Lincoln Centralized Lubrication System
Lincoln Centralized Lubrication System
Lincoln Centralized Lubrication System
Betriebsanleitung
lnstrucciones de funcionamiento
Instructions de service
lstruztoni per II Funzionamento
Zentralschmierpumpe 203 DC
Centralized Lubrication Pump 203 DC
Bomba de lubricaci6n central 203 DC
Lubrification centralisee pompe 203 DC
Lubrificazione Centralizzata Pompa 203 DC
c
.2
"iii
20011327
1'------------------------------'
c
~
I
-c
810-55168·1
Ben utzerlntormatlon LINCOLN
Betriebsanleitung G
2.1l-38002-E04
o
Aile Rechte vorbehalten.
Jegliche Vervieltaltiqunq dieser Benulzerinfonnation, gleich
nach welchem Verfahren, ist ohne vorhelige schriftliche Ge-
nehmigung durch die Fa. Lincoln GmbH & CO. KG, auch
auszugsweise, untersagt.
Anderungen ohne vorherige Ankundigung bleiben vorbehal-
ten.
GB/USA
All lights reserved.
Any duplication of this Owner Manual, in its entirety or in part,
by whatever means is prohibited without the prior consent in
writing of Lincoln GmbH & CO. KG.
Subject to modifications without prior notification.
F
Reservados todos los derechos.
Ninguna parte de este manual para el usuario puede ser
reproducida, almacenada 0 transmitida, de manera alguna ni
por ningun medio, ya sea electrico, quimico, rnecanico,
optico, de grabacion 0 de fotocomposici6n, sin el permiso
previo y por escrito de los titulares del Copyright.
Salvo modificaciones sin aviso previo.
E'
Tous droits reserves.
Toute reproduction, marne partielle, du present manuel, quel
que soit Ie precede utilise, est interdite sans l'autorisation
ecrite prealable de la societe Lincoln GmbH & CO. KG.
Sous reserve de modifications sans notification prealable.
I
Tutti i diritti riservati.
E' vietata qualsiasi riproduzione, anche parziale, del presente
manuale d'uso senza previa approvazione scritta della ditta
Lincoln GmbH & CO. KG.
Con riserva di apportare modifiche senza previa notifica.
LINCOLN
User Manual
Ooeratino lnstructlons
2.1A-381l02-E04
Table of Contents
Page Page
Introduction . A 2 Maintenance A 11
Explanation of Symbols Used A 2 Pump Filling .. A 11
User's Responsibility . .. A 2 Repair .. A 12
Environmental Protection A 2 Pump . A 12
Service A 2 Replace pump element A 12
Printed Circuit Boards A 12
Safety instructions .. A 3 Tests A13
Appropriate Use . A 3 Operational Test! Triggering an
Misuse A 3 Additional Lubrication Cycle A 13
Generai Safety Instructions A 3 To Check the Pressure Relief Valve A 13
Regulations for Prevention of Accidents A 3
Disposal A 3 Troubleshooting A 14
Exclusion of Liability A 3
Operation, Maintenance and Repair A 3 Technical Data A 15
Installation A 4 Pump A 15
Motor . A 15
A5 Pump element with fixed lubricant output A 15
The 203 central lubrication pump . A5 Pump element with adjustable lubricant output A 15
Low-level control (optional) .. A5 Pressure relief valve A 15
Tightening torques A 15
Mode of Operation . A6 Connection Diagram . A 16
Pump elements with fixed lubricant output A6
Pump element 87 with 8ypass-Check Valve A7 Lubricants. .. G16
Pump element with adjustable lubricant output A7 Lubricating greases for QUICKLUB systems A 17
Selling of adjustable pump elements . A8 8io-degradabie greases A 17
Retrofit adjustment of max. lubricant output A8
Pressure Relief Valve A9 Installation A 18
without grease return A9 Specifications for the installation of electric equipment
with grease return (optional) A9 for ADR-application in comercial vehicles A 18
Return Line Connection A ill Lines .. A 18
Control Unit . A 10 Mounting of the Pump -Areas of Risk- . .... A 19
Commissioning . A 10
Certificate for ADR Pump. ..... A20
Technical Description Progressive Metering Devices for Grease and Oil, model SSV
Technical Description for" Pump 203 for 94 to 265 VAC application
Page A 10120
User Manual
Operating Instructions
2.1A-38002-E04
Introduction
I'~ I
To ensure the safe operation of the unit, the user is responsi-
ble for the following:
1. The pump I system shall be operated Q!l!y for the in-
tended use (see next chapter "Safety Instructions") and
its design shall neither be modified nor transformed.
2. The pump I system shall be operated only if it is in a
proper functioning condition and if it is operated in accor-
dance with the maintenance requirements.
1013A94 4273aOO 5001a02 3. The operating personnel must be familiar with this Owner
ATTENTION ATTENTION NOTE Manual and the safety instructions mentioned within and
observe these carefully.
CAUTION CAUTION IMPORTANT
The correct installation and connection of tubes and hoses, if
f WARNING WARNING
The signal words give the seriousness of danger if the follow-
not specified by Uncoln GmbH & Co. KG, is the user's re-
sponsibility. Uncoln GmbH & Co. KG will gladly assist you
ing text is not observed: with any questions pertaining to the installation.
w
c
~
.2
1
.9
i
(J)
PageA2of20
User Manual
Operating Instructions
2.1A·38002·E04
Safety Instructions
PageA30120
User Manual
Operating Instructions
lnstructlons, continuation
1013A94
Installation
safety equipment already fitted to the vehicle or the 1. The ADR Quicklub centralized lubrication pump complies
with the design regulations of annex B of the act governing
should not be modified or made ineffective; the road haulage of hazardous materials valid for Europe
(ADR ' J) and that valid for the Federal Republic of Ger-
should only be removed for the purpose of fitting the many (GGVS 2)
system;
2. Moreover, the pump and its electrical equipment comply
must be reinstalled after fitting the system, with the regulations of annex B.2 (ADR I GGVS regula-
Keep Ouickl.ub centralized lubrication away from tions for electrical equipment) according to Rn 220000 in
sources of heat. Adhere to the operating temperature. conjunction with the transport units mentioned in Rn
10251.
