasors.
Power is the rate of change of energy with respect to time. The unit of power is a watt, which is joule per
second.
CNSC-OP-VPA-01F11 Page 1 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
Purely Resistive Load
For a purely resistive load, the current into the load is in phase with the load voltage, 𝐼 = 𝑉/𝑅,and the current
into the resistive load is
Where:
𝐼𝑅𝑚𝑎𝑥 = 𝑉𝑚𝑎𝑥 /𝑅
As indicated by (2.2.3), the instantaneous power absorbed by the resistance has an average value
𝑉2
𝑃𝑅 = 𝑉𝐼𝑅 = = 𝐼𝑅 2 𝑅 𝑤𝑎𝑡𝑡𝑠 (2.2.4)
𝑅
Where:
𝐼𝐿𝑚𝑎𝑥 = 𝑉𝑚𝑎𝑥 /𝑋𝐿 , and 𝑋𝐿 = 𝜔𝐿 is the inductive reactance.
As indicated by (2.2.6), the instantaneous power absorbed by the inductor is a double-frequency sinusoid with
zero average value.
Where:
𝐼𝐶𝑚𝑎𝑥 = 𝑉𝑚𝑎𝑥 /𝑋𝐶 , and 𝑋𝐶 = 1/𝜔𝐶 is the capacitive reactance.
CNSC-OP-VPA-01F11 Page 2 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
1
= 𝑉𝑚𝑎𝑥 𝐼𝐶𝑚𝑎𝑥 cos[2(𝜔𝑡 + 𝛿) + 90] 𝑤𝑎𝑡𝑡𝑠
2
= −𝑉 𝐼𝐶 sin[2(𝜔𝑡 + 𝛿)] 𝑤𝑎𝑡𝑡𝑠 (2.2.8)
As indicated by (2.2.6), the instantaneous power absorbed by the capacitor is a double-frequency sinusoid
with zero average value.
For general load composed of RLC elements under sinusoidal-steady-state excitation, the load current is of
the form
(2.2.10)
Real Power
Equation (2.2.10) shows that the instantaneous power p 𝑃𝑅 (𝑡)absorbed by the resistive component of the load
is a double-frequency sinusoid with average value P given by
Power Factor
The term 𝑐𝑜𝑠(𝛿 − 𝛽) in (2.2.11) is called the power factor. The phase angle (𝛿 − 𝛽), which is the angle
between the voltage and current, is called the power factor angle.
For dc circuits, the power absorbed by a load is the product of the dc load voltage and the dc load current; for
ac circuits, the average power absorbed by a load is the product of the rms load voltage V, rms load current I, and the
power factor 𝑐𝑜𝑠(𝛿 − 𝛽), as shown by (2.2.11).
For inductive loads, the current lags the voltage, which means 𝛽 is less than 𝛿, and the power factor is said to
be lagging.
For capacitive loads, the current leads the voltage, which means 𝛽 is greater than 𝛿, and the power factor is
said to be leading.
By convention, the power factor 𝑐𝑜𝑠(𝛿 − 𝛽) is positive. If |(𝛿 − 𝛽)| is greater than 90°, then the reference
direction for current may be reversed, resulting in a positive value of 𝑐𝑜𝑠(𝛿 − 𝛽).
Reactive Power
The instantaneous power absorbed by the reactive part of the load, given by the component px(t) in (2.2.10),
is a double-frequency sinusoid with zero average value and with amplitude Q given by
CNSC-OP-VPA-01F11 Page 3 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
Activity 3 Instantaneous, Real, and Reactive Power; Power Factor
The voltage 𝑣(𝑡) = 141.4cos(𝜔𝑡 + 𝛿) is applied to a load consisting of a 10- Ω resistor in parallel with an inductive
reactance 𝑋𝐿 = 𝜔𝐿 = 3.77 𝛀. Calculate the instantaneous power absorbed by the resistor and by the inductor. Also
calculate the real and reactive power absorbed by the load, and the power factor.
The physical significance of real power P is easily understood. The total energy absorbed by a load during a
time interval T, consisting of one cycle of the sinusoidal voltage, is PT watt-seconds (Ws). During a time interval of n
cycles, the energy absorbed is P(nT) watt-seconds, all of which is absorbed by the resistive component of the load. A
kilowatt-hour meter is designed to measure the energy absorbed by a load during a time interval (t 2 – t1), consisting of
an integral number of cycles, by integrating the real power P over the time interval (t2 – t1).
