0% found this document useful (0 votes)
192 views11 pages

IOM3721 Input/Output Module: Installation Instructions

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
192 views11 pages

IOM3721 Input/Output Module: Installation Instructions

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

IOM3721 Input/Output Module

Installation Instructions
MS-IOM3721-0 Part No. 24-10144-130, Rev. A
Release 5.1
Issued May 25, 2011
Supersedes March 11, 2011
Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications Canada
The IOM37 Series Input/Output Module (IOM)
This Class (A) digital apparatus meets all the
controllers are part of the Metasys® system Field
requirements of the Canadian Interference-Causing
Equipment Controller (FEC) family. IOMs expand the
Equipment Regulations.
number of inputs and outputs points connected to
Network Automation Engines (NAEs), Network Control Cet appareil numérique de la Classe (A) respecte
Engines (NCEs), and FECs to monitor and control a toutes les exigences du Règlement sur le matériel
wide variety of Heating, Ventilating, and Air brouilleur du Canada.
Conditioning (HVAC) applications.
Installation
The IOMs operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus and Observe these guidelines when installing an IOM:
integrate into the Web-based Metasys system. • Transport the IOM in the original container to
minimize vibration and shock damage.
IMPORTANT: In Metasys system smoke control
applications, use only the MS-IOM3710-0U model • Verify that all parts shipped with the IOM.
that is UL Listed, UUKL 864 Listed, Smoke Control
• Do not drop the IOM or subject it to physical shock.
Equipment. For Metasys system smoke control
applications, you must refer to the Metasys System Parts Included
UL 864 UUKL Ninth Edition Smoke Control System • one IOM3721 controller with removable terminal
Technical Bulletin (LIT-12011252) for detailed blocks
requirements and procedures for installing and
operating UUKL 864 Listed Metasys system • one installation instructions sheet
devices. Failure to meet the requirements or follow Materials and Special Tools Needed
the procedures in the Metasys System UL 864
• three fasteners appropriate for the mounting
UUKL Ninth Edition Smoke Control System
surface (M4 screws or #8 screws)
Technical Bulletin (LIT-12011252) can void the
UUKL 864 listing for Smoke Control Equipment. • one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
North American Emissions Compliance • small straight blade screwdriver for securing wires
United States in the terminal blocks

This equipment has been tested and found to Mounting


comply with the limits for a Class A digital device Observe these guidelines when mounting an IOM:
pursuant to Part 15 of the FCC Rules. These limits
• Ensure the mounting surface can support the IOM,
are designed to provide reasonable protection
DIN rail, and any user-supplied enclosure.
against harmful interference when this equipment is
operated in a commercial environment. This • Mount the IOM on 35 mm DIN rail whenever
equipment generates, uses, and can radiate radio possible.
frequency energy and, if not installed and used in
• Mount the IOM in the proper mounting position
accordance with the instruction manual, may cause
(Figure 1).
harmful interference to radio communications.
Operation of this equipment in a residential area is • Mount the IOM on a hard, even surface whenever
likely to cause harmful interference, in which case possible in wall-mount applications.
the user will be required to correct the interference
• Use shims or washers to mount the IOM securely
at his/her own expense.
and evenly on the mounting surface.

IOM3721 Input/Output Module Installation Instructions 1


• Mount the IOM in an area free of corrosive vapors 77 87
(3) (3-7/16)
and observe the Ambient Conditions in the 25 34
(1) (1-5/16)
Technical Specifications section.
• Provide for sufficient space around the IOM for
cable and wire connections, easy cover removal,
and good ventilation through the controller (50 mm 125
[2 in.] minimum on the top, bottom, and front of the (4-15/16)
controllers).
140
• Do not mount the IOM on surfaces prone to (5-1/2)
vibration, such as duct work, or in areas where 150

FIG:fec_iom_164mm_back_dims
electromagnetic emissions from other devices or (5-7/8)
wiring can interfere with controller communication.
On panel or enclosure mount applications, observe
these additional guidelines:
52 59 52
• Do not install the IOM in an airtight enclosure. (2-1/16) (2-5/16) (2-1/16)