Use only original lincoln spare parts (see Parts Catalog) or
parts approved by lincoln. 3, The ADR central lubrication pump is in conformity with the
protection class IP6K9K.
Adhere to:
Install the ADR Quicklub203 pump, the metering devices,
the installation instructions of the vehicle or machine
lines and tube fittings as well as the electrical connection
manufacturer as regards all drilling and welding proce-
parts in accordance with the Installation Instructions. Use
dures.
only original lincoln parts.
the minimum distances between the boreholes
5. After completion of the proper installation and commis-
and upper/lower rim of the frame or between two
sioning, the installation of the must be certl-
boreholes.
fled by means of a stamp and of the
cialized workshop or expert. use
form attached to the Operating 203).
6. If the pump and the installation do not comply with the
construction regulations of ADR and GGVS, the type ap-
proval is no longer valid.
7. The Instructions
filled in must added to the
be submitted at the inspection in accordance wilth
clause 4 GGVS (see page 20).
o
s
~
-g
E
"
iii
:g
U)
PageA40120
User Manual LINCOLN
OperatingInstructions
2.1A-38002-E04
Description
w 1006a93
51-----------------------'
~ Fig. 2
QUICKLUB central lubrication pump,2 I reservoir
'g
E
.9
~
:g'
<J)
PageA50f20
User Manual LINCOLN
Operating Instructions
2.1A·38002·E04
Mode of Operation
[]]
Lubricant outpuL............... . approx. 4 cm'lmin
3 4
1003a95
2 4
w
c
,g'- -'_....J
1Q04a95
g
:g
(f)
PageA6of20
User Manual LINCOLN
OperatingInstructions
2.1 A-38002-E04
Mode of Operation, continuation
6251h04
Fig. 6
1- Checkvalve
2- Bypass
1 3 3- Pumppiston
625Ob04
4- Returnspring
4158a99
Fig. 8 Adjustablepumpelement
PageA7of20
User Manual LINCOLN
Operating Instructions ®
2.1A·38002·E04
Mode of Operation, continuation
2 3 4
G 1/4
s 4159a98
2,0 0,12
/ Adjusting of small lubricant outputs
1,7 0,10
/ ::P Before the pump element can be adjusted to a smalllu-
bricant output, the dimension "S"') for the maximum lubri-
1,4 0,08
_/ cant output must be ascertained, and the difference from
vrI
the nominal value 29 must be transferred to any desired
1,0 0,06 settings between 25.5 ... 28.5.
::P Dimension "S" must be adjusted to the desired value in
0.7 0,04 accordance with the delivery diagram.
i I
25,5 26.0 26,5 27,0 27,5 28,0 28,5 29,0
NOTE
S
6001a02 At maximum setting "S" is 29 ±O.1 mm.
g
:g
(J)
Page A 8 of 20
User Manual LINCOLN
Operating Instructions
2.1A-38002·E04
Mode of Operation, continuation
[]]
IMPORTANT
Each pump element must be secured with
a pressure relief valve.
The pressure relief valve is not included in
6001a02 the scope of supply of pump 203 but must
be ordered separately (see Parts Cata-
log).
The pressure relief valve
limits the pressurization in the system.
opens whenever the respective overpressure has been
reached.
is to be selected according to the requirements of the
lubrication system (see the different opening pressures:
10022618a 200,270,350 bar).
Fig. 11 Pressure relief valve If lubricant leaks from the pressure relief valve, this indi-
cates that the system is malfunctioning.
Despite existing fault monitoring devices a regular visual
and functional control must be carried out on the lubrication
system.
NOTE
Between a malfunction (blockage) and the following fault indication (lubricant leakage; moniloring intermit-
tent LED display on the control p.c.b. M08-M15) there may be a longer time delay.
Tha duration of the delay depends on the type and length of the lines, the type of lubricant, the ambient
6001a02 temperature and other influences.
PageA90f20
User Manual
Operating Instructions
2.1A-38002-E04
Mode of Operation, continuation
00002629a 10032618
Fig. 13 Fault indicationin the case of a blockage Fig. 14 Return line connection
In the case of a blockage in the system, the grease pushes The lubricant quantities which cannot be dispensed by the
out the red pin at the pressure relief valve, thus indicating metering device must be returned to the pump via the re-
that there is a fault. turn line connection.
Control Unit
NOTE
The present Technicat Description de-
scribes the "Pump model 203 without
control unit". tnformation concerning the
6001a02
design and operation of the individual con-
trol units can be found in the respective
Technical Descriptions.
m
c
o
~
'8
E
.9
g
:g-
III
PllgeA 100120
User Manual UNCOLN
Operating Instructions
2.1A-38002-E04
Maintenance, ~""n,.; .. and Tests
Maintenance
The maintenance is essentially limited to refilling the res-
ervoir with clean lubricant in good time. However, check
regularly whether the lubricant is really dispensed to all the
lubrication points. I
• NOTE
Whenever work is done on the centralized
lubrication system, particular attention
should be paid to absolute cleanliness.
Also check the main lines and lubricant feed lines for 6001a02 Dirt in the system will cause malfunctions.
damage and replace them, if necessary.
2 I, 4 I, 8 I - Reservoir
Fill the reservoir up to the "Max." mark via the filling nipple, if
any, or via the upper filling opening.
:=> It is possible to use greases up to penetration class NLGI
grade 2 or mineral oils of at least 40 mm'ls (cST).
IMPORTANT
The grease or oil must be free from im-
purities and must not be liable to change
its consistency in the course of time.
6001a02
CAUTION!
If the pump is filled via the upper filling
opening, switch off the power supply
before starting filling.
1011a93
CAUTION!
Risk of bursting if the reservoir is over-
filled.