The physical significance of reactive power Q is not as easily understood. Q refers to the maximum value of
the instantaneous power absorbed by the reactive component of the load. The instantaneous reactive power, given by
the second term px(t) in (2.2.10), is alternately positive and negative, and it expresses the reversible flow of energy to
and from the reactive component of the load. Q may be positive or negative, depending on the sign of (𝛿 − 𝛽) in
(2.2.12). Reactive power Q is a useful quantity when describing the operation of power systems (this will become
evident in later chapters).
Let the voltage across a circuit element be 𝑉 = 𝑉∠δ, and the current into the element be 𝐼 = 𝑉∠β. Then the complex
power S is the product of the voltage and the conjugate of the current:
𝑆 = 𝑉𝐼 ∗ = |𝑉∠δ||𝐼∠β|∗ = 𝑉𝐼∠(δ − β)
= 𝑉𝐼 cos(𝛿 − 𝛽) + 𝑗𝑉𝐼𝑠𝑖𝑛(𝛿 − 𝛽) (2.3.1)
Where (δ − β) is the angle between the voltage and current. Comparing (2.3.1) with (2.2.11) and (2.2.12), S is
recognized as
𝑆 = 𝑃 + 𝑗𝑄 (2.3.2)
A single-phase voltage source with 𝑉 = 100∠130° volts delivers a current 𝐼 = 10∠10° A, which leaves the
positive terminal of the source. Calculate the source real and reactive power, and state whether the source delivers or
absorbs each of these.
CNSC-OP-VPA-01F11 Page 4 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
The load convention is used for the RLC elements shown in Figure 2.2. Therefore, the complex power
absorbed by any of these three elements can be calculated as follows. Assume a load voltage 𝑉 = 𝑉∠δ. Then, from
(2.3.1),
Resistor: (2.3.3)
Inductor: (2.3.4)
Capacitor: (2.3.5)
Power Triangle
𝑆 = √𝑃2 + 𝑄2 (2.3.6)
(δ − β) = 𝑡𝑎𝑛−1 (𝑄/𝑃) (2.3.7)
Q = P tan(δ − β) (2.3.8)
𝑃 𝑃
pf = cos(δ − β) = = (2.3.9)
𝑆 √𝑃2 +𝑄2
A single-phase source delivers 100 kW to a load operating at a power factor of 0.8 lagging. Calculate the
reactive power to be delivered by a capacitor connected in parallel with the load in order to raise the source power
factor to 0.95 lagging. Also draw the power triangle for the source and load. Assume that the source voltage is
constant, and neglect the line impedance between the source and load.
V. Network Equations
For circuits operating in sinusoidal-steady-state, Kirchhoff’s current law (KCL) and voltage law (KVL) apply to
phasor currents and voltages.
STEP 1 For a circuit with (N + 1) nodes (also called buses), select one bus as the reference bus and define
the voltages at the remaining buses with respect to the reference bus.
CNSC-OP-VPA-01F11 Page 5 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
STEP 2 Transform each voltage source in series with an impedance to an equivalent current source in parallel
with that impedance. Also, show admittance values instead of impedance values on the circuit diagram. Each current
source is equal to the voltage source divided by the source impedance.
(2.4.1)
where Y is the (N x N) bus admittance matrix, V is the column vector of N bus voltages, and I is the column
vector of N current sources. The elements Ykn of the bus admittance matrix Y are formed as follows:
The diagonal element Ykk is called the self-admittance or the driving-point admittance of bus k, and the off-
diagonal element Ykn for k 0 n is called the mutual admittance or the transfer admittance between buses k and n.
Since Ykn = Ynk, the matrix Y is symmetric
CNSC-OP-VPA-01F11 Page 6 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
For the circuit of Figure 2.9, (2.4.1) becomes
(2.4.5)
Balanced Y Connections
Figure 2.10 shows a three-phase Y-connected (or ‘‘wye-connected’’) voltage source feeding a balanced-Y-
connected load.
