Siemens - Line Differential Protections SIPROTEC 7SD60
Siemens - Line Differential Protections SIPROTEC 7SD60
Siemens - Line Differential Protections SIPROTEC 7SD60
SIPROTEC 7SD60
Numerical Pilot-Wire Current Differential Protection Relay 7/3
SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends 7/17
SIPROTEC 4 7SD52/53
Multi-End Differential Protection Relay for Two to Six Line Ends 7/43
7
7
SIPROTEC 7SD60
Numerical Pilot-Wire Current Differential Protection Relay
Function overview
Application Construction
The 7SD60 relay is a numerical current The compact 7SD60 protection relay con-
differential protection relay, simple to set, tains all the components for:
and is operated in conjunction with the re-
mote station via a two pilot-wire link. • Measured-value acquisition and evalua-
tion
It is connected to the primary current trans- • Operation and LCD indications
formers via an external summation current
• Alarm and command contacts
transformer. The unit operates internally on
the summated current taken from the sec- • Input and evaluation of binary signals
ondary side of the summation current • Data transmission via the RS485
transformer. The link to the remote station bus interface to DIGSI or a substation
is realized by means of a pair of symmetrical control system
pilot wires allowing distances of up to ap- • Auxiliary voltage supply
proximately 12 km. Adaptation to the pi- The primary current transformers are con-
lot-wire resistance is effected by means of nected to the 4AM49 summation current
software within the unit. Therefore, match- transformer. At the rated current value of
ing is not necessary. either 1 A or 5 A, the latter outputs a cur-
The primary field of application of the unit rent of 20 mA which is measured by the
is protection of short overhead lines and ca- 7SD60 unit. The summation current trans-
bles with two line ends. However, trans- former is supplied together with the pro-
formers and reactors may be located within tection unit, if so ordered.
the protection zone. The unit can be fitted The unit can be supplied in two different
with inrush restraint in such cases. A differ- housings. The one for flush mounting in a
ential protection instantaneous tripping panel or cubicle has connection terminals
7 stage is also provided in this case. Vector at the rear.
group adaptation is not effected inside the
unit and must, if necessary, be effected by The version for panel surface mounting is
means of a matching current transformer. supplied with terminals accessible from the
front. Alternatively, the unit can be sup-
The 7SD60 can be fitted with a pilot-wire plied with two-tier terminals arranged
monitoring function. In addition to moni- above and below the unit.
toring the pilot-wire link to the remote sta-
tion, this also includes bidirectional circuit-
breaker intertripping and a remote tripping
command.
If the differential protection becomes inac-
tive due to a pilot-wire failure, the relay has
an emergency overcurrent function as an
option. It includes one definite-time
overcurrent stage and can be delayed.
This unit substitutes the 7SD24 steady-
state differential protection. However,
LSP2002-afpen.tif
Protection functions
Pilot-wire link / pilot-wire monitoring Lockout of the TRIP command with manual
Protection functions
reset
The link to the remote station comprises a
Overcurrent release / differential current symmetrical pair of wires (e.g. telephone The TRIP command can be locked-out after
monitoring lines). The maximum permissible distance tripping. In particular, in the case of trans-
The differential protection function can be between two stations is approximately formers within the protection zone,
combined with an additional overcurrent 12 km. 7XR9513 (20 kV) or 7XR9515 reclosure of the line is normally effected
release. To this end, the criteria “overcur- (5 kV) isolation transformers can be em- only after the cause of the fault has been as-
rent” and “differential current” are linked ployed for potential isolation against inter- certained by the user. Manual reset is possi-
logically so that a TRIP command is given ference induced by longitudinal voltages ble either via the operator panel (with
out by the differential function only when where the pilot wires run parallel to power password) or via a binary input. As a result,
a differential current and an overcurrent cables over long distances. premature reclosure of the circuit-breaker is
coexist. prevented. The logic state of the TRIP com-
Since the pilot wires form an integral part of
mand remains stored even during failure of
By this means it is often possible to avoid the differential protection, these are nor-
the auxiliary supply voltage, so that it is still
malfunctioning due to pilot-wire short- mally monitored continuously. This func-
present on restoration of the auxiliary sup-
circuit or wire-break of a connection be- tion is available as an option. To achieve
ply voltage.
tween a current transformer and the sum- this, 2 kHz pulses with a defined pulse width
mation current transformer. For this ratio are transmitted to the remote relay via Inrush restraint / instantaneous tripping
purpose, the 7SD60 is fitted with an addi- the pilot wires. Detection of a fault in the pi- stage
tional differential current monitoring func- lot-wire link results in blocking of the dif-
ferential protection. Where transformers or reactors are located
tion, which can effectively block the
within the protection zone, inrush restraint
differential protection after a delay of some
Emergency overcurrent protection can be supplied as an option. This inrush
seconds on reaching of an adjustable value
restraint evaluates the second harmonic of
of differential current in conjunction with If the differential protection becomes inac-
the differential current, which is typical for
simultaneous operational current IM1 within tive due to a pilot-wire failure or an internal
inrush phenomena. If the second har-
the load range. or external blocking of the differential func-
monic value of the differential current re-
7 tion, the relay offers a single-stage, defi-
ferred to the fundamental frequency
Saturation detector nite-time overcurrent function. It works
exceeds a preset value, tripping by the dif-
with the local flowing operational current
Improved stability on single-ended satura- ferential protection is blocked. In the case
IM1. The pickup value and the delay time are of high-current internal faults, whose am-
tion of the primary current transformers is
settable via parameters in the device. plitude exceeds the inrush current peak,
ensured by means of an integrated satura-
tion detector. It provides additional stabil- tripping can be carried out instanta-
Circuit-breaker intertripping / remote trip-
ity during external faults. 5 ms are enough neously.
ping
time to measure an external fault due to a
Vector group adaptation is not effected in-
high restraint and small differential cur- Normally, tripping is effected at both sta-
side the unit and must, where necessary, be
rent. Indication is done within the addi- tions as a result of current comparison.
brought about by means of an external
tional restraint area (see Fig. 7/4). If – due Tripping at one end only can occur when
matching transformer scheme.
to CT saturation – the differential current an overcurrent release is used or with
flows into the trip area, the differential trip short-circuit currents only slightly above
is blocked for a certain time. Transient sat- the tripping value. Circuit-breaker
uration of current transformers caused by intertripping can be parameterized in the
decaying DC components in the short- unit with integral pilot-wire monitor, so
circuit current can thus be recognized. that definite tripping at both ends of the
line is assured.
As a result, the requirements on the cur-
rent transformers are reduced so that they In addition, it is possible by means of a bi-
are only required to conduct the steady- nary input to output a remote tripping
state through-flowing short-circuit current command for both directions. The com-
without saturation. mand transmission time is approximately
80 ms.
Features
Connection diagrams
Fig. 7/6
Standard connection L1-L3-E,
suitable for all types of networks
Fig. 7/7
Protection configuration with
main (7SD60) and backup
overcurrent (7SJ60) protection
Fig. 7/8
Typical circuit for auxiliary voltage supply
Technical data
Technical data
Technical data
Technical data
Unit design
For panel surface mounting with terminals at the side B
with terminals on top and bottom D
For panel flush mounting or cubicle mounting E
Operating language
English – alternatively either German or Spanish can be selected 0
Scope of functions
Differential protection 0
Differential protection, inrush restraint 1
Differential protection, pilot-wire monitoring, remote trip 2
Differential protection, pilot-wire monitoring, remote trip, inrush restraint 3
7
Accessories DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (Windows 2000 or XP Professional)
device templates, Comtrade Viewer, electronic manual included
as well as “Getting started” manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Professional
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
SIGRA 4
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format). Running under MS Windows (Windows 2000 and
XP Professional).
Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM. 7XS5410-0AA00
Connecting cable
Cable between PC/notebook (9-pin connector)
and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
Converter RS485-FO
Rated auxiliary voltage 24 to 250 V DC and 250 V AC
Single optical interface 7XV5650-0BA00
Double optical interface (cascadable) 7XV5651-0BA00
Isolating transformer
Up to 20 kV 7XR9513
Up to 5 kV 7XR9515
Connection diagram
SIPROTEC 4 7SD61
Differential Protection Relay for Two Line Ends
Function overview
Protection functions
• Differential protection for universal use
with power lines and cables on all volt-
age levels with phase-segregated mea-
surement (87L)
• Two line ends capability
• Suitable for transformers in protected
zones (87T)
• Restricted earth-fault protection (87N) if a
transformer is within the protection zone
• Well-suited for serial compensated lines
LSP2247-afpen.tif
Fig. 7/11
Application
Typical applications employing fiber-
optic cables or communication networks
Four applications are shown in Fig. 7/12.
The 7SD610 differential protection relay is
connected to the current transformers and
to the voltage transformers at one end of the
cable, although only the currents are re-
quired for the differential protection func-
tion. The voltage connection improves,
among other things, the frequency measure-
ment and allows the measured values and
the fault records to be extended. Direct con-
nection to the other units is effected via
mono-mode fiber-optic cables and is thus
immune to interference.
Five different modules are available. In the
case of direct connection via fiber-optic
cables, data communication is effected at
512 kbit/s and the command time of the
protection unit is reduced to 15 ms. Parallel
compensation (for the load currents)
is provided within the protection zone of
the cable. By means of the integrated inrush
restraint, the differential protection relay
can tolerate the surge on switching-on of
7
the cable and the compensation reactors,
and thus allows sensitive settings to be used
under load conditions.
7SD610 offers many features to reliably and
safely handle data exchange via communi-
cation networks.
Depending on the bandwidth available a
communication converter for G703-64 kbit/s
or X21-64/128/512 kbit/s can be selected. For
higher communication speed a communica-
tion converter with G703-E1 (2,048 kbit/s)
or G703-T1 (1,554 kbit/s) is available.
The connection to the communication
converter is effected via a cost-effective
820 nm interface with multi-mode fiber.
This communication converter converts
the optical input to electrical signals in ac-
cordance to the specified telecommunica-
tion interface.
The fourth example shows the relays being
connected via a twisted pilot pair. Data
exchange and transmission is effected via Fig. 7/12
pilot wires of a typical length of 15 km. Typical applications
Here a transformer is in the protected zone.
In this application, 7SD610 is set like a
transformer differential relay. Vector group
matching and inrush restraint is provided
by the relay.
The trip time characteristics are exponential Circuit-breaker closure onto a faulty line
functions according to IEC 60255-8. The is also possible provided that the circuit-
preload is considered in the trip times for breaker auxiliary contacts of the remote
overloads. end are connected and monitored. If an
overcurrent arises on closing of the cir-
An adjustable alarm stage can initiate an cuit-breaker at one end of a line (while the
alarm before tripping is initiated. other end is energized) the measured cur-
rent can only be due to a short-circuit. In
Overcurrent protection this case, the energizing line end is tripped
(ANSI 50, 50N, 51, 51N, 67, 67N) instantaneously.
