IOM3721 Input/Output Module: Installation Instructions
IOM3721 Input/Output Module: Installation Instructions
Installation Instructions
MS-IOM3721-0 Part No. 24-10144-130, Rev. A
Release 5.1
Issued May 25, 2011
Supersedes March 11, 2011
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications Canada
The IOM37 Series Input/Output Module (IOM)
This Class (A) digital apparatus meets all the
controllers are part of the Metasys® system Field
requirements of the Canadian Interference-Causing
Equipment Controller (FEC) family. IOMs expand the
Equipment Regulations.
number of inputs and outputs points connected to
Network Automation Engines (NAEs), Network Control Cet appareil numérique de la Classe (A) respecte
Engines (NCEs), and FECs to monitor and control a toutes les exigences du Règlement sur le matériel
wide variety of Heating, Ventilating, and Air brouilleur du Canada.
Conditioning (HVAC) applications.
Installation
The IOMs operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus and Observe these guidelines when installing an IOM:
integrate into the Web-based Metasys system. • Transport the IOM in the original container to
minimize vibration and shock damage.
IMPORTANT: In Metasys system smoke control
applications, use only the MS-IOM3710-0U model • Verify that all parts shipped with the IOM.
that is UL Listed, UUKL 864 Listed, Smoke Control
• Do not drop the IOM or subject it to physical shock.
Equipment. For Metasys system smoke control
applications, you must refer to the Metasys System Parts Included
UL 864 UUKL Ninth Edition Smoke Control System • one IOM3721 controller with removable terminal
Technical Bulletin (LIT-12011252) for detailed blocks
requirements and procedures for installing and
operating UUKL 864 Listed Metasys system • one installation instructions sheet
devices. Failure to meet the requirements or follow Materials and Special Tools Needed
the procedures in the Metasys System UL 864
• three fasteners appropriate for the mounting
UUKL Ninth Edition Smoke Control System
surface (M4 screws or #8 screws)
Technical Bulletin (LIT-12011252) can void the
UUKL 864 listing for Smoke Control Equipment. • one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
North American Emissions Compliance • small straight blade screwdriver for securing wires
United States in the terminal blocks
FIG:fec_iom_164mm_back_dims
electromagnetic emissions from other devices or (5-7/8)
wiring can interfere with controller communication.
On panel or enclosure mount applications, observe
these additional guidelines:
52 59 52
• Do not install the IOM in an airtight enclosure. (2-1/16) (2-5/16) (2-1/16)
• Mount the IOM so that the enclosure walls do not Figure 2: Back of IOM37 Series Controller
obstruct cover removal or ventilation through the Showing Extended Mounting Clips, DIN Rail
controller. Channel, and Mounting Dimensions, mm (in.)
• Mount the IOM so that the power transformer and
To remove the IOM from the DIN rail, pull the bottom
other devices do not radiate excessive heat to the
mounting clips out to the extended position and
controller.
carefully lift the controller off the DIN rail.
Wall Mount Applications
To mount an IOM directly on a wall (or other flat vertical
surface):
FIG:fec_iom_164mm_mount_positions
3 3
IN11
ICOM11
IN9
ICOM9
IN10
ICOM10
IN12
ICOM12
IN13
ICOM13
IN14
ICOM14
IN15
ICOM15
IN16
ICOM16
COM
HOT
BINARY INPUT ADDRESS 24V~
8 POWER
FAULT
SA/FC BUS
EOL
IOM
7 IOM3721
BINARY INPUT
FIG:iom3721_features
ICOM1
ICOM2
ICOM3
ICOM4
ICOM5
ICOM6
ICOM7
ICOM8
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
SHLD PWR
COM
ON SABUS
COM
FCBUS
6 5 4
FIG:sa_bus_terms
IMPORTANT: Electrostatic discharge can damage on SA Bus
on SA Bus
controller components. Use proper electrostatic
SA PWR
SA PWR
discharge precautions during installation, setup, and
COM
COM
servicing to avoid damaging the controller.
+
SA Bus
For detailed information on configuring and wiring an Terminal
Block Plugs Cable Shield
MS/TP Bus, Field Controller (FC) Bus, and Sensor Connection
Actuator (SA) Bus, refer to the MS/TP Communications
Bus Technical Bulletin (LIT-12011034).
To Next To Next
IOM Terminal Blocks and Bus Ports Device on Device on
the SA Bus the SA Bus
See Figure 3 for terminal block and bus port locations
on the IOM3721 controllers. Observe the following Stranded, 4-Wire (2 Twisted Pair) Shielded Cable
guidelines when wiring an IOM. (One twisted pair is the + and - leads.
The second pair is COM and SA PWR.)
SA/FC Bus Terminal Block
Figure 5: SA Bus Terminal Block Wiring
An IOM can be connected to an SA Bus or an FC Bus,
but not to both buses simultaneously. The SA/FC Bus SA/FC Bus Port
terminal block is a removable, 4-terminal plug that fits
into a board-mounted jack. The SA/FC Bus port on the front of the IOM is an
RJ-12, 6-position modular jack that provides a
When connecting the IOM to an FC Bus, wire the bus connection for devices on the SA Bus, a Wireless
terminal block plugs on the IOM, and the other field Commissioning Converter, or a ZFR1811 Wireless
controllers in a daisy-chain configuration using 3-wire Router (depending on the bus the IOM is operating on).
twisted, shielded cable as shown in Figure 4. See
Table 4 for more information. The SA/FC Bus Port is connected internally to the
SA/FC Bus terminal block. See Table 4 for more
When connecting the IOM to an SA Bus, wire the bus information. The SA/FC Bus Port pin assignment is
terminal block plugs on the IOM and other SA Bus shown in Figure 6.
devices in a daisy-chain configuration using 4-wire
twisted, shielded cable as shown in Figure 5. See Sensor, SA Bus, or FC Bus Port
(RJ-12 Modular Jack)
Table 4 for more information.
