Danfoss KVR Pressure Regulating Valves
Danfoss KVR Pressure Regulating Valves
Danfoss KVR Pressure Regulating Valves
Data sheet
Features yy Accurate, adjustable pressure regulation yy ¼ in. Schrader valve for pressure
gauge connection
yy Wide capacity and operating range
yy Available with flare and ODF
yy Pulsation damping design solder connections
yy Stainless steel bellows yy KVR 12- 22: Compliant with ATEX hazard
zone 2
yy Compact angle design for easy
installation in any position yy NRD: for use with HCFC, HFC and HC
refrigerants
yy “Hermetic” brazed construction
5 – 17.5 bar
Adjustment range
Factory setting = 10 bar
KVR: Pe = 31 bar
Maximum test pressure
NRD: Pe = 60 bar
Ordering
KVR 12, KVR 15, KVR 22, KVR 28, KVR 35, NRD
129 121 93.7 139.3 34.9 30.6 34.9 37.7 — — — 1 1/8 — 034L0095
KVR 28
129 121 93.7 139.3 34.9 30.6 34.9 37.7 — — — — 28 034L0099
— — — — — — — — — — — /2
1
— 020-1132
NRD
— — — — — — — — — — — — 12 020-1136
Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]
[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6
R22 R22
10 23.7 33.5 47.4 67.0 94.8 42.5 60.2 85.1 120.4 170.5
20 21.8 30.8 43.6 61.7 87.3 39.2 55.4 78.4 110.9 157.0
KVR 12
KVR 15 30 19.8 28.1 39.7 56.2 79.4 35.6 50.4 71.3 100.9 142.9
KVR 22
40 17.8 25.2 35.6 50.4 71.3 32.0 45.3 64.0 90.6 128.3
50 15.7 22.2 31.4 44.4 62.9 28.2 39.9 56.4 79.9 113.1
10 60.5 85.6 121.1 171.2 242.3 108.9 154.0 217.8 308.2 436.2
20 55.7 78.8 111.4 157.6 223.0 100.2 141.8 200.6 283.8 401.7
KVR 28
30 50.7 71.7 101.4 143.4 202.9 91.2 129.0 182.5 258.2 365.5
KVR 35
40 45.9 64.3 91.0 128.7 182.1 81.9 115.8 163.9 231.8 328.2
50 40.1 58.8 80.3 113.6 160.7 72.2 102.1 144.4 204.4 289.3
R134a R134a
10 22.8 32.3 45.6 64.6 91.3 40.7 57.5 81.4 115.0 163.0
20 20.8 29.4 41.6 58.8 83.2 37.1 52.5 74.2 105.0 149.0
KVR 12
KVR 15 30 18.7 26.5 37.4 53.0 74.9 33.4 47.3 66.9 94.7 134.0
KVR 22
40 16.6 23.5 33.2 47.0 66.5 29.7 42.0 59.4 84.1 119.0
50 14.5 20.5 29.0 41.0 58.0 25.9 36.6 51.8 73.3 104.0
10 58.3 82.4 117.0 165.0 233.0 104.0 147.0 208.0 295.0 418.0
20 53.1 75.1 106.0 150.0 213.0 94.9 134.0 190.0 269.0 361.0
KVR 28
30 47.8 67.6 95.7 135.0 191.0 85.5 121.0 171.0 242.0 343.0
KVR 35
40 42.5 60.0 84.9 120.0 170.0 76.0 108.0 152.0 215.0 305.0
50 37.0 52.3 74.0 105.0 148.0 66.3 93.7 133.0 188.0 266.0
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.
Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]
[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6
R404A/R507 R404A/R507
10 18.4 25.9 36.8 52.0 73.5 32.9 46.4 65.6 92.9 131.3
20 16.4 23.2 32.9 46.5 65.7 29.4 41.6 58.8 83.2 117.6
KVR 12
KVR 15 30 14.5 20.5 29.0 41.0 58.0 25.9 36.6 51.8 73.3 103.7
KVR 22
40 12.9 17.6 25.0 35.4 50.1 22.4 31.6 44.7 63.3 89.7
50 10.5 14.9 21.0 29.7 42.1 18.8 26.6 37.6 53.2 75.4
10 46.9 66.3 93.8 132.3 188.0 84.0 118.7 168.0 237.3 337.1
20 42.0 59.3 83.9 118.7 168.0 75.2 106.1 150.2 213.2 301.4
KVR 28
30 37.0 52.3 73.9 104.6 148.1 66.3 93.7 132.3 188.0 265.7
KVR 35
40 31.9 45.2 63.8 90.3 128.1 57.2 81.0 114.5 161.7 228.9
50 26.9 37.9 53.7 75.9 107.0 48.1 68.0 96.2 136.5 193.2
R407C R407C
10 25.6 36.2 51.2 72.6 102.3 45.9 65.0 91.9 130.0 184.1
20 23.5 33.2 47.1 66.6 94.3 42.3 59.8 84.7 119.8 169.6
KVR 12
KVR 15 30 21.4 30.3 42.9 60.7 85.7 38.4 54.4 77.0 109.0 154.3
KVR 22
40 19.4 27.5 38.8 55.0 77.7 34.9 49.4 69.8 98.8 139.8
50 17.3 24.4 34.5 48.8 69.2 31.0 43.9 62.0 87.9 124.4
10 65.3 92.4 130.7 184.9 261.7 117.6 166.3 235.2 332.9 471.1
20 60.1 85.1 120.3 170.2 240.8 108.2 153.1 216.6 306.5 433.8
KVR 28
30 54.5 77.4 109.5 154.9 219.1 98.5 139.3 197.1 278.9 394.7
KVR 35
40 50.0 70.1 99.2 140.3 198.5 89.3 126.2 178.7 252.7 357.7
50 44.1 62.5 88.3 124.9 176.8 79.4 112.3 158.8 224.8 318.2
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.
Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]
[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6
R22 R22
10 3.3 4.6 6.4 8.8 11.8 6.0 8.4 11.8 16.3 22.2
20 3.5 5.0 6.9 9.6 13.0 6.3 8.9 12.5 17.4 23.9
KVR 12
KVR 15 30 3.7 5.3 7.4 10.3 14.4 6.6 9.4 13.2 18.4 25.4
KVR 22
40 3.9 5.5 7.8 10.9 15.0 6.9 9.8 13.7 19.3 26.7
50 4.1 5.7 8.1 11.3 15.7 7.1 10.1 14.2 20.0 27.7
10 8.5 11.9 16.6 22.8 30.3 15.8 22.2 31.1 43.2 58.7
20 9.1 12.8 17.9 24.8 33.5 16.7 23.5 33.1 46.1 63.1
KVR 28
30 9.7 13.6 19.1 26.6 36.3 17.6 24.8 34.9 48.7 67.2
KVR 35
40 10.2 14.3 20.1 28.1 38.7 18.3 25.9 36.4 51.0 70.6
50 10.5 14.9 20.9 29.2 40.4 18.9 26.6 37.5 52.6 73.2
R134a R134a
10 2.9 4.0 5.6 7.6 9.7 5.4 7.6 10.7 14.7 19.6
20 3.1 4.3 6.0 8.2 10.8 5.6 7.9 11.1 15.4 20.8
KVR 12
KVR 15 30 3.2 4.5 6.3 8.8 11.7 5.8 8.2 11.6 16.1 21.9
KVR 22
40 3.4 4.7 6.6 9.2 12.5 6.0 8.5 11.9 16.6 22.8
50 3.4 4.8 6.8 9.5 13.0 6.1 8.6 12.1 16.9 23.3
10 7.5 10.5 14.5 19.6 25.0 14.4 20.2 28.2 38.8 51.8
20 7.9 11.1 15.5 21.2 27.8 15.0 21.0 29.5 40.8 55.0
KVR 28
30 8.4 11.8 16.4 22.6 30.2 15.5 21.8 30.6 42.5 57.9
KVR 35
40 8.7 12.2 17.1 23.7 32.1 15.9 22.4 31.5 43.9 60.3
50 8.9 12.5 17.6 24.5 33.5 16.1 22.7 32.0 44.7 61.7
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.
Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]
[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6
R404A/R507 R404A/R507
10 3.2 4.5 6.3 8.6 11.7 5.8 8.1 11.3 15.8 21.6
20 3.4 4.7 6.6 9.2 12.4 6.1 8.4 11.8 16.5 22.7
KVR 12
KVR 15 30 3.5 4.9 6.8 9.5 13.0 6.1 8.5 12.0 16.8 23.2
KVR 22
40 3.5 4.9 6.8 9.6 13.1 6.1 8.6 12.1 16.9 23.2
50 3.5 4.9 6.8 9.6 13.1 6.1 8.6 12.1 16.9 23.2
10 8.3 11.7 16.2 22.3 30.0 15.8 22.2 31.1 43.2 58.7
20 8.7 12.2 17.1 23.7 32.2 16.7 23.5 33.1 46.1 63.1
KVR 28
30 8.9 12.5 17.6 24.4 33.5 17.6 24.8 34.9 48.7 67.2
KVR 35
40 9.0 12.6 17.8 24.8 33.0 18.3 25.9 36.4 51.0 70.6
50 9.0 12.6 17.8 24.8 33.5 18.9 26.6 37.5 52.6 73.2
R407C R407C
10 3.6 5.0 6.9 9.5 12.8 6.5 9.1 12.7 17.6 24.0
20 3.8 5.4 7.5 10.4 14.0 6.8 9.6 13.5 18.8 25.8
KVR 12
KVR 15 30 4.0 5.8 8.0 11.1 15.5 7.1 10.2 14.3 19.9 27.4
KVR 22
40 4.2 6.0 8.5 11.9 16.4 7.5 10.7 14.9 21.0 29.1
50 4.5 6.3 8.9 12.4 17.3 7.8 11.1 15.6 22.0 30.5
10 9.2 12.9 17.9 24.7 32.7 17.1 24.0 33.6 46.7 63.4
20 9.8 13.8 19.3 26.8 36.2 18.0 25.4 35.7 49.8 68.1
KVR 28
30 10.5 14.7 20.6 28.7 39.2 19.0 26.8 37.7 52.6 72.6
KVR 35
40 11.1 15.6 21.9 30.6 42.2 19.9 28.2 39.7 55.6 77.0
50 11.6 16.4 23.0 32.1 44.4 20.8 29.3 41.3 57.9 80.5
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.
Sizing For optimum performance, it is important to The following data must be used when sizing
select a KVR valve according to system a KVR valve:
conditions and application. yy Refrigerant: HCFC, HFC and HC: KVR 12-22,
HCFC and non-flammable HFC: KVR 28-35
yy Evaporator capacity Qe (plant capacity)
yy Evaporating temperature te in [°C]
yy Condensing temperature tc in [°C]
yy Connection type: flare or solder
yy Connection size in [in.]
Application example
Correction factors
Step 2
Step 3
Now select the appropriate capacity table and KVR 12, KVR 15, KVR 22 delivers 142.9 kW
choose the line for a condensing temperature at a 1.6 bar pressure drop across the valve.
tc= 30 °C. Based on the required connection size of
Using the corrected evaporator capacity, select a 5
/8 in. ODF, the KVR 15 is the proper selection
valve that provides an equivalent or greater for this example.
capacity at an acceptable pressure drop.
Step 4
1 = 8 mm
2
3
4 14
1. Seal cap
2. Gasket
5
3. Setting screw
4. Main spring 6 15
5. Valve body 7
6. Equalizing bellows
8
7. Valve plate
8. Valve seat 9 17
9. Damping device 10
10. Pressure gauge 11
connection 18
11. Cap 12
12. Gasket 13
13. Insert 16
14. Piston
15. Valve plate
16. Piston guide
17. Valve body
18. Spring
Condensing pressure regulator, type KVR opens In addition, the regulator is equipped with an
upon a rise in pressure on the inlet side, i.e. when effective damping device (9) to safe-guard
the pressure in the condenser reaches the set against pulsations which can normally occur in
value. KVR regulation is dependent only on the refrigeration plant.
inlet pressure. Pressure variations on the outlet The damping device contributes to ensuring
side of the regulator do not affect the degree of a long working life for the regulator without
opening, since type KVR has an equalizing impairing regulation accuracy.
bellows (6). The effective area of this bellows Differential valve type NRD begins to open when
corresponds to that of the valve seat. the pressure drop in the valve is 1.4 bar, and is
fully open when the pressure drop is 3 bar.
Capacity
100%
Rated capacity
Set point
5 13 16 [bar]
Min. setting point Offset Max. setting point
P-band
Adjustment range
KVR, NRD
Connection
Solder C Net
Type Flare NV1 NV2 H1 H2 H3 L L1 B1 B2 øD
ODF Solder weight
[in.] [mm] [in.] [mm]
KVR 12 1
/2 12 1
/2 12 19 19 179 99 66 — — 64 41 10 30 0.4
KVR 15 5
/8 16 5
/8 16 24 24 179 99 66 — — 64 41 12 30 0.4
KVR 22 — — 7
/8 22 — — 179 99 66 — — 64 41 17 30 0.4