The 7SD610 provides a three-stage In the case of circuit-breaker closure, the
overcurrent protection. Two definite- auto-reclosure is blocked at both ends of
time stages and one inverse-time stage the line to prevent a further unsuccessful 0,14
(IDMT) are available, separately for phase closure onto a short-circuit. t= 0,02
Tp
( I I p ) −1
currents and for the earth current. Two op- If circuit-breaker intertripping to the re-
erating modes (backup, emergency) are mote end is activated, intertripping is also
Fig. 7/15 Inverse
selectable. Two stages e.g. can run in backup blocked.
mode, whereas the third stage is configured
7 for emergency operation, e.g. during inter-
• Monitoring of the circuit-breaker auxil-
Auto-reclosure (ANSI 79)
iary contacts
ruption of the protection communication
and/or failure of the voltage in the VT sec- The 7SD610 relay is equipped with an
In addition to the above-mentioned operat-
ondary circuit. The secondary voltage fail- auto-reclose function (AR). The function
ing modes, several other operating princi-
ure can be detected by the integrated fuse includes several operating modes:
ples can be employed by means of the
failure monitor or via a binary input from • 3-pole auto-reclosure for all types of integrated programmable logic (CFC).
a VT miniature cicuit-breaker faults; different dead times are available
(VT m.c.b. trip). Integration of auto-reclosure in the feeder
depending the type of fault
protection allows evaluation of the line-side
The following ANSI/IEC inverse-time • 1-pole auto-reclosure for 1-phase faults, voltages. A number of voltage-dependent
characteristics are available: no reclosing for multi-phase faults supplementary functions are thus available:
• 1-pole auto-reclosure for 1-phase faults
• Inverse and for 2-phase faults without earth, no • DLC
reclosing for multi-phase faults By means of dead-line check, reclosure is
• Short inverse effected only when the line is deenergized
• 1-pole auto-reclosure for 1-phase and
• Long inverse 3-pole auto-reclosing for multi-phase (prevention of asynchronous breaker
closure).
• Moderately inverse faults
• 1-pole auto-reclosure for 1-phase faults • ADT
• Very inverse and 2-phase faults without earth and The adaptive dead time is employed only
if auto-reclosure at the remote station was
• Extremely inverse 3-pole auto-reclosure for other faults
successful (reduction of stress on equip-
• Definite inverse • Multiple-shot auto-reclosure
ment).
• Interaction with an external device for
• RDT
If VTs are connected, separate stages with auto-reclosure via binary inputs and out-
Reduced dead time is employed in con-
directional measurement are available, two puts
junction with auto-reclosure where no
definite-time and two inverse-time stages • Control of the integrated AR function by tele-protection method is employed:
(each for phase and earth). Using the for- external protection When faults within the zone extension, but
ward pickup indication as a signal to the re- • Adaptive auto-reclosure. Only one line external to the protected line, are switched
mote end, a 100 % protection coverage of end is closed after the dead time. If the off for rapid auto-reclosure (RAR), the
the line can be operated in parallel to the fault persists this line end is switched off. RDT function decides on the basis of mea-
differential protection. Otherwise the other line ends are closed surement of the return voltage from the re-
via a command over the communication mote station which has not tripped
links. This avoids stress when heavy fault whether or not to reduce the dead time.
currents are fed from all line ends again.
• Interaction with an external synchro-
check
Protection functions
Commissioning
Special attention has been paid to commis-
LSP2845.tif
sioning. All binary inputs and outputs can
be displayed and activated directly. This can
simplify the wiring check significantly for
Fig. 7/16
the user. The operational and fault events Browser-aided commissioning: Phasor diagram
and the fault records are clearly arranged. 7
Furthermore, all currents and optional volt-
ages and phases are available via communi-
cation link at the local relay and are dis-
played in the relay, with DIGSI 4 or with the
Web Monitor.
The operational and fault events and fault
records from all line ends share a common
time tagging which allows to compare
events registered in the different line ends
on a common time base.
System interface
This interface is used to carry out commu-
nication with a control or protection and
control system and supports a variety of
communication protocols and interface de-
signs, depending on the module connected.
Communication
LSP2163-afpen.tif
IEC 61850 Ethernet
Since 2004, the Ethernet-based IEC 61850
protocol is the worldwide standard for pro-
tection and control systems used by power
supply corporations. Siemens was the first
LSP2164-afpen.tif
manufacturer to support this standard. By
means of this protocol, information can also
be exchanged directly between bay units so
as to set up simple masterless systems for
bay ans system interlocking. Access to the
units via the Ethernet bus is also possible Fig. 7/20 Fig. 7/21
with DIGSI. R232/RS485 electrical communication module Communication module, optical double-ring
IEC 60870-5-103
IEC 60870-5-103 is an internationally stan-
LSP2162-afpen.tif
dardized protocol for the efficient commu-
nication in the protected area.
IEC 60870-5-103 is supported by a number
of protection device manufacturers and is
used worldwide.
PROFIBUS-DP
7 PROFIBUS-DP is an industry-recognized
LSP2810.tif
standard for communications and is sup-
ported by a number of PLC and protection
device manufacturers.
Fig. 7/22 Fig. 7/23
Fiber-optic communication module Fiber-optic Ethernet communication module for
MODBUS RTU IEC 61850 with integrated Ethernet switch
MODBUS RTU is an industry-recognized
standard for communications and is sup-
ported by a number of PLC and protection
device manufacturers.
DNP 3.0
DNP 3.0 (Distributed Network Protocol
Version 3) is a messaging-based communi-
cation protocol. The SIPROTEC 4 units are
fully Level 1 and Level 2 compliant with
DNP 3.0. DNP 3.0 is supported by a num-
ber of protection device manufacturers.
Fig. 7/24
System solution: Communications
Communication
• Two terminal line applications can be digital follow-up technique is available for
implemented without additional logic two-wire protection systems (up to 15 km)
System solutions for protection and station • Interclose command transfer with the and all three-wire protection systems using
control auto-reclosure “Adaptive dead time” existing copper communication links.
(ADT) mode Different communication converters are
Together with the SICAM power automa- • 4 remote signals for fast transfer of
tion system, SIPROTEC 4 can be used with listed under "Accessories".
binary signals
PROFIBUS-FMS. Over the low-cost electri- Communication data:
cal RS485 bus, or interference-free via the • Flexible utilization of the communica-
optical double ring, the units exchange in- tion channels by means of the program- • 32-bit CRC-check according to CCITT
formation with the control system. mable CFC logic and ITU
• Each protection relay possesses a unique
Units featuring IEC 60870-5-103 interfaces The protection data interfaces have different
relay address
can be connected to SICAM in parallel via options to cover new and existing commu-
nication infrastructures. • Continuous communication link supervi-
the RS485 bus or radially by fiber-optic link. sion: Individual faulty data telegrams do
Through this interface, the system is open • FO51), OMA12) module: not constitute an immediate danger, if
for the connection of units of other manu- 820 nm fiber-optic interface with clock re- they occur only sporadically. The statisti-
facturers (see Fig. 7/18). covery/ST connectors for direct connec- cal availability, per minute and hour, of
Because of the standardized interfaces, tion with multi-mode FO cable up to the serial protection data interface can be
SIPROTEC units can also be integrated 1.5 km for the connection to a communi- displayed.
into systems of other manufacturers or in cation converter. • Supported network interfaces
SIMATIC. Electrical RS485 or optical inter- • FO61), OMA22) module: X21/RS422 with 64 or 128 or 512 kbit/s;
faces are available. The optimum physical 820 nm fiber-optic interface/ST connec- or G703-64 kbit/s and G703-E1
data transfer medium can be chosen thanks tors for direct connection up to 3.5 km (2,048 kbit/s) or G703-T1 (1,554 kbit/s).
to opto-electrical converters. Thus, the with multi-mode FO cable. • Max. channel delay time 0.1 ms to 30 ms
RS485 bus allows low-cost wiring in the cu- (in steps of 0.1 ms)
bicles and an interference-free optical con- New fiber-optic interfaces, series FO1x • Protocol HDLC
nection to the master can be established.
7
• FO171): For direct connection
For IEC 61850, an interoperable system so- up to 24 km3), 1300 nm, for mono-mode
lution is offered with SICAM PAS. Via the fiber 9/125 μm, LC-Duplex connector
100 Mbits/s Ethernet bus, the units are • FO181): For direct connection up to
linked with PAS electrically or optically to 60 km3), 1300 nm, for mono-mode fiber
the station PC. The interface is standard- 9/125 μm, LC-Duplex connector
ized, thus also enabling direct connection • FO191): For direct connection up to
of units of other manufacturers to the 100 km3), 1550 nm, for mono-mode
Ethernet bus. With IEC 61850, however, the fiber 9/125 μm, LC-Duplex connector
units can also be used in other manufactur-
ers' systems (see Fig. 7/19). The link to a multiplexed communication
Via modem and service interface, the pro- network is made by separate communica-
tection engineer has access to the protection tion converters (7XV5662). These have a
devices at all times. This permits remote fiber-optic interface with 820 nm and 2 ST
maintenance and diagnosis (cyclic testing). connectors to the protection relay. The link
to the communication network is option-
Parallel to this, local communication is pos- ally an electrical X21/G703-64 kbit/s or
sible, for example, during a major inspec- G703-E1/-T1 interface.
tion.
For operation via copper wire communica-
Serial protection data interface tion (pilot wires or twisted telephone pair),
(R2R interface) a modern communication converter for
copper cables is available. This operates with
The 7SD610 provides one protection data both the two-wire and three-wire copper
interface to cover two line end applications. connections which were used by conven-
In addition to the differential protection tional differential protection systems before.
function, other protection functions can use The communication converter for copper
this interface to increase selectivity and sen- cables is designed for 5 kV insulation volt-
sitivity as well as covering advanced applica- age. An additional 20 kV isolation trans-
tions. former can extend the field of applications
of this technique into ranges with higher in-
• Fast phase-selective teleprotection signal- sulation voltage requirements. The connec- 1) For flush-mounting housing.
ing using the directional stages of the tion via FO cable to the relay is interfer- 2) For surface-mounting housing.
overcurrent protection with POTT or ence-free. With SIPROTEC 4 and the com-
PUTT schemes 3) For surface-mounting housing the internal
munication converter for copper cables a FO module OMA1 will be delivered together
with an external repeater.