FIG:rj12_jack_pinout_left
SHLD
SHLD
COM
COM
FIG:fec_iom_power_port
Supply Power The IOM also can be installed in a wireless application
Terminal Block
using a ZFR1811 Wireless Field Bus Router. To
configure a controller for use with the ZFR1800 Series
24V~
Wireless Field Bus system:
Supply Power
1. Wire the input/output terminals.
Terminal Block
Note: In wireless network applications, do not
COM
HOT
Wires from Plug
24 VAC, Class 2 connect any wires to the SA/FC Bus terminal block.
Power Transformer
2. Connect the ZFR1811 Wireless Field Bus Router to
the SA/FC Bus port (RJ-12 modular jack) on the
Brown Wire Orange Wire
(COM) (24 VAC) front of the IOM.
3. Ensure that the IOM device address DIP switches
Figure 7: 24 VAC Supply Power are set to the correct device address. See Setting
Terminal Block Wiring the Device Address.
The supply power wire colors may be different on 4. Position DIP switch 128 On to enable wireless
transformers from other manufacturers. Refer to the operation on the IOM.
transformer manufacturer’s instructions and the project For more information on installing an IOM in a wireless
installation drawings for wiring details. configuration, refer to the ZFR1811 Wireless Field Bus
Router Installation Instructions (Part No. 24-10325-1).
IMPORTANT: Connect 24 VAC supply power to the
IOM and all other network devices so that IOM Terminal Functions, Ratings,
transformer phasing is uniform across the network Requirements, and Wiring Guidelines
devices. Powering network devices with uniform
24 VAC supply power phasing reduces noise, Input and Output Wiring Guidelines
interference, and ground loop problems. The IOM Table 2 provides information and guidelines about the
does not require an earth ground connection. functions, ratings, and requirements for the IOM input
and output terminals; and references guidelines for
Input and Output Terminal Blocks determining proper wire sizes and cable lengths.
The fixed input and output terminal blocks are mounted In addition to the wiring guidelines in Table 2, observe
along the top bottom of the IOM controller (Figure 3). these guidelines when wiring IOM inputs and outputs:
See Table 2 for more information.
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All input and output cables, regardless of wire size
or number of wires, should consist of stranded,
insulated, and twisted copper wires.
• Shielded cable is not required for input or output
cables.
• Shielded cable is recommended for input and
output cables that are exposed to high
electromagnetic or radio frequency noise.
• Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software
setup. Cable runs over 30 m (100 ft) may require
an offset in the input/output software setup.
1. See Table 3 to determine wire size and cable lengths for cables other than the recommended cables.
Length
137.2 m (450 ft)
FIG:wir_lngth
45.7 m (150 ft)
0.6 mm (22 AWG)
30.5 m (100 ft)
N/A (24 AWG )
15.2 m (50 ft)
0 m (0 ft)
0 50 100 150 200 250 300 350 400 450 500
1. See Table 3 to determine wire size and cable lengths for cables other than the recommended cables.
2. The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
32
16
64
1
8
The eighth switch (labeled 128) on the DIP switch block Setting the Bus EOL Switch
is a mode switch that enables or disables the controller The bus EOL switch allows you to set the IOM as a
to operate on a ZFR1800 Series Wireless Field Bus. terminating device on an SA or FC Bus. The default
Set switch 128 off for wired SA or FC bus applications. EOL switch position is Off. If the IOM is a terminating
Set switch 128 ON for wireless FC Bus applications. device (located at the end) on the daisy chain of field
Metasys MS/TP controllers ship from the factory with controllers on an SA Bus or FC Bus segment, set the
switch 128 set to ON and the remaining device address EOL switch to ON (Figure 10). When the EOL switch is
switches off, which renders each controller a wired On and the controller is powered, the amber EOL
slave device out of the box. (Setting switch 128 set to Light-Emitting Diode (LED) is lit. See Figure 3 for the
ON plus setting 1, 2, or 3 also renders the controller a location of the EOL switch on the IOM3721 controller.
wired slave device.) Wired slave devices are not
O O
supported on Metasys MS/TP buses, but if the N N FIG:EOL_Swtch
Technical Specifications
IOM3721 Input/Output Modules
Product Code Numbers MS-IOM3721-0 Input/Output Module
Supply Voltage 24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
Power Consumption 14 VA maximum
Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing
Addressing DIP switch set; valid field controller device addresses 4–127
(Device addresses 0–3 and 128–255 are reserved and not valid IOM addresses.)
Communications Bus BACnet® MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and field controllers
4-wire SA Bus between field controller, network sensors and other sensor/actuator devices,
includes a lead to source 15 VDC supply power (from field controller) to bus devices.
Processor H8SX/166xR Renesas® 32-bit microcontroller
Memory 640 KB Flash Memory and 128 KB Random Access Memory (RAM)
Input and Output IOM3721:
Capabilities 16 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
Terminations Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Mounting Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface with
three integral mounting clips on controller
Housing Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum Rated
Protection Class: IP20 (IEC529)
Dimensions 150 x 164 x 53 mm (5-7/8 x 6-1/2 x 2-1/8 in.) including terminals and mounting clips
(Height x Width x Depth) Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom and front
face of controller for easy cover removal, ventilation and wire terminations.
Weight 0.5 kg (1.1 lb)
Compliance United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: cUL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal
Equipment Industry Canada Compliant, ICES-003
Europe: Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.