Condensing pressure regulator, type KVR


Differential pressure valve, type NRD

Regulating system KVR and NRD is used to


maintain a constant and sufficiently high
condenser and receiver pressure in
refrigeration and air conditioning plant with
air-cooled condensers.

KVR can also be used together with receiver


pressure regulator, type KVD.

Features yy Accurate, adjustable pressure regulation yy ¼ in. Schrader valve for pressure
gauge connection
yy Wide capacity and operating range
yy Available with flare and ODF
yy Pulsation damping design solder connections

yy Stainless steel bellows yy KVR 12- 22: Compliant with ATEX hazard
zone 2
yy Compact angle design for easy
installation in any position yy NRD: for use with HCFC, HFC and HC
refrigerants
yy “Hermetic” brazed construction

Approvals UL LISTED, file SA7200


GOST AN30

DKRCC.PD.HC0.A4.02 / 520H8750C © Danfoss A/S (RC-MCP / jmn), 2014-10


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Technical data HCFC, HFC and HC: KVR 12-22


Refrigerants
HCFC and non-flammable HFC: KVR 28-35

5 – 17.5 bar
Adjustment range
Factory setting = 10 bar

KVR: PS/MWP = 28 bar


Maximum working pressure
NRD: PS/MWP = 46 bar

KVR: Pe = 31 bar
Maximum test pressure
NRD: Pe = 60 bar

Medium temperature range -45 – 130 °C

KVR 12 – 22 = 6.2 bar


P-band
KVR 28 – 35 = 5 bar

Start opening: Δp = 1.4 bar


Opening differential pressure for NRD
Fully open: Δp = 3 bar

Ordering

KVR 12, KVR 15, KVR 22, KVR 28, KVR 35, NRD

Rated liquid capacity 1) Rated hot gas 1)


Flare Solder
(Evaporator capacity) (Evaporator capacity)
connection 2) Connection
Type [kW] [kW] Code no. Code no.
R404A/ R404A/
R22 R134a R407C R22 R134a R407C [in.] [mm] [in.] [mm]
R507 R507

50.4 47.3 36.6 54.4 13.2 11.6 12.0 14.3 /2


1
12 034L0091 /2
1
— 034L0093
KVR 12
50.4 47.3 36.6 54.4 13.2 11.6 12.0 14.3 — — — — 12 034L0096

KVR 15 50.4 47.3 36.6 54.4 13.2 11.6 12.0 14.3 /8


5
16 034L0092 /8
5
16 034L0097

KVR 22 50.4 47.3 36.6 54.4 13.2 11.6 12.0 14.3 — — — /8


7
22 034L0094

129 121 93.7 139.3 34.9 30.6 34.9 37.7 — — — 1 1/8 — 034L0095
KVR 28
129 121 93.7 139.3 34.9 30.6 34.9 37.7 — — — — 28 034L0099

KVR 35 129 121 93.7 139.3 34.9 30.6 34.9 37.7 — — — 1 /8 3


35 034L0100

— — — — — — — — — — — /2
1
— 020-1132
NRD
— — — — — — — — — — — — 12 020-1136

The connection dimensions 1)


Rated capacity is based on: 2)
KVR are delivered without flare nuts.
chosen must not be too small, – evaporating temperature te= -10 °C Separate flare nuts can be delivered:
since gas velocities in excess of – condensing temperature tc= 30 °C 1/2 in./12 mm, code no. 011L1103
40 m/s at the inlet of the – pressure drop across the valve 5/8 in./16 mm, code no. 011L1167
regulator can give flow noise. ∆p = 0.2 bar for liquid capacity
∆p = 0.4 bar for hot gas capacity
– offset = 3 bar

2 DKRCC.PD.HC0.A4.02 / 520H8750 © Danfoss A/S (RC-MCP / jmn), 2014-10


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Liquid capacity Max. regulator capacity Qe 1)

Liquid capacity in [kW] Liquid capacity in [kW]


Condensing (Evaporator capacity) (Evaporator capacity)
temperature
Type tc Offset 1.5 bar Offset 3 bar

Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]

[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6

R22 R22
10 23.7 33.5 47.4 67.0 94.8  42.5  60.2  85.1 120.4 170.5

20 21.8 30.8 43.6 61.7 87.3  39.2  55.4  78.4 110.9 157.0
KVR 12
KVR 15 30 19.8 28.1 39.7 56.2 79.4  35.6  50.4  71.3 100.9 142.9
KVR 22
40 17.8 25.2 35.6 50.4 71.3  32.0  45.3  64.0  90.6 128.3