Communication
Fig. 7/29
Connection to a pilot wire
Typical connection
Fig. 7/31
Typical connection to current transformers with optional voltage inputs
Technical data
Maximum permissible voltage 300 V DC Refer to ordering code IEC 61850 Ethernet
IEC 60870-5-103
Current consumption, energized Approx. 1.8 mA PROFIBUS-DP
Output relay DNP 3.0, MODBUS
Command / indication relay Isolated RS232/RS485 9-pin subminiature connector (SUB-D)
Baud rate 4800 to 38400 baud
Number 5 (marshallable)
Dielectric test 500 V/50 Hz
1 alarm contact (not marshallable)
Distance for RS232 Max. 15 m
Switching capacity Distance for RS485 Max. 1000 m
Make 1000 W/VA
For fiber-optic cable ST connector
Break 30 VA
Optical wavelength λ = 820 nm
Break (with resistive load) 40 W
Permissible attenuation Max. 8 dB for 62.5/125 µm fiber
Break (with L/R ≤ 50 ms) 25 W
Distance (spanned) Max. 1.5 km
Switching voltage 250 V
Permissible total current 30 A for 0.5 seconds
5 A continuous
Technical data
System interface, continued External communication converter 7XV5662-0AC00 for pilot wires
PROFIBUS RS485 External communication converter
Dielectric test 500 V/50 Hz to interface between relays, optical
Baud rate Max. 12 Mbaud 820 nm interface and a pilot wire or
Distance 1 km at 93.75 kbd; 100 m at 12 Mbd twisted telephone pair.
PROFIBUS fiber-optic2) Typical distance 15 km
Only for flush-mounting housing ST connector Fiber-optic 820 nm with clock re- Max. 1.5 km with 62.5/125 µm
For surface-mounting housing Optical interface with OLM2) covery multi-mode FO cable
Baud rate Max. 1.5 Mbaud
Optical wavelength λ = 820 nm Pilot wire Screw-type terminal 5 kV isolated
Permissible attenuation Max. 8 dB for 62.5/125 μm fiber Permissible time delay (duration of data transmission)
Distance 500 kbit/s 1.6 km; 1500 kbit/s 530 m
Delay of telegrams due to trans- Max. 30 ms per transmission path
Protection data interface (R2R interface) mission for one unit to the other. Permissible max. value can be
FO51), OMA12): Fiber-optic interface For multi-mode fiber 62.5/125 μm, Delay is constantly measured and selected
with clock recovery for direct con- ST connectors adjusted
nection up to 1.5 km or for connec- Permissible fiber attenuation: 8 dB Electrical tests
tion to a comm. converter, 820 nm
Specification
FO61), OMA22): Fiber-optic interface For multi-mode fiber 62.5/125 μm,
Standards IEC 60255 (product standards)
for direct connection up to 3.5 km, ST connectors
ANSI/IEEE C37.90.0/.1/.2
820 nm Permissible fiber attenuation: 16 dB
UL 508
New fiber-optic interfaces, series FO1 For further standards see
FO171): for direct connection up to For mono-mode fiber 9/125 μm, “Individual functions”
24 km3), 1300 nm LC-Duplex connector Insulation tests
Permissible fiber attenuation: 13 dB
Standards IEC 60255-5
FO181): for direct connection up to For mono-mode fiber 9/125 μm,
60 km3), 1300 nm LC-Duplex connector
Voltage test (100 % test) 7
All circuits except for auxiliary 2.5 kV (r.m.s.), 50 / 60 Hz
Permissible fiber attenuation: 29 dB
supply, binary inputs and
FO191): for direct connection up to For mono-mode fiber 9/125 μm, communication interfaces
100 km3), 1550 nm LC-Duplex connector
Auxiliary voltage and binary 3.5 kV DC
Permissible fiber attenuation: 29 dB
inputs (100 % test)
Relay communication equipment
RS485/RS232 rear side communi- 500 V (r.m.s.), 50 / 60 Hz
External communication converter 7XV5662-0AA00 cation interfaces and time
for communication networks X21/G703-64 kbit/s synchronization interface
External communication converter (100 % test)
to interface between the relays, opti- Impulse voltage test (type test)
cal 820 nm interface and the All circuits except for communi- 5 kV (peak); 1.2/50 μs; 0.5 J
X21/RS422/G703-64 kbit/s interface cation interfaces and time syn- 3 positive and 3 negative impulses at
of a communication device chronization interface, class III intervals of 5 s
X21/G703, RS422 selectable by EMC tests for noise immunity; type tests
jumpers. Baud rate selectable by
jumpers Standards IEC 60255-6, IEC 60255-22
(product standards) (type tests)
Input: fiber-optic 820 nm Max. 1.5 km with 62.5/125 µm EN 50082-2 (generic standard)
with clock recovery multi-mode FO cable to device side DIN 57435 part 303
Output: X21 (RS422) electrical 64/128/512 kbit (selectable by jumper) High frequency test 2.5 kV (peak); 1 MHz; τ = 15 ms;
interface on communication device max. 800 m, 15-pin connector IEC 60255-22-1, class III and 400 surges per s;
G703-64 kbit/s electrical interface on 64 kbit/s, max. 800 m, screw-type VDE 0435 part 303, class III test duration 2 s
communication device terminal Electrostatic discharge 8 kV contact discharge; 15 kV air dis-
External communication converter 7XV5662-0AD00 IEC 60255-22-2, class IV charge; both polarities; 150 pF;
for communication networks with G703-E1 or G703-T1 EN 61000-4-2, class IV Ri = 330 Ω
External communication converter Irradiation with RF field, 10 V/m; 27 to 500 MHz
to interface between the relays, non-modulated
optical 820 nm interfac and G703-E1 IEC 60255-22-3 (report), class III
or G703-T1 interface of a communi- Irradiation with RF field, 10 V/m; 80 to 1000 MHz;
cation network amplitude-modulated 80 % AM; 1 kHz
Inputs: 2 fiber-optic inputs 820 nm, Max. 1.5 km with 62.5/125µm IEC 61000-4-3, class III
1 RS232 input multi-mode 1 FO cable to device side
Output:
G703.5 E1: 2,048 kbit/s
G703.6 T1: 1,554 kbit/s
Electrical interface on communica- max. 800 m, screw-type terminal 1) For flush-mounting housing.
tion network 2) For surface mounting housing.
3) For surface mounting housing the internal FO module OMA1
will be delivered together with an external repeater.
Technical data
Irradiation with RF field, 10 V/m; 900 MHz; repetition Mechanical dynamic tests
pulse-modulated IEC 61000-4-3/ frequency 200 Hz; duty cycle 50 % Vibration, shock stress and seismic vibration
ENV 50204, class III
During operation
Fast transients, bursts 4 kV; 5/50 ns; 5 kHz;
IEC 60255-22-4 and burst length = 15 ms; Standards IEC 60255-21 and IEC 60068-2
IEC 61000-4-4, class IV repetition rate 300 ms; Vibration Sinusoidal
both polarities; Ri = 50 Ω; IEC 60255-21-1, class 2 10 to 60 Hz: ± 0.075 mm amplitude;
test duration 1 min IEC 60068-2-6 60 to 150 Hz: 1 g acceleration
High-energy surge voltages Impulse: 1.2/50 μs frequency sweep 1 octave/min
(SURGE), 20 cycles in 3 orthogonal axes
IEC 61000-4-5 installation, class III Shock Half-sinusoidal
Auxiliary supply Common (longitudinal) mode: 2 kV; IEC 60255-21-2, class 1 Acceleration 5 g, duration 11 ms,
12 Ω; 9 μF IEC 60068-2-27 3 shocks on each of the 3 axes in both
Differential (transversal) mode: 1 kV; directions
2 Ω; 18 μF Seismic vibration Sinusoidal
Measurement inputs, binary inputs, Common (longitudinal) mode: 2 kV; IEC 60255-21-2, class 1 1 to 8 Hz: ± 3.5 mm amplitude
binary output relays 42 Ω; 0.5 μF IEC 60068-3-3 (horizontal axis),
Differential (transversal) mode: 1 kV; 1 to 8 Hz: ± 1.5 mm amplitude
42 Ω; 0.5 μF (vertical axis),
8 to 35 Hz: 1 g acceleration
Line-conducted HF, amplitude- 10 V; 150 kHz to 80 MHz; 80 % AM; (horizontal axis),
modulated 1 kHz 8 to 35 Hz: 0.5 g acceleration
IEC 61000-4-6, class III (vertical axis),
Magnetic field with power 30 A/m continuous; 300 A/m for 3 s; frequency sweep 1 octave/min
frequency 50 Hz 0.5 mT; 50 Hz 1 cycle in 3 orthogonal axes
IEC 61000-4-8, class IV; During transport
IEC 60255-6
7 Standards IEC 60255-21 and IEC 60068-2
Oscillatory surge withstand 2.5 to 3 kV (peak); 1 to 1.5 MHz
capability damped wave; 50 surges per second, Vibration Sinusoidal
ANSI/IEEE C37.90.1 duration 2 s, Ri = 150 to 200 Ω IEC 60255-21-1, class 2 5 to 8 Hz: ±7.5 mm amplitude;
IEC 60068-2-6 8 to 150 Hz: 2 g acceleration,
Fast transient surge withstand 4 to 5 kV; 10/150 ns; 50 impulses per Frequency sweep 1 octave/min
capability second; 20 cycles in 3 orthogonal axes
ANSI/IEEE C37.90.1 both polarities; duration 2 s;
Ri = 80 Ω Shock Half-sinusoidal
IEC 60255-21-2, class 1 Acceleration 15 g, duration 11 ms,
Radiated electromagnetic interfer- 35 V/m; 25 to 1000 MHz IEC 60068-2-27 3 shocks on each of the 3 axes in both
ence directions
ANSI/IEEE C37.90.2
Continuous shock Half-sinusoidal
Damped oscillation 2.5 kV (peak value); polarity alternat- IEC 60255-21-2, class 1 Acceleration 10 g, duration 16 ms,
IEC 60694, IEC 61000-4-12 ing 100 kHz; 1 MHz; 10 and 50 MHz; IEC 60068-2-29 1000 shocks on each of the 3 axes
Ri = 200 Ω in both directions
EMC tests for interference emission; type tests
Standard EN 50081-1 (generic standard) Climatic stress test
Conducted interference voltage on 150 kHz to 30 MHz Temperatures
lines, Limit class B
only auxiliary voltage Type-tested acc. to IEC 60068-2-1 –25 °C to +85 °C / –13 °F to +185 °F
IEC-CISPR 22 and -2, test Bd, for 16 h
Radio interference field strength 30 to 1000 MHz Temporarily permissible operating –20 °C to +70 °C / –4 °F to +158 °F
IEC-CISPR 22 Limit class B temperature, tested for 96 h
Recommended permanent operating –5 °C to +55 °C / +25 °F to +131 °F
temperature acc. to IEC 60255-6
(Legibility of display may be im-
paired above +55 °C / +131 °C)
– Limiting temperature during –25 °C to +55 °C / –13 °F to +131 °F
permanent storage
– Limiting temperature during –25 °C to +70 °C / –13 °F to +158 °F
transport
Humidity
Permissible humidity stress; Annual average ≤ 75 % relative hu-
It is recommended to arrange the midity; on 56 days in the year up to
units in such a way that they are 93 % relative humidity; moisture con-
not exposed to direct sunlight or densation during operation is not per-
pronounced temperature changes mitted
that could cause condensation.
