Steel Joist Intro
Steel Joist Intro
Steel Joist Intro
CONTENTS
1994 Revisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Membership . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Steel Joist Institute Publications . . . . . . . . . . . . . . . . . . . 4 LRFD - Load and Resistance Factor Conversion. . . . . . 5 Fire Resistance Ratings with Steel Joists. . . . . . . . . . . . 6
K-SERIES
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Top Chord Extensions and Extended Ends . . . . . . . . . 11 STANDARD SPECIFICATIONS Section 1. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2. Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3. Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 4. Design and Manufacture. . . . . . . . . . . . . . . 15 5. Application . . . . . . . . . . . . . . . . . . . . . . . . . 19 6. Erection Stability and Handling . . . . . . . . . . 22 Definition of Span - U.S. Customary Units . . . . . . . . . . 23 K Load Table - U. S. Customary Units . . . . . . . . . . . . 24 KCS Joist Specifications and Example . . . . . . . . . . . . 28 Load Table - U. S. Customary Units . . . . . . 30 Load Table - Metric Units . . . . . . . . . . . . . . 31 K- Economy Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Definition of Span - Metric Units. . . . . . . . . . . . . . . . . . 37 K- Load Table - Metric Units. . . . . . . . . . . . . . . . . . . . . 38
JOIST GIRDERS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 STANDARD SPECIFICATIONS Section 1000. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . 67 1001. Definition . . . . . . . . . . . . . . . . . . . . . . . . 67 1002. Materials . . . . . . . . . . . . . . . . . . . . . . . . 67 1003. Design and Manufacture. . . . . . . . . . . . 68 1004. Application . . . . . . . . . . . . . . . . . . . . . . 71 1005. Handling and Erection. . . . . . . . . . . . . . 72 1006. How to Specify Joist Girders . . . . . . . . . 73 Weight Tables - U. S. Customary Units . . . . . 74 Weight Tables - Metric Units . . . . . . . . . . . . . . 81 RECOMMENDED CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS Section 1. General. . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 2. Joists and Accessories . . . . . . . . . . . . . . . . 87 3. Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 4. Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . 90 5. Estimating. . . . . . . . . . . . . . . . . . . . . . . . . . 90 6. Plans and Specifications. . . . . . . . . . . . . . . 94 7. Handling and Erection . . . . . . . . . . . . . . . . 95 8. Business Relations . . . . . . . . . . . . . . . . . . . 95
1994
794-11.8M
OPEN WEB, LONGSPAN, AND DEEP LONGSPAN STEEL JOISTS, AND JOIST GIRDERS 1994 REVISIONS
Page
3 4 5 6 13 14 20 20 22 24 28 32 37 38 44 50 51 52 54 57 59 63 67 74 80 81 89 89 93
Section
General History Publications LRFD Fire-Resistance Ratings Top Chord Extensions Section 3.1 Section 5.4(b) Section 5.4(b) Section 6 K - Load Table KCS Joists K - Economy Table K-Series K-Series Metric Load Table Section 102.1 Section 104.5(c) Section 104.5(d) Section 105 LH Load Table DLH Load Table LH Metric Load Table DLH Metric Load Table Section 1002. Joist Girder Weight Table Joist Girder Metric Design example Joist Girder Metric weight table Section 2.5(b) Section 2.5(c) Section 5.5
Change
Added Metric Nomenclature Added 1994 paragraph Revised Pricing. New Revised Stress limitations & revised some fire resistance ratings Added Metric Load Tables for Type S and Type R extensions. Added ASTM A529 Steel, deleted A441 Revised notes in bridging table referencing bolted diagonal (stability) bridging. Added metric bridging table. Revised erection stability requirements Shading added to depict erection stability requirements. New section with Load Tables Shading added to depict erection stability requirements. Definition of span - metric New Added ASTM A529 Steel, deleted A441 Revised erection stability requirements Revised bridging spacing table 104.5.1 Revised erection stability requirements Shading added to depict erection stability requirements. Formula for IJ added to notes preceding the table. Shading added to depict erection stability requirements. Formula for IJ added to notes preceding the table. New New Added ASTM A529 Steel, deleted A441. Added heavy black line indicating 71 2 inch depth bearing seats. New New Revised erection stability requirements and new tables 2.5.1(a) and 2.5.1(b) added. New table 2.5.2 added. Special joist design example using metric units.