𝑬𝒂𝒏 = 10∠0°
𝑬𝒃𝒏 = 10∠ − 120° = 10∠ + 240° (2.5.1)
𝑬𝒄𝒏 = 10∠ + 120° = 10∠ − 240° volts
CNSC-OP-VPA-01F11 Page 7 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
Balanced Line-to-Line Voltages
The voltages Eab; Ebc, and Eca between phases are called line-to-line voltages. Writing a KVL equation for a
closed path around buses a, b, and n in Figure 2.10,
−1−𝑗√3
𝐸𝑎𝑏 = 10∠0° − 10∠ − 120° = 10 − 10[ ] (2.5.3)
2
√3+𝑗1
𝐸𝑎𝑏 = √3(10) ( ) = √3(10∠30°) 𝑣𝑜𝑙𝑡𝑠
2
In a balanced three-phase Y-connected system with positive-sequence sources, the line-to-line voltages are
√3 times the line-to-neutral voltages and lead by 30° . That is,
𝐼𝑎 = 𝐸𝑎𝑛 /𝑍𝑌
𝐼𝑏 = 𝐸𝑏𝑛 /𝑍𝑌 (2.5.7)
𝐼𝑐 = 𝐸𝑐𝑛 /𝑍𝑌
For example, if each phase of the Y-connected load has an impedance 𝑍𝑌 = 2∠30°𝛀, then
10∠0°
𝐼𝑎 = = 5∠ − 30° A
2∠30°
10∠−120°
𝐼𝑏 = = 5∠ − 150° A (2.5.8)
2∠30°
10∠+120°
𝐼𝑐 = = 5∠90° A
2∠30°
CNSC-OP-VPA-01F11 Page 8 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
The neutral current In is determined by writing a KCL equation at bus N in Figure 2.10
𝐼𝑛 = 𝐼𝑎 + 𝐼𝑏 + 𝐼𝑐 (2.5.9)
The line impedances are neglected in Figure 2.14, the source line-to-line voltages are equal to the load line-
to-line voltages, and the Δ-load currents IAB, IBC, and ICA are
For example, if the line-to-line-voltages are given by (2.5.3) - (2.5.5)and if 𝑍Δ = 5∠30°𝛀, then the Δ-load
currents are
10∠30°
𝐼𝐴𝐵 = √3( ) = 3.464∠0° A
5∠30°
10∠−90°
𝐼𝐵𝐶 = √3 ( ) = 3.464∠ − 120° A (2.5.12)
5∠30°
10∠150°
𝐼𝐶𝐴 = √3( ) = 3.464∠120° A
5∠30°
Also, the line currents can be determined by writing a KCL equation at each bus of the Δ load, as follows:
For a balanced-Δ load supplied by a balanced positive-sequence source, the line currents into the load are √3
times the Δ -load currents and lag by 30°. That is,
𝐼𝑎 = √3𝐼𝐴𝐵 ∠ − 30°
𝐼𝑏 = √3𝐼𝐵𝐶 ∠ − 30° (2.5.14)
𝐼𝑐 = √3𝐼𝐶𝐴 ∠ − 30°
CNSC-OP-VPA-01F11 Page 9 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
For Δ load,
√3𝐸𝐴𝐵 ∠−30°
𝐼𝐴 = √3𝐼𝐴𝐵 ∠ − 30° = (2.5.15)
𝑍Δ
For Y load,
𝐸𝐴𝑁 𝐸𝐴𝐵 ∠−30°
𝐼𝐴 = = (2.5.16)
𝑍𝑌 √3𝑍Y
Comparison of (2.5.15) and (2.5.16) indicates that IA will be the same for both the Δ and Y loads when
𝑍Δ
𝑍𝑌 = (2.5.17)
3
A balanced, positive-sequence, Y-connected voltage source with 𝐸𝐴𝐵 = 480∠0° volts is applied to a balanced-Δ load
with 𝑍Δ = 30∠40°Ω. The line impedance between the source and load is 𝑍L = 1∠85°Ω for each phase. Calculate the
line currents, the Δ -load currents, and the voltages at the load terminals
When working with balanced three-phase circuits, only one phase need be analyzed. Δ loads can be
converted to Y loads, and all source and load neutrals can be connected with a zero-ohm neutral wire without
changing the solution. Then one phase of the circuit can be solved. The voltages and currents in the other two phases
are equal in magnitude to and ±120° out of phase with those of the solved phase. Figure 2.18 shows an equivalent
line-to neutral diagram for one phase of the circuit in Example 2.4.
CNSC-OP-VPA-01F11 Page 10 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
When discussing three-phase systems in this text, voltages shall be rms line-to-line voltages unless otherwise
indicated. This is standard industry practice.
Assume that the generator is operating under balanced steady-state conditions with the instantaneous
generator terminal voltage given by
And with the instantaneous current leaving the positive terminal of phase a given by
where VLN is the rms line-to-neutral voltage and IL is the rms line current. The instantaneous power pa(t)
delivered by phase a of the generator is
Assuming balanced operating conditions, the voltages and currents of phases b and c have the same
magnitudes as those of phase a and are ±120°out of phase with phase a. Therefore the instantaneous power
delivered by phase b is
The total instantaneous power 𝑝3∅ (𝑡) delivered by the three-phase gen erator is the sum of the
instantaneous powers delivered by each phase. Using (2.6.3)–(2.6.5):
CNSC-OP-VPA-01F11 Page 11 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
The three cosine terms within the brackets of (2.6.6) can be represented by a balanced set of three phasors.