Technical data
Technical data
Pickup values VPH-PH>>, VPH-PH> 2 to 220 V (step 0.1 V) At 1.5 · setting value IREF >, approx. 35 30
(phase-phase overvoltage) or deactivated At 2.5 · setting value IREF >, approx. 33 29
Pickup values 3V0>>, 3V0> 1 to 220 V (step 0.1 V) Dropout time (in ms), approx. 26 23
(3V0 can be measured via V4 trans- or deactivated
formers or calculated by the relay) Dropout ratio, approx. 0.7
(zero-sequence overvoltage) Overcurrent-time protection for phase and residual currents
Pickup values V1>>, V1> 2 to 220 V (step 0.1 V) Multiple availability 3 times (option)
7 (positive-sequence overvoltage) or deactivated Characteristics
Measured voltage Local positive-sequence Definite-time stages (DT) IPh >>, 3I0 >>, IPh >, 3I0 >
voltage or calculated Inverse-time stages (IT) IP, 3I0P
remote positive-sequence Acc. to IEC Inverse, very inverse, extremely
voltage (compounding) inverse, long-time inverse
Pickup values V2>>, V2> 2 to 220 V (step 0.1 V) Acc. to ANSI Inverse, moderately inverse, very
(negative-sequence overvoltage) or deactivated inverse, extremely inverse, definite
Reset ratio (settable) 0.5 to 0.98 (step 0.01) inverse, short inverse, long inverse
Undervoltage protection Alternatively, user-specified
trip and reset characteristics
Pickup values VPH-Gnd<<, VPH-Gnd< 1 to 100 V (step 0.1 V)
Reset characteristics (IT) Acc. to ANSI with disk emulation
(phase-ground (earth) undervoltage) or deactivated
Current stages
Pickup values VPH-PH<<, VPH-PH< 1 to 175 V (step 0.1 V)
(phase-phase undervoltage) High-current stages IPh >> 0.10 to 35.00 A 1) (steps 0.01 A)
or deactivated
or deactivated (stage ineffective)
Pickup values V1<<, V1< 1 to 100 V (step 0.1 V) TIPh >> 0.00 to 60.00 s (steps 0.01 s)
(positive-sequence undervoltage) or deactivated or deactivated (no trip)
Blocking of undervoltage protection Minimum current; binary input 3I0 >> 0.05 to 35.00 A 1) (steps 0.01 A)
stages or deactivated (stage ineffective)
Reset ratio 1.05 T3I0 >> 0.00 to 60.00 s (steps 0.01 s)
or deactivated (no trip)
Time delays
Definite-time stages IPh > 0.10 to 35.00 A 1) (steps 0.01 A)
Time delay for all over- and 0 to 100 s (steps 0.01 s) or deactivated or deactivated (stage ineffective)
undervoltage stages
TIPh 0.00 to 60.00 s (steps 0.01 s)
Command / pickup time Approx. 40 ms or deactivated (no trip)
Tolerances 3I0 > 0.05 to 35.00 A 1) (steps 0.01 A)
Voltage limit values ≤ 3 % of setting value or 0.5 V or deactivated (stage ineffective)
Time stages 1 % of setting value or 10 ms T3I0 > 0.00 to 60.00 s (steps 0.01 s)
Frequency protection (ANSI 81) or deactivated (no trip)
Number of frequency elements 4
Setting range 45.5 to 54.5 Hz
(in steps of 0.01) at fnom = 50 Hz
55.5 to 64.5 Hz
(in steps of 0.01) at fnom = 60 Hz
Delay times 0 to 600 s or ∞ (in steps of 0.01 s)
Operating voltage range 6 to 230 V (phase-to-ground (earth))
Pickup times Approx. 85 ms
Technical data
Tolerances
10 to 50 % IN Typical ≤ 1 % of 50 % IN CE conformity
50 to 200 % IN Typical ≤ 1 % of measured value This product is in conformity with the Directives of the European Commu-
Voltages 3 x VPhase-Earth; 3 x VPhase-Phase; nities on the harmonization of the laws of the Member States relating to
3V0, V1, V2, Ven electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
Tolerances electrical equipment designed for use within certain voltage limits (Council
10 to 50 % VN Typical ≤ 1 % of 50 % VN Directive 73/23/EEC).
50 to 200 % VN Typical ≤ 1 % of measured value This unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Power with direction indication P, Q, S
Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
Tolerances
P: for |cos ϕ| = 0.7 to 1 and V/VN, Typical ≤ 3 % The unit has been developed and manufactured for application in an indus-
I/IN = 50 to 120 % trial environment according to the EMC standards.
Q: for |sin ϕ| = 0.7 to 1 and V/VN, Typical ≤ 3 % This conformity is the result of a test that was performed by Siemens AG in
I/IN = 50 to 120 % accordance with Article 10 of the Council Directive complying with the
S: for V/VN , I/IN = 50 to 120 % Typical ≤ 2 % generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
Frequency f standard EN 60255-6 for the “low-voltage Directive”.
Tolerance ≤ 20 mHz
Power factor p.f. (cos ϕ)
Tolerance for ⏐cos ϕ⏐ = 0.7 to 1 Typical ≤ 3 %
Remote measurements 3 x IPhase-Earth; 3 I0, 3 x VPhase-Earth; 3V0
Overload measured values Θ/Θ Trip L1; Θ/Θ Trip L2; Θ/Θ Trip L3;
Θ/Θ Trip
1) Rated current can be selected by means of 4) For surface-mounting housing applications, 6) For distances less than 25 km, two optical
jumpers. please select option A (820 nm, 1.5 km) attenuators 7XV5107-0AA00 are required
2) Transition between the two auxiliary voltage together with an external repeater to avoid optical saturation of the receiver
ranges can be selected by means of jumpers. (see "Accessories" for Order No.). element.
3) The binary input thresholds can be selected 5) Not possible for surface-mounting housing 7) For distances less than 50 km, two optical
in three stages by means of jumpers. (position 9 = F). attenuators 7XV5107-0AA00 are required
to avoid optical saturation of the receiver
element.
Additional functions 1
n
tio
n
tec
io
n h
i o it
1 ) eq 9) e c t
ro
pt n w
I 8 rfr 7, 5 rot
yp
)
7N
O v 8 7 T ad a n s i o
N S ult
N S de I 2 p
ds
nc
I8
( A /un NS g e
( A fa
an
ue
I u p te
er (A olta
n h-
m
N S r o ex
t i o art
om
Ov < r v
( A r g er
ec e
, V de
cto rm
ec
o t ed
V> r / u n
ot
v e sfo
p r ict
em
str
an
e
4r
Re
Tr
A
n B 7
n E
n n F
n J
n n K
n n N
n n n P
n n n S
n n n n T
Additional functions 2
Without additional functions 0
With external GPS synchronization of the differential protection 1
Further modules
Protection data interface mod. opt. 1300 nm, mono-mode FO cable,
7 LC-Duplex connector, 24 km C53207-A351-D655-1
Protection data interface mod. opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 60 km C53207-A351-D656-1
Protection data interface mod. opt. 1550 nm, mono-mode FO cable,
LC-Duplex connector, 100 km C53207-A351-D657-1
Optical repeaters
Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 24 km 7XV5461-0BG00
Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 60 km 7XV5461-0BH00
Serial repeater (2-channel), opt. 1550 nm, mono-mode FO cable,
LC-Duplex connector, 100 km 7XV5461-0BJ00
DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (Windows 2000/XP Professional)
device templates, Comtrade Viewer, electronic manual included
as well as “Getting started” manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Professional
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
SIGRA 4
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format). Running under MS Windows (Windows 2000/XP Professional).
Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM. 7XS5410-0AA00
Connecting cable
Cable between PC/notebook (9-pin connector)
and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4 7
Manual for 7SD61 V4.6
English C53000-G1176-C145-4
LSP2089-afpen.tif
LSP2091-afpen.eps
LSP2092-afpen.eps
Connection diagram
7
Fig. 7/39
Connection diagram
Fig. 7/40
Serial interfaces
SIPROTEC 4 7SD52/53
Multi-End Differential and Distance Protection in One Relay
Function overview
Protection functions
• Differential protection with phase-
segregated measurement (87L, 87T)
• Restricted earth-fault protection (87N) if a
transformer is within the protection zone
• Sensitive meas. stage f. high-resist. faults
• Non-switched distance protection with
LSP2173f.eps
LSP2314-afp.eps
tripping (50N/51N/67N)
• Phase-selective intertripping (85)
• Tele (pilot) protection (85/21, 85/67N)
• Weak-infeed protection (27WI)
Fig. 7/41 • Fault locator (FL)
SIPROTEC 4
7SD52/53 differential protection relay
• Power swing detection/tripping (68/68T)
• 3-stage overcurrent protection
(50, 50N, 51, 51N)
• STUB bus protection (50 STUB)
The units measure the delay time in the • Switch-onto-fault protection (50HS)
Description
communication networks and adaptively • Over/undervoltage protection (59/27) 7
The 7SD52/53 relay provides full scheme match their measurements accordingly. • Over/underfrequency protection (81O/U)
differential protection and incorporates all A special GPS-option allows the use of the
• Auto-reclosure (79), Synchro-check (25)
functions usually required for the protec- relays in communication networks, where • Breaker failure protection (50BF)
tion of power lines. It is designed for all the delay time in the transmit and receive • Overload protection (49)
power and distribution levels and protects path may be quite different. • Lockout function (86)
lines with two up to six line ends. The relay
is designed to provide high-speed and The 7SD52/53 has the following features: Control functions
phase-selective fault clearance. The relay − 2 full-scheme main protections in one • Commands f. ctrl of CB and isolators
uses fiber-optic cables or digital communi- unit (differential and distance protec- Monitoring functions
cation networks to exchange telegrams and
includes special features for the use in mul-
tion) • Self-supervision of relay and protection
− High-speed tripping 10 - 15 ms data (R2R) communication
tiplexed communication networks. Also
pilot wires connections can be used with − The serial protection data interfaces • Trip circuit supervision (74TC)
an external converter. This contributes to- (R2R interfaces) of the relays can flexibly • Measured-value supervision
ward improved reliability and availability be adapted to the requirements of all • Oscillographic fault recording
communication media available.
of the electrical power system. • Event logging/fault logging
− If the communication method is • Switching statistics
The relay is suitable for single and changed, flexible retrofitting of commu-
three-phase tripping applications for two nication modules to the existing configu- Front design
up to six line ends. Also, transformers and ration is possible. • User-friendly local operation
compensation coils within the differential − Tolerates loss of one data connection in a • PC front port for relay setting
protection zone are protected as are serial ring topology (routing in 120 ms). The • Function keys and 14 LEDs f. local alarm
and parallel-compensated lines and cables. differential protection scheme is fully
The relays may be employed with any type available in a chain topology. Communication interfaces
of system earthing.