OPEN WEB, LONGSPAN, AND DEEP LONGSPAN STEEL JOISTS, AND JOIST GIRDERS HISTORY
Formed five years after the first open web steel joist was manufactured, the Institute has worked since 1928 to maintain sound engineering practice throughout our industry. As a non-profit organization of active manufacturers, the Institute cooperates with governmental and business agencies to establish steel joist standards. Continuing research and updating are included in its work. The first joist in 1923 was a Warren truss type, with top and bottom chords of round bars and a web formed from a single continuous bent bar. Various other types were developed, but problems also followed because each manufacturer had his own design and fabrication standards. Architects, engineers and builders found it difficult to compare rated capacities and to use fully the economies of steel joist construction. Members of the industry began to organize the Institute, and in 1928 the first standard specifications were adopted, followed in 1929 by the first load table. The joists covered by these early standards were later identified as open web steel joists, SJ-Series. Other landmark adoptions by the Institute include the following: 1953 Introduction of Longspan Steel Joists, L-Series. Specifications and a standard load table, covering spans through 96 feet and depths through 48 inches, were jointly approved with the American Institute of Steel Construction. 1959 Introduction of the S-Series Joists, which replaced the SJ- Series Joists. The allowable tensile stress was increased from 18,000 to 20,000 psi, joist depths were expanded through 24 inches, and spans increased through 48 feet. 1961 (a) Introduction of the J-Series Joists, which replaced the S-Series Joists. The allowable tensile stress was increased from 20,000 psi to 22,000 psi, based on the use of steel with a minimum yield strength of 36,000 psi. (b) Introduction of the LA-Series Joists, which replaced the L-Series Joists. The LA-Series Joists allowed a tensile stress of either 20,000 psi or 22,000 psi, depending on the yield strength of the steel. (c) Introduction of the H-Series Joists, whose design was based on steel with a minimum yield strength of 50,000 psi, and an allowable tensile stress of 30,000 psi. 1962 Introduction of the LH-Series Joists, utilizing steel whose minimum yield strength was between 36,000 psi and 50,000 psi. 1965 Development of a single specification for both the J- and H- Series Joists by the Steel Joist Institute and the American Institute of Steel Construction. 1966 Development and introduction by the SJI and AISC of the LJ- Series Joists, which replaced the LA-Series Joists. Also, the development of a single specification for both the LJ- and the LH-Series Joists, with the use of 36,000 psi minimum yield strength steel for the LJ-Series, and 36,000 psi to 50,000 psi minimum yield strength steel for the LH-Series. 1970 Introduction of the DLJ- and DLH-Series Joists to include depths through 72 inches and spans through 144 feet. 1971 Elimination of the number 2 chord sizes and the addition of joist designations 8J3 and 8H3 to the load tables. 1972 (a) Adoption by the SJI and AISC of a single specification for the LJ-, LH-, DLJ-, and DLH-Series Joists. (b) Adoption by the SJI and AISC of the expanded specifications and load tables for the Open Web Steel Joists which increased the depths through 30 inches, and the spans through 60 feet, plus adding chord sections 9, 10, & 11. 1978 (a) Elimination of the J-, LJ-, and DLJ-Series Joists because of the widespread acceptance of high strength steel joists. (b) Introduction of Joist Girders, complete with specifications and weight tables, in response to the growing need for longer span primary structural members with highly efficient use of steel. 1986 Introduction of the K-Series Joists, which replaced the H-Series Joists. The reasons for developing the K-Series Joists were (1) to achieve greater economies by utilizing the Load Span design concept; (2) To meet the demand for roofs with lighter loads at depths from 18 inches to 30 inches; (3) To offer joists whose load carrying capacities at frequently used spans are those most commonly required; (4) To eliminate the very heavy joists in medium depths for which there was little, if any, demand. 1994 (a) Introduced the KCS Joists to the K-Series in response to the need for a joist with a constant moment and constant shear. The KCS Joist is an alternative joist to be used in special loading conditions. (b) Addition of metric nomenclature for all Joist
OPEN WEB, LONGSPAN, AND DEEP LONGSPAN STEEL JOISTS, AND JOIST GIRDERS
and Joist Girder Series in compliance with government and industry standards. (c) Addition of revised stability criteria. RESPONSIBILITY FOR PRODUCT QUALITY The plant inspections are not a guaranty of the quality of any specific joists or Joist Girders; this responsibility lies fully and solely with the individual manufacturer. SERVICES TO NONMEMBERS The Institutes facilities for checking the design of K-, LH-, and DLH-Series Joists or Joist Girders are available on a cost basis. The Steel Joist Institute does not check joist designs for specific construction projects. Fabrication to Institute Specifications is the responsibility of the individual manufacturer.