• Mount the IOM so that the enclosure walls do not Figure 2: Back of IOM37 Series Controller
obstruct cover removal or ventilation through the Showing Extended Mounting Clips, DIN Rail
controller. Channel, and Mounting Dimensions, mm (in.)
• Mount the IOM so that the power transformer and
To remove the IOM from the DIN rail, pull the bottom
other devices do not radiate excessive heat to the
mounting clips out to the extended position and
controller.
carefully lift the controller off the DIN rail.
Wall Mount Applications
To mount an IOM directly on a wall (or other flat vertical
surface):
FIG:fec_iom_164mm_mount_positions

1. Pull the two bottom mounting clips outward and


ensure they are locked in the extended positions
as shown in Figure 2.
Horizontal Mount Position
Preferred for Wall Mounting Vertical Mount Position 2. Mark the three mounting hole locations on the wall
Required for DIN Rail Mounting Acceptable for Wall Mounting using the dimensions in Figure 2 and one of the
mount positions shown in Figure 1 (or hold the
Figure 1: Controller Mounting Positions controller up to the wall/surface in a proper mount
position and mark the hole locations through the
DIN Rail Mount Applications mounting clips).
DIN rail mounting is the preferred mounting method. 3. Drill holes in the wall at the locations marked in
To mount an IOM on 35 mm DIN rail: Step 2, and insert appropriate wall anchors in all
three holes (if necessary).
1. Securely mount a 20 cm (8 in.) or longer section of
35 mm DIN rail horizontal and centered in the 4. Hold the IOM in place, and insert the screws
desired space so that the controller mounts in the through the mounting clips and into the holes.
horizontal position shown in Figure 1. Carefully tighten all of the screws.
2. Pull the two bottom mounting clips outward to the IMPORTANT: Do not overtighten the mounting
extended position (Figure 2). screws. Overtightening the screws may damage the
3. Hang the controller on the DIN rail by the hooks at mounting clips.
the top of the (DIN rail) channel on the back of the
controller (Figure 2), and position the controller
snugly against the DIN rail.
4. Push the bottom mounting clips inward to secure
the controller on the DIN rail.

2 IOM3721 Input/Output Module Installation Instructions


6 1
2

3 3

IN11

ICOM11
IN9

ICOM9

IN10

ICOM10

IN12

ICOM12

IN13

ICOM13

IN14

ICOM14

IN15

ICOM15

IN16

ICOM16

COM

HOT
BINARY INPUT ADDRESS 24V~

8 POWER
FAULT

SA/FC BUS
EOL
IOM
7 IOM3721
BINARY INPUT

FIG:iom3721_features
ICOM1

ICOM2

ICOM3

ICOM4

ICOM5

ICOM6

ICOM7

ICOM8
IN1

IN2

IN3

IN4

IN5

IN6

IN7

IN8

SHLD PWR
COM
ON SABUS

COM
FCBUS

6 5 4

Figure 3: IOM3721 Controller Physical Features and Wiring Terminals

Table 1: IOM3721 Feature Callouts and Descriptions


Callout Description
1 Device Address DIP Switch Block: (See Setting the Device Address on page 9.)
2 24 VAC, Class 2 Supply Power Terminal Blocks: (See Supply Power Terminal Block on page 4.)
3 Cover Lift Tab: (See Removing the IOM Housing Cover on page 9.)
4 SA Bus or FC Bus Terminal Block: (See SA/FC Bus Terminal Block on page 4.)
5 End-of-Line (EOL) Switch: (See Setting the Bus EOL Switch on page 9.)
6 Binary Input (BI) Terminal Block: Dry Contact Maintained or Pulse Counter/Accumulator Mode
(See IOM Terminal Functions, Ratings, Requirements, and Wiring Guidelines on page 5.)
7 Light-Emitting Diode (LED) Status Indicators: (See Table 6 Status LEDs and Description of LED States on
page 11.)
8 SA/FC Bus Port 6-Pin, RJ-12 Modular Jack: (See SA/FC Bus Port on page 4.)