− Browser-based commissioning tool. • 2 serial protection data (R2R) interfaces
The relay also provides a full-scheme and for ring and chain topology
non-switched distance protection as an op- − Fault locator for one and two terminal
measurement for high accuracy on long • Front interface for connecting a PC
tional main 2 protection. Several telepro-
lines with high load and high fault resis- • System interface for connection to a
tection schemes ensure maximum selectiv-
tance. control system via various protocols
ity and high-speed tripping time.
− Capacitive charge current compensation – IEC 61850 Ethernet
increases the sensitivity of the differential – IEC 60870-5-103
protection on cables and long lines. – PROFIBUS-FMS/-DP and DNP 3.0
• Rear-side service/modem interface
• Time synchronization via IRIG-B or
DCF77 or system interface
Application
ANSI ANSI
87L Δ I for lines / cables 50HS Instantaneous high-current
tripping (switch-onto-fault)
87T Δ I for lines / cables 59 27 Overvoltage/undervoltage
with transformers protection
87N Low impedance restricted 81O/U Over/underfrequency protec-
earth-fault protection for tion
transformers
85 Phase-selective 25 Synchro-check
intertrip, remote trip
86 Lockout function 79 Single or three-pole
auto-reclosure with new
adaptive technology
21 21N Distance protection 49 Overload protection
FL Fault locator 50BF Breaker failure protection
68 68T Power swing detec- 74TC Trip circuit supervision
tion/tripping
85/21 Teleprotection for distance 50-STUB STUB bus protection
protection
27WI Weak-infeed protection
Directional earth(ground)-
7 50N 51N
fault protection
67N
85/67N Teleprotection for earth
(ground)-fault protection
*) Option
Fig. 7/42
Application The link to the other relays is made by The 7SD52/53 offers many features to
multi-mode or mono-mode FO cables. reliably and safely handle data exchange
Typical applications There are 5 options available, which corre- via communication networks.
spondingly cover:
SIPROTEC 7SD52/53 is a full-scheme dif- Depending on the bandwidth available in
ferential protection relay for two up to six • 820 nm, up to 1.5 km, multi-mode the communication system, 64, 128 or
line ends, incorporating all the additional • 820 nm, up to 3.5 km, multi-mode 512 kbits/s can be selected for the X21
functions for protection of overhead lines • 1300 nm, up to 24 km, mono-mode (RS422) interface; the G703 interface with
and cables at all voltage levels. Also trans- • 1300 nm, up to 60 km, mono-mode 64 kbit/s, and G703-E1 (2,048 kbit/s) or
G703-T1 (1,554 kbit/s).
formers and compensation coils within • 1550 nm, up to 100 km, mono-mode
the protection zone are protected. The The connection to the communication
7SD52/53 is suitable for single-pole and Direct fiber-optic connection offers high-
device is effected via cost-effective 820 nm
three-pole tripping. The power system star speed data exchange with 512 kbit/s and
interface with multi-mode FO cables.
point can be solid or impedance-grounded improves the speed for remote signaling.
A communication converter converts the
(earthed), resonant-earthed via Peterson At the main line two differential relays are optical to electrical signals. This offers an
coil or isolated. On the TAP-line, the connected to CTs. The communication is interference-free and isolated connection
7SD52/53 differential relay is connected to made via a multiplexed communication between the relay and the communication
current (CT) and optionally voltage (VT) network. device.
transformers. For the differential func-
tions, only CTs are necessary. By con-
necting the relay to VTs, the integrated
"main 2" distance protection can be ap-
plied (full-scheme, nonswitched). There-
fore, no separate distance protection relay
is required.
Cost-effective power system management The SIPROTEC 4 units have a uniform The use of powerful microcontrollers and
design and a degree of functionality which the application of digital measured-value
The SIPROTEC 4 units are numerical re-
represents a benchmark-level of perfor- conditioning and processing largely sup-
lays which also provide control and moni-
mance in protection and control. If the presses the influence of higher-frequency
toring functions and therefore support the
requirements for protection, control or transients, harmonics and DC compo-
user in view of a cost-effective power sys-
interlocking change, it is possible in the nents.
tem management. The security and reli-
majority of cases to implement such
ability of power supply is increased as a
changes by means of parameterization
result of minimizing the use of hardware.
using DIGSI 4 without having to change
The local operation has been designed ac- the hardware.
cording to ergonomic criteria. Large, easy-
to-read backlit displays are provided.
Construction
LSP2174-afp.tif
LSP2166-afp.tif
is a uniform 245 mm for flush-mounting
housings and 266 mm for surface-mount-
ing housings for all housing widths. All ca-
bles can be connected with or without ring
lugs. Plug-in terminals are available as an
option. It is thus possible to employ pre-
fabricated cable harnesses. In the case of Fig. 7/44 Fig. 7/45
surface mounting on a panel, the connec- Flush-mounting housing Rear view of flush-mounting housing with
tion terminals are located above and below with screw-type terminals covered connection terminals and wirings
in the form of screw-type terminals. The
communication interfaces are located in a
sloped case at the top and bottom of the
housing.
LSP2237-afp.tif
LSP2219-afp.eps
Fig. 7/47
Communication interfaces
in a sloped case in a surface-
mounting housing
Fig. 7/46
Surface-mounting housing with screw-type
terminals
Protection functions
• Differential and restraint currents are
monitored continuously during normal
Differential protection (ANSI 87L, 87T, 87N) operation and are displayed as opera-
tional measurements.
The differential protection function has the • High stability during external faults even
following features: with different current transformers satu-
• It is possible to select the operating mode ration level. For an external fault, only
as "main" or as "main 1", if the back-up 5 ms saturation-free time are necessary
distance protection is activated as to guarantee the stability of the differen-
"main 2". tial configuration.
• Measurements are performed separately • With transformers or compensation coils
for each phase; thus the trip sensitivity is in the protection zone, the sensitive trip
independent of the fault type. stage can be blocked by an inrush detec-
tion function. It works with the second
• An adaptive, sensitive measurement
harmonic of the measured current which
method with high sensitivity for differen-
is compared with the fundamental com-
tial fault currents below the rated current
ponent.
offers the detection of highly resistive
faults. This trip element uses special fil- • With transformers in the protection Fig. 7/48 Tripping characteristic
ters, which offers high security even with zone, vector group adaptation and
high level DC-components in the short- matching of different CT ratios are • Data communication is immune to
circuit current. The trip time of this stage carried out in the relay. Additionally, the electromagnetic interference because
is about 30 ms. zero-sequence current flowing through fiber-optic cables are employed in the
an earthed neutral is eliminated from the critical region
• A high-set differential trip stage which
clears differential fault currents higher
differential measurement. The 7SD52/53 • Supervision of each individual incoming
therefore works like a transformer differ- telegram and of the entire communica-
than the rated current within 10 – 15 ms
ential relay, whereas the line ends may be tion path between the units without
offers fast tripping time and high-speed
fault clearence time.
far away. additional equipment. 7
• A more sensitive protection for trans- •
• When a long line or cable is switched on, Unambiguous identification of each unit
formers within the protection zone is is ensured by assignment of a settable
transient charge currents load the line.
given by measurement of the star-point communication address within a differ-
To avoid a higher setting of the sensitive
current on an earthed winding. There- ential protection topology. Only those
differential trip stage, this setpoint may
fore the IE current measuring input has units mutually known to each other can
be increased for a settable time. This of-
to be used. cooperate. Incorrect interconnection of
fers greater sensitivity under normal load
If the sum of the phase currents of wind- the communication links results in
conditions.
ing is compared with the measured blocking of the protection system.
• With the setting of the CT-errors the star-point current, a sensitive earth-cur-
relay automatically calculates the re- • Detection of reflected telegrams in the
rent differential protection (REF) can be communication system.
straint/stabilization current and adapts implemented.
its permissible sensitivity according to • Detection of delay time changes in
This function is substantially more sensi-
the CT’s data in the differential configu- communication networks.
tive than the differential protection dur-
ration, optimizing sensitivity. ing faults to earth in a winding, detecting • Measurement of the delay time to the
• Different CT ratios at the line ends are fault currents as small as 10 % of the remote line ends with dynamic compen-
handled inside the relay. The mismatch transformer rated current. sation of the delay in the differential
of 1 to 6 is allowed. measurement. Supervision of the maxi-
• The differential protection trip can be Enhanced communication features for mum permissible delay time is included.
guarded with an overcurrent pickup. communication networks • Generation of alarms on heavily dis-
Thus differential current and overcur- turbed communication links. Faulty
rent lead to a final trip decision. The data required for the differential telegram counters are available as
• Easy to set tripping characteristic. calculations are cyclically exchanged in operational measurement.
Because the relay works adaptively, only full-duplex mode in form of synchronous, • With a GPS high-precision 1-s pulse from
the setpoint IDiff > (sensitive stage) and serial telegrams between the protection a GPS receiver the relays can be synchro-
IDiff >> (high-set current differential units. The telegrams are secured with CRC nized with an absolute, exact time at each
stage) must be set according to the check sums, so that transmission errors in line end. In this way, the delay in the re-
charge current of the line/cable. a communication network are immediately ceive and transmit path can be measured
detected.
• With an optional capacitive charge cur- exactly. With this optional feature the relay
rent compensation, the sensitivity can be can be used in communication networks
increased to 40 % of the normal setting where this delay times are quite different.
of IDIFF>. This function is recommended
for long cables and long lines.
Protection functions
Protection functions
Protection functions
Protection functions
Commissioning
LSP2845.tif
Special attention has been paid to commis-
sioning. All binary inputs and outputs can
be displayed and activated directly. This
Fig. 7/55
can simplify the wiring check significantly Browser-aided commissioning: Phasor diagram
7 for the user. The operational and fault
events and the fault records are clearly ar-
ranged.
Furthermore, all currents and optional
voltages and phases are available via com-
munication link at the local relay and are
displayed in the relay, with DIGSI 4 or with
the Web Monitor.
The operational and fault events and fault
records from all line ends share a common
time tagging which allows to compare
events registered in the different line
ends on a common time base.