POLICY
The manufacturers of any standard SJI Products shall be required to submit design data for verification of compliance with Steel Joist Institute Specifications, undergo physical design verification tests (on K-Series only), and undergo periodic in-plant inspections for all products on which they wish to become certified. SJI Member Companies complying with the above conditions shall be licensed to publish the appropriate copy-righted SJI Specifications and Load Tables.
MEMBERSHIP
Open to manufacturers who produce, on a continuing basis, joists of the K-, LH/DLH-Series, and/or Joist Girders, conforming to the Institutes Specifications and Load Tables. Membership requirements differ as described below. APPLICANTS BASED ON K-SERIES JOISTS The Institutes Consulting Engineer checks to see that designs conform to the Institutes Specifications and Load Tables. This comprises an examination of: (1) Complete engineering design details and calculations of all K-Series joists, bridging and accessories for which standards have been adopted; (2) Data obtained from physical tests of a limited number of joists, conducted by an independent laboratory, to verify conclusions from analysis of the applicants engineering design details and calculations. An initial plant inspection and subsequent periodic inspections are required to ensure that the applicant/member possesses the facilities, equipment and personnel required to fabricate properly the K-Series Joists. Joist manufacturers who have previously obtained certification on their H-Series Joists are required to obtain certification on their K-Series design data. Physical tests are required only if substantive changes are made in either joist configuration or member shapes. APPLICANTS BASED ON LH- OR DLH-SERIES JOISTS OR JOIST GIRDERS Designs are checked by the Consulting Engineer. Periodic in-plant inspections (but no physical tests) are required.
The following method may be used to convert the Steel Joist Institutes Specifications for use in Load and Resistance Factor Design ( LRFD )
Method: WU = 1.65 Wsji, or Wsji = WU /1.65
Where, WU = ultimate joist capacity Wsji = SJI Load Table Load (black figure) Load tables for LRFD can be obtained directly from the current SJI Load Tables by using the formula: Wn = Wsji x 0.9 x 1.65 Where, Wn = nominal joist capacity 0.9 = Resistance Factor ( ) K Series Example: Given: WU = 1.2 WD + 1.6 WL Problem: Select a joist from the current load tables for Wsji Wu/1.65( ) L = 40 ft. WD = 50 plf WL = 150 plf Use Roof Live load deflection L/240 WU = 1.2 x 50 + 1.6 x 150 = 300 plf Wsji 300/(1.65 x 0.9) = 202 plf Select 22K6: Wsji @ 40 ft. span = 207 plf > 202 plf. OK Deflection Live Load L/240 WsjiLL = 1.5 x 111 = 166 plf > 150 plf OK The above procedure outlines the specification of a K Series Joist to support a uniform gravity load utilizing LRFD. When loads other than uniform gravity loads (such as wind uplift loads, concentrated loads, end moments or non-uniform loads) are a design consideration, the Specifying Professional shall clearly indicate on the structural drawings whether these loads are factored or unfactored. To remain consistent with established LRFD design procedures it is recommended that factored loads be specified. The above procedure is also applicable to the LH/DLH Series Joists and Joist Girders.