Wiring IMPORTANT: Do not connect supply power to the


WARNING: Risk of Electric Shock controller before finishing wiring and checking all
Disconnect or isolate all power supplies wiring connections. Short circuits or improperly
! before making electrical connections. connected wires can result in damage to the
controller and void any warranty.
More than one disconnect or isolation
may be required to completely de-
energize equipment. Contact with IMPORTANT: Do not exceed the controller
components carrying hazardous voltage electrical ratings. Exceeding controller electrical
can cause electric shock and may result ratings can result in permanent damage to the
in severe personal injury or death. controller and void any warranty.

IMPORTANT: Use copper conductors only. Make


all wiring in accordance with local, national, and
regional regulations.

IOM3721 Input/Output Module Installation Instructions 3


Terminating Device Daisy Chained Device

FIG:sa_bus_terms
IMPORTANT: Electrostatic discharge can damage on SA Bus
on SA Bus
controller components. Use proper electrostatic

SA PWR

SA PWR
discharge precautions during installation, setup, and

COM

COM
servicing to avoid damaging the controller.

+
SA Bus
For detailed information on configuring and wiring an Terminal
Block Plugs Cable Shield
MS/TP Bus, Field Controller (FC) Bus, and Sensor Connection
Actuator (SA) Bus, refer to the MS/TP Communications
Bus Technical Bulletin (LIT-12011034).
To Next To Next
IOM Terminal Blocks and Bus Ports Device on Device on
the SA Bus the SA Bus
See Figure 3 for terminal block and bus port locations
on the IOM3721 controllers. Observe the following Stranded, 4-Wire (2 Twisted Pair) Shielded Cable
guidelines when wiring an IOM. (One twisted pair is the + and - leads.
The second pair is COM and SA PWR.)
SA/FC Bus Terminal Block
Figure 5: SA Bus Terminal Block Wiring
An IOM can be connected to an SA Bus or an FC Bus,
but not to both buses simultaneously. The SA/FC Bus SA/FC Bus Port
terminal block is a removable, 4-terminal plug that fits
into a board-mounted jack. The SA/FC Bus port on the front of the IOM is an
RJ-12, 6-position modular jack that provides a
When connecting the IOM to an FC Bus, wire the bus connection for devices on the SA Bus, a Wireless
terminal block plugs on the IOM, and the other field Commissioning Converter, or a ZFR1811 Wireless
controllers in a daisy-chain configuration using 3-wire Router (depending on the bus the IOM is operating on).
twisted, shielded cable as shown in Figure 4. See
Table 4 for more information. The SA/FC Bus Port is connected internally to the
SA/FC Bus terminal block. See Table 4 for more
When connecting the IOM to an SA Bus, wire the bus information. The SA/FC Bus Port pin assignment is
terminal block plugs on the IOM and other SA Bus shown in Figure 6.
devices in a daisy-chain configuration using 4-wire
twisted, shielded cable as shown in Figure 5. See Sensor, SA Bus, or FC Bus Port
(RJ-12 Modular Jack)
Table 4 for more information.

Power (15 VDC)


FIG: fc_bus_terms

Terminating Device Daisy Chained Device


on FC Bus Segment on FC Bus Segment 6
Bus and Power Common
5

FIG:rj12_jack_pinout_left
SHLD
SHLD

COM
COM

Power (15 VDC) 4


_
+
_
+

FC Bus Bus and Power Common 3


Terminal 2
Block Plugs SA or FC Bus -
Isolated Shield 1
Connection SA or FC Bus +
Terminal
Figure 6: Pin Number Assignments for
Sensor, SA Bus, and FC Bus Ports on
To Next To Next FEC, IOM, and VMA16
Device on Device on
the FC Bus the FC Bus
Segment Segment
Supply Power Terminal Block
Stranded 3-Wire Twisted Shielded Cable The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a
Figure 4: FC Bus Terminal Block Wiring
board-mounted jack on the top right of the controller.
Note: The IOM’s SA PWR/SHLD terminal does not Wire the 24 VAC supply power wires from the
supply 15 VDC. The SA PWR/SHLD terminal is transformer to the HOT and COM terminals on the
isolated and can be used to connect (daisy chain) the terminal plug as shown in Figure 7. The middle
15 VDC power leads on the SA Bus (Figure 5) or the terminal on the supply power terminal block is not
cable shields on the FC Bus (Figure 4). used. See Table 4 for more information.