Communication
LSP2163-afpen.tif
IEC 61850 Ethernet
Since 2004, the Ethernet-based
IEC 61850 protocol is the world-
wide standard for protection and
control systems used by power
LSP2164-afpen.tif
supply corporations. Siemens was
the first manufacturer to support
this standard. By means of this
protocol, information can also be
exchanged directly between bay
units so as to set up simple master- Fig. 7/59 Fig. 7/60
less systems for bay and system in- R232/RS485 electrical communication module Communication module, optical double-ring
terlocking. Access to the units via
the Ethernet bus is also possible
with DIGSI.
LSP2162-afpen.tif
IEC 60870-5-103
IEC 60870-5-103 is an internation-
ally standardized protocol for the
efficient communication in the
protected area. IEC 60870-5-103 is
supported by a number of protec-
tion device manufacturers and is
used worldwide. 7
LSP2810.tif
PROFIBUS-DP
Fig. 7/61 Fig. 7/62
PROFIBUS-DP is an industry-
Fiber-optic communication module Fiber-optic Ethernet communication module for
recognized standard for communi- IEC 61850 with integrated Ethernet switch
cations and is supported by a num-
ber of PLC and protection device
manufacturers.
DNP 3.0
DNP 3.0 (Distributed Network
Protocol Version 3) is a messaging-
based communication protocol.
The SIPROTEC 4 units are fully
Level 1 and Level 2 compliant with
DNP 3.0. DNP 3.0 is supported by
a number of protection device
manufacturers.
Fig. 7/63
System solution: Communications
Communication
Fig. 7/68
Connection to a pilot wire
Typical connection
Fig. 7/69
Example of connection for current and voltage transformers
Fig. 7/70
Alternative connection of current transformers for sensitive
ground(earth)-current measuring with core-balance current transformers
Typical connection
Typical connection
Technical data
Technical data
System interface, continued External communication converter 7XV5662-0AC00 for pilot wires
PROFIBUS RS485 External communication converter
Dielectric test 500 V/50 Hz to interface between relays, optical
Baud rate Max. 12 Mbaud 820 nm interface and a pilot wire or
Distance 1 km at 93.75 kB; 100 m at 12 MB twisted telephone pair.
PROFIBUS fiber-optic2) Typical distance 15 km
Only for flush-mounting housing ST connector Fiber-optic 820 nm with clock Max. 1.5 km with 62.5/125 µm
For surface-mounting housing Optical interface with OLM2) recovery multi-mode FO cable
Baud rate Max. 1.5 Mbaud
Optical wavelength λ = 820 nm Pilot wire Screw-type terminal 5 kV isolated
Permissible attenuation Max. 8 dB for glass-fiber 62.5/125 μm Permissible time delay (duration of data transmission)
Distance 500 kB/s 1.6 km, 1500 kB/s 530 m
Delay of telegrams due to trans- Max. 30 ms per transmission path
Protection data interface (R2R interface) mission for one unit to the other. Permissible max. value can be
FO51), OMA12): Fiber-optic interface For multi-mode fiber 62.5/125 μm, Delay is constantly measured and selected
with clock recovery for direct connec- ST connectors adjusted
tion up to 1.5 km or for connection to Permissible fiber attenuation 8 dB
a communication converter, 820 nm
Electrical tests
FO61), OMA22): Fiber-optic interface For multi-mode fiber 62.5/125 μm,
Specifications
for direct connection up to 3.5 km, ST connectors
820 nm Permissible fiber attenuation 16 dB Standards IEC 60255 (product standards)
ANSI/IEEE C37.90.0/.1/.2
New fiber-optic interfaces, series FO1x
UL 508
FO171): for direct connection up to For mono-mode fiber 9/125 μm, For further standards see
24 km3), 1300 nm LC-Duplex connector “Individual functions”
Permissible fiber attenuation 13 dB
Insulation tests
FO181): for direct connection up to For mono-mode fiber 9/125 μm,
7 60 km3), 1300 nm LC-Duplex connector
Standards IEC 60255-5
Permissible fiber attenuation 29 dB Voltage test (100 % test)
All circuits except for auxiliary 2.5 kV (r.m.s.), 50/60 Hz
FO191): for direct connection up to For mono-mode fiber 9/125 μm,
supply, binary inputs and
100 km3), 1550 nm LC-Duplex connector
communication interfaces
Permissible fiber attenuation 29 dB
Auxiliary voltage and binary 3.5 kV DC
Relay communication equipment
inputs (100 % test)
External communication converter 7XV5662-0AA00
RS485/RS232 rear side communi- 500 V (r.m.s.), 50/60 Hz
for communication networks X21/G703-64 kbit/s
cation interfaces and time
External communication converter to synchronization interface
interface between the relays, optical (100 % test)
820 nm interface and the X21(RS422)
G703-64 kbit/s interface of a commu- Impulse voltage test (type test)
nication device All circuits except for communi- 5 kV (peak); 1.2/50 μs; 0.5 J
cation interfaces and time syn- 3 positive and 3 negative impulses at
X21/G703, RS422 selectable by jump- chronization interface, class III intervals of 5 s
ers. Baud rate selectable by jumpers
EMC tests for noise immunity; type tests
Input: fiber-optic 820 nm Max. 1.5 km with 62.5/125 µm
with clock recovery multi-mode FO cable to device side Standards IEC 60255-6, IEC 60255-22
(product standards) (type tests)
Output: X21 (RS422) electrical 64/128/512 kbit (selectable by jumper) EN 50082-2 (generic standard)
interface on communication device max. 800 m, 15-pin connector DIN 57435 part 303
G703-64 kbit/s electrical interface on 64 kbit/s, max. 800 m, screw-type High frequency test 2.5 kV (peak); 1 MHz; τ = 15 ms;
communication device terminal IEC 60255-22-1, class III and 400 surges per s;
External communication converter 7XV5662-0AD00 VDE 0435 part 303, class III test duration 2 s
for communication networks with G703-E1 or G703-T1 Electrostatic discharge 8 kV contact discharge; 15 kV air
External communication converter to IEC 60255-22-2, class IV discharge; both polarities; 150 pF;
interface between the relays, optical EN 61000-4-2, class IV Ri = 330 Ω
820 nm interface and G703-E1 or Irradiation with RF field, 10 V/m; 27 to 500 MHz
G703-T1 interface of a communica- non-modulated
tion network. IEC 60255-22-3 (report), class III
Inputs: 2 fiber-optic inputs 820 nm, Max. 1.5 km with 62.5/125µm Irradiation with RF field, 10 V/m; 80 to 1000 MHz;
1RS232 input multi-mode 1 FO cable to device side amplitude-modulated 80 % AM; 1 kHz
Output: IEC 61000-4-3, class III
G703.5 E1: 2,048 kbit/s
G703.6 T1: 1,554 kbit/s
Electrical interface on communica- max. 800 m, screw-type terminal
tion network 1) For flush-mounting housing.
2) For surface-mounting housing.
3) For surface-mounting housing the internal FO module OMA1
will be delivered together with an external repeater.
Technical data
Vibration, shock stress and seismic vibration Differential protection (ANSI 87L, 87T)
Technical data
Vector group adaptation with transformers in the differential zone Ground(earth)-fault pickup
Adaptation of connection symbol 0 to 11 (x 30 °) (step 1) Neutral (residual) current 3I0 0.05 to 4 A (1A)/ 0.25 to 20 A (5A)
(Ground current) (step 0.01 A)
Neutral point connection Grounded (earthed) or not grounded
(earthed) (for each winding) Zero-sequence voltage 3V0>
for earthed networks 1 to 100 V (step 1 V) or deactivated
Inrush restraint for resonant-earthed networks 10 to 200 V (step 1 V)
Restraint ratio Zero-sequence compensation
2nd harmonic I2fN/IfN 10 % to 45 % (step 1 %) Selectable input formats RE/RL and XE/XL
Max. current for restraint 1.1 A to 25 A1) (step 0.1 A) k0 and ϕ(k0)
Crossblock function Can be switched on and off Separately selectable for zones Z1
higher zones (Z1B, Z2 to Z5)
Max. operative time for crossblock 0 to 60 s (step 0.01 s) or
Toper crossblk deactivated (operating up to release) RE/RL and XE/XL -0.33 to 7 (step 0.01)
Distance protection (ANSI 21, 21N) k0 0 to 4 (step 0.001)
ϕ(k0) -135 to 135 ° (step 0.01 °)
Distance protection zones 6, 1 of which as controlled zone, all
zones can be set forward or/and Parallel line mutual compensation (refer to ordering code)
reverse RM/RL and XM/XL 0.00 to 8 (step 0.01)
Time stages for tripping delay 6 for multi-phase faults Phase reference on double Phase preference or no preference
3 for single-phase faults earth-faults in resonant-earthed/ (selectable)
Setting range 0 to 30 s or deactivated (steps 0.01 s) non-earthed network
Characteristic (refer to ordering code) Load encroachment
Selectable separately for phase quadrilateral and/or Minimum load resistance 0.10 to 600 Ω(1A) / 0.02 to 120 Ω(5A)
and ground (earth) faults Mho (only impedance pickup) (step 0.001 Ω) or deactivated
Types of pickup Overcurrent pickup (I>); Maximum load angle 20 to 60 ° (step 1 °)
Voltage-dependent overcurrent Directional decision for all types of With sound phase polarization and/or
7 pickup (V< / I>); faults voltage memory
Voltage-dependent and phase an-
gle-dependent overcurrent pickup Directional sensitivity Dynamically unlimited
(V< / I> / ϕ>); Tolerances For sinusodial quantities
Impedance pickup (Z<) Impedances
ΔX
Types of tripping Three-pole for all types of faults; (in conformity with DIN 57435, ≤ 5 % for 30 ° ≤ ϕ SC ≤ 90 °
Part 303) X
Single-pole for single-phase faults /
otherwise three-pole; ΔR
≤ 5 % for 0 ° ≤ ϕ SC ≤ 60 °
Single-pole for single-phase faults and R
two-pole phase-to-phase faults /
otherwise three-pole ΔZ
≤ 5% for-30°≤ (ϕ SC -ϕline)≤+30°
Time range 0 to 30 s (step 0.01 s) or deactivated Z
Line angle ϕ L 30 ° to 89 ° (step 1 °) Response values (in conformity
with DIN 57435, Part 303)
Inclination angle for quadrilateral 30° to 90° (step 1°)
V and I ≤ 5 % of setting value
characteristic
Angle (ϕ) ≤3°
Quadrilateral reactance reach X 0.05 to 600 Ω(1A) / 0.01 to 120 Ω(5A)
Timer tolerance ± 1 % of set value or 10 ms
(step 0.001 Ω)
Quadrilateral resistance reach R
for phase-to-phase faults and 0.05 to 600 Ω(1A) / 0.01 to 120 Ω(5A)
phase-to-ground(earth) faults (step 0.001Ω) Operating times
Mho impedance reach ZR 0.05 to 200 Ω(1A) / 0.01 to 40 Ω(5A) Minimum trip time Approx. 17 ms at 50 Hz
(step 0.01 Ω) with fast relays Approx. 15 ms at 60 Hz
Minimum trip time Approx. 12 ms at 50 Hz
Minimum phase current I 0.05 to 4 A (1A) / 0.25 to 20 A (5A)
with high-speed relays Approx. 10 ms at 60 Hz
(step 0.01 A)
Reset time Approx. 30 ms
Overcurrent pickup I>> 0.25 to 10 A (1A) / 1.25 to 50 A (5A)
(for I>>, V</I>, V</I>/ϕ>) (step 0.01 A)
Minimum current pickup I> 0.05 to 4 A (1A) / 0.25 to 20 A (5A)
(for V</I>, V</I>/ϕ> and Z<) (step 0.01 A)
Minimum current pickup Iϕ> 0.1 to 8 A (1A) / 0.5 to 40 A (5A)
(for V</I>, V</I>/ϕ>) (step 0.01 A)
Undervoltage pickup (for V</I> and
V</I>/ϕ>)
Vph-e< 20 to 70 V (step 1 V)
Vph-ph< 40 to 130 V (step 1 V)
Load angle pickup (for V</I>/ϕ>)
Load angle ϕ 30 ° to 80 °
Load angle ϕ 90 ° to 120 °
1) Secondary data for IN = 1 A; with IN = 5 A the values must be multiplied.