Concrete Restrained Assembly Rating Type of Protection System Thickness Above Deck 2 1/2 1 Hr. Exposed Grid 2 1/2 Exposed Grid 1 1/2 Hr. Gypsum Brd. Cementitious Sprayed Fiber Concealed Grid 2 1/2 2 2 1/2 2 2 1/2 2 1/2 2 1/4 2 1/2 2 1/2 2 1/2 2 1/2 Exposed Grid 2 1/2 2 1/2 2 1/2 2 1/2 2 Hr. Gypsum Board 2 1/2 2 1/2 2 1/2 Cementitious Sprayed Fiber Concealed Grid 2 1/2 2 1/2 3 1/2 3 1/4 3 1/2 3 1/4 3 Hr. Exposed Grid 3 1/2 NW LW NW NW LW NW LW NW NW NW NW NW NW 10K1 10K1 12K1 16K6 Min. 3/4 dia. web 16K6 Min. 3/4 dia. web 10K1 10K1 10K1 10K1 10K1 48 48 Unrestricted Unrestricted Unrestricted 48 48 48 48 72 2 2 1/2 NW NW NW NW NW LW NW LW NW NW NW NW NW NW NW NW NW NW NW NW 12K1,18LH02 10K1 10K1 10K1 12K1 16K6 Min. 3/4 dia. web 16K6 Min. 3/4 dia. web 10K1 8K1,10K1 10K1 10K1 10K1 10K1 10K1 10K1 12K1,18LH02 10K1 10K1 Unrestricted 48 48 48 48 Unrestricted Unrestricted 48 48 48 48 48 48 48 48 Unrestricted 48 48 Minimum Joist Size See Note #3 & #4 10K1 Maximum Joist Spacing See Note #2 72
Type NW
Primary Support Member Min. Depth & Wt. See Note #3 20g @14.0 plf. Min. Area Top & Bottom Chord 1.12 Sq. Inch 20G @13.0 plf. 20G @13.0 plf. 20g @13.0 plf. 20G @20.0 plf. 20G @20.0 plf. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. W6x12 W8x31 20G @13.0 plf. 20G @13.0 plf. 20G @14.0 plf. Min. Area Top & Bottom Chord 1.12 Sq. inch 20G @13.0 plf. 20G @13.0 plf. 20G @20.0 plf. 20G @20.0 plf. 20G @20.0 plf. 20G @13.0 plf. 20G @13.0 plf. W6x12 20G @13.0 plf. 20G @14.0 plf. Min. Area Top & Bottom Chord 1.12 Sq. inch 20G @13.0 plf. 20G @13.0 plf.