Therefore, the sum of these three terms is zero for any value of 𝛽 , and for all values of t. Equation (2.6.6) then
reduces to
Equation (2.6.7) can be written in terms of the line-to-line voltage VLL instead of the line-to-neutral voltage VLN.
Under balanced operating conditions,
The total instantaneous power absorbed by a three-phase motor under balanced steady-state conditions is
also a constant. Figure 2.19 can be used to represent a three-phase motor by reversing the line currents to enter
rather than leave the positive terminals. Then (2.6.1)–(2.6.8), valid for power delivered by a generator, are also valid
for power absorbed by a motor. These equations are also valid for the instantaneous power absorbed by a balanced
three-phase impedance load.
The phasor representations of the voltage and current in (2.6.1) and (2.6.2) are
where 𝐼𝑎 leaves positive terminal “𝑎” of the generator. The complex power 𝑆𝑎 delivered by phase 𝑎 of the
generator is
Under balanced operating conditions, the complex powers delivered by phases b and c are identical to 𝑆𝑎 ,
and the total complex power 𝑆3∅ delivered by the generator is
𝑆3∅ = 𝑆𝑎 + 𝑆𝑏 + 𝑆𝑐 = 3𝑆𝑎
= 3𝑉𝐿𝑁 𝐼𝐿 ∠(δ − β)
= 3𝑉𝐿𝑁 𝐼𝐿 cos(δ − β) + j3𝑉𝐿𝑁 𝐼𝐿 sin(δ − β) (2.6.12)
Where
COLLEGE OF ENGINEERING
And
𝑄3∅ = 𝐼𝑚 (𝑆3∅ ) = 3𝑉𝐿𝑁 𝐼𝐿 sin(δ − β)
= √3𝑉𝐿𝐿 𝐼𝐿 sin(δ − β) 𝑣𝑎𝑟 (2.6.15)
The preceding expressions for complex, real, reactive, and apparent power delivered by a three-phase
generator are also valid for the complex, real, reactive, and apparent power absorbed by a three-phase motor.
Equations (2.6.13)–(2.6.16) are also valid for balanced-Y and - Δ impedance loads. For a balanced-Y load,
the line-to-neutral voltage across the phase a load impedance and the current entering the positive terminal of that
load impedance can be represented by (2.6.9) and (2.6.10). Then (2.6.11)–(2.6.16) are valid for the power absorbed
by the balanced-Y load.
For a balanced- Δ load, the line-to-line voltage across the phase a–b load impedance and the current into the
positive terminal of that load impedance can be represented by
where VLL is the rms line-to-line voltage and 𝐼Δ is the rms Δ -load current. The complex power 𝑆𝑎𝑏 b absorbed
by the phase a–b load impedance is then
Where the Δ -load current 𝐼Δ is expressed in terms of the line current 𝐼L = √3𝐼Δ in (2.6.22) and (2.6.23). also
the total apparent power is
Equations (2.6.21)–(2.6.24) developed for the balanced- Δ load are identical to (2.6.13)–(2.6.16).
CNSC-OP-VPA-01F11 Page 13 of 14
Revision: 0
Republic of the Philippines
CAMARINES NORTE STATE COLLEGE
F. Pimentel Avenue, Brgy. 2, Daet, Camarines Norte
COLLEGE OF ENGINEERING
Assignment Power in Balanced Three-Phase System
Two balanced three-phase motors in parallel, an induction motor drawing 400 kW at 0.8 power factor lagging and a
synchronous motor drawing 150 kVA at 0.9 power factor leading, are supplied by a balanced, three-phase 4160-volt
source. Cable impedances between the source and load are neglected, (a) Draw the power triangle for each motor
and for the combined-motor load. (b) Determine the power factor of the combined-motor load. (c) Determine the
magnitude of the line current delivered by the source. (d) A delta-connected capacitor bank is now installed in
parallel with the combined-motor load. What value of capacitive reactance is required in each leg of the capacitor
bank to make the source power factor unity? (e) Determine the magnitude of the line current delivered by the
source with the capacitor bank installed.
Prepared by:
CNSC-OP-VPA-01F11 Page 14 of 14
Revision: 0