50 15.7 22.2 31.4 44.4 62.9  28.2  39.9  56.4  79.9 113.1

10 60.5 85.6 121.1 171.2 242.3 108.9 154.0 217.8 308.2 436.2

20 55.7 78.8 111.4 157.6 223.0 100.2 141.8 200.6 283.8 401.7
KVR 28
30 50.7 71.7 101.4 143.4 202.9  91.2 129.0 182.5 258.2 365.5
KVR 35
40 45.9 64.3 91.0 128.7 182.1  81.9 115.8 163.9 231.8 328.2

50 40.1 58.8 80.3 113.6 160.7  72.2 102.1 144.4 204.4 289.3

R134a R134a
10 22.8 32.3 45.6 64.6 91.3  40.7  57.5  81.4 115.0 163.0

20 20.8 29.4 41.6 58.8 83.2  37.1  52.5  74.2 105.0 149.0
KVR 12
KVR 15 30 18.7 26.5 37.4 53.0 74.9  33.4  47.3  66.9  94.7 134.0
KVR 22
40 16.6 23.5 33.2 47.0 66.5  29.7  42.0  59.4  84.1 119.0

50 14.5 20.5 29.0 41.0 58.0  25.9  36.6  51.8  73.3 104.0

10 58.3 82.4 117.0 165.0 233.0 104.0 147.0 208.0 295.0 418.0

20 53.1 75.1 106.0 150.0 213.0  94.9 134.0 190.0 269.0 361.0
KVR 28
30 47.8 67.6 95.7 135.0 191.0  85.5 121.0 171.0 242.0 343.0
KVR 35
40 42.5 60.0 84.9 120.0 170.0  76.0 108.0 152.0 215.0 305.0

50 37.0 52.3 74.0 105.0 148.0  66.3  93.7 133.0 188.0 266.0
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.

Correction factors for evaporating temperature te

te [°C] -40 -30 -20 -10 0 10

R22 1.09 1.05 1.02 1.0 0.98 0.96

R134a 1.14 1.09 1.04 1.0 0.96 0.93

Plant capacity x correction factor = table capacity

© Danfoss A/S (RC-MCP / jmn), 2014-10 DKRCC.PD.HC0.A4.02 / 520H8750 3


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Liquid capacity Max. regulator capacity Qe 1)


(continued)
Liquid capacity in [kW] Liquid capacity in [kW]
Condensing (Evaporator capacity) (Evaporator capacity)
temperature
Type tc Offset 1.5 bar Offset 3 bar

Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]

[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6

R404A/R507 R404A/R507
10 18.4 25.9 36.8 52.0 73.5 32.9  46.4  65.6  92.9 131.3

20 16.4 23.2 32.9 46.5 65.7 29.4  41.6  58.8  83.2 117.6
KVR 12
KVR 15 30 14.5 20.5 29.0 41.0 58.0 25.9  36.6  51.8  73.3 103.7
KVR 22
40 12.9 17.6 25.0 35.4 50.1 22.4  31.6  44.7  63.3  89.7

50 10.5 14.9 21.0 29.7 42.1 18.8  26.6  37.6  53.2  75.4

10 46.9 66.3 93.8 132.3 188.0 84.0 118.7 168.0 237.3 337.1

20 42.0 59.3 83.9 118.7 168.0 75.2 106.1 150.2 213.2 301.4
KVR 28
30 37.0 52.3 73.9 104.6 148.1 66.3  93.7 132.3 188.0 265.7
KVR 35
40 31.9 45.2 63.8 90.3 128.1 57.2  81.0 114.5 161.7 228.9

50 26.9 37.9 53.7 75.9 107.0 48.1  68.0  96.2 136.5 193.2

R407C R407C
10 25.6 36.2 51.2 72.6 102.3  45.9  65.0  91.9 130.0 184.1

20 23.5 33.2 47.1 66.6 94.3  42.3  59.8  84.7 119.8 169.6
KVR 12
KVR 15 30 21.4 30.3 42.9 60.7 85.7  38.4  54.4  77.0 109.0 154.3
KVR 22
40 19.4 27.5 38.8 55.0 77.7  34.9  49.4  69.8  98.8 139.8

50 17.3 24.4 34.5 48.8 69.2  31.0  43.9  62.0  87.9 124.4

10 65.3 92.4 130.7 184.9 261.7 117.6 166.3 235.2 332.9 471.1

20 60.1 85.1 120.3 170.2 240.8 108.2 153.1 216.6 306.5 433.8
KVR 28
30 54.5 77.4 109.5 154.9 219.1  98.5 139.3 197.1 278.9 394.7
KVR 35
40 50.0 70.1 99.2 140.3 198.5  89.3 126.2 178.7 252.7 357.7

50 44.1 62.5 88.3 124.9 176.8  79.4 112.3 158.8 224.8 318.2
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.

