Sepam Series 80 NPP - 59735

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Product data sheet

Specifications

transformer - T87 - Sepam series 80


59735

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Relay application Transformer

Range of product Sepam series 80


Sepam series 80 NPP

Device short name T87

Control and monitoring type Circuit breaker/contactor control ANSI code: 94/69 (option)
Latching/acknowledgement ANSI code: 86
Logic discrimination ANSI code: 68 (option)
Switching of groups of settings
Annunciation ANSI code: 30
Automatic transfer (AT) (option)
Logipam programming (ladder language) (option)
Logic equation editor 200 operators

Metering type Positive sequence voltage Vd/rotation direction


Frequency
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option)
Phase current I1, I2, I3 RMS
Demand current I1, I2, I3
Peak demand current IM1, IM2, IM3
Measured residual current I'0
Voltage U21, U32, U13, V1, V2, V3
Residual voltage V0
Negative sequence voltage Vi
Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Peak demand power PM, QM
Power factor
Temperature (16 RTDs) (option)
Phase current I'1, I'2, I'3 RMS
Measured residual current I0, calculated I'0∑
Calculated residual current I'0∑

Network and machine diagnosis Unbalance ratio/negative sequence current Ii


type Disturbance recording
Thermal capacity used
Remaining operating time before overload tripping
Waiting time after overload tripping
Running hours counter/operating time
Tripping context
Phase fault and earth fault trip counters
Harmonic distortion (THD), current and voltage Ithd, Uthd
Difference in amplitude, frequency and phase of voltages with synchro-check option
Apparent positive sequence impedance Zd
Apparent phase-to-phase impedances Z21, Z32, Z13
Differential current Idiff1, idiff2, Idiff3
Through current It1, It2, It3
Current phase displacement θ
Phase displacement
Datalog (DLG)

Switchgear diagnosis type Cumulative breaking current


CT/VT supervision ANSI code: 60FL
Trip circuit supervision ANSI code: 74 (option)
Auxiliary power supply monitoring
Nb of operations, operating time, charging time, nb of racking out operations (option)

Aug 25, 2022 1


Complementary
Type of measurement Temperature
Power factor
Frequency
Voltage
Current
Energy
Peak demand power
Harmonic distorsion (I THD & U THD)
Power (P,Q)

Protection type Thermostat / buchholz ANSI code: 26/63 (option)


Neutral voltage displacement ANSI code: 59N
Breaker failure ANSI code: 50BF
Directional earth fault ANSI code: 67N/67NC
Directional phase overcurrent ANSI code: 67
Synchro-check ANSI code: 25 (option)
Overvoltage (L-L or L-N) ANSI code: 59
Temperature monitoring (16 RTDs) ANSI code: 38/49T (option)
Thermal overload for machines ANSI code: 49RMS
Restricted earth fault ANSI code: 64REF
Overfluxing (V/Hz) ANSI code: 24
Two-winding transformer differential ANSI code: 87T
Negative sequence/unbalance ANSI code: 46
Overfrequency ANSI code: 81H
Underfrequency ANSI code: 81L
Positive sequence undercurrent ANSI code: 27D
Remanent undervoltage ANSI code: 27R
Undervoltage (L-L or L-N) ANSI code: 27
Negative sequence overvoltage ANSI code: 47
Phase overcurrent ANSI code: 50/51
Earth fault/sensitive earth fault ANSI code: 50N/51N
Earth fault/sensitive earth fault ANSI code: 50G/51G
Directional active overpower ANSI code: 32P

Communication port protocol Measurement readout ( option ) : Modbus


Remote indication and time tagging of events ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Transfer of disturbance recording data ( option ) : Modbus

Input output max capacity 42 inputs + 23 outputs

Communication compatibility DNP3


IEC 61850
IEC 61850 goose message
Modbus RTU
Modbus TCPIP
IEC 60870-5-103

User machine interface type Remote


Mimic-based
Advanced
Without

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Weight 1.0 g

Package 1 Height 0.1 cm

Package 1 width 0.1 cm

Package 1 Length 0.2 cm

Offer Sustainability
REACh Regulation REACh Declaration

EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)


EU RoHS Declaration

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration

2