When filling the reservoir by means of
pumps with a large delivery volume do not
exceed the max. filling mark.
1013A94
NOTE
If the reservoir has been completely
emptied, the pump may require until 10
minutes before it operates with its full
6001a02 output.
Page A 11 of 20
User Manual LINCOLN
Operating Instructions G
2.1A-38002-E04
Maintenance, ~on",; .. and Tests, continuation
Repair
Pump Use only original Lincoln spare parts for repair on the
pumps.
The pump should be returned to the factory for warranty
work or major repairs.
Replace pump element
:l Remove the pressure relief valve from the pump element.
:l Unscrew the pump element.
IMPORTANT
Take care that the piston, the pull-back
spring and the washer are not left lying in
the grease, otherwise the reservoir must be
6001302
disassembled in order to remove these
pieces.
IMPORTANT
Do not leave the piston, spring and washer
in the housing because they may block the
motor.
NOTE
Pump elements with adjustable lubricant
output are to be set to the required output
before installation.
Printed circuu Boards :l Note down the jumper positions of the defective control
p.c.b. Therefore, make use oflhe chapter "Configuration of
printed circuit boards" in the User Manual of the respective
control p.c.b,
:l Pack the defective control p.c.b. properly so that it will
reach the factory without any further damages.
::l Set the jumper configuration on the new control p.c.b.
according to the one noted down from the old control p.c.b,
w
.~
~
1
.9
g
:g
U)
Page A 120f20
User Manual UNCOLN
Operating Instructions ®
2.1A-38002-E04
Repair and Tests, continuation
Tests
Operational Test I Triggering an Additional lubrication To check the pump operation it is possible to perform an
additional test. Refar to the Technical Description of the
respective printed circuit board.
2nd option
:l Connect the manual pump of the pressure and checking
set 604-36879-1 to the pressure relief valve and check the
opening pressure by means of the manual pump.
:l The pressure relief valve should open at a pressure of 250
or 350 bar depending on its design.
iMPORTANT
Do not connect the pressure gauge di-
rectly to the pump element. High pressure
may exceed the above-mentioned range,
6001a02 causing the motor to stall. The motor is
designed in such a way that it can stall for
about 30 minutes withou: being damaged.
Page A 130120
User Manual
Operating Instructions
2.1A-38002-E04
NOTE
The pump operation can be checked from the outside by observing whether the stirring paddle is rotaling (e.g.
by triggering an additionallubricalion).
For troubleshooting in the case with integrated control units, please refer to the respective Technical
Cause: Remedy:
Power supply interrupted ::> Check the power supply and fuses.
::> If necessary rectify the fault and/or replace the fuses.
Electric motor defective ::> Check the line leading from the fuses to the pump plug.
::> Check the power supply to the motor. If necessary, replace
the motor.
Defective control printed circuit board ::> Verify the function of the control p.c.b. (see Operating
Instructions ofthe respective control p.c.b.)
Remedy:
NOTE
If a lubricant low-level is available, the low
level is indicated by the flashing light of the
signal lamp in the case of pumps without
6001a02 printed circuit board. The flashing frequency
depends on the speed of the motor.
Reservoir empty ::> Fill up the reservoir with clean grease or oil. Allow pump to
run (trigger an additional lube cycle, also see Operating
Instructions of the respective control p.c.b.) until lubricant
penetrates from all the lubrication points.
NOTE
Depending on the ambient temperature
andlor sort of lubricant it may take 10 min-
utes of operation before the pump elements
6001,02 reach their full lubricant output.
Air bubbles in the lubricant ::> Trigger an additional lubrication cycle (also see Operating
Instructions ofthe respective control p.c.b.). Loosen the
outlet fitting or the main line on the pressure relief valve.
The lubricant must penetrate without air bubbles.
NOTE
When push-in type fittings are used, the
high-pressure hose, which is under pressure,
cannot be easily disconnected from the
6001a02 pressure relief vetve. For this purpose,
loosen the pressure relief valve or, if exists,
the filling nipple on the pressure relief valve
in order to relieve the high-pressure hose.
Unsuitable lubricant has been used ::> Renew the lubricant. See the Lubricant List pages16 ff.
Suction hole of the pump element clogged ::> Remove the pump element. Check the suction hole for
foreign particles. If there are any, remove them.
Pump piston worn Replace the pump element.
Check valve in the the element.
Page A 140/20
User Manual UNCO
Operating Instructions
2.1 A-38002-E04
Technical Data
PUMP MOTOR
Admissible operating temperature .. -40 0 C to 70 °C 1j DC gear motor (interference-suppressed)
Number of outlets . . 1,2 or 3 Operating voltage .. 12 VDC or 24 VDC
Reservoir capacity 2 I, 4 I, 8 I Max. current input
Refilling via hydraulic lubrication fitting or from top -12VDC .......... 6,5A
Lubricant greases up to NLGI grade 2 -24VDC. ....................... 3A
& mineral oils of at least 40mm'Is (cST) at 40° C Speed, dependent on the counter-pressure approx.17 rpm
Type of protection IP6K 9K ace. to DIN 40050 T9
NOTE
....................UL type 4X only lor indoor use, 12 and 13
The pump motor is designed for inter-
mittent operation. For continuous opera-
11 NOTE tion applications contact the manufacturer
The pump is designed for the above first.
6001a02
mentionad temperature range. However,
most times the lubricants are pumpable
up to -25°C only. For lower temperatures
6001a02
use low-temperature lubricants.