4 IOM3721 Input/Output Module Installation Instructions


Wireless Network Applications

FIG:fec_iom_power_port
Supply Power The IOM also can be installed in a wireless application
Terminal Block
using a ZFR1811 Wireless Field Bus Router. To
configure a controller for use with the ZFR1800 Series
24V~
Wireless Field Bus system:

Supply Power
1. Wire the input/output terminals.
Terminal Block
Note: In wireless network applications, do not

COM

HOT
Wires from Plug
24 VAC, Class 2 connect any wires to the SA/FC Bus terminal block.
Power Transformer
2. Connect the ZFR1811 Wireless Field Bus Router to
the SA/FC Bus port (RJ-12 modular jack) on the
Brown Wire Orange Wire
(COM) (24 VAC) front of the IOM.
3. Ensure that the IOM device address DIP switches
Figure 7: 24 VAC Supply Power are set to the correct device address. See Setting
Terminal Block Wiring the Device Address.
The supply power wire colors may be different on 4. Position DIP switch 128 On to enable wireless
transformers from other manufacturers. Refer to the operation on the IOM.
transformer manufacturer’s instructions and the project For more information on installing an IOM in a wireless
installation drawings for wiring details. configuration, refer to the ZFR1811 Wireless Field Bus
Router Installation Instructions (Part No. 24-10325-1).
IMPORTANT: Connect 24 VAC supply power to the
IOM and all other network devices so that IOM Terminal Functions, Ratings,
transformer phasing is uniform across the network Requirements, and Wiring Guidelines
devices. Powering network devices with uniform
24 VAC supply power phasing reduces noise, Input and Output Wiring Guidelines
interference, and ground loop problems. The IOM Table 2 provides information and guidelines about the
does not require an earth ground connection. functions, ratings, and requirements for the IOM input
and output terminals; and references guidelines for
Input and Output Terminal Blocks determining proper wire sizes and cable lengths.
The fixed input and output terminal blocks are mounted In addition to the wiring guidelines in Table 2, observe
along the top bottom of the IOM controller (Figure 3). these guidelines when wiring IOM inputs and outputs:
See Table 2 for more information.
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
• All input and output cables, regardless of wire size
or number of wires, should consist of stranded,
insulated, and twisted copper wires.
• Shielded cable is not required for input or output
cables.
• Shielded cable is recommended for input and
output cables that are exposed to high
electromagnetic or radio frequency noise.
• Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software
setup. Cable runs over 30 m (100 ft) may require
an offset in the input/output software setup.

IOM3721 Input/Output Module Installation Instructions 5


Table 2: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Terminal Function, Ratings, and Requirements Determine Wire Size and
Label Labels Maximum Cable Length1
BINARY INPUT INn Binary Input - Dry Contact Maintained Mode See Guideline A in Table 3.
0.01 second min. pulse width
Internal 18 V, 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V, 3k ohm pull up
ICOMn Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons, except the
Configurable Output (CO) common (OCOMn) when the
CO is defined as an Analog Output.