D216 G228 G229 G243 G502 G701 G801 G023 G031 G036 G213 G227 G228 G243 G256 D216 G505 G514
G253 G529 D502 D701 D801 G033 G036 G213 G229 G256
NW NW LW, NW
Unrestricted 48 48
Built Up Roof Restrained Assembly Rating Type of Protection System Type of Insulation Minimum Metal Deck Joist Size Min. Size See Note #3 & #4 26 Ga. 22 Ga. 28 Ga. Exposed Grid Rigid Insulation 26 Ga. 24,22 Ga. 26,24,22 Ga. 24 Ga. 26 Ga. 26 Ga. 22 Ga. 26,22Ga. Insulating Fill 28 Ga. 28,26 Ga. 28 Ga. 28,26 GA. Gypsum Insulating Fill Rigid Insulation Exposed Grid 26 Ga. 24 Ga. 26,24,22GA. 24 Ga. 26 Ga. Insulating Fill Rigid Insulation Insulating Fill Rigid Insulation Rigid Insulation Rigid Insulation Insulating Fill 26,22 Ga. 28,26 Ga. 22 Ga. 18,16 Ga. 24 Ga. 22 Ga. 22 Ga. 28,22 Ga. 10K1 12K3 12K3 12K1 12K1 12K1 12K3 12K3 12K5 or 14K4 10K1 12K1 10K1 12K1 10K1 12K1 12K3 12K3 12K1 12K3 12K5, 14K4 12K1 12K1 12K5 14k3 12K1 10K1 12K5,14K3 10K1 10K1 Maximum Joist Spacing
Primary Support Member Min. Depth & Wt. See Note #3 20G @20.00 plf. 20G @13.0 plf. or W8x18 20G @13.0 plf. 20G @13.0 plf. W6x12 W6x12 20G @14.0 plf. 20G @13.0 plf. 20G @13.0 plf. W8x15 20g @13.0 plf. W8x24 20G @13.0 plf. W6x12 20G @14.0 plf. 20G @13.0 plf. 20G @13.0 plf. W6x12
U.L. Design Number P211 P214 P224 P225 P227 P230 P250 P254 P231 P246 P251 P255 P261 P509 P225 P227 P250 P231 P251 P404 P251 P237 P404 P514 P405
48 72 48 60 72 72 48 72 48 48 72 72 72 72 72 48 60 72 48 48 72 72 72 72 72 72 48 48
1 Hr.
1 1/2 Hr.
3 Hr.
Metal Lathe
Built Up Roof Restrained Assembly Rating Type of Protection System Type of Insulation Rigid Insulation Minimum Metal Deck Joist Size Min. Size See Note #3 & #4 22 Ga. 22 Ga. 22 Ga 1 Hr. 1 1/2 Hr. 2 Hr. Sprayed Fiber Rigid Insulation 22 Ga 22 Ga. 22 Ga. 22 Ga. 22 Ga. Cementitious and Sprayed Fiber 24 Ga. Insulating Fill 28 Ga. 24 Ga. 24 Ga. 22 Ga 14K4 or LH 14K4 16K6 10K1 12K3 12K3 12K1 14K4 12K5, 14K3 12K5, 14K3 12K5 12K3 12K3 Maximum Joist Spacing See Note #5 Unrestricted Unrestricted Unrestricted Unrestricted Unrestricted Unrestricted Unrestricted 96" 96" 96" 96" 96" 96" Primary Support Member Min. Depth & Wt. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. 20G @13.0 plf. U.L. Design Number P701 P711 P801 P815 P816 P817 P818 P902 P907 P920 P921 P922 P923
Cementitious
NOTES: 1. The UNDERWRITERS LABORATORY FIRE RESISTANCE DIRECTORY lists hundreds of assemblies and their fire ratings. As a convenience a selected number of assemblies are listed on 3 preceding pages. This listing is intended as a guide only and the specifying professional must refer to the U.L. Directory for complete design information. 2. The maximum joist spacing shown for FloorCeiling Assemblies may be increased from the spacing listed in the U.L. Directory to a maximum of 48 inches on center, provided the floor slab meets the structural requirements and the spacing of hanger wires supporting the ceiling is not increased. 3. Some U.L. Design Assemblies stipulate minimum size materials for Steel Joist and Joist Girder components, and/or bridging. It is the responsibility of the specifying professional to show all special requirements on the Structural Drawings. 4. Some U.L. Fire Assembly Designs stipulate an allowable maximum joist design stress level less than the 30 ksi (207MPa) used in the K-Series Joist Specifications. It is the responsibility of the specifying professional to apply the proper stress level reductions (if required) when selecting Joists and/or Joist Girders. To adjust the stress level of K-Series Joists or Joist Girders multiply the design load by the required factor [30/26 (207/179), 30/24 (207/165), 30/22 (207/1520)], and then using this increased load select a Joist or Joist Girder from the load and/or weight tables. 5. Some U.L. Roof-Ceiling Design assemblies using direct applied protection limit the spacing of the joists for certain types and gages of metal decking refer to the U.L. Directory for this information.