Pump element with fixed lubricant output Pump element with adjustable lubricant output
Piston diameter r, K5 .. 5 mm KR . 7 mm
- Lubricant output .. approx. 2 cm'/min - Lubricant output 0.04 to 0,18 cm'/stroke
Piston diameter, (standard) K6 . . 6 mm ........................... . 0,7 to 3 cm'lmin
- Lubricant output ;;; approx. 2,8 cm'lmin Max. operating pressure. 350 bar
Piston diameter, K7, C7 mm Connection thread ... G 1/4"
- Lubricant output approx. 4 cm'/min - suitable for tube dia . 6 mm
Piston diameter, B7 . . 7 mm - suitable for tube dia .. 8 mm
- Lubricant output approx, 2 cm'/min
Max. operating pressure. . 350 bar
IMPORTANT
Connection thread. . G 1/4"
The lubricant outputs listed refer to
- suitable for tube dia . . 6 mm
grease of NLGI grade 2 measured at
suitablefor chiselpaste;contactthe manufacturer of the lubrication
2) 20°C, backpressure 100 bar, and nominal
system. voltage 12/24 V. Any differing pressures
6001002
or temperatures result in different lubri-
cant outputs. Any system design must be
based on the above values.
TIGHTENING TORQUES
Install pump . 18Nm
Electric motor on housing 12Nm
Pump element in housing .. 25Nm
Closure plug in housing . 12Nm
Return line connector in housing . 10-12Nm
c
o
~
'8E
"
Page A 150120
User Manual LINCOLN
Operating Instructions
2.1A-31l002-E04
Technical continuation
Connecting Diagram
~ _._------
Fig. 19 Connection diagram Ouickl.ub 203 without control unit (connection by means of Hirschmann square type plug DIN 43650-A)
A~ pumphousing F- low-levelcontrol
8 connection plug 1 switching capacity max. 60 W N A
"-' - line socket1 withconnection cable, 3-wire switching voltagemax. 230 VAC
D- connection plug2 switching currentmax. 1 A
E- line socket2 M- electricmotor
IMPORTANT
All further connection diagrems can be seen in the respective Technical Description "Electronic control units for
centralized lubrication pump 203".
lubricants
The manufacturer of the centralized lubrication system
IMPORTANT can accept no liability for:
The manufacturer of the centrelized lubri- damages on parts of the centralized lubrication system
cation system tests the lubricants exclu- caused by chemical or biological changes of the lubricant
sively on their transportability in the used.
6001a02
centralized lubrication systems, not on damages due to the use of greases that are not or only
their compatibility with other material. conditionally transportable in centralized lubrication sys-
tems.
The lubricants tested did not cause any damage due to in-
compatibility on the material used by us. The composition of IMPORTANT
Ihe lubricants, their behavior during the transport and their The lubricants released by us have not
compatibility with other material are not known to us. lubri- been tested with regard to their long-term
cant recipes may change. In case of doubt, send your re- behavior. Therefore, we can giva no guar-
quest for more information to the manufacturer of the central- anty for damages caused by chemical
ized lubrication system. reactions of the lubricant with components
of the centralized lubrication system.
Page A 16of20
User Manual LINCOLN
Operating Instructions
2.1 A-38002-E04
lubricants, continuation
NOTE
Ouickl.ub centralized lubrication systems can supply com- Absolute cleanliness is essential when
mercial greases up to NlGI grade 2 or mineral oils of at least handling lubricants. Impurities will remain
40 mm'lsec (cST) at 40"C. suspended in the lubricant and cannot
6001a02
settle. This will block the deliver; channels
causing damage to the bearings.
Biodegradable
~ ..,...
IARAl BAB EP2 LiICa
AUTOl Top 2000 Bio Ca _25' C
'AVIA Biogrease 1 Li up to 0' C
DEA Dolon E 2 Li -15' C
FUCHS Plantogel S2 LiICa
ro
c
o KlOBER KIOberbioM32-82 Li _20' C
~
:g Use lubricants with solid matter additives only after having consulted the manufacturer of the system!
E
B
1ij
:g
</)
Page A 17 0120
User Manual LINCOLN
OperatingInstructions
2.1A·38002·E04
Installation
xn
c;
o
S
~E
$)
I
<J)
Page A 180f20
User Manual UNCOLN
Operating Instructions
2.1A·38002·E04
Installation, continuation
Zone 0
Zone 1
ro
c
o
~ L-
u --'
4332a01
Page A 190120
User Manual
OperatingInstructions
2.1A·38002·E04
Certificate for 203- -ADR
Report: 054-01
th
For presentation at the inspection performed according to ADR chapters 9.2.2, 9.3.7 and 9.7.8 (status 15 modification);
VdTOV-explanatory leaflet 5205; ISO 6722-4; ISO/DIS 14572; EN 40050 and EN 60079-14 by an officially authorized expert of
automotive traffic.
This is to certify that the P 203-ADR Centralized lubrication Pump has been properly installed by us in the following vehicle:
Type ..
Manufacturer .
Model
in accordance with the works installation instructions using original parts of the manufacturer.
a) Centralized lubrication pump with integrated control unit, model P 203- .....-ADR
Component designation: TO.EGG.054-01
c) Electric lines for the centralized lubrication pump in accordance with the
regulations of chapter 9.2.2 01the ADR
Furthermore, this is to certify that the system has been properly installed in
consideration of the construction regulations of ADR.
l'ageA200f20
Owner Manual
Technical Description
2.6A-20002-C00
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Survey
Pump Voltage [V] Control unit Setting ranges Part no. Applications
P1: 4 to 60 minutes
12/24 P2: 1 hour to 15 hours
203 integrated A 1: 8 seconds to 120
V10-V13*,** seconds 236-13891-1
V20-V23*,** A 2: 2 to 30 minutes 236-13891-2
integrated P : 4 to 60 minutes
M00-M23*** P : 1 to 15 hours 236-13870-1
Ü : 5 or 30 minutes
without control
unit or with
external control
unit*
12/24
203 integrated
V10-V13*,** ADR 236-13891-1
12/24
203 integrated B : 6 hours, fixed 236-13857-1
H* A: 2 to 30 minutes
12/24
203 integrated B : 6 hours, fixed 236-13857-1
H * ADR A : 2 to 30 minutes
A - Operating time ranges B - Time of availability P - Pause time range Ü - Monitoring time
Subject to change without notice
Note: The applications of the progressive systems are various. There is therefore a corresponding control unit available for each
individual application.