Technical data
Power swing detection (ANSI 68, 68T) Inverse-time stage (ANSI 51, 51N)
Power swing detection principle Measurement of the rate of imped- Phase current pickup 0.1 to 4 A (1A) /0.5 to 20 A (5A)
ance vector change and monitoring of (step 0.01 A) or deactivated
the vector path Neutral (residual) current pickup 0.05 to 4 A (1A) /0.25 to 20 A (5A)
Max. detectable power swing fre- Approx. 7 Hz (step 0.01 A) or deactivated
quency Characteristics
Operating modes Power swing blocking and/or power Characteristics Normal inverse
swing tripping (out-of-step tripping) according to IEC 60255-3 Very inverse
Power swing blocking programs All zones blocked Extremely inverse
Z1/Z1B blocked Long time inverse
Z2 to Z5 blocked Time multiplier Tp = 0.05 to 3 s (step 0.01 s)
Z1, Z1B, Z2 blocked or deactivated
Detection of faults during power Reset of power swing blocking for all Pickup threshold Approx. 1.1 x I / Ip
swing blocking types of faults
Reset threshold Approx. 1.05 x I / Ip
Tele (pilot) protection for distance protection (ANSI 85-21)
Tolerances
Modes of operation PUTT (Z1B acceleration); DUTT Operating time for 2 ≤I/Ip ≤ 20 ≤ 5 % of setpoint ± 15 ms
PUTT (acceleration with pickup);
POTT; Directional comparison; Characteristics Inverse
Reverse interlocking according to ANSI/IEEE Short inverse
Pilot-wire comparison; Unblocking; Long inverse
Blocking Moderately inverse
Very inverse
Additional functions Echo function Extremely inverse
(refer to weak-infeed function) Definite inverse
Transient blocking for schemes with
measuring range extension Time dial 0.5 to 15 (step 0.01) or deactivated
Transmission and reception signals Phase-selective signals available for Pickup threshold Approx. 1.1 x M 7
maximum selectivity with single-pole Reset threshold Approx. 1.05 x M
tripping; signals for 2 and 3-end-
Tolerances
lines
Operating time for 2 ≤ M ≤ 20 ≤ 5 % of setpoint ± 15 ms
Direct transfer trip (DTT)
Instantaneous high-speed switch-onto-fault overcurrent protection
Direct phase-selective tripping via Alternatively with or without (ANSI 50HS)
binary input auto-reclosure
Operating mode Active only after c.b. closing;
Trip time delay 0 to 30 s (step 0.01 s) or deactivated instantaneous trip after pickup
Timer tolerance ± 1 % of setting value or 10 ms Characteristic 2 definite-time stages
Backup overcurrent protection (ANSI 50N, 51N) Pickup current I >>> 0.1 to 15 A (1A) /0.5 to 75 A (5A)
Operating modes Active only with loss of data (step 0.01 A) or deactivated
connection and voltage or always Pickup current I >>>> 1 to 25 A (1A)/5 to 125 A (5A)
active (step 0.01 A) or deactivated
Characteristics 3 definite-time stages / 1 inverse-time Reset ratio Approx. 0.95
stage
Tolerances < 3 % of set value or 1 % of IN
Definite-time stage (ANSI 50, 50N )
Directional ground (earth)-fault overcurrent protection
Pickup definite time stage 1, 0.1 to 25 A (1A) / 0.5 to 125 A (5A) for high-resistance faults in systems with earthed star point
phase current (step 0.01 A) or deactivated (ANSI 50N, 51N, 67N)
Pickup definite-time stage 1, 0.5 to 25 A (1A) / 0.25 to 125 A (5A) Characteristic 3 definite-time stages / 1 inverse-time
neutral (residual) current (step 0.01 A) or deactivated stage or 4 definite-time stages or
Pickup definite-time stage 2, 0.1 to 25 A (1A) / 0.5 to 125 A (5A) 3 definite-time stages / 1 V0invers. stage
phase current (step 0.01 A) or deactivated Phase selector Permits 1-pole tripping for single-
Pickup definite-time stage 2, 0.05 to 25 A (1A) / 0.25 to 125 A (5A) phase faults or 3-pole tripping for
neutral (residual) current (step 0.01 A) or deactivated multi-phase faults
Pickup definite-time stage 3, 0.1 to 25 A (1A) / 0.5 to 125 A (5A) Inrush restraint Selectable for every stage
phase current (step 0.01 A) or deactivated Instantaneous trip after Selectable for every stage
Pickup definite-time stage 3, 0.05 to 25 A (1A) / 0.25 to 125 A (5A) switch-onto-fault
neutral (residual) current (step 0.01 A) or deactivated Influence of harmonics
Time delay for definite-time stages 0 to 30 s, (step 0.01 s) or deactivated Stages 1 and 2 (I>>> and I>>) 3rd and higher harmonics are com-
pletely suppressed by digital filtering
Tolerances
Current pickup ≤ 3 % of set value or 1 % of IN Stages 3 and 4 2nd and higher harmonics are com-
Delay times ± 1 % of set value or 10 ms (I> and inverse 4th stage) pletely suppressed by digital filtering
Operating time Approx. 25 ms
Technical data
Technical data
Voltage protection (ANSI 59, 27) Breaker failure protection (ANSI 50BF)
Operating modes Local tripping or only indication Number of stages 2
Overvoltage protection Pickup of current element 0.05 to 20 A(1A) / 0.25 to 100 A(5A)
(step 0.01 A)
Pickup values VPH-Gnd>>, VPH-Gnd> 1 to 170 V (step 0.1 V)
(phase-ground (earth) overvoltage) or deactivated Time delays T11phase, T13phase, T2 0 to 30 s (steps 0.01 s) or deactivated
Pickup values VPH-PH>>, VPH-PH> 2 to 220 V (step 0.1 V) Additional functions End-fault protection
(phase-phase overvoltage) or deactivated CB pole discrepancy monitoring
Pickup values 3V0>>, 3V0> Reset time Approx. 15 ms, typical; 25 ms max.
1 to 220 V (step 0.1 V)
(3V0 can be measured via V4 trans- or deactivated Tolerances
formers or calculated by the relay) Current limit value ≤ 5 % of setting value or 1 % Inom
(zero-sequence overvoltage) Time stages 1 % of setting value or 10 ms
Pickup values V1>>, V1> 2 to 220 V (step 0.1 V) Auto-reclosure (ANSI 79)
(positive-sequence overvoltage) or deactivated Number of auto-reclosures Up to 8
Measured voltage Local positive-sequence Operating mode Only 1-pole; only 3-pole, 1 or 3-pole
voltage or calculated
remote positive-sequence Operating modes with line voltage DLC – dead-line check
voltage (compounding) check ADT – adaptive dead time
RDT – reduced dead time
Pickup values V2>>, V2> 2 to 220 V (step 0.1 V)
(negative-sequence overvoltage) or deactivated Dead times T1-ph, T3-ph, TSeq 0 to 1800 s (step 0.01 s) or deactivated
Action times 0.01 to 300 s (step 0.01 s) or deactivated
Reset ratio (settable) 0.5 to 0.98 (step 0.01)
Reclaim times 0.5 to 300 s (step 0.01 s)
Undervoltage protection
Start-signal monitoring time 0.01 to 300 s (step 0.01 s)
Pickup values VPH-Gnd<<, VPH-Gnd< 1 to 100 V (step 0.1 V)
(phase-ground (earth) undervoltage) or deactivated Additional functions Synchro-check request
Pickup values VPH-PH<<, VPH-PH< 1 to 175 V (step 0.1 V)
3-phase intertripping
InterCLOSE command
7
(phase-phase undervoltage) or deactivated to the remote end
Pickup values V1<<, V1< 1 to 100 V (step 0.1 V) Check of CB ready state
(positive-sequence undervoltage) or deactivated Blocking with manual CLOSE
Blocking of undervoltage protection Minimum current; binary input Voltage limit values for DLC, ADT,
stages RDT
Healthy line voltage 30 to 90 V (step 1 V)
Reset ratio 1.05 Dead line 2 to 70 V (step 1 V)
Time delays Tolerances
Time delay for all over- and 0 to 100 s (steps 0.01 s) or deactivated Time stages 1 % of setting value or 10 ms
undervoltage stages Voltage limit values ≤ 3 % of setting value or 0.5 V
Command / pickup time Approx. 30 ms Synchro-check (ANSI 25)
Tolerances Initiate options Auto-reclosure;
Voltage limit values ≤ 3 % of setting value or 0.5 V Manual CLOSE control
Time stages 1 % of setting value or 10 ms Control commands
Frequency protection (ANSI 81) Operating modes
with auto-reclosure Synchro-check
Number of frequency elements 4
Line dead/busbar live
Setting range 45.5 to 54.5 Hz Line live/busbar dead
(in steps of 0.01) at fnom = 50 Hz Line and busbar dead
55.5 to 64.5 Hz Bypassing
(in steps of 0.01) at fnom = 60 Hz For manual closure
Delay times 0 to 600 s or ∞ (in steps of 0.01 s) and control commands As for auto-reclosure
Operating voltage range 6 to 230 V (phase-to-ground (earth)) Permissible voltage difference 1 to 60 V (step 0.1 V)
Pickup times Approx. 80 ms Permissible frequency difference 0.03 to 2 Hz (step 0.01 Hz)
Dropout times Approx. 80 ms Permissible angle difference 2 to 80 ° (step 1 °)
Hysteresis Approx. 20 mHz Max. duration of synchronization 0.01 to 600 s (step 0.01 s) or deactivated
Dropout condition Voltage = 0 V and current = 0 A
Release delay with synchronous 0 to 30 s (step 0.01 s)
Tolerances networks
Frequency 12 m Hz for V = 29 to 230 V
Tolerances
Delay times 1 % of the setting value or 10 ms
Time stages 1 % of setting value or 10 ms
Voltage limit values ≤ 2 % of setting value or 2 V
Technical data
Restricted earth-fault protection (ANSI 87N) Thermal overload protection (ANSI 49)
Multiple availability 2 times (option) Setting ranges
Factor k acc. to IEC 60255-8 1 to 4 (steps 0.01)
Settings
Time constant τ 1 to 999.9 min (steps 0.1 min)
Differential current IREF >/INobj 0.05 to 2.00 (steps 0.01)