Correction factors for evaporating temperature te

te [°C] -40 -30 -20 -10 0 10

R404A/R507 1.18 1.11 1.05 1.0 0.95 0.92

R407C 1.12 1.08 1.04 1.0 0.97 0.93

Plant capacity x correction factor = table capacity

4 DKRCC.PD.HC0.A4.02 / 520H8750 © Danfoss A/S (RC-MCP / jmn), 2014-10


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Hot gas capacity Max. regulator capacity Qe 1)

Hot gas capacity in [kW] Hot gas capacity in [kW]


Condensing (Evaporator capacity) (Evaporator capacity)
temperature
Type tc Offset 1.5 bar Offset 3 bar

Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]

[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6

R22 R22
10 3.3 4.6 6.4 8.8 11.8  6.0  8.4 11.8 16.3 22.2

20 3.5 5.0 6.9 9.6 13.0  6.3  8.9 12.5 17.4 23.9
KVR 12
KVR 15 30 3.7 5.3 7.4 10.3 14.4  6.6  9.4 13.2 18.4 25.4
KVR 22
40 3.9 5.5 7.8 10.9 15.0  6.9  9.8 13.7 19.3 26.7

50 4.1 5.7 8.1 11.3 15.7  7.1 10.1 14.2 20.0 27.7

10 8.5 11.9 16.6 22.8 30.3 15.8 22.2 31.1 43.2 58.7

20 9.1 12.8 17.9 24.8 33.5 16.7 23.5 33.1 46.1 63.1
KVR 28
30 9.7 13.6 19.1 26.6 36.3 17.6 24.8 34.9 48.7 67.2
KVR 35
40 10.2 14.3 20.1 28.1 38.7 18.3 25.9 36.4 51.0 70.6

50 10.5 14.9 20.9 29.2 40.4 18.9 26.6 37.5 52.6 73.2

R134a R134a
10 2.9 4.0 5.6 7.6 9.7  5.4  7.6 10.7 14.7 19.6

20 3.1 4.3 6.0 8.2 10.8  5.6  7.9 11.1 15.4 20.8
KVR 12
KVR 15 30 3.2 4.5 6.3 8.8 11.7  5.8  8.2 11.6 16.1 21.9
KVR 22
40 3.4 4.7 6.6 9.2 12.5  6.0  8.5 11.9 16.6 22.8

50 3.4 4.8 6.8 9.5 13.0  6.1  8.6 12.1 16.9 23.3

10 7.5 10.5 14.5 19.6 25.0 14.4 20.2 28.2 38.8 51.8

20 7.9 11.1 15.5 21.2 27.8 15.0 21.0 29.5 40.8 55.0
KVR 28
30 8.4 11.8 16.4 22.6 30.2 15.5 21.8 30.6 42.5 57.9
KVR 35
40 8.7 12.2 17.1 23.7 32.1 15.9 22.4 31.5 43.9 60.3

50 8.9 12.5 17.6 24.5 33.5 16.1 22.7 32.0 44.7 61.7
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.

Correction factors for evaporating temperature te

te [°C] -40 -30 -20 -10 0 10

R22 1.09 1.05 1.02 1.0 0.98 0.96

R134a 1.14 1.09 1.04 1.0 0.96 0.93

Plant capacity x correction factor = table capacity

© Danfoss A/S (RC-MCP / jmn), 2014-10 DKRCC.PD.HC0.A4.02 / 520H8750 5


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Hot gas capacity Max. regulator capacity Qe 1)


(continued)
Hot gas capacity in [kW] Hot gas capacity in [kW]
Condensing (Evaporator capacity) (Evaporator capacity)
temperature
Type tc Offset 1.5 bar Offset 3 bar

Pressure drop across valve ∆p [bar] Pressure drop across valve ∆p [bar]