Page 2 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Table of Contents
Page Page
Page 3 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
1191c95
1191d95
When the driving switch (terminal 15) is switched on, the cen-
tralized lubrication system is ready for operation
1060a95
*
This designation shows the version of the PCB installed in the pump. It forms part of the pump designation on the name-
plate on each pump.
In the case of P 203-...-.K.-.A. ...-V10 the PCB 236-13891-1 is installed, see connection diagrams 1, 14 and 16.
In the case of P 203 - ... - .K. - .A.. ..-V20 the PCB 236-13891-2 see connection diagram 2, 17.
Page 4 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Mode of Operation
The printed circuit board is integrated in the pump hou-
sing.
00002616
20002443b
1059a95
Subject to change without notice
Page 5 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
- determines the frequency of the lubrication cycles within a - depends on the systems lubricant requirement ;
working cycle; - is adjustable;
- is started and stopped via the machine contact or driving - is finished when the machine contact or the driving switch is
switch; switched off.
- is adjustable. The longer the operating time, the greater the lubricant re-
When the machine contact or the driving switch is switched quirement and vice-versa.
off, the pause times which have already elapsed are stored When the machine contact or the driving switch is switched
and added up (refer to T1, Fig. 6) until the time which has off, the operating times which have already elapsed are
been set on the blue rotary switch (Fig.8) is reached. stored and added up until the time which has been set on the
The pause time setting may be different for each application. red rotary switch (Fig. 10) is reached. After this, the lubricati-
It must be adjusted in accordance with the respective lubri- on cycle starts again.
cation cycles. Also see To set the pause time. The operating time setting may be different for each applica-
tion. It must be adjusted in accordance with the respective
lubricant requirement. Also see To set the operating time.
Time storage
Page 6 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Time Setting
* To set the pause or operating time, remove the cover on the
pump housing.
00002617
Fig. 7 - The cover to access the printed circuit board has been removed
Switch position 1 2 3 4 5 6 7 8 9 A B C D E F
Minutes 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60
Hours 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Factory setting
or ................................................................................ 24 minutes
Factory setting of the jumper: see chart page 15. The combi-
20002452a nation number can be learnt from the pump type designation
Fig. 9 - Preselection of the time range
code mentioned on the nameplate of each pump.
Page 7 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
20002453b
Switch position 1 2 3 4 5 6 7 8 9 A B C D E F
Minutes 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Factory setting
Factory setting of the jumper: see chart page 15. The com-
bination numbers can be learnt from the pump type desi-
gnation code mentioned on the nameplate of each pump.
20002437
Fault indication
Rotary switch set at 0 Pushbutton 5 Fig. 12 continuously actuated (short circuit)
When one of the rotary switches 2, 3 Fig. 12 is on the 0 If a short circuit occurs at the pushbutton or is present at
setting a fault is shown at the right-hand LED 3. the external illuminated pushbutton Fig.13 or at the con-
Subject to change without notice
The fault is indicated by 4 flashes of the LED. necting parts a fault is shown at the red LED 3, fig. 12.
The pump motor also runs according the flash frequency. If The fault is indicated by 3 flashes of the LED when the
the warning is ignored the controller automatically adopts voltage supply is switched on.
the factory-set values for the operating or pause time The motor of the pump also runs according to the flash
frequency.
Page 8 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Repair
The defective printed circuit boards should be suitably packed If the printed circuit board must be replaced, a model
and returned to the factory. V 10 (V20) will always be delivered. See chart page 15.
Before installing another printed circuit board, take care that
the setting of the jumper or that of the operating/pause time
is the same as on the old printed circuit board.
Note: In the case of model 203 pump, version 2A1, with exter-
nal illuminated pushbutton, it is also possible to trigger an addi-
tional lubrication cycle via this pushbutton.
Subject to change without notice
20002458
Page 9 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Troubleshooting
Note: The pump operation can be checked from the outside by circuit board are lit or whehter the signal lamp of the illumi-
observing whether the stirring paddle is rotating (e.g. by trigge- nated pushbutton (if any) is lit.
ring an additional lubrication), whether the LED on the printed
Voltage supply interrupted Check the voltage supply to the pump. If necessary, elimina-
te the fault.
Voltage supply to the printed-circuit interrupted Check the line leading from the pump plug to the printed cir-
cuit board.
If the voltage is applied, the left-hand LED is lit.
Voltage supply interrupted betweeen the printed circuit board Triggering an additional lubrication cycle
and the motor If the voltage is applied, the right-hand LED is lit.
One of the two rotary switches 2, 4 Fig. 12 is on 0. Set rotary switch to a number or a letter.
Signal: 4 flashes
Short circuit at pushbutton 5 Fig. 12 or, if present, at the illu- Check whether the short circuit is at he PCB or, if present,
minated push button or at their connecting parts at the illuminated pushbutton.
Signal: 3 flashes If necessary, exchange the PCB or the illuminated pushbut-
ton.
.
Subject to change without notice
Page 10 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Technical Data
All the printed circuit boards comply with the EMC (Electroma-
gnetic compatibility) guidelines for road vehicles acc. to DIN
40839 T1, 3 and 4
and the EMC guideline 89 / 336 / EWG
Emitted interference acc. to ................. EN 55011 / 03.91 and
........................................................ EN 50081-1 / 01.92
Noise immunity acc. to ............................. EN 50082-2 / 03.95
The type 203 pumps with PCB V10 - V13 (V20 - V23) comply
with the Automotive EMC Directive 95/54/EEC and with the
EC approval mark e1
021016
shown on the nameplate
Subject to change without notice
Page 11 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
1192c95
A- Printed circuit board 1A1 - Pump without illuminated pushbutton G- Cable connector 2*
B- Pump housing 2A1 - Pump with cable connection for H- Line socket 2 (grey)
C- Cable connector 1 illuminated pushbutton* for connection cable, 3-wire*
D- Line socket 1 (black) F - Machine contact I- Pushbutton for additional lubrication
for connection cable, 3-wire J - Signal lamp in the case of low-level
* on request control
Attention! If a pump model 103 CS...E2 is replaced by a pump model P203-...-...-2A1.10, the lamp connection of the
illuminated pushbutton must be changed from minus to plus.
