RS-232/USB Serial Interface Module: Installation Instructions
RS-232/USB Serial Interface Module: Installation Instructions
RS-232/USB Serial Interface Module: Installation Instructions
Installation Instructions
RS-232/USB Serial
EN Interface Module
DX4010V2 | Installation Instructions | Trademarks
Trademarks
• BlackBox® is either a registered trademark or a
trademark of BlackBox Corporation in the United
States and/or other countries.
Contents
1.0 General Information ....................................4
2.0 Specifications ..............................................4
3.0 Installation Standards .................................4
4.0 Wiring........................................................... 5
5.0 DX4010V2 Jumper Pin Settings ................ 6
5.1 Enable LED Jumper Pins (P2) ..................... 6
5.2 DB9 Ground Enable Pins (P1) ..................... 6
5.3 Address DIP Switches.................................. 7
6.0 Remote Programming Direct Connection 7
7.0 DB9 DTE RS-232 Connector (P6) ............ 10
8.0 RJ-16 Data Bus Connector (P3) .............. 11
9.0 USB Data Bus Connector ........................ 11
9.1 Installing USB Drivers ................................ 11
Figures
Figure 1: DX4010V2 Component Layout .............. 4
Figure 2: Control Panel Connections .................... 5
Figure 3: External Power Supply Connections...... 5
Figure 4: Serial Device Connections..................... 5
Figure 5: Parallel Device Connections .................. 6
Figure 6: P2 Jumper Settings ............................... 6
Figure 7: DIP Switch Location and Orientation ..... 7
Figure 8: DB9 Connector Layout ........................ 10
Figure 9: P3 Connector....................................... 11
Figure 10: Select File ............................................ 11
Figure 11: Security Warning ................................. 11
Figure 12: Install Shield ........................................ 11
Figure 13: Security Warning ................................. 11
Figure 14: Destination Location ............................ 12
Figure 15: Ready to Install .................................... 12
Figure 16: Setup Status ........................................ 12
Figure 17: Installation Complete ........................... 12
Figure 18: USB Driver Installer ............................. 12
Figure 19: Scanning.............................................. 12
Figure 20: Installation Complete ........................... 12
Figure 21: System Properties ............................... 13
Figure 22: Device Manager................................... 13
Figure 23: Panel Communication.......................... 13
Tables
Table 1: DX4010V2 Specifications ...................... 4
Table 2: Diagnostic LED Functions ..................... 6
Table 3: Option Bus Address DIP Switch Settings8
Table 4: SDI Bus Address DIP Switch Settings ... 9
Table 5: Alternate Wiring Configuration ............. 10
instructions.
1
The baud rate for the printer output on a 1- DB9 GND enable pins (P1)
DS7400Xi must be greater than 300 baud. 2- RJ-16 data bus connector (P3)
3- Data bus (TS1)
Operating 0°C to +50°C (+32°F to +122°F)
Temperature
4- Address DIP switches (S1)
Relative 5 to 85% @ +30°C (+86°F) 5- Diagnostic LEDs
Humidity non-condensing 6- Diagnostic LED enable pins (P2)
Control Panel Option bus control panels: D6412, 7- USB Connector (P7)
Compatibility D4412, DS7240, DS7220, DS7400Xi 8- DB9 DTE RS-232 connector (P6)
(v2.02 or higher)
SDI bus control panels (v6.0 or
higher): D9412GV2, D7412GV2, 3.0 Installation Procedure
D7212GV2, D9412G, D7412G,
D7212G, D9124, D9112, D7412, and Failure to follow the instructions in this
D7212 manual can result in personal injury or
damage to the equipment.
4.0 Wiring + -
Remove all power to the control panel (AC 7
and standby battery) before making or
breaking any connections. Failure to do so 1- DX4010V2 data bus
can result in personal injury or damage to 2- Control panel data bus
the equipment.
3- Option AUX common/SDI common (black)
Wire Length Restrictions 4- Option data/SDI B (green)
• 0.8 mm (#22 AWG): 305 m (1000 ft) 5- Option data/SDI A (yellow)
• 1.2 mm (#18 AWG): 610 m (2000 ft) 6- Option AUX power +/SDI power (red)
7- External 12 VDC power supply
• USB or Serial Cables are not to exceed 2 meters
(6 ft) in length. Figure 4 shows serial device-to-DX4010V2
connections using the DB9 DTE RS-232 connector
SDI option bus wiring is limited to 305 m (P6).
(1000 ft).
Figure 4: Serial Device Connections
Connect the DX4010V2 to the control panel data and LED
1 2
B 3
P1
DB9 GND
P3 ENABLE
G 4
1
Y 5
1- Serial (RS-232) device such as a PC (with
R 6 RPS, BIS, PC9000, or other third party
application) or a serial printer for supported
1- DX4010V2 data bus control panels.
2- Control panel data bus
3- Option AUX common/SDI common (black) Refer to Section 7.0 DB9 DTE RS-232
Connector (P6) on page 10 for additional
4- Option data/SDI B (green)
information.