1. See Table 3 to determine wire size and cable lengths for cables other than the recommended cables.

Table 3 defines cable length guidelines for the various


wire sizes that may be used for input and output wiring.
Table 3: Cable Length Guidelines for Recommended Wire Sizes
Guideline Wire Size/Gauge and Type Maximum Cable Length Assumptions
and Type
A 1.5 mm2 (18 AWG) stranded copper 457 m (1,500 ft) twisted wire 100 mV maximum voltage drop
Depending on the cable length and
0.8 mm (20 AWG) stranded copper 297 m (975 ft) twisted wire
the connected input or output device,
183 m (600 ft) twisted wire you may have to define an offset in
0.6 mm (22 AWG) stranded copper
the setup software for the input or
N/A (24 AWG) stranded copper 107 m (350 ft) twisted wire output point.
B 1.5 mm2 (18 AWG) stranded copper 229 m (750 ft) twisted wire 100 mV maximum voltage drop
Depending on the cable length and
0.8 mm (20 AWG) stranded copper 137 m (450 ft) twisted wire
the connected input or output device,
91 m (300 ft) twisted wire you may have to define an offset in
0.6 mm (22 AWG) stranded copper
the setup software for the input or
N/A (24 AWG) stranded copper 61 m (200 ft) twisted wire output point.
C See Figure 8 to select wire size/gauge. See Figure 8 to determine N/A
Use stranded copper wire. cable length. Use twisted
wire cable.

6 IOM3721 Input/Output Module Installation Instructions


Maximum Cable Length versus Load Current
Use Figure 8 to estimate the maximum cable length
relative to the wire size and the load current (in mA)
when wiring inputs and outputs.

Length
137.2 m (450 ft)

121.9 m (400 ft)

106.7 m (350 ft)


2
1.5 mm (18 AWG)
91.4 m (300 ft)

76.2 m (250 ft)


0.8 mm (20 AWG)
61 m (200 ft)

FIG:wir_lngth
45.7 m (150 ft)
0.6 mm (22 AWG)
30.5 m (100 ft)
N/A (24 AWG )
15.2 m (50 ft)

0 m (0 ft)
0 50 100 150 200 250 300 350 400 450 500

Load Current (mA)

Figure 8: Maximum Wire Length by Current and Wire Size

IOM3721 Input/Output Module Installation Instructions 7


FC/SA Bus and Supply Power Wiring Guidelines • All FC and SA Bus cables, regardless of wire size,
Table 4 provides information about the functions, should be twisted, insulated, stranded copper wire.
ratings, and requirements for the IOM communication • Shielded cable is strongly recommended for all FC
bus and supply power terminals; and references and SA Bus cables.
guidelines for wire sizes, cable types, and cable
lengths when wiring the IOM communication buses and • Refer to the MS/TP Communications Bus
supply power. Technical Bulletin (LIT-12011034) for detailed
information regarding wire size and cable length
In addition to the guidelines in Table 4, observe these requirements for the FC and SA buses.
guidelines when wiring an SA or FC Bus and the
24 VAC supply power:
• Run all low-voltage wiring and cables separate
from high-voltage wiring.
Table 4: Communication Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and
Cables
Terminal Terminal Function, Electrical Ratings/Requirements Recommended Cable Type1
Block/Port Labels
Label
FCBUS2 + FC or SA Bus Communications FC Bus: 0.6 mm (22 AWG)
or - stranded, 3-wire twisted, shielded
cable recommended
SABUS2 COM Signal Reference (Common) for FC or SA Bus
(Terminals) SA Bus 0.6 mm (22 AWG)
communications
stranded, 4-wire (2 twisted-pairs),
SHLD Isolated terminal (optional shield drain connection on shielded cable recommended
or FC Bus or connection for 15 VDC power lead on SA Bus) Note: On the SA Bus, the + and -
SAPWR Note: The SA PWR terminal on an IOM does not supply wires are one twisted pair and the
15 VDC. 15 VDC power for devices (requiring power) on COM and SA PWR are the second
the SA Bus is supplied by the SA Bus supervisor. twisted pair of wires.
SA/FC BUS2 RJ-12 6-Position Modular Connector provides: Wireless Commissioning
(Port) FC or SA Bus Communications Converter retractable cable or
FC or SA Bus Signal Reference and 15 VDC Common 24 AWG 3-pair CAT 3 Cable
Provides 15 VDC Source Power for the Wireless <30.5 m (100 ft)
Commissioning Converter or ZFR1811 Wireless Router
(Maximum total current draw for SA Bus is 240 mA.)
24~ HOT 24 VAC Power Supply - Hot 0.8 mm to 1.5 mm2
Supplies 20-30 VAC (Nominal 24 VAC) (20 to 16 AWG) 2-wire
COM 24 VAC Power Supply Common (Isolated from all other
Common terminals on controller)