- Low-level control*
Page 12 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
1155d95
A- Printed circuit board 2A1 - Pump with cable connection K- Cable connector 2**
B- Pump housing for illuminated pushbutton** L- Line socket 2 (grey)
C- Cable connector 1 F - Driving switch with connection cable, 3-wire**
D- Line socket 1 (black) G - Fuse 10 A M- Illuminated pushbutton**
with connection cable, 3-wire H - Cable, black O- Signal lamp in the case of low-level
1A1 - Pump without illuminated pushbutton I- Cable, brown control
P- Battery cutoff*
Caution: Do not connect the red core (not shown: cf. J Fig. 17)
of the 3-core connecting cable to the wire box 1 (D, Fig. 16)
since the PCB is connected internally between 30 and 15.
Subject to change without notice
Attention! If a pump model 103 CS...E2 is replaced by a pump model P203-...-...-2A1.10, the lamp connection of the
illuminated pushbutton must be changed from minus to plus.
Page 13 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
1155e95
A- Printed circuit board 2A1 -Pump with cable connection K- Cable connector 2**
B- Pump housing for illuminated pushbutton** L- Line socket 2 (grey)
C- Cable connector 1 F - Driving switch with connection cable, 3-wire**
D- Line socket 1 (black) G - Fuse 10 A M- Illuminated pushbutton**
with connection cable, 3-wire H - Cable, black O- Signal lamp in the case of low-level
1A1 - Pump without illuminated pushbutton I- Cable, brown control
J - Cable, red P- Battery cutoff*
Attention! If a pump model 103 CS...E2 is replaced by a pump model P203-...-...-2A1.10, the lamp connection of the
illuminated pushbutton must be changed from minus to plus.
1009b93
* equipment available on request
Fig. 18 - Terminals of the printed circuit board 236-13891-2
Page 14 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Combination no.
V 10, V 20
Standard X X
V 11, V 21 X X
V 12, V 22 X X
V 13, V 23 X X
Subject to change without notice
Page 15 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Technical Description
2.6A-20002-C00
Subject to change without notice
Page 16 from 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
QUICKLUB
Progressive Metering Devices
for Grease and Oil
Typ SSV
4137b97
Subject to modifications
Page A 1
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Safety Instructions
Page A 2
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Table of Contents
Page Page
* The design of the printed circuit board is indicated by the model designation which is part of the pump type identification code mentioned on the
pump nameplate. Example: B. : P 203-2XN - 1K6 - 24 - 1A1.10 - V00
Subject to modifications
Page A 3
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
10002709
Page A 4
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Applications
QUICKLUB progressive metering devices offer the option of
combining several lubrication points on a machine to one or
more central lubrication points, as shown in Fig. 4 which illu-
strates this basic feature.
1205a95
1 - Hand-operated pump
2 - Pneumatically operated pump
3 - Electrically operated pump
4 - Lubrication fitting block
4024a95
5 - Hand-operated filling pump
Fig. 5 - Possible pump connections
4025a95
1207a95
Page A 5
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1206a95
Phase 1
The lubricant enters the metering device from above (white
arrow) and flows to the right-hand end of piston A.
Piston A (black arrow) is moved to the left under the pressure
of the lubricant, causing the lubricant ahead of the left-hand
end of piston A to be dispensed to outlet 2 (dashed arrow).
Lubricant, pressureless
2007a99
Fig. 9 - Phase 1
Phase 2
Once piston A has reached its left-hand final position, the
junction channel to the right-hand end of piston B is opened.
The lubricant which arrives from above (white arrow)also
moves piston B (black arrow) to the left, causing the lubricant
quantity ahead of the the left-hand end of piston B to be dis-
pensed to outlet 7 (dashed arrow).
2008a95
Lubricant, pressureless
Fig. 10 - Phase 2
Subject to modifications
Page A 6
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Phase 3
Once piston B has reached its left-hand final position, the
junction channel to the right-hand end of piston A is opened.
The lubricant which flows from above (white arrow) moves
piston C (black arrow) to the left, causing the lubricant quan-
tity ahead of the left-hand end of piston C to be dispensed to
outlet 5 (dashed arrow).
2009a95
Phase 4
The channel to the right-hand end of piston D is now open
(black arrow).
The lubricant which is fed from above (white arrow) moves
piston D to the left, causing the lubricant quantity ahead of
the left-hand end of piston D to be dispensed out of the me-
tering device via outlet 3 (dashed arrow).
Phase 5
In phase 4, piston D had opened the junction channel to the
left-hand end of piston A.
The lubricant flowing in (white arrow) moves piston A to the
right (black arrow), causing the lubricant quantity to be dis-
pensed to outlet 1(dashed arrow).
In the subsequent distribution sequence, pistons B - D are
moved from the left to the right one after the other.
A complete distribution sequence is finished and a new cycle
can begin.
Lubricant under pump pressure
Fig.13 - Phase 5
Lubricant, pressureless
When the lubricant supply is interrupted
Subject to modifications
Page A 7
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
The main metering device (B, Fig. 14) and the secondary
metering devices are connected by a main line G. This fea-
ture automatically causes the linkage of the progressive sy-
stem connected downstream of the pump.
If only one piston does not move in any metering device or if
the metering device can no longer dispense any lubricant via
its outlets, this metering device will block itself.
If one of the secondary metering devices is blocked, the main
metering device is also blocked. The whole progressive sy-
stem installed downstream of the pump stops operating.
The fundamental internal structure of the progressive mete-
ring device guarantees the self-monitoring of the sequence
1064b95 within the metering device.
Fig. 14 - Example of a lubrication system The linkage makes it possible to monitor the operation of the
whole system.