Temperature alarm stage Θalarm/Θtrip 50 to 100 % in relation to the trip
Limit angle ϕ REF 110 ° (fixed) temperature
Time delay TREF 0.00 to 60.00 s (steps 0.01 s) Current alarm stage Ialarm
or deactivated (no trip) Secondary 1 A 0.1 to 4 A (step 0.1)
The set times are pure delay times Secondary 5 A 0.5 to 20 A (step 0.1)
Operating times
I 2 − I pre
2
Pickup time (in ms) at frequency 50 Hz 60 Hz Trip time characteristic t = τ ln
I 2 − (k ⋅ I N )
2
Technical data
Minimum/maximum memory Further additional functions
Indication Measured values with date and time Measurement supervision Current sum
Resetting Cyclically Current symmetry
Via binary input Voltage sum
Via the keyboard Voltage symmetry
Via serial interface Voltage phase sequence
Fuse failure monitor
Values
Min./max. of measured values 3 x IPhase; I1; 3 x VPhase-Ground; 3 x Annunciations
VPhase-to-phase; 3V0; V1; Event logging Buffer size 200
P+; P–; Q+; Q–; S; f; power factor Fault logging Storage of signals of the last 8 faults,
(+); power factor (–) buffer size 800
Min./max. of mean values 3 x IPhase; I1; P; Q; S Switching statistics Number of breaking operations per
Energy meters c.b. pole
Sum of breaking current per phase
Four-quadrant meters WP+; WP–; WQ+; WQ– Breaking current of last trip operation
Tolerance Max. breaking current per phase
for ⏐cos ϕ⏐ > 0.7 and V > 50 % 5% Circuit-breaker test TRIP/CLOSE cycle 3-phase
Vnom and I> 50 % Inom TRIP/CLOSE cycle per phase
Oscillographic fault recording Setting range 0.00 to 30 s (step 0.01 s)
Analog channels 3 x IPhase, 3I0, 3I0PAR, 3I0 Gnd sensitive, Dead time for CB TRIP/CLOSE 0.00 to 30 s (step 0.01 s)
3 x IDiff, 3 x IStab cycle
3 x VPhase, 3V0, VSYNC, Ven, Vx Commissioning support Operational measured values
Max. number of available recordings 8, backed-up by battery if auxiliary Circuit-breaker test
voltage supply fails Read binary test
Initiate binary inputs
Sampling intervals 20 samplings per cycle
Set binary outputs
Total storage time Approx. 15 s Set serial interface outputs 7
Binary channels Pickup and trip information; number Lockout of a device
and contents can be freely configured Test mode ot the differential
by the user protection topology
Max. number of displayed binary 40
channels CE conformity
Control This product is in conformity with the Directives of the European Commu-
Number of switching units Depends on the number of binary / nities on the harmonization of the laws of the Member States relating to
indication inputs and indication / electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
command outputs electrical equipment designed for use within certain voltage limits (Council
Directive 73/23/EEC).
Control commands Single command / double command
1, 1 plus 1 common or 2 pole This unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Feed back CLOSE, TRIP, intermediate position
Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
Interlocking Freely configurable
The unit has been developed and manufactured for application in an indus-
Local control Control via menu, function keys trial environment according to the EMC standards.
Remote control Control protection, DIGSI, pilot This conformity is the result of a test that was performed by Siemens AG in
wires accordance with Article 10 of the Council Directive complying with the
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
standard EN 60255-6 for the “low-voltage Directive”.
Relay type
Multi-end differential prot. relay for two line end operation1) 2
Multi-end differential prot. relay for multi-line end op. (2 to 6) 3
Measurement input
IPH = 1 A2), IGnd = 1 A (min. = 0.05 A) 1
IPH = 1 A2), IGnd = high sensitive (min. = 0.003 A) 2
IPH = 5 A2), IGnd = 5 A (min. = 0.25 A) 5
Operator panel with: IPH = 5 A2), IGnd = high sensitive (min. = 0.003 A) 6
– function keys,
– numerical keys,
Rated auxiliary voltage (power supply, binary indication voltage)
– PC interface
– display (pos. 5) 24 to 48 V DC, binary input threshold 17 V4) 2
– key-operated 60 to 125 V DC3), binary input threshold 17 V4) 4
switches (pos. 5) 110 to 250 V DC3), 115 V AC, binary input threshold 73 V4) 5
220 to 250 V DC3), 115 V AC, binary input threshold 154 V4) 6
1) For SICAM energy automation 3) For surface-mounting housing appli- 5) For distances less than 25 km, two optical
system. cations, please select option A attenuators 7XV5107-0AA00 are required
2) Optical double ring interfaces are not (820 nm, 1.5 km) together with an to avoid optical saturation of the receiver
available with surface-mounting hous- external repeater (for Order No., element.
ings. Please, order the version with see Accessories). 6) For distances less than 50 km, two optical
RS485 interface and a separate electri- 4) If position 9 = "E, G, H, Q, R" (surface- attenuators 7XV5107-0AA00 are required
cal/optional converter. mounting housing), please order relay to avoid optical saturation of the receiver
with electrical Ethernet interface. element.
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
M 4r Ov
ea e e
M sur 24 m o t ( A rcu
Functions
in ed re e c N S rre
Description
,m v m om I 5 nt
a x alue ot m 0 , tim
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
,m s ei a 50 e
Ex Tr nd n d Br
ter e a exte
n n an ica s ea N , pro
of na de v e sfo tio (A ker 5 1 te
di l G d , 5 cti
Additional functions 2
Additional functions 1
cto rm ns NS fa
ffe P ( A r g er 1 N on
I 5 ilur )
for two to six line ends
re S s N S r o ex 0B e p
nt yn I u p te F) ro
n
n
n
n
n
n
n
n
n
n
n
n
n
ial ch
Ca pr ro Fa 87T ada nsio Di tec
pa ot . ul ) pt n w re tio
co cit ec
tio at t l o i o it
n h pr c t i o n
m ive n bo cat ot n
pe c th o r ( A ecti a l e
n s ha
n
n
n
n
n
n
n
n
n
n
n
n
ati rg lin w i N S on a r t
e e e th I , e h-
n
n
on c Fa
ur u nd m Di 50N arth faul
re
nt at lt l o s eas
ur sta , e t
1 l cat em qu nc 51N d ne
in or ad e p , 6 tw
7SD5 multi-end differential protection relay
ee w en 7 o
t
n
n
n
n
n
n
n d th i ch rila ro
ar te tec N) rks
Ov m ac ra tio
t
e
n
n
er
V> / u n as Di eris l an n w
, d ur sta ti d it
Ov V < e r v em n
sp c c (A mho h
en
er (A olta
( A /un NS g e t ec e p
(I> ial p ro
NS
I
N S de I 2 p , V ick tect 21, 2
I 8 rfr 7,5 r o t (A /I u io
n
n
n
n
1 ) eq 9) e c t NS , V p m n w 1N)
ue io I /I e it
n
n
n
n
n
Re nc
str yp Pa 21, /ϕ, Z thod h
p r ict ra 21 < s
ro
Order No.
o t ed lle N) )
ec e tec l li
t i o art tio ne
n
n
n
n
n
n h- co
( A fa Po
w m
N S ult pe
I8 (A er s ns
7N NS wi ati
) I 6 ng on
8, de
68 tec
T) tio
n
F
H
D
C
G
E
V
S
N
U
T
Q
P
M
R
L
K
7
6
5
4
3
2
1
0
code
7 Line Differential Protection / 7SD52/53
Order
7SD5¨¨¨-¨¨¨¨¨-¨¨¨¨ ¨¨¨
7/75
7
7 Line Differential Protection / 7SD52/53
Further modules
Protection data interface mod. opt. 1300 nm, mono-mode FO cable,
7 LC-Duplex connector, 24 km C53207-A351-D655-1
Protection data interface mod. opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 60 km C53207-A351-D656-1
Protection data interface mod. opt. 1550 nm, mono-mode FO cable,
LC-Duplex connector, 100 km C53207-A351-D657-1
Optical repeaters
Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 24 km 7XV5461-0BG00
Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 60 km 7XV5461-0BH00
Serial repeater (2-channel), opt. 1550 nm, mono-mode FO cable,
LC-Duplex connector, 100 km 7XV5461-0BJ00
DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (Windows 2000 or XP Professional)
device templates, Comtrade Viewer, electronic manual included
as well as “Getting started” manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Professional
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
SIGRA 4
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format). Running under MS Windows (Windows 2000 or XP Professional).
Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM. 7XS5410-0AA00
Connecting cable
Cable between PC/notebook (9-pin connector)
and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
7
Manual for 7SD522/523 V4.6
English C53000-G1176-C169
Fig. 7/76 Mounting rail for 19" rack Crimp CI2 0.5 to 1 mm 2 0-827039-1 4000 AMP 1)
connector 0-827396-1 1 AMP 1)
2
CI2 1 to 2.5 mm 0-827040-1 4000 AMP 1)
0-827397-1 1 AMP 1)
LSP2090-afpen.eps
LSP2091-afpen.eps
2
Type III+ 0.75 to 1.5 mm 0-163083-7 4000 AMP 1)
1)
0-163084-2 1 AMP
1)
Crimping For Type III+ 0-539635-1 1 AMP
Fig. 7/77 Fig. 7/78 1)
tool and matching female 0-539668-2 AMP
2-pin connector 3-pin connector
For CI2 0-734372-1 1 AMP 1)
1)
and matching female 1-734387-1 AMP
LSP2093-afpen.eps
LSP2092-afpen.eps
Connection diagram
BO8
BO9
BO10
BO11
BO12
BO13
BO14
BO15
Fig. 7/83
Fig. 7/81 Basic version in housing 1/2 x 19” with 8 binary inputs
and 16 binary outputs
Connection diagram
BO8
BO9
BO10
BO11
BO12
BO13
BO14
BO15
Fig. 7/85
Connection diagram
BO8
BO9
BO10
BO11
BO12
BO13
BO14
BO15
Fig. 7/87