1. See Table 3 to determine wire size and cable lengths for cables other than the recommended cables.
2. The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

8 IOM3721 Input/Output Module Installation Instructions


Setup and Adjustments Write the controller’s device address on the white label
below the DIP switch block on the controller cover.
Setting the Device Address
Before operating a Metasys MS/TP controller on an SA Table 5 describes the valid FC Bus and SA Bus
or FC Bus, the controller must be set to a valid and devices addresses for Johnson Controls® MS/TP
unique device address on the bus. Set the Metasys communications bus applications.
controller’s device address using the DIP switches at Table 5: SA/FC Bus Device Address Descriptions
the top of the controller (Figure 3 and Figure 9). Device Description
To set the device address, set all of the DIP switches Address
Off. Then, set one or more of the seven switches 0 Reserved for FC Bus supervisory controller.
(labeled 1 though 64) to ON so that the total of the (128 Off)
switch numbers (set in the ON position) equals the 1-3 Reserved for peripheral devices. (128 Off)
desired device address. Start with the highest number
4-127 For Master devices on a wired SA Bus or
switch that is less than or equal to the desired device FC Bus. (128 Off)
address. For example (Figure 9), if the desired address
0-3 Reserved and not used on Metasys MS/TP
is 21, position switch 16 to ON first, then position (128 ON) buses.
switch 4 ON, followed by 1 (16+4+1= 21). Addresses 0 Note: Metasys controllers ship with 128 ON
through 127 can be set with these seven switches. and the remaining address switches off.
4 - 127 For wireless MS/TP Master devices on
ON (128 ON) FC Buses only. (128 ON plus 4 through 127)
FIG:fec_iom_dip_switch
Note: Switch 128 is used to Note: Do not connect a Metasys controller
enable or disable a controller with these device addresses to an active
for wireless operation.
wired SA or FC Bus. When a controller with
128

32
16
64

1
8

one of these device address is connected to


4

a wired field bus, the field bus is rendered


inoperable until the controller is disconnected
Figure 9: Device Address Switches Set to 21 or switch 128 is set to off.

The eighth switch (labeled 128) on the DIP switch block Setting the Bus EOL Switch
is a mode switch that enables or disables the controller The bus EOL switch allows you to set the IOM as a
to operate on a ZFR1800 Series Wireless Field Bus. terminating device on an SA or FC Bus. The default
Set switch 128 off for wired SA or FC bus applications. EOL switch position is Off. If the IOM is a terminating
Set switch 128 ON for wireless FC Bus applications. device (located at the end) on the daisy chain of field
Metasys MS/TP controllers ship from the factory with controllers on an SA Bus or FC Bus segment, set the
switch 128 set to ON and the remaining device address EOL switch to ON (Figure 10). When the EOL switch is
switches off, which renders each controller a wired On and the controller is powered, the amber EOL
slave device out of the box. (Setting switch 128 set to Light-Emitting Diode (LED) is lit. See Figure 3 for the
ON plus setting 1, 2, or 3 also renders the controller a location of the EOL switch on the IOM3721 controller.
wired slave device.) Wired slave devices are not
O O
supported on Metasys MS/TP buses, but if the N N FIG:EOL_Swtch

controller is connected to an active field bus with the


factory address setting, the controller will not interfere EOL ON Position EOL Off Position
with normal field bus operation.
Figure 10: EOL Switch Positions
Set the controllers’ device addresses on each SA or
FC Bus starting with address 4. To ensure the best bus Removing the IOM Housing Cover
performance, set sequential address numbers on the
controllers with no gaps in the device address range (4, Some IOM models require removing the cover to
5, 6, 7, 8, and so on). The controllers do not need to be access the EOL switch or Input/Oterminal jumpers.
connected to the daisy chain bus in their numerical
IMPORTANT: Electrostatic discharge can damage
device address order.
controller components. Use proper electrostatic
discharge precautions during installation, setup, and
servicing to avoid damaging the controller.