A - Safety valve E - Pressure plastic tube (Ø 6 x 1.5 mm)
B - Main metering device SSV 6 F - Secondary metering device
C - Secondary metering device SSV 8 SSV 12
D - Secondary metering device SSV 6 G - High pressure plastic hose
(Ø 8.6 x 2.3 mm)
Visual monitoring
1011a96
00002634 SSV ... - N (they are available for SSV 6, 8, 10 and 12). They
Fig. 16 - Piston detector installed on the metering device must be installed in the system instead of a normal metering
device.
Page A 8
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
4092a97
1012c96
Fig. 18 - Install the outlet fittings and closure plugs in accordance with the dosage
2 - Delivery hole of the piston 6 - Valve body with clamping ring (brass) 10 - New closure plug (M 10 x 1), outlet
3 - Closure plug (M 10 x 1), installed with 7 - Cutting ring borehole with hex. socket head and
copper washer (old) 8 - Coupling nut sealing edge, replacement for pos. 3
4 - Closure plug (new M 11 x 1, old R 1/8),
piston (with champfered)
Page A 9
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
The output quantities can be raised by closing outlet boreho- Clamping ring (Fig. 18) closes the junction channels 9 to the
les. other outlet channels.
Install an outlet fitting assembly 5 (M 10x1) in each outlet Note: In the case of push-in type fittings the clamping ring is
borehole which will be used. Refer to Fig. 18, 19, 20. always a firm component part of the valve body.
Never remove closure plug 4 (M 11x1 chamfered) on the
piston side or remove it only for installing a piston detector. Important: In the case of the progressive metering devices
model SSV 6 - 12 and the divider blocks SSV 14 - SSV 22
Note: Never use closure plug 12 (Fig. 18) or 7 (Fig.19, 20) as a the outlets 1 and/or 2 must never be closed. In the case of
piston closure plug 4 (G 1/8) on older models of meteringde- the combined progressive metering devices model SSV 14 -
vices. 22, the two outlets with the highest numbers must never
Never use closure plug 12 (Fig. 18) or 7 (Fig. 19, 20) as a be closed, otherwise the system would block due to the struc-
piston closure plug 4. ture of the metering device.
1203c95
Fig. 19 - Install the push-in type outlet fittings and the closure plugs in accordance with the dosage
1 - Inlet fitting with protective cap * 5 - Valve body assembly (with reinforced collar)
2 - Delivery borehole of the piston 6 - Junction channels
3 - Closure plug (M 10x1) with copper washer installed in outlet 7 - New closure plug with hex. socket head and sealing edge,
borehole (old) outlet borehole replacement for pos. 3
4 - Closure plug (new M 11x1, old R 1/8 chamfered), piston
Subject to modifications
* on request
Page A 10
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1204c95
Fig. 20 - Install the push-in type outlets fittings and closure plugs in accordance with the dosage
x - Outlet quantity (1x: single, 2x: double, etc.) borehole located above the discharge borehole. Refer to
1... 10 Outlet numbers outlets 3 and 5 on Fig. 21.
A - Clamping ring (brass)
Page A 11
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Check valves
Install one complete check valve in each outlet borehole which
will be used.
Check valves for tube dia. 4 mm and 6 mm are available.
4239a99
Page A 12
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Important ! For the inlet fittings use only tube fittings with
reinforced collet 1a (Fig. 24) and sealing ring 1b at the thread.
1a - Collet
1b - Sealing ring
1008a98
Check valves
Page A 13
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
4156a98
The pressure plastic tubes are marked with white lines (Fig.
27) as an installation aid.
* Cut the pressure plastic tube off at one of the white lines be-
4157a98
fore it is mounted. Then insert the plastic pressure tube into
Fig. 27 - Check valve with knurled collet and pressure plastic tube the fitting up to the next white mark. This will ensure a correct
installation of the pressure plastic tube in the threaded tube
fitting.
00002632
Page A 14
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1 - Threaded sleeve Important: Before screwing the parts 1 and 3, rub them with
2 - High - pressure plastic hose Ø 8.6 x 2.3 mm oil.
3 - Hose stud
Note: The outside diameter of the main line may show variati-
ons in dimension. In such a case, press the threaded sleeve 1
at the end where it will be screwed onto the main line so that it
becomes oval in shape (1 to 2 mm). This will prevent the high
pressure plastic hose from being pushed out of the sleeve
when the hose stud is screwed.
1029a96
1 - Threaded sleeve
2 - High - pressure plastic hose Ø 8.6 x 2.3 mm
3 - Adjusting gauge 432-23077-1
Subject to modifications
Page A 15
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Troubleshooting
Cause: Correction:
Bearing, lines or metering device clogged. Find out which is the cause of the blockage and rectify it in
In the case of the metering devices SSV 6 through 12 and accordance with he following example:
the metering device blocks SSV 14 to SSV 22 the outlet
boreholes 1 and/or 2 are closed. In the case of the combined
metering devices SSV 14 through 22 the two outlet boreho- Allow pump to run (see To trigger an additional lubrication
les with the highest numbers are closed. cycle).
Loosen all main line connections G one after the other from
The fault can be identified by: the main metering device (B, Fig. 31) leading to the secon-
a)grease leaking at the safety valve; dary metering devices. If f. ex. grease or oil emerges under
b) the fact that the indicator pins installed on the metering de- pressure from outlet 1 of main metering device B, the blocka-
vices (if any) no longer move; ge will be found in the lubrication circuit of the secondary me-
c) the fault signal of the signal lamp (if any) or LED display tering device D.
1064a95
Page A 16
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Cause: Correction:
Cause: Correction:
Lubricant metering not correct Check the lubricant metering acc. to the lubrication chart
Respective valve body has been assembled without clam- Remove the valve body and install a clamping ring
ping ring
Setting of the pause time or operating time incorrect Check the time setting. Refer to the corresponding setting in
the respective Operating Instructions.
Cause: Correction:
Setting of the operating time or pause time incorrect Check the time setting at the printed circuit boards. Refer to
the corresponding setting in the respective Operating In-
structions.