[°C] 0.1 0.2 0.4 0.8 1.6 0.1 0.2 0.4 0.8 1.6

R404A/R507 R404A/R507
10 3.2 4.5 6.3 8.6 11.7  5.8  8.1 11.3 15.8 21.6

20 3.4 4.7 6.6 9.2 12.4  6.1  8.4 11.8 16.5 22.7
KVR 12
KVR 15 30 3.5 4.9 6.8 9.5 13.0  6.1  8.5 12.0 16.8 23.2
KVR 22
40 3.5 4.9 6.8 9.6 13.1  6.1  8.6 12.1 16.9 23.2

50 3.5 4.9 6.8 9.6 13.1  6.1  8.6 12.1 16.9 23.2

10 8.3 11.7 16.2 22.3 30.0 15.8 22.2 31.1 43.2 58.7

20 8.7 12.2 17.1 23.7 32.2 16.7 23.5 33.1 46.1 63.1
KVR 28
30 8.9 12.5 17.6 24.4 33.5 17.6 24.8 34.9 48.7 67.2
KVR 35
40 9.0 12.6 17.8 24.8 33.0 18.3 25.9 36.4 51.0 70.6

50 9.0 12.6 17.8 24.8 33.5 18.9 26.6 37.5 52.6 73.2

R407C R407C
10 3.6 5.0 6.9 9.5 12.8  6.5  9.1 12.7 17.6 24.0

20 3.8 5.4 7.5 10.4 14.0  6.8  9.6 13.5 18.8 25.8
KVR 12
KVR 15 30 4.0 5.8 8.0 11.1 15.5  7.1 10.2 14.3 19.9 27.4
KVR 22
40 4.2 6.0 8.5 11.9 16.4  7.5 10.7 14.9 21.0 29.1

50 4.5 6.3 8.9 12.4 17.3  7.8 11.1 15.6 22.0 30.5

10 9.2 12.9 17.9 24.7 32.7 17.1 24.0 33.6 46.7 63.4

20 9.8 13.8 19.3 26.8 36.2 18.0 25.4 35.7 49.8 68.1
KVR 28
30 10.5 14.7 20.6 28.7 39.2 19.0 26.8 37.7 52.6 72.6
KVR 35
40 11.1 15.6 21.9 30.6 42.2 19.9 28.2 39.7 55.6 77.0

50 11.6 16.4 23.0 32.1 44.4 20.8 29.3 41.3 57.9 80.5
1)
The capacities are based on:
Evaporating temperature te= -10 °C.
For other evaporating temperatures see table below.

Correction factors for evaporating temperature te

te [°C] -40 -30 -20 -10 0 10

R404A/R507 1.18 1.11 1.05 1.0 0.95 0.92

R407C 1.12 1.08 1.04 1.0 0.97 0.93

Plant capacity x correction factor = table capacity

6 DKRCC.PD.HC0.A4.02 / 520H8750 © Danfoss A/S (RC-MCP / jmn), 2014-10


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Sizing For optimum performance, it is important to The following data must be used when sizing
select a KVR valve according to system a KVR valve:
conditions and application. yy Refrigerant: HCFC, HFC and HC: KVR 12-22,
HCFC and non-flammable HFC: KVR 28-35
yy Evaporator capacity Qe (plant capacity)
yy Evaporating temperature te in [°C]
yy Condensing temperature tc in [°C]
yy Connection type: flare or solder
yy Connection size in [in.]

Valve selection Example KVR in a liquid capacity application


When selecting the appropiate valve it may yy Refrigerant: R22 example
be necessary to convert the actual evaporator yy Evaporator capacity: Qe = 100 kW
capacity using a correction factors. This (plant capacity)
is required when your system conditions yy Evaporating temperature: te = -40 °C
are different than the table conditions. yy Condensing temperature: tc= 30 °C
The selection is also dependant on the yy Connection type: Solder
acceptable pressure drop across the valve. yy Connection size: 5/8 in.
The following example illustrates how this
is done.

Application example

Liquid capacity application

Hot gas capacity application

© Danfoss A/S (RC-MCP / jmn), 2014-10 DKRCC.PD.HC0.A4.02 / 520H8750 7


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Valve selection Step 1


(continued)
Determine the correction factor for evaporating From the correction factors table an evaporating
temperature te. temperature of -40 °C, R22 corresponds to
a factor of 1.09.