IOM3721 Input/Output Module Installation Instructions 9


2. Pivot the top of the cover further to release it from
IMPORTANT: Disconnect all power sources to the
the lower two latches.
controller before changing the position of the EOL
switch on the controller. Failure to disconnect power Replace the cover by placing it squarely over the base,
before changing the EOL switch position can result and then gently and evenly push the cover on to the
in damage to the controller and void any warranties. latches until they snap into the latched position.

The controller cover is held in place by four plastic Commissioning


latches that extend from the base and snap into slots Commission the IOM with the Controller Configuration
on the inside of the housing cover. To remove the Tool (CCT), either via the Bluetooth® Wireless
controller cover: Commissioning Converter, ZigBee™ wireless dongle,
or in passthrough mode when connected to an NAE or
1. Place your fingernails under the two cover lift tabs
NCE. Refer to CCT Help (LIT-12011147).
on the sides of the housing cover (Figure 3) and
gently pry the top of the cover away from the base Troubleshooting
to release the cover from the two upper latches.
Observe the LEDs on the front of the controller and see
Table 6 to troubleshoot the controller.
Table 6: Status LEDs and Description of LED States
LED Label LED Normal LED Descriptions of LED States
Color State
POWER Green On Steady Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse
is open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
FAULT Red Off Steady Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download
required, if controller is in Boot mode, or a firmware mismatch exists
between the FEC and the ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal
operation
SA/FC BUS Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
EOL Amber Off (Except on On Steady = EOL switch in ON position
terminating devices) Off Steady = EOL switch in Off position

Repair Information Accessories


If the IOM37 controller fails to operate within its See Table 7 to order accessories.
specifications, replace the unit. For a replacement
controller, contact the nearest Johnson Controls
representative.
Table 7: IOM37 Controller Accessories Ordering Information (Part 1 of 2)
Product Code Number Description
MS-BTCVT-1 Wireless Commissioning Converter, with Bluetooth® Technology
MS-DIS1710-0 Local Controller Display
MS-ZFR1811-0 Wireless Field Bus Router for wireless IOM applications
TP-2420 Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
Y65T31-01 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in. Primary
Leads and Secondary Screw Terminals, Class 2
AS-XFR050-0 Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure
AP-TBK4SA-0 Replacement MS/TP SA Bus Terminal, 4-Position, Brown, Bulk Pack

10 IOM3721 Input/Output Module Installation Instructions


Table 7: IOM37 Controller Accessories Ordering Information (Part 2 of 2)
Product Code Number Description
AP-TBK4FC-0 Replacement MS/TP FC Bus Terminal, 4-Position, Blue, Bulk Pack
AP-TBK3PW-0 Replacement Power Terminal, 3-Position Connector, Gray, Bulk Pack

1. Additional Y60 Series transformers are also available.

Technical Specifications
IOM3721 Input/Output Modules
Product Code Numbers MS-IOM3721-0 Input/Output Module
Supply Voltage 24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
Power Consumption 14 VA maximum
Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing
Storage: -40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing
Addressing DIP switch set; valid field controller device addresses 4–127
(Device addresses 0–3 and 128–255 are reserved and not valid IOM addresses.)
Communications Bus BACnet® MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and field controllers
4-wire SA Bus between field controller, network sensors and other sensor/actuator devices,
includes a lead to source 15 VDC supply power (from field controller) to bus devices.
Processor H8SX/166xR Renesas® 32-bit microcontroller
Memory 640 KB Flash Memory and 128 KB Random Access Memory (RAM)
Input and Output IOM3721:
Capabilities 16 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
Terminations Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Mounting Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface with
three integral mounting clips on controller
Housing Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum Rated
Protection Class: IP20 (IEC529)
Dimensions 150 x 164 x 53 mm (5-7/8 x 6-1/2 x 2-1/8 in.) including terminals and mounting clips
(Height x Width x Depth) Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom and front
face of controller for easy cover removal, ventilation and wire terminations.
Weight 0.5 kg (1.1 lb)
Compliance United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: cUL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal
Equipment Industry Canada Compliant, ICES-003
Europe: Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.

Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.

IOM3721 Input/Output Module Installation Instructions 11

Published in U.S.A. www.johnsoncontrols.com

You might also like