Subject to modifications
Page A 17
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
4093a97
1007a96
1006a96
Page A 18
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1016a96
1004a96
1005a96
Page A 19
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1017a96
1003a96
Page A 20
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
9. Lubricant output of the pumps 203* and 205** Lubricant output of the pump 215
- at 100 bar backpressure Max. number of outlets.................................................15
- at 20°C
- at 24 V rated voltage Lubricant output per piston stroke:
Pump element K5 ........... 2 cm3/min*; 0.10 cm³/stroke** Pump element piston dia. 6 mm ........................ 0.10 cm³
Pump element K6 ........ 2.8 cm3/min*; 0.15 cm³/stroke** Pump element piston dia. 7 mm ........................ 0.23 cm³
Pump element K7 ........... 4 cm3/min*; 0.22 cm³/stroke**
Adjustable pump element K7...0.04 - 0.18 cm³/stroke* ** Adjusting range ............................................ 25% to 100%
1001a96
10. Adjusting the running time (operating time) of the For the running time of a system select the time for the big-
pump (not for pumps with microprocessor control) gest secondary metering device, as a function of the main
The chart below shows the required pump operating times in metering device used.
the case of various combinations of the main metering de- If the time mentioned below cannot be preselected, take the
vice and the biggest secondary metering device. next larger time value.
With the indicated times each lubrication point receives
lubricant at least once a day.
Lubricant output of Single Double Single Double Single Double Single Double
the main metering device
Secondary metering
device
Subject to modifications
SSV 10 5 min 2,5 min 6,5 min 3.5 min 8,5 min 4,5 min 10 min 5 min
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
During the operating time (pump running time) the used lub- It is important to take care that the lubricant is renewed or top-
ricant is renewed or topped up in the bearings. ped up within a predetermined time of application of the machi-
The frequency of renewal/topping up and the quantity which ne or vehicle so that there is no damage to the bearings.
must be supplied to a single lubrication point depends on If normal or larger bearings are connected to the secondary
several factors, e.g.: metering devices model SSV 10 or SSV 12 or up to SSV 22,
- bearing size these metering devices must receive the double or multiple
- kind of bearing - open or closed bearing, rolling bearing or quantity.
friction bearing In the case of smaller bearings with a small lubricant require-
- frictional force ment the SSV 10 or SSV 12 will receive a single lubricant
- bearing loads quantity.
- adjustable running times of the pump, etc.
The required quantity may be very different as a result of the
above mentioned factors.
4022a95
1018a96
Page A 22
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1019a96
1020a96
1021a96
Page A 23
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1022a96
Important: The lubricant division should be made only via 2 steps of metering devices, i.e. main metering device - secondary
metering device - lubrication point
1023a96
Page A 24
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
1024a96
PA Pressure loss, main line PC Pressure loss, main line PD Pressure loss, secondary metering device
PB Pressure loss, main metering device between main and secondary metering device PE Pressure loss, lubricant feed line
The following chart serves as a reference when calculating the maximum size of a QUICKLUB system, under consideration of the
lubricant sorts and ambient temperature.
Lubricant penetration class Maximum pressure loss with tube 6x1,5 mm (NW 3 mm)
Note: The data relating to the pressure loss per metering de-
vice refer to metering devices with 6, 8, 10 and 12 outlets, na-
mely the main and secondary metering devices.
Subject to modifications
The sum of all pressures, from PA to PE plus 5 bar for the All the values mentioned in the tablet are average values
rolling bearings (lubrication point) or plus 15 bar for friction based on real test results.
bearings must not exceed 80% of the recommended wor- The NLGI class of the grease only indicates the statistical
king pressure of the pump. density. It does not indicate the dynamic pumpability of the
grease. The flow properties of greases of the same NLGI
class may be very different.
Page A 25
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Technical Data
Lubricant output per outlet and per stroke ............ 0.2cm³ MainLine
Max. operating pressure ....................................... 350 bar Min. bursting pressure (in connection with
Min. operating pressure .......................................... 20 bar hose clamp, screwed). .......................................... 600 bar
Max.differential pressure Min. bending radius. ............................................... 35 mm
between two outlets ............................................... 100 bar Min. temperature .................................................... - 40° C
Outlet connection for tube ..................................... Ø 6mm
Inlet connection ......................................................... G 1/8 Lubricant Feed Line
Operating temperature ............................. - 25° C to 70°C Min. bending radius ................................................ 50 mm
Bursting pressure at 20° C .........................approx. 210 bar
Screw-Type and Push-inType Tube Fittings Min. temperature .................................................... - 40° C
High pressure range, p max. ................................ 350 bar
Inlet tube fittings of the metering devices
Outlet fittings, main metering device
Low-pressure range, p max. ................................. 250 bar
Outlet fittings, secondary metering devices
Inlet fittings to the lubrication point
Tightening torques
Page A 26
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Dimensions
2012a95
1015a96
Subject to modifications
Page A 27
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259
Owner Manual
Operating Instructions
2.2A-10001-C99
Lubricants
The QUICKLUB pump 203 can dispense greases up to NLGI Important: Absolute cleanliness is essential when handling
class 2 or mineral oils with min. 40 mm²/s (cST) at 40°C. lubricants. Impurities will remain suspended in the lubricant
and cannot settle. This will block the delivery channels causing
damage to the bearings.
AGIP F1 Grease 24 Ca
BP Lubricating grease Ca
BP C1 lubricating grease Ca
CASTROL CL - Grease Ca
ESSO Cazar K2 Ca
FUCHS FN 745 Ca
MOBIL Mobilgrease Li
OPTIMOL Longtime PD 2 Li - 20 ° C
SHELL Retinax C Ca
Biodegradable greases
AVIA Biogrease 1 Li to 0 ° C
Subject to modifications
DEA Dolon E 2 Li
Page A 28
LINCOLN GmbH Postfach 1263 D-69183 Walldorf Tel +49 (6227) 33-0 Fax +49 (6227) 33-259