Correction factors

te [°C] -40 -30 -20 -10 0 10

R22 1.09 1.05 1.02 1.0 0.98 0.96

R134a 1.14 1.09 1.04 1.0 0.96 0.93

R404A, R507 1.18 1.11 1.05 1.0 0.95 0.92

R407C 1.12 1.08 1.04 1.0 0.97 0.93

Plant capacity x correction factor = table


capacity

Step 2

Corrected evaporator capacity is


Qe = 100 x 1.09 = 109.0 kW

Step 3

Now select the appropriate capacity table and KVR 12, KVR 15, KVR 22 delivers 142.9 kW
choose the line for a condensing temperature at a 1.6 bar pressure drop across the valve.
tc= 30 °C. Based on the required connection size of
Using the corrected evaporator capacity, select a 5
/8 in. ODF, the KVR 15 is the proper selection
valve that provides an equivalent or greater for this example.
capacity at an acceptable pressure drop.

Step 4

KVR 15, 5/8 in. solder connection:


code no. 034L0097 (see ordering list)

8 DKRCC.PD.HC0.A4.02 / 520H8750 © Danfoss A/S (RC-MCP / jmn), 2014-10


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Design / Function KVR NRD

1 = 8 mm

2
3
4 14
1. Seal cap
2. Gasket
5
3. Setting screw
4. Main spring 6 15
5. Valve body 7
6. Equalizing bellows
8
7. Valve plate
8. Valve seat 9 17
9. Damping device 10
10. Pressure gauge 11
connection 18
11. Cap 12
12. Gasket 13
13. Insert 16
14. Piston
15. Valve plate
16. Piston guide
17. Valve body
18. Spring

Condensing pressure regulator, type KVR opens In addition, the regulator is equipped with an
upon a rise in pressure on the inlet side, i.e. when effective damping device (9) to safe-guard
the pressure in the condenser reaches the set against pulsations which can normally occur in
value. KVR regulation is dependent only on the refrigeration plant.
inlet pressure. Pressure variations on the outlet The damping device contributes to ensuring
side of the regulator do not affect the degree of a long working life for the regulator without
opening, since type KVR has an equalizing impairing regulation accuracy.
bellows (6). The effective area of this bellows Differential valve type NRD begins to open when
corresponds to that of the valve seat. the pressure drop in the valve is 1.4 bar, and is
fully open when the pressure drop is 3 bar.

© Danfoss A/S (RC-MCP / jmn), 2014-10 DKRCC.PD.HC0.A4.02 / 520H8750 9


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

P-band and Offset Principle diagram

Capacity

100%

Rated capacity

Set point

5 13 16 [bar]
Min. setting point Offset Max. setting point
P-band
Adjustment range

Proportional band Offset


The proportional band or P-band is defined as The offset is defined as the amount of pressure
the amount of pressure required to move the required to move the valve plate from closed
valve plate from closed (set point) to fully open position (set point) to the necessary opening
position. degree for the actual load.
The offset is always a part of the P-band.
Example:
If the valve is set to open at 10 bar and the Example with R22:
valve P-band is 6.2, the valve will give maximum A working temperature of 36 °C ~ 13 bar is
capacity when the inlet pressure reaches required, and the temperature must not drop
16.2 bar. below 27 °C ~ 10 bar (set point).
The offset will then be 3 bar.

10 DKRCC.PD.HC0.A4.02 / 520H8750 © Danfoss A/S (RC-MCP / jmn), 2014-10


Data sheet Condensing pressure regulator, type KVR and differential pressure valve, type NRD

Dimensions [mm] KVR NRD


and weights [kg]

KVR, NRD

Connection
Solder C Net
Type Flare NV1 NV2 H1 H2 H3 L L1 B1 B2 øD
ODF Solder weight
[in.] [mm] [in.] [mm]

KVR 12 1
/2 12 1
/2 12 19 19 179  99  66 — —  64 41 10 30 0.4

KVR 15 5
/8 16 5
/8 16 24 24 179  99  66 — —  64 41 12 30 0.4

KVR 22 — — 7
/8 22 — — 179  99  66 — —  64 41 17 30 0.4

KVR 28 — — 1 1/8 28 — — 259 151 103 — — 105 48 20 43 1.0

KVR 35 — — 1 3/8 35 — — 259 151 103 — — 105 48 25 43 1.0

NRD — — — — — — — — — 131 10 — — — 22 0.1

© Danfoss A/S (RC-MCP / jmn), 2014-10 DKRCC.PD.HC0.A4.02 / 520H8750 11