5- Option data/SDI A (yellow)
6- Option AUX power +/SDI power (red)
If an external 12 VDC power supply is used, wire as
shown in Figure 3.
Rx Tx Tx Rx
BUS SER
P2
Rx Tx Tx Rx
BUS SER
P2
P1
DB9 GND
ENABLE
1
P3
P1
DB9 GND
P3 ENABLE
2 3 4
1 1- DB9 GND enable pins (P1)
2- Diagnostic LED enable pins (P2)
3- Disabled
Printers are not supported on the USB 4- Enabled
bus.
1- Parallel converter cable box (BlackBox P/N:
Table 2: Diagnostic LED Functions
PI045A
2- Parallel printer (compatible option bus control
panels only) Diagnostic Function
LED
5.0 DX4010V2 Jumper Pin BUS RX Data bus receives data from control
panel
Settings BUS TX Data bus transmits data to control
panel
5.1 Enable LED Jumper Pins (P2) SER RX RS-232 receives data from serial
Use the diagnostic LEDs for troubleshooting. To device
enable the LEDs, place a jumper plug across the SER TX RS-232 transmits data to serial device
jumper pins labeled P2.
Refer to Figure 6 for jumper pin settings. 5.2 DB9 Ground Enable Pins (P1)
The DX4010V2 draws more current when Some devices connected to the DB9 DTE RS-232
the diagnostic LEDs are enabled. Do not connector (P6) can cause a ground fault condition on
enable the diagnostic LEDs under normal the control panel. If this occurs, removing the plug
operating conditions. across the P1 jumper pins clears the ground fault
condition.
Some devices might still cause a ground
fault even if the P1 jumper plug is
removed.
ON
4
3
1 2 3 4 5 6 7 8
1 2 4 8 16 32 64 128
Some automation software packages might require that you restart the application if USB
connection is lost during use.
DIP Switch Settings
DIP S1 S2 S3 S4 S5 S6 S7 S8
Switches
Module 1 2 4 8 16 32 64 128
Address (Mode) (Option/SDI) (Checksum +1)
0* ON ON ON ON ON OFF ON OFF
1 OFF ON ON ON ON OFF ON OFF
2 ON OFF ON ON ON OFF ON OFF
3 OFF OFF ON ON ON OFF ON OFF
4 ON ON OFF ON ON OFF ON OFF
5 OFF ON OFF ON ON OFF ON OFF
6 ON OFF OFF ON ON OFF ON OFF
7 OFF OFF OFF ON ON OFF ON OFF
8 ON ON ON OFF ON OFF ON OFF
9 OFF ON ON OFF ON OFF ON OFF
10 ON OFF ON OFF ON OFF ON OFF
11 OFF OFF ON OFF ON OFF ON OFF
12 ON ON OFF OFF ON OFF ON OFF
13** OFF ON OFF OFF ON OFF ON OFF
14** ON OFF OFF OFF ON OFF ON OFF
15 OFF OFF OFF OFF ON OFF ON OFF
134 ON ON OFF ON ON ON ON ON
135 OFF ON OFF ON ON ON ON ON
136 ON OFF OFF ON ON ON ON ON
137 OFF OFF OFF ON ON ON ON ON
138 ON ON ON OFF ON ON ON ON
139 OFF ON ON OFF ON ON ON ON
140 ON OFF ON OFF ON ON ON ON
141 OFF OFF ON OFF ON ON ON ON
142 ON ON OFF OFF ON ON ON ON
143 OFF ON OFF OFF ON ON ON ON
144 ON OFF OFF OFF ON ON ON ON
145 OFF OFF OFF OFF ON ON ON ON
250 ON ON ON ON ON ON ON ON
251 OFF ON ON ON ON ON ON ON
252 ON OFF ON ON ON ON ON ON
253 OFF OFF ON ON ON ON ON ON
* Installer’s mode: Use for direct connection of remote programming and diagnostic tools.
** DS7412 emulation
The DS7400Xi (USA) only supports one DX4010V2.
Option bus control panels: D6412, D4412, DS7240, DS7220, DS7400Xi (v2.02 or higher).
SDI bus control panels (v6.0 or higher): D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G,
D7212G, D9124, D9112, D7412, and D7212.
2. Click Run.
8.0 RJ-16 Data Bus Figure 11: Security Warning
Connector (P3)
Figure 9: P3 Connector
LED
Rx Tx Tx Rx
BUS SER
P2
1 DB9 GND
P1
P3 ENABLE
Figure 10: Select File 4. Click I accept the terms of the license
agreement. Then click Next.
Figure 13: Security Warning
5. Click Next to accept the default location. 8. Select Launch the CP210x VCP Driver
Installer, then click Finish.
Figure 14: Destination Location
Figure 17: Installation Complete
6. Click Install.
Figure 15: Ready to Install 9. Click Install.
Figure 18: USB Driver Installer